Trox Technik AWT User Manual

Page 1
03/2017 – DE/en
Ventilation grilles for instal­lation into walls, sills or rec­tangular ducts
Type AWT
Ventilation grille with special profiled blades (rectangular cross section)
■ Nominal sizes 325 × 125 – 1225 × 325 mm
■ Grille face made of aluminium with anodised finish
■ Tested for installation in gymnasiums
■ Front border with countersunk holes, 30 mm wide
Optional equipment and accessories
■ Grille face in RAL CLASSIC colours
■ Installation subframe
X
XAWT
testregistrierung
PD – AWT – 1
Ball impact resistant ventilation grille made of alumi­nium, with fixed horizontal blades
Page 2
Ventilation grilles for installation into walls, sills or rectangular ducts
General information
03/2017 –
AWT
DE/en
Type
AWT General information AWT – 2
Function AWT – 3 Technical data AWT – 6 Quick sizing AWT – 7 Specification text AWT – 8 Order code AWT – 9 Dimensions and weight AWT – 10 Product details AWT – 11 Installation examples AWT – 12 Installation details AWT – 13 Commissioning AWT – 14 Basic information and nomenclature AWT – 15
Application
– Type AWT ventilation grille to be used for
supply air or extract air – For gymnasiums – Meets the requirements for impact resistance
of DIN 18032, part 3 – Directed supply air discharge for mixed flow
ventilation – For variable and constant volume flows – For supply air to room air temperature
differences from –12 to +4 K – For installation in walls, sills and rectangular
ducts
Special characteristics
– Fixed blades – Countersunk holes
Nominal sizes
– Nominal length: 325, 425, 525, 625, 825, 1025,
1225 mm
– Nominal height: 125, 225, 325 mm
Other dimensions upon request
Parts and characteristics
– Rectangular profile border sections with
rounded edges – Fixed horizontal blades – Factory fitted perimeter seal – Vertical centre mullion for nominal lengths over
625 mm
Attachments
– AG, AS, D, DG: For volume flow rate balancing
and for air direction control
Accessories
– Installation subframe: For the fast and simple
installation of ventilation grilles
Construction features
– Robust blades – Front border with countersunk holes
Materials and surfaces
– Border and blades made of aluminium – Border and blades anodised, E6-C-0, natural
colour
– P1: Border and blades powder-coated, RAL
CLASSIC colour
Standards and guidelines
– Sound power level of the air-regenerated noise
measured according to EN ISO 5135
Maintenance
– Maintenance-free as construction and
materials are not subject to wear
– Inspection and cleaning to VDI 6022
Page
PD – AWT – 2
Application
Description
Page 3
Ventilation grilles for installation into walls, sills or rectangular ducts
Function
03/2017 – DE/en
AWT
Functional description
Ventilation grilles are air terminal devices for the supply air and extract air of ventilation and air conditioning systems. They direct the supply air into the room. Ventilation grilles with adjustable blades allow for adapting the discharge direction to the local conditions. The result is a mixed flow ventilation in comfort zones and industrial zones, with good overall room ventilation. Induction slows the airflow down, i.e. the airflow velocity decreases as the distance from the grille increases. The distance at which the airflow velocity reaches a certain defined value, e.g.
0.2 m/s, is called throw distance. The supply air jet from wall grilles that are installed near the ceiling
achieves a larger throw distance than a free jet (from a grille that is not installed near the ceiling). Single grilles, groups of grilles and continuous horizontal runs all achieve different throw distances. In cooling mode it is necessary to take account of the jet deviation towards the occupied zone, which increases as the supply air to room air temperature difference increases and the discharge velocity decreases. In heating mode the supply air jet deviates towards the ceiling. This has no negative effect on the airflow velocity in the occupied zone, but it may affect the complete ventilation of the room.
PD – AWT – 3
Schematic illustration of a ventilation grille with longitudinal blades
①
②
③
①Frontborder ②Longitudinalblades
③Centremullion
Air pattern in cooling mode, with ceiling effect, sectional view
Distancefromceiling≤0.3m
Air pattern in cooling mode, without ceiling effect, sectional view
Distancefromceiling≤0.8m
Page 4
Ventilation grilles for installation into walls, sills or rectangular ducts
Function
03/2017 –
AWT
DE/enPD – AWT – 4
Air pattern with ceiling effect, top view
ls
Air pattern without ceiling effect, top view
ls
Air pattern with ceiling effect, sectional view
ls
Distancefromceiling≤0.3m
Air pattern without ceiling effect, sectional view
ls
Distancefromceiling≤0.8m
Air pattern with ceiling effect, group of grilles, top view
ls
Distancebetweensinglegrilles≥0.15×l
S
Air pattern without ceiling effect, group of grilles, top view
ls
Distancebetweensinglegrilles≥0.2×l
S
Page 5
Ventilation grilles for installation into walls, sills or rectangular ducts
Function
03/2017 – DE/en
AWT
PD – AWT – 5
Several single grilles arranged in a row and with not
much distance between them have the same effect as a continuous horizontal run.
Air pattern, group of grilles, top view
b
b < 0.1 × l
S
Page 6
Ventilation grilles for installation into walls, sills or rectangular ducts
Technical data
03/2017 –
AWT
DE/enPD – AWT – 6
Geometric free area
H
L [mm]
325 425 525 625 825 1025 1225
A
geo
mm m² 125 0.013 0.018 0.023 0.028 0.037 0.047 0.057 225 0.031 0.042 0.054 0.065 0.087 0.109 0.132 325 0.066 0.084 0.102 0.136 0.171 0.206
Effective air discharge area (supply air)
H
L [mm]
325 425 525 625 825 1025 1225
A
eff
mm m² 125 0.015 0.020 0.025 0.031 0.040 0.050 0.060 225 0.031 0.040 0.050 0.060 0.078 0.097 0.116 325 0.060 0.073 0.086 0.116 0.152 0.174
Effective area of extract air grille
H
L [mm]
325 425 525 625 825 1025 1225
A
eff
mm m² 125 0.011 0.015 0.018 0.023 0.029 0.036 0.043 225 0.023 0.029 0.036 0.043 0.057 0.071 0.078 325 0.043 0.052 0.063 0.083 0.104 0.122
Nominal sizes 325 × 125 to 1225 × 325 mm Minimum volume flow rate 17 – 275 l/s or 61 – 990 m³/h Maximum volume flow rate, with LWA max. 40 dB(A)
without attachments
95 – 950 l/s or 342 – 3420 m³/h
Supply air to room air temperature difference –12 to +4 K
Volume flow rates apply to supply air
Page 7
Ventilation grilles for installation into walls, sills or rectangular ducts
Quick sizing
03/2017 – DE/en
AWT
PD – AWT – 7
× LWA = 40 dB(A) with unrestricted airflow+ LWA = 40 dB(A) with airflow restricted by 50 %
AWT, volume flow rate ranges
1225 × 325
1025 × 325
825 × 325
625 × 325
525 × 325
425 × 325
1225 × 225
1025 × 225
825 × 225
625 × 225
525 × 225
425 × 225
325 × 225
1225 × 125
1025 × 125
825 × 125
625 × 125
525 × 125
425 × 125
325 × 125
225 × 125
m3/h60 200100 500 1000 2000 5000
l/s15 20 50 100 200 500 1000 1500
Nenngröße
Page 8
Ventilation grilles for installation into walls, sills or rectangular ducts
Specification text
03/2017 –
AWT
DE/en
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Ball impact resistant ventilation grilles, rectangular, made of aluminium, for supply and extract air. Rectangular profile border sections with rounded edges Preferably for wall and sill installation but also suitable for rectangular ducts. Ready-to-install component which consists of a border and fixed horizontal blades. Countersunk holes for fixing the grille to the installation surface. Meets the requirements of DIN 18032, part 3. Sound power level of the air-regenerated noise measured according to EN ISO 5135.
Special characteristics
– Fixed blades – Countersunk holes
Materials and surfaces
– Border and blades made of aluminium – Border and blades anodised, E6-C-0, natural
colour
– P1: Border and blades powder-coated, RAL
CLASSIC colour
Technical data
– Nominal sizes: 325 × 125 to 1225 × 325 mm – Minimum volume flow rate (supply air):
17 – 275 l/s or 61 – 990 m³/h
– Maximum volume flow rate (supply air), at LWA
max. 40 dB(A) without attachments: 95 – 950 l/ s or 342 – 3420 m³/h
– Supply air to room air temperature difference:
–12 to +4 K
Sizing data
–  ____________ _______________________
[m³/h]
– Δpt ___________ _______________________
[Pa] Air-regenerated noise – LWA ___________ _______________________
[dB(A)]
PD – AWT – 8
Page 9
Ventilation grilles for installation into walls, sills or rectangular ducts
Order code
03/2017 – DE/en
AWT
PD – AWT – 9
AWT
AWT – AG / 825×225 / A1 / P1 – RAL ...
Type
AWT Single grille
Attachments
A Without (grille face only) AG Damper unit, opposed action blades D Air direction control, blades installed at 90°
to the front blades, independently adjustable
DG D combined with AG
Nominalsize[mm]
L × H
Installationsubframe
No entry: none A1 With
Exposedsurface
No entry: anodised, E6-C-0, natural colour P1 Powder-coated, specify RAL CLASSIC
colour
Gloss level RAL 9010 50 % RAL 9006 30 % All other RAL colours 70 %
Order example: AWT-AG/625×225/A1
Attachments Damper unit, opposed action blades Nominal size 625 × 225 mm Installation subframe With installation subframe Exposed surface Anodised, E6-C-0, natural colour
Page 10
Ventilation grilles for installation into walls, sills or rectangular ducts
Dimensions and weight
03/2017 –
AWT
DE/en
The weight table shows the available nominal sizes
PD – AWT – 10
AWT
H
L [mm]
325 425 525 625 825 1025 1225
m mm kg 125 1.3 1.6 2.0 2.3 3.0 3.6 4.3 225 1.9 2.4 2.9 3.4 4.4 5.4 6.4 325 3.2 3.8 4.5 5.8 7.1 8.5
Weights apply to ventilation grilles without attachments
AT, 30 mm wide front border
16,7
H + 5
H + 27
30
L + 27
45
7
30
L Nominal length
Vertical centre mullion if L > 625 mm
H Nominal height
Page 11
Ventilation grilles for installation into walls, sills or rectangular ducts
Product details
03/2017 – DE/en
AWT
PD – AWT – 11
AWT blade
25
9
Front border, 30 mm
52
7
30
Page 12
Ventilation grilles for installation into walls, sills or rectangular ducts
Installation examples
03/2017 –
AWT
DE/enPD – AWT – 12
Nominal length over 625 mm: with vertical centre mullion
Wall installation
Page 13
Ventilation grilles for installation into walls, sills or rectangular ducts
Installation details
03/2017 – DE/en
AWT
Installation and commissioning
– Installation preferably in walls, sills and
rectangular ducts
– Installation with installation subframe is
recommended
– If no installation subframe is used, the border
should be fixed with screws
These are only schematic diagrams to illustrate installation details.
PD – AWT – 13
Page 14
Ventilation grilles for installation into walls, sills or rectangular ducts
Commissioning
03/2017 –
AWT
DE/en
Volume flow rate balancing
When several ventilation grilles are installed on the same duct, it may be necessary to balance the volume flow rates. – AG: Damper unit with opposed action blades,
adjustable, secured with a locking screw
– AS: Damper unit with hit and miss damper,
adjustable, secured with a locking screw
Air pattern
– Adjustable blades: Set the air control blades
individually or together and depending on the local conditions
– D, DG: Air control blades, fitted at 90° to the
front blades, can be adapted to the local conditions
PD – AWT – 14
Attachments -AG, -DG and Types AGW, DGW
Attachments -AS, -KS, -RS and Type ASW
Volume flow rate balancing -*G
X X
Volume flow rate balancing -S
X
X
Page 15
Ventilation grilles for installation into walls, sills or rectangular ducts
Basic information and nomenclature
03/2017 – DE/en
AWT
Principal dimensions
L [mm]
Nominal length of the ventilation grille
H [mm]
Nominal height of the ventilation grille
m [kg]
Weight
Nomenclature
LWA [dB(A)]
Sound power level of the air-regenerated noise
[m³/h]and[l/s]
Volume flow rate
Δpt [Pa]
Total differential pressure
lS [m]
Distance from single grille or horizontal run section (throw distance)
PD – AWT – 15