The expansion module EM-BAC-MOD is used to integrate the following devices into a BACnet (MS/TP) or a
Modbus (R
the central BMS:
EASYLAB controller TCU3
EASYLAB adapter modules T
TROX UNIVERSAL CONTROLLER
This configuration manual is an addition to the installation manual and contains information on how to configure EM-BAC-MOD as an interface to the central
BMS.
Illustrations in this manual are mainly for information
and may dif
Other applicable documentation
In addition to these instructions, the following documents apply:
Installation manual for expansion module EM-BAC-
MOD
Documentation on
–EASYLAB controller TCU3
–Adapter module TAM
–TROX UNIVERSAL CONTROLLER
Project-specific wiring documents, if any
TROX Technical Service
To ensure that your request is processed as quickly as
possible, please keep the following information ready:
TU) network and in this way connect them to
AM
fer from the actual design of EM-BAC-MOD.
Limitation of liability
The information in this manual has been compiled with
reference to the applicable standards and guidelines,
the state of the art, and our expertise and experience of
many years.
The manufacturer does not accept any liability for damages resulting from:
Non-compliance with this manual
Incorrect use
Operation or handling by untrained individuals
Unauthorised modifications
echnical changes
T
Use of non-approved replacement parts
The actual scope of delivery may differ from the information in this manual for bespoke constructions, additional order options or as a result of recent technical
changes.
The obligations agreed in the order
and conditions, the manufacturer's terms of delivery,
and the legal regulations in effect at the time the contract is signed shall apply.
We reserve the right to make technical changes.
Defects liability
For details regarding defects liability please refer to
Section VI, Warranty Claims, of the Delivery and Payment Terms of TROX GmbH.
The Delivery and Payment Terms of TROX GmbH are
available at www.troxtechnik.com.
, the general terms
Product name
TROX order number
Delivery date
Brief description of the fault
Onlinewww.troxtechnik.com
Phone+49 2845 202-400
Copyright
This document, including all illustrations, is protected by
copyright and pertains only to the corresponding
product.
Any use without our consent may be an infringement of
copyright, and the violator will be held liable for any
damage.
This applies in particular to:
Publishing content
Copying content
ranslating content
T
Microcopying content
Saving content to electronic systems and editing it
Symbols are used in this manual to alert readers to
areas of potential hazard. Signal words express the
degree of the hazard.
DANGER!
Imminently hazardous situation which is due to live
components and which, if not avoided, will result in
death or serious injury due to electrical voltage.
DANGER!
Imminently hazardous situation which, if not avoided,
will result in death or serious injury
NOTICE!
.
Residual risks
Failure of the network interface does not affect the control function of the volume flow controller but does af
data exchange with the central BMS. Safety-related
applications require further precautions.
fect
1.2 Safety signs
The following symbols and signs are usually found in
the work area. They apply to the very location where
they are found.
Electrical voltage
Location where a hazard due to electrical voltage exists.
Earthing
Potentially hazardous situation which, if not avoided,
may result in property damage.
ENVIRONMENT!
Environmental pollution hazard.
1.1 Correct use
Expansion module EM-BAC-MOD provides a BACnet
MS/TP or Modbus R
components as well as for the TROX UNIVERSAL
CONTROLLER.
Use the expansion module for the following devices:
EASYLAB controller TCU3
EASYLAB adapter module TAM
TROX UNIVERSAL CONTROLLER
1.1.1 Incorrect use
Do not use the expansion module for areas of application that are not described in this manual.
Do not use the expansion module:
outdoors
in wet areas
in areas with potentially explosive atmospheres
TU interface for EASYLAB base
This symbol marks all equipotential bonding connection
points on EM-BAC-MOD.
Residual risks
1.3
EM-BAC-MOD is a state-of-the-art product and meets
current safety requirements. Residual risks cannot be
excluded, however, and you should proceed with caution.
Always observe the safety notes in this manual to
reduce health hazards and prevent any hazardous situations.
Electric current
DANGER!
Danger of death due to electric current!
Danger of death if live components are touched.
–Switch off the supply voltage and secure it
against being switched on again before working
on the unit.
–
Only skilled qualified electricians are allowed to
work on live components.
–Equipotential bonding is required.
Expansion module EM-BAC-MOD-015
Page 6
Security
Environmental protection
1.4 Risk of damage to property
Temperature differences
NOTICE!
Risk of damage to property due to large temperature differences
If EM-BAC-MOD has been kept in an unheated area,
condensation may form and damage the electronic
components beyond repair
–Let EM-BAC-MOD warm up to room temperature
before you install it.
Electrostatic charge
NOTICE!
Risk of damage to property due to electrostatic
charge
Electrostatic charge can damage the electronics of
the expansion module.
–Before you remove the expansion module from
its protective wrapping, touch an equipotentially
bonded metal surface, e.g. a water pipe, for electrical earthing.
–
Avoid skin contact with any components or
printed circuits on the expansion module or the
main PCB.
–Wear conductive footwear and antistatic clothing.
.
Any work has to be carried out by individuals who can
be expected to carry out their assigned duties reliably
Individuals whose reaction time is delayed due to
alcohol, drugs or other medication must not carry out
any work.
.
1.7 Environmental protection
The following substances and materials which are
hazardous to the environment are used:
Electrical and electronic parts
Electrical and electronic parts may contain toxic materials and substances. These parts have to be disposed
of separately from other waste, i.e. taken to your local
reuse and recycling centre or disposed of by a specialist
disposal company.
Batteries
Batteries contain toxic heavy metals. They are hazardous waste and must be taken to a hazardous waste
collection point or disposed of by a specialist company.
1.5 System owner's responsibility
System owner's obligations
EM-BAC-MOD is intended for commercial use. The
system owner is therefore subject to the legal obligations of occupational health and safety regulations.
In addition to the safety notes in this manual, the applicable regulations for safety
environmental protection must also be complied with.
, accident prevention and
1.6 Qualified staff
Qualification
The work described in this manual has to be carried out
by individuals with the qualification, training, knowledge
and experience described below:
Network administrator
Network administrators design, install, configure and
maintain the IT infrastructure in companies or organisations.
Expansion module EM-BAC-MOD-016
Page 7
Configuration
2 Configuration
Before you use EM-BAC-MOD as a BACnet or Modbus
interface module, you have to configure it to the actual
application. T
module.
o do so, use the switches on the interface
Communication parameters
4.Use the DIP switch ③ to set the following parame-
ters:
S2 + S3 - Transmission speed EIA-485
S5 + S6 - Parity
S8- Terminal resistor
Ask the responsible specialist consultant for the
values to be set.
Setting the transmission speed for BACnet
BACnetS2S3
9600 BdOffOff
19200 BdOnOff
38400 BdOffOn
76800 BdOnOn
Setting the transmission speed for Modbus
ModbusS2S3
9600 BdOffOff
Fig. 1: EM-BAC-MOD
①
Switch to select BACnet MS/TP or Modbus RTU
protocol
②
Switches to set the network addresses, 01-99
③
DIP switch to set communication parameters
Setting the protocol type
1.Use the slide switch ① to set the BACnet MS/TP
or Modbus R
Setting the network address
2.Use the two address code switches X and Y ② to
set a network address (01 to 99). Address 00 is
reserved for broadcast mode.
A maximum of 32 devices (network addresses)
can be operated on one network segment. Cau-tion: a dif
every device.
Setting the device family
3.If the device is to be used with an EASYLAB/
TROX UNIVERSAL controller or a adapter module
AM, use the DIP switch ③ to set switch S1 to
T
Off.
TU protocol.
ferent network address must be set for
19200 BdOnOff
38400 BdOffOn
57600 BdOnOn
Setting parity
ParityS5S6
NoneOffOff
NoneOnOff
OddOffOn
EvenOnOn
Terminal resistor for EIA-485 network from
rev
. 2
Terminal resistorS8
DisabledOff
EnabledOn
Expansion module EM-BAC-MOD-017
Page 8
Commissioning
Required TCU3 software version
3 Commissioning
Personnel:
Network administrator
Once you have set the configuration switch to adapt
EM-BAC-MOD to the network, the controller and the
network can be commissioned.
Commissioning a BACnet or Modbus network requires
specialist knowledge as well as special network
adapters and software. Only specialist personnel should
do the commissioning.
3.1
Required TCU3 software version
The expansion module EM-BAC-MOD with firmware 4.1
requires the following software versions:
EASYLAB or adapter module TAM
–Software version 8.0 or higher
TROX UNIVERSAL CONTROLLER
–Software version 2.1 or higher
The software version is displayed in the EasyConnect
software, ‘Diagnosis’ , ‘Basic Device’ line.
A product sticker on the main PCB also carries the software version number (only for version 3 or higher).
With earlier software versions there is no data exchange
between the expansion module EM-BAC-MOD and con-
. This means that the network is not able to read
troller
out current values from the controller or to send any
values.
You need not adapt the controller configuration with
the EasyConnect configuration software for the
expansion module to work.
Expansion module EM-BAC-MOD-018
Page 9
Interface information
BACnet interface
4 Interface information
BACnet interface
4.1
Application
The expansion module EM-BAC-MOD supports the following BACnet interface functions in the BACnet protocol settings:
Native BACnet, i.e. the BACnet interface is imple-
mented on the field module (EASYLAB volume flow
controller)
External hardware components such as physical
gateways are not required
BACnet interface documentation includes the fol-
lowing documents: Protocol Implementation Conformance Statement (PICS), BACnet Interoperability
Building Blocks Supported (BIBBS), as well as a
description of the device object and the supported
objects
Abbreviations
EASYLAB:
FH- Fume cupboard controller
RR- Room controller for supply air or extract air
(RS, RE, PC)
RR RMF- Room controller with active room manage-
ment function
EC, SC- Single controller for supply air or extract air
(EC, SC)
TAM- Adapter module
TAM
RMF
WR- Defaults for the volume flow controller or
RD- Data provided by the volume flow con-
TROX UNIVERSAL CONTROLLER:
RS/RE- Volume flow controllers for supply or
RS/RE
RMF
PR*/PD*- Room pressure controller or duct for
PR*/PD*
RMF
- Adapter module with active room management function
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
on page 9
N
N
Expansion module EM-BAC-MOD-0111
Page 12
Interface information
BACnet interface
Analogue Value Objects
In-
DescriptionUnitUnitAcc-
stanc
e
TCU3TAMTROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
1VolflowSetl/s
(87)
2VolflowActl/s
(87)
3VolTotalExhl/s
(87)
4VolTotalSupl/s
(87)
5PressSetpa
(53)
6PressActpa
(53)
7VelocitySetm/s
(74)
8VelocityActm/s
(74)
9WireSen-
sorPos
%
(98)
10DampPos%
(98)
FHRRRR
RMF
EC,SCTAMTAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
xxxxxxxRDN
xxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxRDN
xxxxRDN
xRDN
xRDN
xRDN
xxxxxxxxRDN
11Damp-
PosMax_FH%(98)
12Damp-
PosMin_FH
13Damp-
PosMax_RE%(98)
14Damp-
PosMin_RE
15Damp-
PosMax_TE%(98)
16Damp-
PosMin_TE
17Damp-
PosMax_RS%(98)
18Damp-
PosMin_RS
19VolOffset_T%
20VolOffset_P%
Abbreviations
Ä
on page 9
%
(98)
%
(98)
%
(98)
%
(98)
(98)
(98)
xxxxxxRDN
xxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxWR,RDN
xxWR,RDN
Expansion module EM-BAC-MOD-0112
Page 13
In-
stanc
e
Interface information
BACnet interface
DescriptionUnitUnitAcc-
TCU3TAMTROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
21SystemDe-
vices
–
(95)
22VolflowExhl/s
(87)
23VolflowSupl/s
(87)
24SC_SetPos%
(98)
25SC_GetPos%
(98)
26Damp-
PosMax_EC%(98)
27Damp-
PosMin_EC
%
(98)
28Damp-
PosMax_SC%(98)
29Damp-
PosMin_SC
%
(98)
30Damp-
PosMax_TS%(98)
FHRRRR
RMF
EC,SCTAMTAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
xxxxxxxxxxRDN
xxxxxxxxxWR,RDN
xxxxxxxxxWR,RDN
not used
not used
xxxxxxRDN
xxxxxxRDN
xxxxxxRDN
xxxxxxRDN
xxxxxxRDN
31Damp-
PosMin_TS
32VolflowSet_Rl/s
33PressSet_Rpa
34Volt_AI2volt
35Volt_AI3volt
36Volt_AO2volt
Abbreviations
Ä
on page 9
%
(98)
(87)
(57)
(5)
(5)
(5)
xxxxxxRDN
xxWR,RDN
xxWR,RDN
xxxxxxRDN
xxxxxxRDN
xxxxxxWR,RDN
Expansion module EM-BAC-MOD-0113
Page 14
Interface information
BACnet interface
Binary Value Objects
In-
DescriptionUnitAcc-
stanc
e
TCU3TAMTROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
1LocalAlarm
FHRRRR
RMF
xxxxxxxxxxRD
EC,SCTAMTAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
(COVU)
2SummaryA-
xxxxxxRD
larm (COVU)
3PressAlarm
xxxxxxRD
(COVU)
4ManOP_Dis-
able
1
x
xxxxWR,
RD
5PressSetSelxxWR,
RD
6DI1xxxxxxxxxxRD
7DI2xxxxxxxxxxRD
8DI3xxxxxxxxxxRD
9DI4xxxxxxxxxxRD
10DI5xxxxxxxxxxRD
11DI6xxxxxxxxxxRD
12DO1xxxxxxxxxxRD
13DO2xxxxxxxxxxRD
14DO3xxxxxxxxxxRD
15DO4xxxxxxxxxxRD
16DO5xxxxxxxxxxRD
17DO6xxxxxxxxxxRD
18SC_Alarmnot used
19DO1_SetxxxxxxxxxxWR,
RD
20DO2_SetxxxxxxxxxxWR,
RD
21DO3_SetxxxxxxxxxxWR,
RD
22DO4_SetxxxxxxxxxxWR,
RD
23DO5_SetxxxxxxxxxxWR,
RD
24DO6_SetxxxxxxxxxxWR,
RD
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
on page 9
Expansion module EM-BAC-MOD-0114
Page 15
In-
stanc
e
Interface information
BACnet interface
DescriptionUnitAcc-
TCU3TAMTROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
FHRRRR
EC,SCTAMTAM
RMF
25DO1_SetBy-
xxxxxxxxxxRD
Local
26DO2_SetBy-
xxxxxxxxxxRD
Local
27DO3_SetBy-
xxxxxxxxxxRD
Local
28DO4_SetBy-
xxxxxxxxxxRD
Local
29DO5_SetBy-
xxxxxxxxxxRD
Local
30DO6_SetBy-
xxxxxxxxxxRD
Local
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
on page 9
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
Expansion module EM-BAC-MOD-0115
Page 16
Interface information
Modbus interface
4.2 Modbus interface
Application
The expansion module EM-BAC-MOD supports the following Modbus interface functions in the Modbus protocol settings:
Modbus is an open serial master-slave communica-
tion protocol which has become a de facto standard
for the industry
The master (e.g. central BMS) can address a
number of slaves (EASYLAB volume flow controllers) and use Modbus functions to request information from individual data points
Data access is based on numbered data registers
which the master has to define in order to request
data using Modbus functions
The slave responds by either returning the
requested information or an exception code (error)
Example: The Read Holding Registers func-
tion (register no. 3) returns the volume flow rate
actual value of the addressed controller
General information for a Modbus device can be
read out using the Read Device
Identifikation function
RR RMF- Room controller with active room manage-
ment function
EC, SC- Single controller for supply air or extract air
(EC, SC)
TAM- Adapter module
TAM
RMF
WR- Defaults for the volume flow controller or
RD- Data provided by the volume flow con-
TROX UNIVERSAL CONTROLLER:
RS/RE- Volume flow controllers for supply or
RS/RE
RMF
PR*/PD*- Room pressure controller or duct for
PR*/PD*
RMF
- Adapter module with active room management function
room, from the central BMS
troller or room
extract air
- Volume flow controller with active room
management function
supply or extract air
- Room pressure controller or duct with
active room management function
Abbreviations
EASYLAB:
FH- Fume cupboard controller
RR- Room controller for supply air or extract air
(RS, RE, PC)
Modbus functions
Function no.DesignationMeaning
1 (0x01)Read CoilsRead states of 1 to 8 bits according to bit list
3 (0x03)Read Holding RegistersRead several consecutive registers
4 (0x04)Read Input RegistersRead several consecutive registers
5 (0x05)Write Single CoilWrite state of a single bit
6 (0x06)Write Single RegisterWrite single register
8 (0x08)DiagnosticsCheck Modbus communication
16 (0x10)Write Multiple RegistersWrite several consecutive registers
43 (0x2B)Read Device IdentificationRead identification data for the device
14 (0x0E)Read Device IdentificationRead identification data for the device
Expansion module EM-BAC-MOD-0116
Page 17
Interface information
Modbus interface
Exception codes
CodesDesignationMeaning
1Illegal Function CodeUnknown function or subfunction code
2Illegal Data AddressInvalid register address
3Illegal Data ValueInconsistent coding for number of registers/bytes, data value
Exception codes (error codes) are returned in case of invalid function or register access.
Register list for Read***Registers and Write***Registers functions
RegisterUnitAcc-
TCU3TAMTROX UNIVERSAL
ess
Sup-
COV
Available with equipment function
No.DescriptionFHRRRR-
RMF
EC,SCTAMTAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
0Mode
1ManOP_Disable
1
xxxxWRN
x
1
xxxxWRN
x
2ModeActxxxxxxRDN
3VolflowActxxxxxxxxRDN
4VolflowSetxxxxxxRDN
5VelocityActxRDN
6VelocitySetxRDN
7VolTotalExhxxxxxxxxxxRDN
8VolTotalSupxxxxxxxxxxRDN
9VolOffset_TxxWRN
10VolOffset_PxxWRN
11PressActxxxxRDN
port
12PressSetxxxxRDN
13PressSetSelxxWRN
14DampPosxxxxxxxxRDN
15Damp-
xxxxxxRDN
PosMax_FH V
alue
16Damp-
xxxxxxRDN
PosMax_FH Status
17Damp-
xxxxxxRDN
PosMin_FH V
alue
1
only for individually selected operating mode (stand-alone operation)
Ä
Abbreviations
‘Abbreviations’ on page 9
Expansion module EM-BAC-MOD-0117
Page 18
Interface information
Modbus interface
RegisterUnitAcc-
TCU3TAMTROX UNIVERSAL
No.DescriptionFHRRRR-
RMF
18Damp-
xxxxxxRDN
PosMin_FH Status
19Damp-
xxxxxxxxxxRDN
PosMax_RE V
alue
20Damp-
xxxxxxxxxxRDN
PosMax_RE Status
21Damp-
xxxxxxxxxxRDN
PosMin_RE V
alue
22Damp-
xxxxxxxxxxRDN
PosMin_RE Status
Available with equipment function
EC,SCTAMTAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
ess
Sup-
port
COV
23Damp-
PosMax_TE V
alue
24Damp-
PosMax_TE Status
25Damp-
PosMin_TE V
alue
26Damp-
PosMin_TE Status
27Damp-
PosMax_RS V
alue
28Damp-
PosMax_RS Status
29Damp-
PosMin_RS V
alue
30Damp-
PosMin_RS Status
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
xxxxxxxxxxRDN
31LocalAlarmxxxxxxxxxxRDY
32SummaryAlarmxxxxxxRDY
33PressAlarmxxxxxxRDY
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
‘Abbreviations’ on page 9
Expansion module EM-BAC-MOD-0118
Page 19
Interface information
Modbus interface
RegisterUnitAcc-
TCU3TAMTROX UNIVERSAL
ess
Sup-
COV
Available with equipment function
No.DescriptionFHRRRR-
RMF
EC,SCTAMTAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
34WireSensorPosxRDN
35SwitchPosxRDN
36RoomModeActxxxxxxRDN
37SystemDevicesxxxxxxxxxxRDN
38SunBlindxxxxWRN
39StateDIxxxxxxxxxxRDN
40StateDOxxxxxxxxxxRDN
41VolflowExhxxxxxxxxxWRN
42VolflowSupxxxxxxxxxWRN
43SC_SetLockHigh-
not used
Prio
44SC_GetLockHigh-
not used
Prio
port
45SC_SetPos -
V
alue
46SC_SetPos -
not used
not used
Status
47SC_GetPosnot used
48SC_Alarmnot used
49DampPosMax_EC
- V
alue
50DampPosMax_EC
xxxxxxRDN
xxxxxxRDN
- Status
51DampPosMin_EC
- V
alue
52DampPosMin_EC
xxxxxxRDN
xxxxxxRDN
- Status
53DampPosMax_SC
- V
alue
54DampPosMax_SC
xxxxxxRDN
xxxxxxRDN
- Status
55DampPosMin_SC
- V
alue
xxxxxxRDN
56DampPosMin_SC
xxxxxxRDN
- Status
57DampPosMax_TS
- V
alue
1
only for individually selected operating mode (stand-alone operation)
Ä
Abbreviations
‘Abbreviations’ on page 9
xxxxxxRDN
Expansion module EM-BAC-MOD-0119
Page 20
Interface information
Modbus interface
RegisterUnitAcc-
TCU3TAMTROX UNIVERSAL
ess
Sup-
port
COV
Available with equipment function
No.DescriptionFHRRRR-
RMF
EC,SCTAMTAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
58DampPosMax_TS
xxxxxxRDN
- Status
59DampPosMin_TS
- V
alue
60DampPosMin_TS
xxxxxxRDN
xxxxxxxxxxRDN
- Status
61DO_SetxxxxxxxxxxWRN
62DO_SetByLocalxxxxxxxxxxRDN
63VolflowSet_RxxWR,RDN
64PressSet_RxxWR,RDN
65Volt_AI2xxxxxxRDN
66Volt_AI3xxxxxxRDN
67Volt_AO2xxxxxxWR,RDN
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
‘Abbreviations’ on page 9
Expansion module EM-BAC-MOD-0120
Page 21
Interface information
Data points – detailed description > Input variables
4.3 Data points – detailed description
The following is a detailed description of the information
that each data point provides; input variables and output
variables are described separately:
Name of data point
Access as viewed from the central BMS
WR – Defaults for the volume flow controller or
–
room, from the central BMS
–RD – Data provided by the volume flow con-
troller or room
List of volume flow controller equipment functions
for which the variable is available
–FH – Fume cupboard controller
–RR – Room controller for supply air or extract air
(RS, RE, PC)
–RR RMF – Room controller with active room
management function
–EC, SC – Single controller for supply air or
extract air (EC, SC)
–TAM – Adapter module
–TAM RMF – Adapter module with active room
management function
Unit of measure (applies only to BACnet objects of
type Analogue Value Object)
Function and special functional values with their
meaning
Access to the data point using a BACnet object or
Modbus register
TROX UNIVERSAL CONTROLLER:
RS/RE- Volume flow controllers for supply or
extract air
RS/RE
RMF
PR*/PD*- Room pressure controller or duct for
PR*/PD*
RMF
- Volume flow controller with active room
management function
supply or extract air
- Room pressure controller or duct with
active room management function
4.3.1 Input variables
COVO mode (only BACnet)
BMS access: WR RD
Equipment function: FH, RR, RR with RMF
TAM, TAM with RMF
Function
BACnet control function used to indicate how unsoli-
cited Change of Value notifications (COVU), that are
used to mark some Binary Value Objects, should be
sent
Data point
BACnet: Multistate V
–1 = no broadcast
–2 = local broadcast (only local in the MS/TP net-
work of EM-BAC-MOD)
–3 = global broadcast (in all networks)
alue Object - Instance 1
, EC, SC,
Expansion module EM-BAC-MOD-0121
Page 22
Interface information
Data points – detailed description > Input variables
MODE
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR with RMFM, TAM with RMF
TROX UNIVERSAL
–RE/RS with RMF, PR*/PD* with RMF
Function
FH: Operating mode default setting for a single fume
Output of the volume flow rate setpoint value for the
volume flow controller
Data point
BACnet: Analog V
Modbus: Register 4
alue Object – Instance 1
Expansion module EM-BAC-MOD-0127
Page 28
Interface information
Data points – detailed description > Output variables
VolflowAct
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the volume flow rate actual value of the
volume flow controller
Data point
BACnet: Analog V
Modbus: Register 3
VolTotalExh
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total extract air volume flow rate of an
room
This includes the extract air volume flow rates of all
fume cupboards and extract air contollers as well as
any additional extract air volume flow rates (constant
and variable) from other controllers.
Data point
alue Object – Instance 2
VolTotalSup
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total supply air flow rate of an room
This includes the supply air volume flow rates of all
supply air controllers as well as any additional supply
air volume flow rates (constant and variable).
Data point
BACnet: Analog V
Modbus: Register 8
PressSet
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
–
TROX UNIVERSAL
–PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the dif
value within the system
Data point
BACnet: Analog V
Modbus: Register 12
alue Object – Instance 4
ferential pressure control setpoint
alue Object – Instance 5
BACnet: Analog V
Modbus: Register 7
alue Object – Instance 3
Expansion module EM-BAC-MOD-0128
Page 29
Interface information
Data points – detailed description > Output variables
PressAct
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the dif
value within the system
The actual value is recorded by a differential pres-
sure transducer connected to the RR with RMF or to
AM with RMF.
the T
Data point
BACnet: Analog V
Modbus: Register 11
VelocitySet
BMS access: RD
Equipment function:
EASYLAB
FH
–
TROX UNIVERSAL
–not used
Unit: m/s
Function
Output of the face velocity setpoint value if the fume
cupboard controller is equipped with a face velocity
transducer (FH-VS)
Data point
BACnet: Analog V
Modbus: Register 6
ferential pressure control actual
alue Object – Instance 6
alue Object – Instance 7
VelocityAct
BMS access: RD
Equipment function:
EASYLAB
FH
–
TROX UNIVERSAL
–not used
Unit: m/s
Function
Output of the face velocity actual value if the fume
cupboard controller is equipped with a face velocity
transducer (FH-VS)
Data point
BACnet: Analog V
Modbus: Register 5
WireSensorPos
BMS access: RD
Equipment function:
EASYLAB
FH
–
TROX UNIVERSAL
–not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the sash position of the fume cupboard as
a percentage value between the closed position
(0 %) and the open position (100 %)
(Applies only if the fume cupboard controller is
equipped with a sash distance sensor (FH-DS, FH-
, FH-VD))
DV
Data point
BACnet: Analog V
Modbus: Register 34
alue Object – Instance 8
alue Object – Instance 9
Expansion module EM-BAC-MOD-0129
Page 30
Interface information
Data points – detailed description > Output variables
SystemDevices
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Number of identified EASYLAB system components
Data point
BACnet: Analog V
Modbus Register 37
SC_GetPos
Equipment function: not available
Volt_AI2
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: V DC
Function
Output of the voltage at analogue input AI2
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue V
Modbus: Register 65
alue Object – Instance 21
alue Object – Instance 34
Volt_AI3
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: V DC
Function
Output of the voltage at analogue input AI3
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue V
Modbus: Register 66
LocalAlarm
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of a local alarm for a fume cupboard con-
, extract air controller, supply air controller,
troller
room controller or TAM
Alarm conditions can be defined using the EasyConnect configuration software.
Functional values
alue Object – Instance 35
0 = No local alarm
1 = Local alarm
Data point
BACnet: Binary V
Modbus: Bit list - bit 2 or register 31
Expansion module EM-BAC-MOD-0130
alue Object – Instance 1
Page 31
Interface information
Data points – detailed description > Output variables
SummaryAlarm
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–RE/RS with RMF, PR*/PD* with RMF
Function
Output of a consolidated alarm
An alarm signal is generated when a controller emits
an alarm or fault message.
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Standard configuration: volume flow rate alarm.
Functional values
0 = No consolidated alarm
1 = Consolidated alarm
Data point
DI* (BACnet), StateDI (Modbus)
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Status of digital inputs DI1 – DI6 of the controller or
adapter module
Data point
BACnet:
Binary V
(DI6)
–0 = inactive
–1 = active
Modbus:
Register 39, bit 0 (DI1) – bit 5 (DI6)
–Bit not set = inactive
–Bit set = active
alue Object – Instance 6 (DI1) – Instance 11
BACnet: Binary V
Modbus: Bit list - bit 3 or register 32
PressAlarm
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
–
TROX UNIVERSAL
–RE/RS with RMF, PR*/PD* with RMF
Function
Output of a room pressure alarm when room pres-
sure control is active
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Functional values
0 = No dif
1 = Differential pressure alarm
Data point
BACnet: Binary V
Modbus: Bit list - bit 4 or register 33
ferential pressure alarm
alue Object – Instance 2
alue Object – Instance 3
DO* (BACnet), StateDO (Modbus)
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Status of digital outputs DO1 – DO6 of the controller
or adapter module
Data point
BACnet:
Binary V
17 (DO6)
–0 = inactive
–1 = active
Modbus:
Register 40, bit 0 (DO1) – bit 5 (DO6)
–Bit not set = inactive
–Bit set = active
SC_Alarm
Equipment function: not available
alue Object – Instance 12 (DO1) – Instance
Expansion module EM-BAC-MOD-0131
Page 32
Interface information
Data points – detailed description > Output variables
DO*_SetByLocal (BACnet), DO_SetByLocal
(Modbus)
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Feedback from the controller about switch outputs
DO1 … DO6 used by the controller or adapter
module
Register 62, bit 0 (DO1_Set) – bit 5 (DO6_Set)
–Bit not set = output inactive
–Bit set = output active
DampPosMax_FH
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the widest open damper
1, 2, 4
blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air
Data point
BACnet: Analog V
alue Object – Instance 11 – value
and event state
Modbus: Register 15 (value) and register 16 (event
state)
DampPos
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC
–
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position
1
Data point
BACnet: Analog V
alue Object – Instance 10
Modbus: Register 14
DampPosMin_FH
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the least wide open damper
1, 2, 5
blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air
Data point
BACnet: Analog V
alue Object – Instance 12 – value
and event state
Modbus: Register 17 (value) and register 18 (event
state)
Expansion module EM-BAC-MOD-0132
Page 33
Interface information
Data points – detailed description > Output variables
DampPosMax_RE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
1, 2, 4
blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air
Data point
DampPosMin_RE
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: percentage value in 0.5 % increments
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open
damper blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air
Data point
1, 2, 5
BACnet: Analog V
and event state
Modbus: Register 19 (value) and register 20 (event
state)
alue Object – Instance 13 – value
BACnet: Analog V
and event state
Modbus: Register 21 (value) and register 22 (event
state)
alue Object – Instance 14 – value
Expansion module EM-BAC-MOD-0133
Page 34
Interface information
Data points – detailed description > Output variables
DampPosMax_TE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller
with the widest open damper blade
1, 3, 4
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and
room extract air
For UNIVERSAL: output of the damper blade posi-
tion of the extract air room pressure controller in the
system with the widest open damper blade
1, 3, 4
Data point
DampPosMin_TE
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller
with the least wide open damper blade
1, 3, 5
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and
room extract air
For UNIVERSAL: output of the damper blade posi-
tion of the extract air room pressure controller in the
system with the widest closed damper blade
1, 3, 4
Data point
BACnet: Analog V
alue Object – Instance 15 – value
and event state
Modbus: Register 23 (value) and register 24 (event
state)
BACnet: Analog V
alue Object – Instance 16 – value
and event state
Modbus: Register 25 (value) and register 26 (event
state)
Expansion module EM-BAC-MOD-0134
Page 35
Interface information
Data points – detailed description > Output variables
DampPosMax_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the widest open damper
1, 4
blade
Data point
BACnet: Analog V
alue Object – Instance 17 – value
and event state
Modbus: Register 27 (value) and register 28 (event
state)
DampPosMax_EC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
1, 4
blade
Data point
BACnet: Analog V
alue Object – Instance 26 – value
and event state
Modbus: Register 49 (value) and register 50 (event
state)
DampPosMin_RS
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit:
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the least wide open
damper blade
1, 5
Data point
BACnet: Analog V
alue Object – Instance 18 – value
and event state
Modbus: Register 29 (value) and register 30 (event
state)
DampPosMin_EC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open
damper blade
1, 5
Data point
BACnet: Analog V
alue Object – Instance 27 – value
and event state
Modbus: Register 51 (value) and register 52 (event
state)
Expansion module EM-BAC-MOD-0135
Page 36
Interface information
Data points – detailed description > Output variables
DampPosMax_SC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the widest open damper blade
1, 4
Data point
BACnet: Analog V
alue Object – Instance 28 – value
and event state
Modbus: Register 53 (value) and register 54 (event
state)
DampPosMax_TS
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the widest open
damper blade
1, 4
For UNIVERSAL: output of the damper blade posi-
tion of the supply air duct pressure controller in the
system with the widest open damper blade
1, 3, 4
Data point
DampPosMin_SC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
–
RMF
TROX UNIVERSAL
–not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the least wide open damper blade
1, 5
Data point
BACnet: Analog V
alue Object – Instance 29 – value
and event state
Modbus: Register 55 (value) and register 56 (event
state)
BACnet: Analog V
alue Object – Instance 30 – value
and event state
Modbus: Register 57 (value) and register 58 (event
state)
Expansion module EM-BAC-MOD-0136
Page 37
Interface information
Data points – detailed description > Output variables
DampPosMin_TS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the least wide
open damper blade
1, 5
For UNIVERSAL: output of the damper blade posi-
tion of the supply air duct pressure controller in the
system with the widest closed damper blade
1, 3, 4
Data point
BACnet: Analog V
alue Object – Instance 31 – value
and event state
Modbus: Register 59 (value) and register 60 (event
state)
1
Damper blade positions DampPos**_** are transmitted
as a percentage value between 0% (closed) and 100%
(open).
2
The output variables DampPosMax_FH, DampPosMin_FH, DampPosMax_EC, and DampPosMin_EC,
as well as DampPosMax_RE and DampPosMin_RE are
provided for the evaluation of the damper blade positions in separate extract air systems (3 fans) for fume
cupboards, extract air and room extract air
3
The output variables DampPosMax_TE and Damp-
.
PosMin_TE are provided for the evaluation of the
damper blade positions in the extract air system (1 fan)
for fume cupboards, extract air and room extract air.
4
Status information for damper blade positions DampPosMax_**
BACnet
–
Functional value = 1: All damper blades in
OPEN position (special operating mode,
value = 100%). Override not possible
–Functional value = 2: All damper blades in
standard operating mode. Override possible
–Functional value = 3: At least one damper blade
in OPEN position (special operating mode)
Modbus Register: 16, 20, 24, 28
–Event state = 0: All damper blades in standard
operating mode. Override possible
–Event state = –1 (FF): All damper blades in
OPEN position (special operating mode, value
= 100 %). Override not possible
–Event state = 1: At least one damper blade in
OPEN position (special operating mode)
5
Status information for damper blade positions DampPosMin_**
BACnet
–
Functional value = 1: All damper blades in shutoff mode (special operating mode, value = 0%).
Override not possible
–Functional value = 2: All damper blades in
standard operating mode. Override possible
–Functional value = 3: At least one damper blade
in shut-off mode (special operating mode)
Modbus Register: 18, 22, 26, 30
–Event state = 0: All damper blades in standard
operating mode. Override possible
–Event state = –1 (FF): All damper blades in shut-
off mode (special operating mode, value = 0 %).
Override not possible