Installation
Take off the controls enclosure lid; to do so, loosen and
remove the M5 pozi screws from the front of the
enclosure, then remove the lid.
Connect the unit according to the wiring diagram.
Refer to TROX wiring diagram within controls
enclosure on each unit (as shown above).
Use sheathed cable, ensuring the cable is suitably
secured and supported (e.g. cable gland). A
Ø20mm hole is provided for mains electrical entry
to the controls enclosure.
The unit voltage rating will be specified on the
rating label inside the controls enclosure, either:
230Vac, 1ph, 50-60Hz
or
400Vac, 3ph, 50-60Hz
Making electrical connections professionally:
Check and ensure that the actual supply voltage
is as indicated by the unit rating label fixed inside
the controls enclosure.
Ensure that the unit has been correctly earthed.
Check that the controls enclosure lid is installed
and securely fastened.
The unit and controls must remain completely
accessible for maintenance.
Communications, network and BMS wiring
should be separated from power, controls and
signal wiring.
If the units have been stored for more than 3
months, all electrical terminals should be
checked and insulation resistance checks must
be carried out.
Check the insulation resistance of the heating
elements is greater than 1MΩ.
All wiring must comply with local wiring
regulations. The factory made internal wiring
complies with BS 7671: IET Wiring Regulations
5 Initial commissioning
Personnel:
Skilled qualified electrician
5.1 Unit inspection
Before initial commissioning:
Remove protective film, if any.
Ensure that the unit is clean, and clean if
necessary.
Check and ensure that the actual supply voltage
is in accordance with the unit electrical rating
label.
Ensure that the unit has been correctly earthed.
5.2 Initial start up
Standalone Electric Heater Units Type TVZ
9
Danger of electric shock! Do not touch any live
components! Electrical equipment carries a
dangerous electrical voltage.
Only skilled qualified electricians are allowed
to work on the electrical system.
Isolate the power supply before working on
any electrical equipment.
DANGER!
The unit must not be energised until all initial
commissioning checks have been completed
satisfactorily.
Rectification works to correct incomplete
initial commissioning checks should be
carried out by skilled, qualified operatives.
CAUTION!
Once all unit inspection checks have been
completed and any issues identified are
rectified, the unit must have the minimum airflow
flowing before it can be energized.
CAUTION!