Trox Technik EM-BAC-MOD-01 Configuration Manual

Page 1
Configuration manual
Expansion module
EM-BAC-MOD-01
Description of data points for BACnet/MS/TP or
Modbus RTU interface for EASYLAB/TROX UNIVERSAL
Firmware from 4.1 onwards
GB/en
Read the instructions prior to performing any task!
Page 2
TROX GmbH
Heinrich-T
47504 Neukirchen-Vluyn
Germany
Telephone: +49 2845 202-0
Fax: +49 2845 202-265
email: trox@trox.de
Internet: http://www.troxtechnik.com
06/2019
rox-Platz
© TROX GmbH 2017
2
Expansion module EM-BAC-MOD-01
Page 3
Supplemental instructions
About this manual
The expansion module EM-BAC-MOD is used to inte­grate the following devices into a BACnet (MS/TP) or a Modbus (R the central BMS:
EASYLAB controller TCU3 EASYLAB adapter modules T TROX UNIVERSAL CONTROLLER
This configuration manual is an addition to the installa­tion manual and contains information on how to con­figure EM-BAC-MOD as an interface to the central BMS.
Illustrations in this manual are mainly for information and may dif
Other applicable documentation
In addition to these instructions, the following docu­ments apply:
Installation manual for expansion module EM-BAC-
MOD
Documentation on
EASYLAB controller TCU3 – Adapter module TAM – TROX UNIVERSAL CONTROLLER
Project-specific wiring documents, if any
TROX Technical Service
To ensure that your request is processed as quickly as possible, please keep the following information ready:
TU) network and in this way connect them to
AM
fer from the actual design of EM-BAC-MOD.
Limitation of liability
The information in this manual has been compiled with reference to the applicable standards and guidelines, the state of the art, and our expertise and experience of many years.
The manufacturer does not accept any liability for dam­ages resulting from:
Non-compliance with this manual Incorrect use Operation or handling by untrained individuals Unauthorised modifications
echnical changes
T Use of non-approved replacement parts
The actual scope of delivery may differ from the infor­mation in this manual for bespoke constructions, addi­tional order options or as a result of recent technical changes.
The obligations agreed in the order and conditions, the manufacturer's terms of delivery, and the legal regulations in effect at the time the con­tract is signed shall apply.
We reserve the right to make technical changes.
Defects liability
For details regarding defects liability please refer to Section VI, Warranty Claims, of the Delivery and Pay­ment Terms of TROX GmbH.
The Delivery and Payment Terms of TROX GmbH are available at www.troxtechnik.com.
, the general terms
Product name TROX order number Delivery date Brief description of the fault
Online www.troxtechnik.com
Phone +49 2845 202-400
Copyright
This document, including all illustrations, is protected by copyright and pertains only to the corresponding product.
Any use without our consent may be an infringement of copyright, and the violator will be held liable for any damage.
This applies in particular to:
Publishing content Copying content
ranslating content
T Microcopying content Saving content to electronic systems and editing it
Expansion module EM-BAC-MOD-01 3
Page 4
Table of contents
1 Security.............................................................. 5
1.1 Correct use.................................................. 5
1.1.1 Incorrect use............................................. 5
1.2 Safety signs................................................. 5
1.3 Residual risks.............................................. 5
1.4 Risk of damage to property......................... 6
1.5 System owner's responsibility..................... 6
1.6 Qualified staff............................................... 6
1.7 Environmental protection............................. 6
2 Configuration..................................................... 7
3
Commissioning.................................................. 8
3.1 Required TCU3 software version ............... 8
4 Interface information......................................... 9
4.1 BACnet interface......................................... 9
4.2 Modbus interface....................................... 16
4.3 Data points – detailed description............. 21
4.3.1 Input variables........................................ 21
4.3.2 Output variables..................................... 26
5 Index................................................................. 38
Expansion module EM-BAC-MOD-014
Page 5
Security

Residual risks

1 Security

Safety notes
Symbols are used in this manual to alert readers to areas of potential hazard. Signal words express the degree of the hazard.
DANGER!
Imminently hazardous situation which is due to live components and which, if not avoided, will result in death or serious injury due to electrical voltage.
DANGER!
Imminently hazardous situation which, if not avoided, will result in death or serious injury
NOTICE!
.
Residual risks
Failure of the network interface does not affect the con­trol function of the volume flow controller but does af data exchange with the central BMS. Safety-related applications require further precautions.
fect

1.2 Safety signs

The following symbols and signs are usually found in the work area. They apply to the very location where they are found.
Electrical voltage
Location where a hazard due to electrical voltage exists.
Earthing
Potentially hazardous situation which, if not avoided, may result in property damage.
ENVIRONMENT!
Environmental pollution hazard.

1.1 Correct use

Expansion module EM-BAC-MOD provides a BACnet MS/TP or Modbus R components as well as for the TROX UNIVERSAL CONTROLLER.
Use the expansion module for the following devices:
EASYLAB controller TCU3 EASYLAB adapter module TAM TROX UNIVERSAL CONTROLLER

1.1.1 Incorrect use

Do not use the expansion module for areas of applica­tion that are not described in this manual.
Do not use the expansion module:
outdoors in wet areas in areas with potentially explosive atmospheres
TU interface for EASYLAB base
This symbol marks all equipotential bonding connection points on EM-BAC-MOD.
Residual risks
1.3
EM-BAC-MOD is a state-of-the-art product and meets current safety requirements. Residual risks cannot be excluded, however, and you should proceed with cau­tion.
Always observe the safety notes in this manual to reduce health hazards and prevent any hazardous sit­uations.
Electric current
DANGER!
Danger of death due to electric current!
Danger of death if live components are touched.
Switch off the supply voltage and secure it
against being switched on again before working on the unit.
Only skilled qualified electricians are allowed to work on live components.
Equipotential bonding is required.
Expansion module EM-BAC-MOD-01 5
Page 6
Security
Environmental protection

1.4 Risk of damage to property

Temperature differences
NOTICE!
Risk of damage to property due to large tempera­ture differences
If EM-BAC-MOD has been kept in an unheated area, condensation may form and damage the electronic components beyond repair
Let EM-BAC-MOD warm up to room temperature
before you install it.
Electrostatic charge
NOTICE!
Risk of damage to property due to electrostatic charge
Electrostatic charge can damage the electronics of the expansion module.
Before you remove the expansion module from
its protective wrapping, touch an equipotentially bonded metal surface, e.g. a water pipe, for elec­trical earthing.
Avoid skin contact with any components or printed circuits on the expansion module or the main PCB.
Wear conductive footwear and antistatic clothing.
.
Any work has to be carried out by individuals who can be expected to carry out their assigned duties reliably Individuals whose reaction time is delayed due to alcohol, drugs or other medication must not carry out any work.
.

1.7 Environmental protection

The following substances and materials which are hazardous to the environment are used:
Electrical and electronic parts
Electrical and electronic parts may contain toxic mate­rials and substances. These parts have to be disposed of separately from other waste, i.e. taken to your local reuse and recycling centre or disposed of by a specialist disposal company.
Batteries
Batteries contain toxic heavy metals. They are haz­ardous waste and must be taken to a hazardous waste collection point or disposed of by a specialist company.

1.5 System owner's responsibility

System owner's obligations
EM-BAC-MOD is intended for commercial use. The system owner is therefore subject to the legal obliga­tions of occupational health and safety regulations.
In addition to the safety notes in this manual, the appli­cable regulations for safety environmental protection must also be complied with.
, accident prevention and

1.6 Qualified staff

Qualification
The work described in this manual has to be carried out by individuals with the qualification, training, knowledge and experience described below:
Network administrator
Network administrators design, install, configure and maintain the IT infrastructure in companies or organisa­tions.
Expansion module EM-BAC-MOD-016
Page 7
Configuration

2 Configuration

Before you use EM-BAC-MOD as a BACnet or Modbus interface module, you have to configure it to the actual application. T module.
o do so, use the switches on the interface
Communication parameters
4. Use the DIP switch to set the following parame-
ters:
S2 + S3 - Transmission speed EIA-485
S5 + S6 - Parity
S8 - Terminal resistor
Ask the responsible specialist consultant for the values to be set.
Setting the transmission speed for BACnet
BACnet S2 S3
9600 Bd Off Off
19200 Bd On Off
38400 Bd Off On
76800 Bd On On
Setting the transmission speed for Modbus
Modbus S2 S3
9600 Bd Off Off
Fig. 1: EM-BAC-MOD
Switch to select BACnet MS/TP or Modbus RTU protocol
Switches to set the network addresses, 01-99
DIP switch to set communication parameters
Setting the protocol type
1. Use the slide switch to set the BACnet MS/TP
or Modbus R
Setting the network address
2. Use the two address code switches X and Y to
set a network address (01 to 99). Address 00 is reserved for broadcast mode.
A maximum of 32 devices (network addresses) can be operated on one network segment. Cau- tion: a dif every device.
Setting the device family
3. If the device is to be used with an EASYLAB/
TROX UNIVERSAL controller or a adapter module
AM, use the DIP switch to set switch S1 to
T Off.
TU protocol.
ferent network address must be set for
19200 Bd On Off
38400 Bd Off On
57600 Bd On On
Setting parity
Parity S5 S6
None Off Off
None On Off
Odd Off On
Even On On
Terminal resistor for EIA-485 network from rev
. 2
Terminal resistor S8
Disabled Off
Enabled On
Expansion module EM-BAC-MOD-01 7
Page 8
Commissioning

Required TCU3 software version

3 Commissioning

Personnel:
Network administrator
Once you have set the configuration switch to adapt EM-BAC-MOD to the network, the controller and the network can be commissioned.
Commissioning a BACnet or Modbus network requires specialist knowledge as well as special network adapters and software. Only specialist personnel should do the commissioning.
3.1
Required TCU3 software version
The expansion module EM-BAC-MOD with firmware 4.1 requires the following software versions:
EASYLAB or adapter module TAM
Software version 8.0 or higher
TROX UNIVERSAL CONTROLLER
Software version 2.1 or higher
The software version is displayed in the EasyConnect software, ‘Diagnosis’ , ‘Basic Device’ line.
A product sticker on the main PCB also carries the soft­ware version number (only for version 3 or higher).
With earlier software versions there is no data exchange between the expansion module EM-BAC-MOD and con-
. This means that the network is not able to read
troller out current values from the controller or to send any values.
You need not adapt the controller configuration with the EasyConnect configuration software for the expansion module to work.
Expansion module EM-BAC-MOD-018
Page 9
Interface information

BACnet interface

4 Interface information

BACnet interface
4.1
Application
The expansion module EM-BAC-MOD supports the fol­lowing BACnet interface functions in the BACnet pro­tocol settings:
Native BACnet, i.e. the BACnet interface is imple-
mented on the field module (EASYLAB volume flow controller)
External hardware components such as physical
gateways are not required
BACnet interface documentation includes the fol-
lowing documents: Protocol Implementation Con­formance Statement (PICS), BACnet Interoperability Building Blocks Supported (BIBBS), as well as a description of the device object and the supported objects
Abbreviations
EASYLAB:
FH - Fume cupboard controller
RR - Room controller for supply air or extract air
(RS, RE, PC)
RR RMF - Room controller with active room manage-
ment function
EC, SC - Single controller for supply air or extract air
(EC, SC)
TAM - Adapter module
TAM RMF
WR - Defaults for the volume flow controller or
RD - Data provided by the volume flow con-
TROX UNIVERSAL CONTROLLER:
RS/RE - Volume flow controllers for supply or
RS/RE RMF
PR*/PD* - Room pressure controller or duct for
PR*/PD* RMF
- Adapter module with active room manage­ment function
room, from the central BMS
troller or room
extract air
- Volume flow controller with active room
management function
supply or extract air
- Room pressure controller or duct with
active room management function
BACnet PICS (Protocol Implementation Conformance Statement) – Overview
Principal categories Values
Date 2019-04-03
Vendor name TROX GmbH
Vendor identifier 329
Product name EM-BAC-MOD
Model no. M536HD7
Application 4.1
Firmware Revison 4.1
BACnet Protocol Revision 12
Standardised Device Profile BACnet Application Specific Controller (B-ASC)
Segmentation Capability No
Data Link Layer Options MS/TP master (Clause 9), Baudrates 9600, 19200,
38400, 76800
Device Address Binding No
Network Security Options Non-secure device – capable of operating without
BACnet network security
Character Sets Supported ISO 10646 (UTF-8)
Expansion module EM-BAC-MOD-01 9
Page 10
Interface information
BACnet interface
Configuration switches
Hexadecimal Switches X, Y Network address
DIP Switch 1 OFF ON
Controller EASYLAB TCU3 Other
DIP Switch 2 OFF ON OFF ON
DIP Switch 3 OFF OFF ON ON
Baud rate 9600 19200 38400 76800
BIBBS - BACnet Interoperability Building Blocks Supported
Data Sharing-ReadProperty-B DS-RP-B
Data Sharing-WriteProperty-B DS-WP-B
Data Sharing-COV-Unsolicited-B DS-COVU-B
Device Management-Dynamic Device Binding-B DM-DDB-B
Device Management-Dynamic Object Binding-B DM-DOB-B
Device Management-Device Communication Control-B DM-DCC-B
Device Management-ReinitialiseDevice-B DM-RD-B
DeviceObject
Property Value Access
Object identifier Device instance; default instance = 32900 + set network
address
Object name Default="EM-BACnet"; project-specific description can be
entered, 62 characters max.
Object type Device (8) RD
System_Status OPERATIONAL (0) RD
Vendor_Name "TROX GmbH" RD
Vendor_Identifier 329 RD
WR, RD; E
WR, RD; E
Model_Name "EM-BAC-MOD" RD
Description Default = “EASYLAB”; description can be entered, 126 char-
acters max.
Location Default = ""; description can be entered, 62 characters max. WR, RD; E
Firmware_Revision “4.1” (EASYLAB) RD
Application_Software_Version “4.1” (EASYLAB) RD
Protocol_Version 1 RD
Protocol_Revision 12 RD
Protocol Services Supported Who-is, who-has, read-property, write-property, device-com-
munication-control, reinitialise-device
Expansion module EM-BAC-MOD-0110
WR, RD; E
RD
Page 11
Interface information
BACnet interface
Property Value Access
Protocol_Object_Types_Supported DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTI-
ST
ATE_VALUE
Object_List EASYLAB: device, analogue-value 1…36, binary-value 1…
RD
RD
30, multistate-value 1…8
Max_ADPU_Length_Accepted 480 RD
Segmentation_Supported NO_SEGMENTATION (3) RD
APDU_Timeout 10000 RD
Number_Of_APDU_Retries 3 RD
Device_Address_Binding RD
Database_Revision 0 RD
Description Controller Type “EASYLAB” RD
Max_Master Default 127 WR, RD; E
Max_Info_Frames Default 1 WR, RD; E
Multistate Value Objects
In-
stanc
e
Description Unit Acc-
TCU3 TAM TROX UNIVERSAL
ess
Sup-
port
COV
Available with equipment function
FH RR RR
RMF
EC,SCTAM TAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
1 COVU mode x x x x x x x x WR,
RD
2 Mode
1
x
x x x x WR,
RD
3 ModeAct x x x x x x RD N
4 RoomModeAct x x x x x x RD N
5 SwitchPos x RD N
6 Sunblind x x x x WR,
RD
7 SC_SetLock-
not used
HighPrio
8 SC_GetLock-
not used
HighPrio
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
on page 9
N
N
Expansion module EM-BAC-MOD-01 11
Page 12
Interface information
BACnet interface
Analogue Value Objects
In-
Description Unit Unit Acc-
stanc
e
TCU3 TAM TROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
1 VolflowSet l/s
(87)
2 VolflowAct l/s
(87)
3 VolTotalExh l/s
(87)
4 VolTotalSup l/s
(87)
5 PressSet pa
(53)
6 PressAct pa
(53)
7 VelocitySet m/s
(74)
8 VelocityAct m/s
(74)
9 WireSen-
sorPos
% (98)
10 DampPos %
(98)
FH RR RR
RMF
EC,SCTAM TAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
x x x x x x x RD N
x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x RD N
x x x x RD N
x RD N
x RD N
x RD N
x x x x x x x x RD N
11 Damp-
PosMax_FH%(98)
12 Damp-
PosMin_FH
13 Damp-
PosMax_RE%(98)
14 Damp-
PosMin_RE
15 Damp-
PosMax_TE%(98)
16 Damp-
PosMin_TE
17 Damp-
PosMax_RS%(98)
18 Damp-
PosMin_RS
19 VolOffset_T %
20 VolOffset_P %
Abbreviations
Ä
on page 9
% (98)
% (98)
% (98)
% (98)
(98)
(98)
x x x x x x RD N
x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x WR,RDN
x x WR,RDN
Expansion module EM-BAC-MOD-0112
Page 13
In-
stanc
e
Interface information
BACnet interface
Description Unit Unit Acc-
TCU3 TAM TROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
21 SystemDe-
vices
– (95)
22 VolflowExh l/s
(87)
23 VolflowSup l/s
(87)
24 SC_SetPos %
(98)
25 SC_GetPos %
(98)
26 Damp-
PosMax_EC%(98)
27 Damp-
PosMin_EC
% (98)
28 Damp-
PosMax_SC%(98)
29 Damp-
PosMin_SC
% (98)
30 Damp-
PosMax_TS%(98)
FH RR RR
RMF
EC,SCTAM TAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
x x x x x x x x x x RD N
x x x x x x x x x WR,RDN
x x x x x x x x x WR,RDN
not used
not used
x x x x x x RD N
x x x x x x RD N
x x x x x x RD N
x x x x x x RD N
x x x x x x RD N
31 Damp-
PosMin_TS
32 VolflowSet_R l/s
33 PressSet_R pa
34 Volt_AI2 volt
35 Volt_AI3 volt
36 Volt_AO2 volt
Abbreviations
Ä
on page 9
% (98)
(87)
(57)
(5)
(5)
(5)
x x x x x x RD N
x x WR,RDN
x x WR,RDN
x x x x x x RD N
x x x x x x RD N
x x x x x x WR,RDN
Expansion module EM-BAC-MOD-01 13
Page 14
Interface information
BACnet interface
Binary Value Objects
In-
Description Unit Acc-
stanc
e
TCU3 TAM TROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
1 LocalAlarm
FH RR RR
RMF
x x x x x x x x x x RD
EC,SCTAM TAM
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
(COVU)
2 SummaryA-
x x x x x x RD
larm (COVU)
3 PressAlarm
x x x x x x RD
(COVU)
4 ManOP_Dis-
able
1
x
x x x x WR,
RD
5 PressSetSel x x WR,
RD
6 DI1 x x x x x x x x x x RD
7 DI2 x x x x x x x x x x RD
8 DI3 x x x x x x x x x x RD
9 DI4 x x x x x x x x x x RD
10 DI5 x x x x x x x x x x RD
11 DI6 x x x x x x x x x x RD
12 DO1 x x x x x x x x x x RD
13 DO2 x x x x x x x x x x RD
14 DO3 x x x x x x x x x x RD
15 DO4 x x x x x x x x x x RD
16 DO5 x x x x x x x x x x RD
17 DO6 x x x x x x x x x x RD
18 SC_Alarm not used
19 DO1_Set x x x x x x x x x x WR,
RD
20 DO2_Set x x x x x x x x x x WR,
RD
21 DO3_Set x x x x x x x x x x WR,
RD
22 DO4_Set x x x x x x x x x x WR,
RD
23 DO5_Set x x x x x x x x x x WR,
RD
24 DO6_Set x x x x x x x x x x WR,
RD
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
on page 9
Expansion module EM-BAC-MOD-0114
Page 15
In-
stanc
e
Interface information
BACnet interface
Description Unit Acc-
TCU3 TAM TROX UNIVERSAL
Available with equipment function
ess
Sup-
port
COV
FH RR RR
EC,SCTAM TAM
RMF
25 DO1_SetBy-
x x x x x x x x x x RD
Local
26 DO2_SetBy-
x x x x x x x x x x RD
Local
27 DO3_SetBy-
x x x x x x x x x x RD
Local
28 DO4_SetBy-
x x x x x x x x x x RD
Local
29 DO5_SetBy-
x x x x x x x x x x RD
Local
30 DO6_SetBy-
x x x x x x x x x x RD
Local
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
on page 9
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
Expansion module EM-BAC-MOD-01 15
Page 16
Interface information
Modbus interface

4.2 Modbus interface

Application
The expansion module EM-BAC-MOD supports the fol­lowing Modbus interface functions in the Modbus pro­tocol settings:
Modbus is an open serial master-slave communica-
tion protocol which has become a de facto standard for the industry
The master (e.g. central BMS) can address a
number of slaves (EASYLAB volume flow control­lers) and use Modbus functions to request informa­tion from individual data points
Data access is based on numbered data registers
which the master has to define in order to request data using Modbus functions
The slave responds by either returning the
requested information or an exception code (error)
Example: The Read Holding Registers func-
tion (register no. 3) returns the volume flow rate actual value of the addressed controller
General information for a Modbus device can be
read out using the Read Device Identifikation function
RR RMF - Room controller with active room manage-
ment function
EC, SC - Single controller for supply air or extract air
(EC, SC)
TAM - Adapter module
TAM RMF
WR - Defaults for the volume flow controller or
RD - Data provided by the volume flow con-
TROX UNIVERSAL CONTROLLER:
RS/RE - Volume flow controllers for supply or
RS/RE RMF
PR*/PD* - Room pressure controller or duct for
PR*/PD* RMF
- Adapter module with active room manage­ment function
room, from the central BMS
troller or room
extract air
- Volume flow controller with active room management function
supply or extract air
- Room pressure controller or duct with active room management function
Abbreviations
EASYLAB:
FH - Fume cupboard controller
RR - Room controller for supply air or extract air
(RS, RE, PC)
Modbus functions
Function no. Designation Meaning
1 (0x01) Read Coils Read states of 1 to 8 bits according to bit list
3 (0x03) Read Holding Registers Read several consecutive registers
4 (0x04) Read Input Registers Read several consecutive registers
5 (0x05) Write Single Coil Write state of a single bit
6 (0x06) Write Single Register Write single register
8 (0x08) Diagnostics Check Modbus communication
16 (0x10) Write Multiple Registers Write several consecutive registers
43 (0x2B) Read Device Identification Read identification data for the device
14 (0x0E) Read Device Identification Read identification data for the device
Expansion module EM-BAC-MOD-0116
Page 17
Interface information
Modbus interface
Exception codes
Codes Designation Meaning
1 Illegal Function Code Unknown function or subfunction code
2 Illegal Data Address Invalid register address
3 Illegal Data Value Inconsistent coding for number of registers/bytes, data value
Exception codes (error codes) are returned in case of invalid function or register access.
Register list for Read***Registers and Write***Registers functions
Register Unit Acc-
TCU3 TAM TROX UNIVERSAL
ess
Sup-
COV
Available with equipment function
No. Description FH RR RR-
RMF
EC,SCTAM TAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
0 Mode
1 ManOP_Disable
1
x x x x WR N
x
1
x x x x WR N
x
2 ModeAct x x x x x x RD N
3 VolflowAct x x x x x x x x RD N
4 VolflowSet x x x x x x RD N
5 VelocityAct x RD N
6 VelocitySet x RD N
7 VolTotalExh x x x x x x x x x x RD N
8 VolTotalSup x x x x x x x x x x RD N
9 VolOffset_T x x WR N
10 VolOffset_P x x WR N
11 PressAct x x x x RD N
port
12 PressSet x x x x RD N
13 PressSetSel x x WR N
14 DampPos x x x x x x x x RD N
15 Damp-
x x x x x x RD N PosMax_FH ­ V
alue
16 Damp-
x x x x x x RD N PosMax_FH ­ Status
17 Damp-
x x x x x x RD N PosMin_FH ­ V
alue
1
only for individually selected operating mode (stand-alone operation)
Ä
Abbreviations
‘Abbreviations’ on page 9
Expansion module EM-BAC-MOD-01 17
Page 18
Interface information
Modbus interface
Register Unit Acc-
TCU3 TAM TROX UNIVERSAL
No. Description FH RR RR-
RMF
18 Damp-
x x x x x x RD N PosMin_FH ­ Status
19 Damp-
x x x x x x x x x x RD N PosMax_RE ­ V
alue
20 Damp-
x x x x x x x x x x RD N PosMax_RE ­ Status
21 Damp-
x x x x x x x x x x RD N PosMin_RE ­ V
alue
22 Damp-
x x x x x x x x x x RD N PosMin_RE ­ Status
Available with equipment function
EC,SCTAM TAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
ess
Sup-
port
COV
23 Damp-
PosMax_TE ­ V
alue
24 Damp-
PosMax_TE ­ Status
25 Damp-
PosMin_TE ­ V
alue
26 Damp-
PosMin_TE ­ Status
27 Damp-
PosMax_RS ­ V
alue
28 Damp-
PosMax_RS ­ Status
29 Damp-
PosMin_RS ­ V
alue
30 Damp-
PosMin_RS ­ Status
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
x x x x x x x x x x RD N
31 LocalAlarm x x x x x x x x x x RD Y
32 SummaryAlarm x x x x x x RD Y
33 PressAlarm x x x x x x RD Y
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
‘Abbreviations’ on page 9
Expansion module EM-BAC-MOD-0118
Page 19
Interface information
Modbus interface
Register Unit Acc-
TCU3 TAM TROX UNIVERSAL
ess
Sup-
COV
Available with equipment function
No. Description FH RR RR-
RMF
EC,SCTAM TAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
34 WireSensorPos x RD N
35 SwitchPos x RD N
36 RoomModeAct x x x x x x RD N
37 SystemDevices x x x x x x x x x x RD N
38 SunBlind x x x x WR N
39 StateDI x x x x x x x x x x RD N
40 StateDO x x x x x x x x x x RD N
41 VolflowExh x x x x x x x x x WR N
42 VolflowSup x x x x x x x x x WR N
43 SC_SetLockHigh-
not used
Prio
44 SC_GetLockHigh-
not used
Prio
port
45 SC_SetPos -
V
alue
46 SC_SetPos -
not used
not used
Status
47 SC_GetPos not used
48 SC_Alarm not used
49 DampPosMax_EC
- V
alue
50 DampPosMax_EC
x x x x x x RD N
x x x x x x RD N
- Status
51 DampPosMin_EC
- V
alue
52 DampPosMin_EC
x x x x x x RD N
x x x x x x RD N
- Status
53 DampPosMax_SC
- V
alue
54 DampPosMax_SC
x x x x x x RD N
x x x x x x RD N
- Status
55 DampPosMin_SC
- V
alue
x x x x x x RD N
56 DampPosMin_SC
x x x x x x RD N
- Status
57 DampPosMax_TS
- V
alue
1
only for individually selected operating mode (stand-alone operation)
Ä
Abbreviations
‘Abbreviations’ on page 9
x x x x x x RD N
Expansion module EM-BAC-MOD-01 19
Page 20
Interface information
Modbus interface
Register Unit Acc-
TCU3 TAM TROX UNIVERSAL
ess
Sup-
port
COV
Available with equipment function
No. Description FH RR RR-
RMF
EC,SCTAM TAM-
RMF
RS/RERS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
58 DampPosMax_TS
x x x x x x RD N
- Status
59 DampPosMin_TS
- V
alue
60 DampPosMin_TS
x x x x x x RD N
x x x x x x x x x x RD N
- Status
61 DO_Set x x x x x x x x x x WR N
62 DO_SetByLocal x x x x x x x x x x RD N
63 VolflowSet_R x x WR,RDN
64 PressSet_R x x WR,RDN
65 Volt_AI2 x x x x x x RD N
66 Volt_AI3 x x x x x x RD N
67 Volt_AO2 x x x x x x WR,RDN
1
only for individually selected operating mode (stand-alone operation)
Abbreviations
Ä
‘Abbreviations’ on page 9
Expansion module EM-BAC-MOD-0120
Page 21
Interface information
Data points – detailed description > Input variables

4.3 Data points – detailed description

The following is a detailed description of the information that each data point provides; input variables and output variables are described separately:
Name of data point Access as viewed from the central BMS
WR – Defaults for the volume flow controller or
room, from the central BMS
RD – Data provided by the volume flow con-
troller or room
List of volume flow controller equipment functions
for which the variable is available – FH – Fume cupboard controller – RR – Room controller for supply air or extract air
(RS, RE, PC)
RR RMF – Room controller with active room
management function
EC, SC – Single controller for supply air or
extract air (EC, SC) – TAM – Adapter module – TAM RMF – Adapter module with active room
management function
Unit of measure (applies only to BACnet objects of
type Analogue Value Object)
Function and special functional values with their
meaning
Access to the data point using a BACnet object or
Modbus register
TROX UNIVERSAL CONTROLLER:
RS/RE - Volume flow controllers for supply or
extract air
RS/RE RMF
PR*/PD* - Room pressure controller or duct for
PR*/PD* RMF
- Volume flow controller with active room management function
supply or extract air
- Room pressure controller or duct with active room management function

4.3.1 Input variables

COVO mode (only BACnet)
BMS access: WR RD
Equipment function: FH, RR, RR with RMF TAM, TAM with RMF
Function
BACnet control function used to indicate how unsoli-
cited Change of Value notifications (COVU), that are used to mark some Binary Value Objects, should be sent
Data point
BACnet: Multistate V
1 = no broadcast – 2 = local broadcast (only local in the MS/TP net-
work of EM-BAC-MOD)
3 = global broadcast (in all networks)
alue Object - Instance 1
, EC, SC,
Expansion module EM-BAC-MOD-01 21
Page 22
Interface information
Data points – detailed description > Input variables
MODE
BMS access: WR RD
Equipment function:
EASYLAB
FH, RR with RMFM, TAM with RMF
TROX UNIVERSAL
RE/RS with RMF, PR*/PD* with RMF
Function
FH: Operating mode default setting for a single fume
cupboard controller mode default setting (stand-alone operation)
RMF: Operating mode default setting for the entire
room
The valid binding of the input variable results in a
valid operating mode default setting via BACnet or Modbus
The invalid binding or no setting does not lead to
any operating mode default setting in the con­troller or room.
Which operating mode is then used depends on
the default options available on the controller
, only with individual operating
Sunblind
BMS access: WR RD
Equipment function:
EASYLAB
FH, RR with RMF, TAM with RMF
TROX UNIVERSAL
RE/RS with RMF, PR*/PD* with RMF
Function
Control input signal for shading, connected to the
controller or adapter module
Switch outputs DO5 and DO6 will be used This BACnet or Modbus default overrides any other
defaults from the local room control panel
Data point
BACnet: Multistate V
1 = No default – 2 = Close blinds (activate switch output DO6) – 3 = Open blinds (activate switch output DO5)
Modbus: Register 38
0 = Close blinds – 1 = Open blinds – 0xFF = No default
alue Object – Instance 6
Functional values (BACnet / Modbus)
1/0 = No default: The central BMS does not default
an operating mode for the controller or room. The operating mode is set locally
control panel, on the fume cupboard control panel, or using switch contacts.
If the operating mode is not set locally, the controller activates standard mode.
2/1 = Standard mode: Normal operation in the day-
time (in Germany: usually according to DIN 1946, part 7, 25 m³/h extract air per m² main useful floor area)
3/2 = Reduced operation: Low mode in comparison
to standard mode, e.g. as a night-time setback
4/3 = Increased operation: High mode in compar-
ison to standard mode, e.g. in an emergency
5/4 = Shut-off: Shut-off of the volume flow controller,
e.g. to save energy at night or to shut down the system
6/5 = OPEN position: Open position of the volume
flow controller
Data point
BACnet: Multistate V Modbus: Register 0
alue Object – Instance 2
, e.g. on the room
SC_SetLockHighPrio
Equipment function: not available
VolOffset_T
BMS access: WR RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Signalling of an external volume flow rate shift, e.g.
for adjusting the room air change rate or for external temperature control
The shift signal is transferred as a percentage value
of a volume flow rate change range that has been configured in the controller
Data point
BACnet: Analog V Modbus: Register 9
Expansion module EM-BAC-MOD-0122
alue Object – Instance 19
Page 23
Interface information
Data points – detailed description > Input variables
VolOffset_P
BMS access: WR RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100%)
Function
Signalling of a flow rate setpoint shift for external dif-
ferential pressure control
The shift signal is transferred as a percentage value
of a volume flow rate change range that has been configured in the controller
Data point
BACnet: Analog V Modbus: Register 10
VolflowExh
BMS access: WR RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, TAM, TAM with RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Integration of an extract air flow into the room bal-
ance of the system
This default volume flow is considered for all volume
flow calculations (balance and setpoint values)
Data point
BACnet: Analog V Modbus: Register 41
alue Object – Instance 20
alue Object – Instance 22
VolflowSup
BMS access: WR RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, TAM, TAM with RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Integration of a supply air flow into the room balance
of the system
This default volume flow is considered for all volume
flow calculations (balance and setpoint values)
Data point
BACnet: Analog V Modbus: Register 42
SC_SetPos
Equipment function: not available
VolflowSet_R
BMS access: WR RD
Equipment function:
EASYLAB
not used
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Default setting of volume flow rate setpoint (room),
only for standard mode
Data point
BACnet: Analog V Modbus: Register 63
alue Object – Instance 23
alue Object – Instance 32
Expansion module EM-BAC-MOD-01 23
Page 24
Interface information
Data points – detailed description > Input variables
PressSet_R
BMS access: WR RD
Equipment function:
EASYLAB
not used
TROX UNIVERSAL
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Local default setting of room pressure or duct pres-
sure setpoint value
Data point
BACnet: Analog V Modbus: Register 64
Volt_AO2
BMS access: WR RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: V DC
Function
Enabling/disabling manual control Upon enabling manual control the corresponding
symbol appears on the control panel.
Default setting of voltage for analogue output AO2 0 – 10 V DC, in increments of 0.1 V
Data point
alue Object – Instance 33
ManOp_Disable
BMS access: WR RD
Equipment function:
EASYLAB
FH, RR with RMF, TAM with RMF
TROX UNIVERSAL
RE/RS with RMF, PR*/PD* with RMF
Function
Enabling/disabling manual control Upon enabling manual control the corresponding
symbol appears on the control panel.
For further information on manual control please refer to the EASYLAB design manual.
FH: Operating mode default setting for a fume cup-
board controller default setting (stand-alone operation)
RMF: operating mode default setting for the entire
room
Functional values
0: Manual control has been enabled on the control
panel. Operating mode defaults set on DI override BACnet
or Modbus defaults.
1: Manual control has been disabled on the control
panel. Operating mode default settings from BACnet or
Modbus have the highest priority
Data point
BACnet: Binary V Modbus: Bit list - bit 0 or register 1
, only with individual operating mode
.
alue Object – Instance 4
BACnet: Analog V Modbus: Register 67
alue Object – Instance 36
Expansion module EM-BAC-MOD-0124
Page 25
PressSetSel
BMS access: WR RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
not used
Function
Input for switching between two pressure set points
when dif activated (setpoint values stored in the room man­agement function).
Functional values
ferential pressure control of the system is
Interface information
Data points – detailed description > Input variables
0: Use dif 1: Use differential pressure setpoint 2
Data point
BACnet: Binary V Modbus: Bit list - bit 1 or register 13
DO*_Set (BACnet) / DO_Set (Modbus)
BMS access: WR RD
Equipment function:
EASYLAB
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
Function
Control input signal for unused switch outputs DO1
– DO6 of the controller or adapter module
Data point
BACnet: Binary V
(DO1_Set) – Instance 24 (DO6_Set) – 0 = output inactive – 1 = output active
Modbus: Register 61 – bit 0 (DO1_Set) – bit 5
(DO6_Set) – Bit not set = output inactive – Bit set = output active
ferential pressure setpoint 1
alue Object – Instance 5
FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF
with RMF
alue Object – Instance 19
Expansion module EM-BAC-MOD-01 25
Page 26
Interface information
Data points – detailed description > Output variables

4.3.2 Output variables

ReadDeviceIdentification (only Modbus)
BMS access: RD
Equipment function: FH, RR, RR with RMF TAM, TAM with RMF
Function
Provides status information for the Modbus device
Data point
BACnet : see Device Object description
Ä
on page 10
Modbus: Device response
Byte 0: Slave Address 1-99 – Byte 1: Function Code 0x2B – Byte 3: Read Device ID Code 0x01 – Byte 4: Conformity Level 0x01 – Byte 5: More Follows 0x00 – Byte 6: Next Object ID 0x00 – Byte 7: Number of Objects 0x03 – Byte 8: ID: VendorName 0x00 – Byte 9: Obj-Length 9 – Byte 10-18: Obj-Value "TROX GmbH" – Byte 19 ID: ProductCode 0x01 – Byte 20: Obj-Length 23 – Byte 21-43: Obj-Value "EM-BAC-MOD -
EASYLAB" – Byte 44 ID: MajMinRevision 0x02 – Byte 45: Obj-Length 4 – Byte 46-49: Obj-Value "V3.0"
, EC, SC,
ModeAct
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
RE/RS with RMF, PR*/PD* with RMF
Function
Output of the operating mode of the volume flow
controller
For more information on each operating mode see
Ä
the description of the 'Mode' input variable
4.3.1 ‘Input variables’ on page 21 .
Functional values (BACnet / Modbus)
1/0 = No default 2/1 = Standard mode 3/2 = Reduced operation 4/3 = Increased operation 5/4 = Shut-of 6/5 = OPEN position
Data point
BACnet: Multistate V Modbus: Register 2
f
alue Object – Instance 3
Chapter
Expansion module EM-BAC-MOD-0126
Page 27
Interface information
Data points – detailed description > Output variables
RoomModeAct
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of the room operating mode
For more information on each operating mode see
the description of the 'Mode' input variable
Functional values (BACnet / Modbus)
1/0 = No default 2/1 = Standard mode 3/2 = Reduced operation 4/3 = Increased operation 5/4 = Shut-of 6/5 = OPEN position
Data point
BACnet: Multistate V Modbus: Register 36
f
alue Object – Instance 4
SwitchPos
BMS access: RD
Equipment function:
EASYLAB
FH
TROX UNIVERSAL
not used
Function
Output of the current switching step of the fume cup-
board as a numeric value if the fume cupboard con­troller is equipped with switch contacts for 2-point or 3-point control (FH2P
Data point
BACnet:
Multistate V – 1 = invalid state – 2 = switching step 1 – 3 = switching step 2 – 4 = switching step 3
Modbus:
Register 35 – 0 = invalid state – 1 = switching step 1 – 2 = switching step 2 – 3 = switching step 3
SC_GetLockHighPrio
Equipment function: not available
alue Object – Instance 5
, FH-3P)
VolflowSet
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
RE/RS, RE/RS with RMF
Unit: l/s
Function
Output of the volume flow rate setpoint value for the
volume flow controller
Data point
BACnet: Analog V Modbus: Register 4
alue Object – Instance 1
Expansion module EM-BAC-MOD-01 27
Page 28
Interface information
Data points – detailed description > Output variables
VolflowAct
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the volume flow rate actual value of the
volume flow controller
Data point
BACnet: Analog V Modbus: Register 3
VolTotalExh
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total extract air volume flow rate of an
room
This includes the extract air volume flow rates of all fume cupboards and extract air contollers as well as any additional extract air volume flow rates (constant and variable) from other controllers.
Data point
alue Object – Instance 2
VolTotalSup
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total supply air flow rate of an room
This includes the supply air volume flow rates of all supply air controllers as well as any additional supply air volume flow rates (constant and variable).
Data point
BACnet: Analog V Modbus: Register 8
PressSet
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the dif
value within the system
Data point
BACnet: Analog V Modbus: Register 12
alue Object – Instance 4
ferential pressure control setpoint
alue Object – Instance 5
BACnet: Analog V Modbus: Register 7
alue Object – Instance 3
Expansion module EM-BAC-MOD-0128
Page 29
Interface information
Data points – detailed description > Output variables
PressAct
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the dif
value within the system
The actual value is recorded by a differential pres-
sure transducer connected to the RR with RMF or to
AM with RMF.
the T
Data point
BACnet: Analog V Modbus: Register 11
VelocitySet
BMS access: RD
Equipment function:
EASYLAB
FH
TROX UNIVERSAL
not used
Unit: m/s
Function
Output of the face velocity setpoint value if the fume
cupboard controller is equipped with a face velocity transducer (FH-VS)
Data point
BACnet: Analog V Modbus: Register 6
ferential pressure control actual
alue Object – Instance 6
alue Object – Instance 7
VelocityAct
BMS access: RD
Equipment function:
EASYLAB
FH
TROX UNIVERSAL
not used
Unit: m/s
Function
Output of the face velocity actual value if the fume
cupboard controller is equipped with a face velocity transducer (FH-VS)
Data point
BACnet: Analog V Modbus: Register 5
WireSensorPos
BMS access: RD
Equipment function:
EASYLAB
FH
TROX UNIVERSAL
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the sash position of the fume cupboard as
a percentage value between the closed position (0 %) and the open position (100 %)
(Applies only if the fume cupboard controller is equipped with a sash distance sensor (FH-DS, FH-
, FH-VD))
DV
Data point
BACnet: Analog V Modbus: Register 34
alue Object – Instance 8
alue Object – Instance 9
Expansion module EM-BAC-MOD-01 29
Page 30
Interface information
Data points – detailed description > Output variables
SystemDevices
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Number of identified EASYLAB system components
Data point
BACnet: Analog V Modbus Register 37
SC_GetPos
Equipment function: not available
Volt_AI2
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: V DC
Function
Output of the voltage at analogue input AI2 0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue V Modbus: Register 65
alue Object – Instance 21
alue Object – Instance 34
Volt_AI3
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: V DC
Function
Output of the voltage at analogue input AI3 0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue V Modbus: Register 66
LocalAlarm
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of a local alarm for a fume cupboard con-
, extract air controller, supply air controller,
troller room controller or TAM
Alarm conditions can be defined using the EasyCon­nect configuration software.
Functional values
alue Object – Instance 35
0 = No local alarm 1 = Local alarm
Data point
BACnet: Binary V Modbus: Bit list - bit 2 or register 31
Expansion module EM-BAC-MOD-0130
alue Object – Instance 1
Page 31
Interface information
Data points – detailed description > Output variables
SummaryAlarm
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
RE/RS with RMF, PR*/PD* with RMF
Function
Output of a consolidated alarm
An alarm signal is generated when a controller emits
an alarm or fault message.
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Standard configuration: volume flow rate alarm.
Functional values
0 = No consolidated alarm 1 = Consolidated alarm
Data point
DI* (BACnet), StateDI (Modbus)
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Status of digital inputs DI1 – DI6 of the controller or
adapter module
Data point
BACnet:
Binary V (DI6)
0 = inactive – 1 = active
Modbus:
Register 39, bit 0 (DI1) – bit 5 (DI6) – Bit not set = inactive – Bit set = active
alue Object – Instance 6 (DI1) – Instance 11
BACnet: Binary V Modbus: Bit list - bit 3 or register 32
PressAlarm
BMS access: RD
Equipment function:
EASYLAB
RR with RMF, TAM with RMF
TROX UNIVERSAL
RE/RS with RMF, PR*/PD* with RMF
Function
Output of a room pressure alarm when room pres-
sure control is active
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Functional values
0 = No dif 1 = Differential pressure alarm
Data point
BACnet: Binary V Modbus: Bit list - bit 4 or register 33
ferential pressure alarm
alue Object – Instance 2
alue Object – Instance 3
DO* (BACnet), StateDO (Modbus)
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Status of digital outputs DO1 – DO6 of the controller
or adapter module
Data point
BACnet:
Binary V 17 (DO6)
0 = inactive – 1 = active
Modbus:
Register 40, bit 0 (DO1) – bit 5 (DO6) – Bit not set = inactive – Bit set = active
SC_Alarm
Equipment function: not available
alue Object – Instance 12 (DO1) – Instance
Expansion module EM-BAC-MOD-01 31
Page 32
Interface information
Data points – detailed description > Output variables
DO*_SetByLocal (BACnet), DO_SetByLocal (Modbus)
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Feedback from the controller about switch outputs
DO1 … DO6 used by the controller or adapter module
Data point
BACnet:
Binary V
alue Object – Instance 25 (DO1_Setby-
Local) – Instance 30 (DO6_SetbyLocal) – 0 = output inactive – 1 = output active
Modbus:
Register 62, bit 0 (DO1_Set) – bit 5 (DO6_Set) – Bit not set = output inactive – Bit set = output active
DampPosMax_FH
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the widest open damper
1, 2, 4
blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup­board extract air and room extract air
Data point
BACnet: Analog V
alue Object – Instance 11 – value
and event state
Modbus: Register 15 (value) and register 16 (event
state)
DampPos
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position
1
Data point
BACnet: Analog V
alue Object – Instance 10
Modbus: Register 14
DampPosMin_FH
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the least wide open damper
1, 2, 5
blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup­board extract air and room extract air
Data point
BACnet: Analog V
alue Object – Instance 12 – value
and event state
Modbus: Register 17 (value) and register 18 (event
state)
Expansion module EM-BAC-MOD-0132
Page 33
Interface information
Data points – detailed description > Output variables
DampPosMax_RE
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
1, 2, 4
blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup­board extract air and room extract air
Data point
DampPosMin_RE
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: percentage value in 0.5 % increments Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open damper blade
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup­board extract air and room extract air
Data point
1, 2, 5
BACnet: Analog V
and event state
Modbus: Register 19 (value) and register 20 (event
state)
alue Object – Instance 13 – value
BACnet: Analog V
and event state
Modbus: Register 21 (value) and register 22 (event
state)
alue Object – Instance 14 – value
Expansion module EM-BAC-MOD-01 33
Page 34
Interface information
Data points – detailed description > Output variables
DampPosMax_TE
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller with the widest open damper blade
1, 3, 4
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and room extract air
For UNIVERSAL: output of the damper blade posi-
tion of the extract air room pressure controller in the system with the widest open damper blade
1, 3, 4
Data point
DampPosMin_TE
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller with the least wide open damper blade
1, 3, 5
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and room extract air
For UNIVERSAL: output of the damper blade posi-
tion of the extract air room pressure controller in the system with the widest closed damper blade
1, 3, 4
Data point
BACnet: Analog V
alue Object – Instance 15 – value
and event state
Modbus: Register 23 (value) and register 24 (event
state)
BACnet: Analog V
alue Object – Instance 16 – value
and event state
Modbus: Register 25 (value) and register 26 (event
state)
Expansion module EM-BAC-MOD-0134
Page 35
Interface information
Data points – detailed description > Output variables
DampPosMax_RS
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the widest open damper
1, 4
blade
Data point
BACnet: Analog V
alue Object – Instance 17 – value
and event state
Modbus: Register 27 (value) and register 28 (event
state)
DampPosMax_EC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
1, 4
blade
Data point
BACnet: Analog V
alue Object – Instance 26 – value
and event state
Modbus: Register 49 (value) and register 50 (event
state)
DampPosMin_RS
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit:
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the least wide open damper blade
1, 5
Data point
BACnet: Analog V
alue Object – Instance 18 – value
and event state
Modbus: Register 29 (value) and register 30 (event
state)
DampPosMin_EC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open damper blade
1, 5
Data point
BACnet: Analog V
alue Object – Instance 27 – value
and event state
Modbus: Register 51 (value) and register 52 (event
state)
Expansion module EM-BAC-MOD-01 35
Page 36
Interface information
Data points – detailed description > Output variables
DampPosMax_SC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the widest open damper blade
1, 4
Data point
BACnet: Analog V
alue Object – Instance 28 – value
and event state
Modbus: Register 53 (value) and register 54 (event
state)
DampPosMax_TS
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the widest open damper blade
1, 4
For UNIVERSAL: output of the damper blade posi-
tion of the supply air duct pressure controller in the system with the widest open damper blade
1, 3, 4
Data point
DampPosMin_SC
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the least wide open damper blade
1, 5
Data point
BACnet: Analog V
alue Object – Instance 29 – value
and event state
Modbus: Register 55 (value) and register 56 (event
state)
BACnet: Analog V
alue Object – Instance 30 – value
and event state
Modbus: Register 57 (value) and register 58 (event
state)
Expansion module EM-BAC-MOD-0136
Page 37
Interface information
Data points – detailed description > Output variables
DampPosMin_TS
BMS access: RD
Equipment function:
EASYLAB
FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF
TROX UNIVERSAL
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 % Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the least wide open damper blade
1, 5
For UNIVERSAL: output of the damper blade posi-
tion of the supply air duct pressure controller in the system with the widest closed damper blade
1, 3, 4
Data point
BACnet: Analog V
alue Object – Instance 31 – value
and event state
Modbus: Register 59 (value) and register 60 (event
state)
1
Damper blade positions DampPos**_** are transmitted as a percentage value between 0% (closed) and 100% (open).
2
The output variables DampPosMax_FH, Damp­PosMin_FH, DampPosMax_EC, and DampPosMin_EC, as well as DampPosMax_RE and DampPosMin_RE are provided for the evaluation of the damper blade posi­tions in separate extract air systems (3 fans) for fume cupboards, extract air and room extract air
3
The output variables DampPosMax_TE and Damp-
.
PosMin_TE are provided for the evaluation of the damper blade positions in the extract air system (1 fan) for fume cupboards, extract air and room extract air.
4
Status information for damper blade positions Damp­PosMax_**
BACnet
Functional value = 1: All damper blades in OPEN position (special operating mode, value = 100%). Override not possible
Functional value = 2: All damper blades in
standard operating mode. Override possible
Functional value = 3: At least one damper blade
in OPEN position (special operating mode)
Modbus Register: 16, 20, 24, 28
Event state = 0: All damper blades in standard
operating mode. Override possible
Event state = –1 (FF): All damper blades in
OPEN position (special operating mode, value = 100 %). Override not possible
Event state = 1: At least one damper blade in
OPEN position (special operating mode)
5
Status information for damper blade positions Damp­PosMin_**
BACnet
Functional value = 1: All damper blades in shut­off mode (special operating mode, value = 0%). Override not possible
Functional value = 2: All damper blades in
standard operating mode. Override possible
Functional value = 3: At least one damper blade
in shut-off mode (special operating mode)
Modbus Register: 18, 22, 26, 30
Event state = 0: All damper blades in standard
operating mode. Override possible
Event state = –1 (FF): All damper blades in shut-
off mode (special operating mode, value = 0 %). Override not possible
Event state = 1: At least one damper blade in
shut-off mode (special operating mode)
Expansion module EM-BAC-MOD-01 37
Page 38
Index

5 Index

B
BACnet
Modbus.................................................................
16
C
Copyright...................................................................... 3
Correct use................................................................... 5
D
Damage to property..................................................... 6
Defects liability............................................................. 3
E
Electric current............................................................. 5
Electrostatic charge...................................................... 6
Environmental protection
Batteries.................................................................. 6
Electrical and electronic parts................................. 6
Rechargable batteries............................................. 6
H
Hotline.......................................................................... 3
I
Incorrect use................................................................ 5
Interface information
BACnet.................................................................... 9
L
Limitation of liability...................................................... 3
O
Other applicable documentation.................................. 3
Q
Qualification................................................................. 6
R
Residual risks............................................................... 5
S
Security........................................................................ 5
Service......................................................................... 3
Signs............................................................................ 5
Software version.......................................................... 8
Staff.............................................................................. 6
Symbols....................................................................... 5
System owner's obligations.......................................... 6
T
Technical service.......................................................... 3
Temperature differences.............................................. 6
Expansion module EM-BAC-MOD-0138
Page 39
Expansion module EM-BAC-MOD-01 39
Page 40
TROX GmbH
Heinrich-T 47504 Neukirchen-Vluyn Germany
rox-Platz
+49 2845 202-0 +49 2845 202-265 trox@trox.de http://www.troxtechnik.com
© TROX GmbH 2017
Loading...