Trox Technik EM-TRF, EM-TRF-USV Operating And Installation Instruction Manual

EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
The art of handling airThe art of handling air
Operating and Installation Manual
EASYLAB Expansion modules Type EM-TRF
for 230 V AC mains voltage
for 230 V AC mains voltage; provides uninterruptible power supply (UPS)
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
2
1 General information __________________ 3
Other applicable documentation ________ 3 Symbols used in this manual ____________ 3
2 Safety and correct use ________________ 4
General information regarding safety ______ 4 General safety measures ______________ 4 Correct use ________________________ 4 Incorrect use ________________________ 4 Residual risks ______________________ 4
3 Product description __________________ 5
Product overview and functional description 5 Technical data ______________________ 6
4 Transport, storage and packaging ________ 7
5 Installation __________________________ 8
Installing the EM-TRF and EM-TRF-USV __ 8
Fitting the safety latch ________________ 9
Installing the EM-TRF-USV - contd. ______ 9
6 Wiring ____________________________ 11
Wiring the EM-TRF and EM-TRF-USV ____ 11
Wiring the EM-TRF-USV - contd. ________ 11
7 Commissioning ______________________ 12
8 Maintenance ________________________ 12
9 Decommissioning ____________________ 12
Disposal of the battery pack ____________ 12
Contents
TROX GmbH
Heinrich-Trox-Platz D-47504 Neukirchen-Vluyn
Phone +49 (0) 28 45 20 20 Fax +49(0) 28 45 20 22 65
E-Mail trox@trox.de www.troxtechnik.com
Subject to change / All rights reserved © TROX GmbH
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
3
Danger!
Designates danger to life and limb due to electrical voltage.
Warning!
Designates danger to life and limb.
Important!
Designates danger that can cause minor personal injury or damage to property.
Symbols used in this manual
This operating and installation manual describes the EM-TRF and EM-TRF-USV expansion modules that are used to connect TCU 3 EASYLAB controllers and TAM adapter modules to a 230 V AC supply voltage.
To ensure complete functioning of the expansion modules it is essential to read this operating and installation manual before starting any work, and to comply with it. The manual must be given to the facilities manager when handing over the system. The facilities manager must include the manual with the system documentation.
The manufacturer does not accept any liability for any malfunction or damage resulting from non­compliance with the manual or non-compliance with relevant statutory regulations.
Other applicable documentation
In addition to this manual, the following documents
apply:
• Control Systems catalogue – EASYLAB EM-TRF, EM-TRF-USV
expansion modules – EASYLAB TCU3 controller – EASYLAB TAM adapter module
• EASYLAB TCU3 controller Operating and Installation Manual (M375EV0)
• Project-specific wiring documents
1 General information
General information regarding safety
Only skilled qualified personnel are allowed to perform the described work on the expansion modules. Only skilled qualified electricians are allowed to work on the electrical system.
For all work performed on the EASYLAB components, the following regulations and guidelines must be complied with. This applies in particular to the following German country specific regulations or as appropriate in the country where the installation is taking place:
• Equipment and Product Safety Laws (GPSG)
• Industrial Health and Safety Regulations (BetrSichV)
• Accident Prevention Regulations (BGV A1, BGV A3)
General safety measures
• Large temperature differences
Condensation can damage the electronics beyond repair. If the expansion module has been kept in an unheated area, wait at least two hours before switching on the supply voltage for commissioning.
• Electrostatic charge
Electrostatic charge can damage the electronics. To avoid this, first touch an equipotentially bonded metal surface, e.g. a water pipe, for electrical earthing before you remove the expansion module from its protective wrapping. Avoid skin contact with any components or printed circuits on the expansion module or the main PCB.
• Weight
The expansion PCB is equipped with a transformer that has a comparatively high weight. To avoid injury and damage, be sure to grip the PCB properly and to handle it with care.
• Installing the PCB
Tighten the mounting screws only hand-tight to avoid damage to the PCB or to the fixing points in the casing.
• Foreign matter and liquids
If liquid gets onto the PCB or inside the expansion module, let the expansion module completely dry before commissioning. Remove foreign matter, if any.
If the device emits a smell or smoke, have it checked by the manufacturer.
4
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
2 Safety and correct use
Correct use
The EM-TRF and EM-TRF-USV expansion modules are used to connect TCU 3 EASYLAB controllers and TAM adapter modules to a 230 V AC supply voltage.
• Use the expansion module only with a TCU3 EASYLAB controller or a TAM adapter module.
• Do not connect EASYLAB controllers with an EM-TRF or EM-TRF-USV expansion module to a 24 V power supply.
• Only connect the expansion module to the dedicated socket on the main PCB of the TCU3 or TAM.
• Observe the technical data of the expansion module.
Incorrect use
Do not use the expansion module outdoors, in wet areas, or in potentially explosive atmospheres.
Residual risks
Uninterruptible power supply is provided only with the EM-TRF-USV being connected to a fully charged battery pack. For maximum operating times with uninterrupted power supply refer to the technical data.
Product overview
5
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
Product overview and functional description
 Micro fuse
F 500 mA T, 250 V  Terminal block for supply voltage  PCB connection plug
3 Product description
Functional description
Once the expansion module has been connected to the 230 V AC supply voltage (mains voltage), the transformer reduces this voltage to 24 V AC to be supplied to the controller and its modules. An LED indicates whether voltage is being supplied.
Additional function of the EM-TRF-USV
If the supply voltage (mains voltage) fails, the battery pack takes over and supplies voltage to the controller and any connected components. The alarm function is always maintained; if the emergency voltage supply covers also the air conditioning system, that function is also maintained.
EM-TRF
EM-TRF-USV
L N PE
L N PE
 Operating state indicator light  Socket for battery pack  Battery pack
6
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
3 Product description
EM-TRF · EM-TRF-USV
Supply voltage 230 V AC ±10 %, 50-60 Hz
Power consumption
up to 40 VA for a controller with all expansion modules up to 35 VA for a fume cupboard controller with control panel up to 33 VA for a room controller with room control panel up to 29 VA for a room controller without room control panel up to 9 VA for an EASYLAB TAM adapter module
Primary fuse 500 mA, slow blow, 250 V
Terminal block Cable cross-section up to 2.5 mm²
Acceptable temperature range
for storage −10 to +70 °C for operation 0 to +50 °C
Protection level IP 20
Dimensions B × H × T: 78 × 65 × 100 mm
Weight 1,3 kg
Technical data
Additional data for the EM-TRF-USV
USP operation One controller (TCU3 or TAM) with a control panel
Approx. 4.5 h for maintaining normal operation Approx. 6 h for a defined blade position and indication of mains voltage interruption
Shelf life 6 months from delivery to commissioning
Service life Up to 4 years
Weight 2,4 kg (incl. Battery pack 1,1 kg)
7
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
Delivery check
Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, inform the shipping company and your TROX contact person immediately.
A complete shipment includes:
• Expansion module PCB
• PCB connection plug
• Safety latch
• Fixing screws
• Operating and installation manual
Additionally for the EM-TRF-USV expansion module:
• Battery pack with connecting cable and plug
• Fixing bracket
• Fixing screws
Transport on site
• If possible, take the expansion module in the transport packaging up to the installation location.
• Do not remove the protective wrapping until just before installation.
Storage
If you need to store the expansion module temporarily, make sure that the following conditions apply:
• Leave the unit in its packaging and do not expose it to the effects of weather.
• Store the unit in a dry place and away from direct sunlight.
• Temperature: –10°C to +70°C Maximum humidity: 90% (non-condensing)
Packaging
Properly dispose of packaging material.
4 Transport, storage and packaging
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
8
For installation, wiring, and commissioning observe the recognised technical regulations, especially safety and accident prevention regulations.
For any wiring work follow the national and local regulations and guidelines for electrical installation.
Danger!
Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage.
• Only skilled qualified electricians are allowed to work on the electrical system.
• Switch off the power supply before working on any electrical equipment.
Important!
Danger of injury or damage to electronic parts from the weight of the transformer.
To avoid injury and damage, be sure to grip the PCB properly and to handle it with care.
Installing the EM-TRF and EM-TRF-USV
Step 1
1.Interrupt the voltage supply to the TCU3 controller or TAM adapter module.
2.Open the lid.
3.Slide the 6-pin PCB connection plug  onto the expansion module PCB. The tiny plastic bridge on the plug fits into the cut-out of the expansion module PCB. Make sure that the plug locks into place.
Step 2
1.Lower the expansion module with the connection plug into the casing of the TCU3 or TAM and place it in such a way that the connection plug is aligned with the appropriate cut-out of the main PCB.
2.Push the expansion module towards the main PCB until the connection plug has been firmly placed in the cut-out, and the fixing points (holes) of the expansion module PCB and the main PCB are aligned.
3.Fix the expansion module with the supplied four fixing screws.
5 Installation
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
9
5 Installation
Fitting the safety latch
For safety reasons the TCU3 casing must be locked in such a way that it can only be opened with a tool when a 230 V power supply is connected.
1. Place the supplied safety latch on the casing.
2. Drill a hole into the casing (Ø 3mm).
3. Fix the latch with the supplied screw to the lid of the casing.
The casing can now only be opened with a tool.
Installing the EM-TRF-USV - contd.
Step 3
Mounting the battery pack.
1.Mount the battery pack on the VAV terminal unit as shown.
Mounting on the TVLK  Battery pack
 Screw  VAV terminal unit
Safety latch
Screw
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
10
If necessary, the bracket  can be bent for fixing it to the control unit.
5 Installation
Installation examples  Battery pack
 Screw  Bracket  VAV terminal unit Important: Be careful when fixing the brackets to
the casing - the movement of the damper blade must not be restricted in any way.
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
11
For installation, wiring, and commissioning observe the recognised technical regulations, especially safety and accident prevention regulations.
For any wiring work follow the national and local regulations and guidelines for electrical installation.
Danger!
Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage.
• Only skilled qualified electricians are allowed to work on the electrical system.
• Switch off the power supply before working on any electrical equipment.
Wiring the EM-TRF and EM-TRF-USV
• Never connect two voltages! When the expansion module for 230 V AC is used, do not connect a 24 V AC/DC voltage to the main PCB.
• Connect the 230 V AC supply voltage to the upper terminals.
• Use the lower terminals to connect the supply voltage for the next controller or for the fume cupboard lighting control (EM-LIGHT expansion module).
• Fix all connection cables to the wire clamping bracket in the casing.
The terminals for the supply voltage carry a code that identifies their application:
• L: 230 V AC, live wire
• N: 230 V AC, neutral conductor
• PE: protective earth
Wiring the EM-TRF-USV - contd.
• Connect the cable of the battery pack to the 2-pole socket .
• Be careful when connecting any cables so as to not disconnect inadvertently the measuring tubes of the volume flow controller.
230 V AC
6 Wiring
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (8/2018)
12
EM-TRF-USV – Operating status
LED Operating status
Green, permanent
Mains operation; the battery pack remains fully charged
Green, flashing
Mains operation; the battery pack is being charged
Green-red, flashing
USP operation; thebattery pack is being used (discharged)
Red
Mains operation; the battery pack is defective or not connected
Commissioning
No special commissioning steps are required.
EM-TRF-USV
The preferred function in case of a power failure can be configured. With the standard settings (as delivered) the essential functions for operation will be maintained. The EasyConnect configuration software provides a commissioning wizard that guides users in making project-specific adjustments.
• Maintain standard operation, i.e. control function (factory setting)
• Close the control damper
• Open the control damper
• Hold the last damper blade position
Diagnosis
An LED indicates the operating state of the EM­TRF-USV expansion module.
Maintenance
The EM-TRF and EM-TRF-USV expansion modules do not require any maintenance.
Disposal of the battery pack
The battery pack of the EASYLAB system is a rechargeable Ni-Cd battery pack. Only dispose of batteries in an environmentally sound manner and in compliance with national and local laws and regulations.
Batteries as well as rechargeable battery packs must not be disposed of with household waste. Consumers are required by law to return them for recycling.