Trox EK-JZ Installation And Operating Manual

Installation and operating manual
GB/en
Smoke control damper
Type EK-JZ
according to EN12101-8
Declaration of performance DoP / EK-JZ / 001
Read the instructions prior to performing any task!
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
Phone: +49 (0) 2845 2020
Fax: +49 (0) 2845 202-265
E-mail: trox@trox.de
Internet: http://www.troxtechnik.com
A00000062392, 2, GB/en
04/2017
2
© 2017
Smoke control damper T
ype EK-JZ
General information
General information
About this manual
This operating and installation manual enables oper­ating or service personnel to correctly install the TROX product described below and to use it safely and effi­ciently.
This operating and installation manual is intended for use by fitting and installation companies, in-house tech­nicians, technical staf qualified electricians or air conditioning technicians.
It is essential that these individuals read and fully under­stand this manual before starting any work. The basic prerequisite for safe working is to comply with the safety notes and all instructions in this manual.
The local regulations for health and safety at work and general safety regulations also apply.
This manual must be given to the system owner when handing over the system. The system owner must include the manual with the system documentation. The manual must be kept in a place that is accessible at all times.
Illustrations in this manual are mainly for information and may differ from the actual design.
f, properly trained persons, and
Limitation of liability
The information in this manual has been compiled with reference to the applicable standards and guidelines, the state of the art, and our expertise and experience of many years.
The manufacturer does not accept any liability for dam­ages resulting from:
Non-compliance with this manual Incorrect use Operation or handling by untrained individuals Unauthorised modifications
echnical changes
T Use of non-approved replacement parts
The actual scope of delivery may differ from the infor­mation in this manual for bespoke constructions, addi­tional order options or as a result of recent technical changes.
The obligations agreed in the order, the general terms and conditions, the manufacturer's terms of delivery, and the legal regulations in effect at the time the con­tract is signed shall apply.
We reserve the right to make technical changes.
Copyright
This document, including all illustrations, is protected by copyright and pertains only to the corresponding product.
Any use without our consent may be an infringement of copyright, and the violator will be held liable for any damage.
This applies in particular to:
Publishing content Copying content
ranslating content
T Microcopying content Saving content to electronic systems and editing it
TROX Technical Service
To ensure that your request is processed as quickly as possible, please keep the following information ready:
Product name TROX order number Delivery date Brief description of the fault
Defects liability
For details regarding defects liability please refer to Section VI, Warranty Claims, of the Delivery and Pay­ment Terms of TROX GmbH.
The Delivery and Payment Terms of TROX GmbH are available at www.troxtechnik.com.
Online www.troxtechnik.com
Phone +49 2845 202-400
Smoke control damper Type EK-JZ 3
General information
Safety notes
Symbols are used in this manual to alert readers to areas of potential hazard. Signal words express the degree of the hazard.
DANGER!
Imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING!
Potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION!
Potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
NOTICE!
Potentially hazardous situation which, if not avoided, may result in property damage.
Safety notes as part of instructions
Safety notes may refer to individual instructions. In this case, safety notes will be included in the instructions and hence facilitate following the instructions. The above listed signal words will be used.
Example:
1. Untighten the screw.
2.
CAUTION!
Danger of finger entrapment when closing the lid.
Be careful when closing the lid.
3. Tighten the screw.
Specific safety notes
The following symbols are used in safety notes to alert you to specific hazards:
Warning signs Type of danger
Warning – danger zone.
ENVIRONMENT!
Environmental pollution hazard.
Tips and recommendations
Useful tips and recommendations as well as informa­tion for efficient and fault-free operation.
Smoke control damper Type EK-JZ4
1 Safety.................................................................. 6
1.1 General safety notes................................... 6
1.2 Correct use.................................................. 6
1.3 Qualified staff............................................... 6
2 Technical data.................................................... 7
2.1 General data................................................ 7
2.2 Dimensions and weight............................... 8
2.3 Open/Close actuators................................ 10
3 Transport and storage..................................... 11
4 Parts and function........................................... 13
5
Installation........................................................ 14
5.1 Installation situations................................. 14
5.2 Safety notes on installation....................... 14
5.3 General installation information................. 14
5.3.1 After installation...................................... 15
5.4 Solid walls................................................. 16
5.4.1 Installation in shaft walls......................... 16
5.4.2 Installation in solid walls ........................ 18
5.4.3 Installation on shaft walls....................... 20
5.5 Fire-resistant smoke extract ducts............ 22
5.5.1 Installation on vertical smoke extract
ducts....................................................... 22
5.5.2 Installation on horizontal smoke extract
ducts....................................................... 24
5.5.3 Installation in horizontal smoke extract
ducts....................................................... 26
5.5.4 Installation at the end of horizontal
smoke extract ducts............................... 28
5.6 Suspending the smoke control damper..... 30
5.6.1 General................................................... 30
5.6.2 Fixing to the ceiling slab......................... 30
5.6.3 Suspending the smoke control damper.. 30
6 Connecting the smoke extract duct............... 31
6.1 Smoke extract ducts.................................. 31
6.2 Cover grille................................................ 32
6.3 Inspection access...................................... 32
7 Electrical connection...................................... 33
8 Commissioning/functional test...................... 37
8.1 Commissioning.......................................... 37
8.2 Functional test........................................... 37
9 Maintenance..................................................... 38
10 Decommissioning, removal and disposal..... 40
11 Index................................................................. 41
Table of contents
Smoke control damper Type EK-JZ 5
Safety
Qualified staff

1 Safety

1.1 General safety notes

Sharp edges, sharp corners and thin sheet metal parts
CAUTION!
Danger of injury from sharp edges, sharp cor­ners and thin sheet metal parts!
Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes.
Be careful when carrying out any work. – Wear protective gloves, safety shoes and a hard
hat.
Electrical voltage
DANGER!
Danger of electric shock! Do not touch any live com­ponents! Electrical equipment carries a dangerous electrical voltage.
Only skilled qualified electricians are allowed to
work on the electrical system.
Switch off the power supply before working on
any electrical equipment.

1.2 Correct use

Type EK-JZ smoke control dampers are used in
smoke and heat exhaust systems to remove smoke and heat. They may be used with the following sys­tems:
pressurisation systems
natural smoke and heat exhaust systems
– – heat exhaust systems
Operation of smoke control dampers is allowed only
in compliance with installation regulations and the technical data in this installation and operating manual.
Modifying the smoke control damper or using
replacement parts that have not been approved by TROX is not permitted.
Incorrect use
WARNING!
Danger due to incorrect use!
Incorrect use of the smoke control damper can lead to dangerous situations.
Never use the smoke control damper:
in areas with potentially explosive atmospheres – outdoors without suf
effects of weather
in atmospheres where chemical reactions,
whether planned or unplanned, may cause damage to the smoke control damper or lead to corrosion
ficient protection against the

1.3 Qualified staff

WARNING!
Danger of injury due to insufficiently qualified individuals!
Incorrect use may cause considerable injury or damage to property.
Only skilled qualified personnel must carry out
work.
The following degrees of qualification are required for the work described in the operating manual:
Skilled qualified electrician
Skilled qualified electricians are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to work on elec­trical systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.
Specialist personnel
Specialist personnel are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to carry out their assigned duties, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.
Smoke control damper Type EK-JZ6

2 Technical data

2.1 General data

Nominal sizes B x H 200 × 430 – 1200 × 2030 mm
Casing length 250 mm
Volume flow rate range up to 24361 l/s
up to 87700 m³/h
Differential pressure range Pressure level 2, -1000...500 Pa
Operating temperature at least -30 °C to 50 °C
Upstream velocity ≤ 10 m/s with the maximum size
>10...15 m/s with smaller sizes, up to 87700 m³/h
Closed blade air leakage EN 1751, Class 4
Casing air leakage EN 1751, Class C
Technical data
General data
EC conformity
Declaration of performance DoP / EK-JZ / 001
Rating plate
EU Construction Products Regulation EN 12101-8 – Smoke and heat control systems –
Smoke control dampers
EN 1366-10 – Fire resistance tests for service installa-
tions – Smoke control dampers
EN 1366-2 – Fire resistance tests for service installa-
tions – Part 2: Fire dampers
EN 13501-4 – Fire classification of construction products
and building elements – Fire resistance tests on compo­nents of smoke control
EN 1751 – V
devices
no. 305/201
entilation for buildings – Air terminal
1
Fig. 1: Smoke control damper rating plate (example)
CE mark
Manufacturer's address
No. of the declaration of performance
Type
The last two digits of the year in which the CE marking was affixed
Smoke control damper Type EK-JZ 7
Year of manufacture
W
ebsite from which the DoP can be downloaded
Regulated characteristics; the fire resistance class depends on the application and may vary
Number of the European standard and year of its publication
Notified body
Technical data
Dimensions and weight

2.2 Dimensions and weight

Fig. 2: EK-JZ
B x H = nominal size = area exposed to the airflow
Subframe for connection to the duct (steel, operating side only Keep clear to provide access to the actuator encasing
, optional)
Smoke control damper Type EK-JZ8
Installation side
Operating side
Technical data
Dimensions and weight
Dimensions [mm] Number
B H C Blades Handles
200..1200
(50 mm)
B
[mm]
200 29 37 46 54 62 71 79 87 95
250 31 39 48 56 65 73 82 91 99
300 32 41 50 59 67 76 85 94 103
430 630 830 1030 1230 1430 1630 1830 2030
430 2 1
630 3 1
830 4 1
1030 5 1
1230 6 1
1430 550 7 2
1630 650 8 2
1830 9 2
2030 10 2
Weight [kg]
H [mm]
350 33 43 53 61 70 79 88 98 107
400 35 44 54 63 73 82 92 101 111
450 36 46 56 66 75 85 95 105 114
500 38 48 58 68 78 88 98 108 118
550 39 50 61 70 81 91 101 112 122
600 41 51 62 73 83 94 105 115 126
650 42 53 64 75 86 97 108 119 130
700 44 55 66 77 89 100 111 122 134
750 45 57 69 80 91 103 114 126 137
800 47 58 70 82 94 106 118 129 141
850 48 60 72 84 97 109 121 133 145
900 49 62 75 87 99 112 124 136 149
950 51 64 77 89 102 115 127 140 153
1000 52 65 78 91 104 117 130 143 156
1050 54 67 80 94 107 120 134 147 160
1100 55 69 83 96 110 123 137 150 164
1150 57 71 85 98 112 126 140 154 168
1200 58 72 87 101 115 129 143 158 172
Smoke control damper Type EK-JZ 9
Technical data
Open/Close actuators

2.3 Open/Close actuators

Open/Close actuator BLE...
Construction 230-12 TR 24-12-ST TR
Supply voltage 230 V AC 50/60 Hz 24 V AC 50/60 Hz /
24 V DC
Power rating Opening and closing 5 W 7.5 W
Hold position < 1 W < 0.5 W
Rating 12 VA, Imax. 2.7 A at 5 ms 9 VA, Imax. 2.7 A at 5 ms
Running time < 30 s (90°)
Limit switch Type of contact 2 changeover contacts
Switching voltage 5 V DC...250 V AC
Switching current 1 mA...3 A
IEC protection class II III
Protection level IP 54
Open/Close actuator BE...
Construction 230-12 TR 24-12-ST TR
Supply voltage 230 V AC 50/60 Hz 24 V AC 50/60 Hz /
24 V DC
Power rating Opening and closing 8 W 12 W
Hold position 0.5 W
Rating 15 VA, Imax. 7.9 A at 5 ms 18 VA, Imax. 8.2 A at 5 ms
Running time < 60 s (90°)
Limit switch Type of contact 2 changeover contacts
Switching voltage 5 V DC…250 V AC
Switching current 1 mA…6 A
IEC protection class II III
Protection level IP 54
Smoke control damper Type EK-JZ10
Transport and storage

3 Transport and storage

Delivery check
Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, contact the ship­ping company and your supplier immediately.
A complete shipment includes:
Smoke control damper(s)
Attachments/accessories, if any
Installation and operating manual (one per ship-
ment)
Transport on site
If possible, take the smoke control damper in its trans­port packaging up to the installation location.
Smaller dampers can be lifted and placed in the installa­tion opening by two people. Ask someone to give you a hand.
Dampers which are supplied with U channel sections as a transport aid have to be moved with suitable lifting equipment, e.g. a forklift truck.
1. Unpack the damper and place it upright on the floor. Do not remove the straps yet.
2. Place the U channel sections between the upper­most blade and the frame.
3. Move the fork carefully underneath the uppermost blade, then lift it. Put a piece of wood or anything similar between the blade and the fork so as not to damage the blade.
Smoke control damper Type EK-JZ 11
Transport and storage
Carefully lift the smoke control damper with the forklift truck and place it in the installation opening.
4. Once you have installed the smoke control damper, remove the straps; in case of mortar­based installation, remove the straps only after the mortar has cured. Remove the corner protectors. Dispose of the straps and corner protectors.
Storage
If the unit has to be stored temporarily:
Remove any plastic wrapping. Protect the unit from dust and contamination. Store the unit in a dry place and away from direct
sunlight.
Do not expose the unit to the ef
even in its packaging).
Do not store the unit below -30 °C or above 50 °C.
Packaging
Properly dispose of packaging material.
fects of weather (not
Smoke control damper Type EK-JZ12
Parts and function

4 Parts and function

Smoke control dampers are used in mechanical smoke extract systems. They are used for extracting smoke gases and for providing additional supply air to one or more fire compartments.
Smoke control dampers are made from calcium silicate boards, and the electric actuator and the optional con­trol module are encased such that the functional relia­bility is ensured even in the event of a fire.
Regular maintenance of the smoke control damper is required to ensure its functional reliability
nance’ on page 38.
Fig. 3: EK-JZ smoke control damper
Casing
Blades
Blade tip seal (special profile seal)
Side seal
Travel stop, bottom
Rating plate
Actuator
Cover fixing
Linkage
Actuator encasing
Cover of the actuator encasing (sectional view)
Handle (to remove the cover)
Travel stop, top
Ä
9 ‘Mainte-
Smoke extract
Fig. 4: Smoke extract system
EK-JZ in a solid shaft wall
EK-JZ in a solid wall
EK-JZ on a solid shaft wall
Installation on a vertical smoke extract duct (shaft)
Installation on horizontal smoke extract ducts
Installation in horizontal smoke extract ducts
Installation at the end of horizontal smoke extract ducts
EK-JZ as additional supply air inlet
Cover grille
During normal operation Type EK-JZ smoke control dampers remain closed. For smoke extract, the smoke control dampers in the affected fire compartment fully open such that smoke can be extracted. All other smoke control dampers remain closed.
In the event of a fire, smoke control dampers that are used as additional supply air inlets in the affected fire compartment also open such that smoke can be extracted. T free from smoke, smoke control dampers used as addi­tional supply air inlets should be installed near the ground.
The control input signal for the actuator may come from a duct smoke detector or from the central fire alarm system. Using cables with specific circuit integrity for the supply voltage ensures that the actuator is supplied with voltage even in the event of a fire and hence that its function and the communication are maintained.
Ventilation
During ventilation operation the smoke control dampers of the smoke extract system remain fully open. Smoke control dampers which are used as additional supply air inlets remain closed during ventilation operation.
Depending on where the dampers are installed, country­specific regulations may apply to ventilation applica­tions.
o ensure the creation of a layer that is nearly
Smoke control damper Type EK-JZ 13
Installation
General installation information

5 Installation

5.1 Installation situations

Installation situations
Supporting construc­tion
Solid walls
Gross density ≥ 500 kg/m³
Fire-resistant smoke extract ducts
tested to EN 1366-8, gross density ≥ 520 kg/m³
E = Dry mortarless installation

5.2 Safety notes on installation

Sharp edges, sharp corners and thin sheet metal parts
CAUTION!
Danger of injury from sharp edges, sharp cor­ners and thin sheet metal parts!
Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes.
Be careful when carrying out any work. – Wear protective gloves, safety shoes and a hard
hat.

5.3 General installation information

NOTICE!
Installation location Minimum
thickness
[mm]
In solid shaft walls (Fig. 4/1) 100 EI 120 S T (N)
In solid walls (Fig. 4/2) 100 EI 90 S T (N)
On solid shaft walls (Fig. 4/3) 100 EI 120 S T
On vertical smoke extract ducts (Fig. 4/4)
On horizontal smoke extract ducts (Fig. 4/5)
In horizontal smoke extract ducts (Fig. 4/6)
At the end of horizontal smoke extract ducts (Fig. 4/7)
35 EI 120 S LE
Please note:
Smoke control damper and electric actuator must
remain accessible for maintenance.
Make sure that no loads are imposed on the casing
as this may impair the function of the smoke control damper.
Install the smoke control damper without torsion. Mortar-based installation: The installation gap must
be large enough such that mortar can be filled in even in case of thicker walls.
Before installation: Perform a functional test and
close the smoke control damper.
Installation position
The smoke control damper has to be installed such that the damper blade shaft is horizontal. The actuator encasing has to remain accessible even after installa­tion. The actuator encasing has to be on the right side of the damper.
Performance
level
Installa-
tion type
N = Mortar-based installation
LE = As specified for the duct
Ä
37
Installa-
tion infor-
mation
Ä
16
Ä
18
Ä
20
Ä
22
Ä
24
Ä
26
Ä
28
Be careful to not damage the smoke control damper
Protect the smoke control damper from contami-
nation and damage.
Cover the flange openings and the actuator (e.g.
with plastic foil) to protect them from mortar and dripping water.
Smoke control damper Type EK-JZ14
Fig. 5: Horizontal installation
100
a If you install several smoke control dampers, there
should be a gap of at least 200 mm between them.
Mineral wool as filling material
Unless otherwise stated in the relevant installation details, mineral wool with a gross density of and a melting point of
1000 °C must be used.
≥ 80 kg/m³
Installation
General installation information > After installation
The following mortars are acceptable:
DIN 1053: Groups II, IIa, III, IIIa; fire protection
mortar of groups II, III
EN 998-2: Classes M 2.5 to M 10 or fire protection
mortar of classes M 2.5 to M 10
Equivalent mortars that meet the requirements of
the above standards, gypsum mortar or concrete
Ceramic fibre paper
Fig. 7: Ceramic fibre paper, applying
Glue one strip or two parallel strips of ceramic fibre paper (Fig. 7/1) to the underside of the damper frame such that the edges of the paper are flush with the edges of the damper frame. Do not glue the ceramic fibre paper onto the trim panels.
Ceramic fibre paper is available as an accessory (optional); alternatively, it can be provided by others. The paper has to meet the following requirements:
Fig. 6: Installation gap
Wall
Mineral wool
Ablative coating
EK-JZ
For a smooth look you can apply ablative coating of one of the following types to the mineral wool in the installa­tion gap:
Hilti:
Ablative coating CFS-CT
Hensel:
Ablative coating HENSOMASTIK 5 KS Farbe
Promat:
Ablative coating Promastopp-CC
Mortars for mortar-based installation
In case of mortar-based installation, the open spaces between the fire damper casing and the wall or ceiling slab must be closed of be avoided. The mortar bed depth should be equal to the thickness of the wall but must be at least 100 mm.
f with mortar. Entrapped air is to
Kerafix 2000 premium or equivalent Self-adhesive Thickness: 3 to 10 mm Width:
40 mm

5.3.1 After installation

Remove the straps (in case of mortar-based installa-
tion, do this only after the mortar has cured)
Check that the diagonal length of the damper is cor-
rect.
Clean the smoke control damper Test the function of the smoke control damper Connect the smoke extract duct. Make electrical connections.
.
.
Smoke control damper Type EK-JZ 15
b
h
W
250
W
W
B + 280
b
H + 80
s
2
s
1
s
1
h
A
A-A
A
A-A
s2: 20 – 100
s1: 20 – 40
90°
Installation
Solid walls > Installation in shaft walls

5.4 Solid walls

5.4.1 Installation in shaft walls

Fig. 8: Installation in a solid shaft wall
EK-JZ
Mineral wool
Solid shaft wall
Cover grille (only if the damper is not connected to a duct)
Ceramic fibre paper
Screw connection (suitable for the type of wall; screws to be provided by others)
Mortar
Personnel:
Smoke control damper Type EK-JZ16
Ⓐ Ⓑ
Installation side
Operating side h × b Installation opening s
1
s
2
Mineral wool: 20 – 40 mm
Mineral wool: 20 – 40 mm; mortar: 20 – 100 mm W Wall thickness
100 mm
Installation
Solid walls > Installation in shaft walls
Specialist personnel
Materials:
Mineral wool Ceramic fibre paper Mortar
Fire-resistant screws (with suitability certificate)
Requirements:
Solid walls made of, for example, concrete, aerated concrete or masonry, gross density ≥ 500 kg/m³ and
W ≥ 100 mm
≥ 40 mm distance to load-bearing structural elements ≥ 200 mm distance between two smoke control dampers
Installation
1. Create an installation opening according to Fig. 8. The installation opening has to be rectangular, with smooth
surfaces (± 5 mm).
If the surfaces are not smooth, use mortar to make them smooth.
Place mineral wool along the left side (vertical), approx. 20 to 40 mm thick.
2. Glue one strip or two parallel strips of ceramic fibre paper ( that the edges of paper are flush with the edges of the damper frame,
3. Place the smoke control damper with the ceramic fibre paper in the installation opening and press it towards the mineral wool on the left. Make sure that the damper is vertical; use wedges to hold the damper in the cor­rect position; the damper has to be installed without torsion (check the diagonal length; allowed tolerance: 2 mm).
Install the damper such that the operating side is flush with the wall (A-A section).
4. Fill the installation gap on the right with mineral wool. If the gap is wider than 40 mm, it has to be filled with mortar. Fill the gap with mortar, ideally until it is as thick as the wall, but at least
Fill the installation gap at the top with mineral wool. Note: Do not use mortar for the gap at the top.
Do not leave any gaps or spaces between the damper and the wall. If you have used any objects to facilitate damper installation, e.g. wedges, remove them now. Fill any remaining hollow spaces with mineral wool or mortar.
5.
Ä
‘Mineral wool as filling material’ on page 15
Ä
‘Ceramic fibre paper’ on page 15
Ä
‘Mortars for mortar-based installation’ on page 15
CAUTION!
Fig. 8/5) to the underside of the damper frame such
Ä
15.
100 mm.
Malfunction of the smoke control damper
Use only the fixing points marked on the damper frame (drilled hole, indentations) to screw fix the smoke control damper. Do not use any screws anywhere else on the damper frame as they may prevent the blades from closing properly. Fixing points on the H section only from
Drill screw holes at the fixing points marked on the damper frame (Fig. 8/6), then screw fix the damper to the wall. Be careful when you tighten the screws; do not exercise any tension as this may damage the damper.
Smoke control damper Type EK-JZ 17
H 1230 mm.
 - 
W
250
W
W
b
h
B + 280
b
H + 80
s
2
s
1
s
1
h
A
A-A
A
A-A
s2: 20 – 100
s2: 20 – 40
90°
Installation
Solid walls > Installation in solid walls

5.4.2 Installation in solid walls

Fig. 9: Installation in a solid shaft wall
EK-JZ
Mineral wool
Solid wall
Cover grille (only if the damper is not connected to a duct)
Ceramic fibre paper
Screw connection (suitable for the type of wall;
⑧ Ⓐ Ⓑ
Calcium silicate smoke extract duct Installation side
Operating side h × b Installation opening s
1
s
2
Mineral wool: 20 – 40 mm
Mineral wool: 20 – 40 mm; mortar: 20 – 100 mm W Wall thickness
screws to be provided by others)
Mortar
Personnel:
Specialist personnel
Smoke control damper Type EK-JZ18
100 mm
Installation
Solid walls > Installation in solid walls
Materials:
Mineral wool Ceramic fibre paper Mortar
Fire-resistant screws (with suitability certificate)
Requirements:
Solid walls made of, for example, concrete, aerated concrete or masonry, gross density ≥ 500 kg/m³ and
W ≥ 100 mm
≥ 40 mm distance to load-bearing structural elements ≥ 200 mm distance between two smoke control dampers
Installation
1. Create an installation opening according to Fig. 9. The installation opening has to be rectangular, with smooth
surfaces (± 5 mm).
If the surfaces are not smooth, use mortar to make them smooth.
Place mineral wool along the left side (vertical), approx. 20 to 40 mm thick.
2. Glue one strip or two parallel strips of ceramic fibre paper ( that the edges of paper are flush with the edges of the damper frame,
3. Place the smoke control damper with the ceramic fibre paper in the installation opening and press it towards the mineral wool on the left. Make sure that the damper is vertical; use wedges to hold the damper in the cor­rect position; the damper has to be installed without torsion (check the diagonal length; allowed tolerance: 2 mm).
Install the damper such that the operating side is flush with the wall (A-A section).
4. Fill the installation gap on the right with mineral wool. If the gap is wider than 40 mm, it has to be filled with mortar. Fill the gap with mortar, ideally until it is as thick as the wall, but at least
Fill the installation gap at the top with mineral wool. Note: Do not use mortar for the gap at the top.
Do not leave any gaps or spaces between the damper and the wall. If you have used any objects to facilitate damper installation, e.g. wedges, remove them now. Fill any remaining hollow spaces with mineral wool or mortar.
5.
Ä
‘Mineral wool as filling material’ on page 15
Ä
‘Ceramic fibre paper’ on page 15
Ä
‘Mortars for mortar-based installation’ on page 15
CAUTION!
Fig. 8/5) to the underside of the damper frame such
Ä
15.
100 mm.
Malfunction of the smoke control damper
Use only the fixing points marked on the damper frame (drilled hole, indentations) (Fig. 9/6) to screw fix the smoke control damper. Do not use any screws anywhere else on the damper frame as they may prevent the blades from closing properly
Drill screw holes at the fixing points marked on the frame (Fig. 9/6), then screw fix the frame to the wall. Be careful when you tighten the screws; do not exercise any tension as this may damage the damper.
6. Connect a smoke extract duct made of calcium silicate to the installation side of the damper (Fig. 9/8),
Ä
6 ‘Connecting the smoke extract duct’ on page 31.
Connect a smoke extract duct made of calcium silicate or sheet steel to the operating side of the damper
Ä
6 ‘Connecting the smoke extract duct’ on page 31. If the operating side is not connected to a duct, a cover
Ä
grille is required
6.2 ‘Cover grille’ on page 32.
. Fixing points on the H section only from H 1230 mm.
Smoke control damper Type EK-JZ 19
60
35
25240 95
250
W
95
125
b x h
h
b
A-A
A
B
B
B-B
Installation
Solid walls > Installation on shaft walls

5.4.3 Installation on shaft walls

Fig. 10: Installation on a solid shaft wall
EK-JZ
Angle section made from strips of fire-rated PRO­MATECT®-LS board d = 35 mm or equivalent
Solid shaft wall
Dry wall screw 4
Screw connection with approved anchors
× 70 mm (by others)
∅ ≤ 6 mm (by others); 200 mm distance between
screws
Cover grille (only if the damper is not connected to a duct)
Installation with a suitable load-bearing support, e.g. a mounting system or a block of stone of the same width as the damper
Installation onto the concrete floor, onto a con­crete plinth or onto the fully bricked up space underneath the damper
⑨ Ⓐ Ⓑ
Ceramic fibre paper strip Installation side Operating side
h × b Installation opening = B x H W Wall thickness 100 mm
Smoke control damper Type EK-JZ20
Installation
Solid walls > Installation on shaft walls
Personnel:
Specialist personnel
Materials:
Fire-rated PROMATECT®-LS board d = 35 mm or equivalent
  Ceramic fibre paper
Requirements:
Solid walls made of, for example, concrete, aerated concrete or masonry, gross density ≥ 500 kg/m³ and
W ≥ 100 mm
≥ 40 mm distance to load-bearing structural elements ≥ 200 mm distance between two smoke control dampers
Installation
1. Create an installation opening according to
2. Use two strips of fire-rated board to make an angle section (
side of the smoke control damper
If you install the damper onto the floor or onto a plinth ( of the damper; take instead a strip of ceramic fibre paper (Fig. 10/9) and glue it to the underside of the damper frame. Make sure that the strip edges are flush with the frame edges; use two paper strips if necessary.
3. Place the smoke control damper in front of the installation opening. If necessary a mounting system or block of stone).
4. Fit angle sections to the remaining three sides of the smoke control damper
Apply glue (e.g. K84, Promat or equivalent) to the joints ( and the damper casing, then fix the strips with dry wall screws 4 3 mm), 150 mm distance between screws.
Ä
‘Ceramic fibre paper’ on page 15
Fig. 10.
.
Fig. 10/2), then fix the angle section to the under-
Fig. 10/8), no angle section is required on the underside
, support the damper (e.g. with
.
Fig. 10/2) between the strips and between the strips
× 70 mm to the damper casing (pre-drill holes,
Screw fix the angle sections to the wall; use fire-resistant screws (suitability certificate) that are suitable for the material of the wall; 200 mm distance between screws.
Smoke control damper Type EK-JZ 21
W
250
b x h
60
240 95
95
35 25
①⑤②
A-A
A
A
h
b
Installation
Fire-resistant smoke extract ducts > Installation on vertical smoke extra...

5.5 Fire-resistant smoke extract ducts

5.5.1 Installation on vertical smoke extract ducts

Fig. 11: Installation on a vertical smoke extract duct (shaft)
EK-JZ
Angle section made from strips of fire-rated PRO-
TECT®-LS board d = 35 mm or equivalent
MA
Smoke extract duct made of calcium silicate
Dry wall screw
Cover grille (only if the damper is not connected to
× 70 mm (by others)
4
Ⓐ Ⓑ
h × b Installation opening = B x H W Wall thickness 35 mm
Installation side Operating side
a duct)
Personnel:
Specialist personnel
Materials:
Fire-rated PROMA
Steel staples ≥ 63/11.2/1.5 mm
Dry wall screws 4
Requirements:
Smoke extract duct, fire-resistant, tested to EN 1366-8, gross density ≥ 520 kg/m³, wall thickness
TECT®-LS board d = 35 mm or equivalent
× 70 mm
Installation
1. Create an installation opening according to Fig. 11.
Smoke control damper Type EK-JZ22
≥ 35 mm
Installation
Fire-resistant smoke extract ducts > Installation on vertical smoke extra...
2. Use two strips of fire-rated board to make an angle section (Fig. 11/2), then fix the angle section to the under­side of the smoke control damper
3. Place the smoke control damper in front of the installation opening. If necessary, support the damper (e.g. with a mounting system or block of stone).
4. Fit angle sections to the remaining three sides of the smoke control damper.
.
Apply glue (e.g. K84, Promat or equivalent) to the joints (Fig. 1 and the damper casing, then fix the strips with dry wall screws 4 × 70 mm to the damper casing (pre-drill holes, 3 mm), 150 mm distance between screws.
Use dry wall screws 4 × 70 mm to fix the angle sections to the smoke extract duct, 150 mm distance between screws.
CAUTION!
Dampers that weigh > 100 kg have to be suspended on page 30.
1/2) between the strips and between the strips
Ä
5.6 ‘Suspending the smoke control damper’
Smoke control damper Type EK-JZ 23
35
25
100
60
95
35
A
A
A - A
C - C
B - B
C
C
B
B
180
10
35
60
95
35
Installation
Fire-resistant smoke extract ducts > Installation on horizontal smoke ext...

5.5.2 Installation on horizontal smoke extract ducts

Fig. 12: Installation in fire-resistant horizontal smoke extract duct
EK-JZ
Solid ceiling slab
Fire-resistant smoke extract duct
Angle section made from strips of fire-rated PRO­MATECT®-LS board d = 35 mm or equivalent
Smoke control damper Type EK-JZ24
Suspension
Ä
5.6 ‘Suspending the smoke control
damper’ on page 30
Steel staples ≥ 63/11.2/1.5 mm
Connecting strips according to instructions by the manufacturer of the smoke extract duct
necting the smoke extract duct’ on page 31
Cover grille (only if the damper is not connected to a duct)
Ä
6 ‘Con-
Installation
Fire-resistant smoke extract ducts > Installation on horizontal smoke ext...
Personnel:
Specialist personnel
Materials:
Fire-rated PROMATECT®-LS board d = 35 mm or equivalent
Steel staples ≥ 63/11.2/1.5 mm
Suspension
Requirements:
Smoke extract duct, fire-resistant, tested to EN 1366-8, gross density ≥ 520 kg/m³, wall thickness ≥ 35 mm
Installation
1. Create and suspend a fire-resistant smoke extract duct according to the manufacturer's instructions.
2.
Place the smoke control damper onto the fire-resistant duct and suspend the damper smoke control damper’ on page 30.
3. Connect the fire-resistant smoke extract duct to the smoke control damper by placing an angle section
Ä
between the duct and the damper
Be sure to follow the manufacturer's instructions.
4. If the smoke extract duct and the smoke control damper are of the same height, you can use a connecting strip (Fig. 12/7) instead of an angle section.
6 ‘Connecting the smoke extract duct’ on page 31.
Ä
5.6 ‘Suspending the
Smoke control damper Type EK-JZ 25
A - A 90°
A
A
6035
80
35
Installation
Fire-resistant smoke extract ducts > Installation in horizontal smoke ext...

5.5.3 Installation in horizontal smoke extract ducts

Fig. 13: Installation in a horizontal smoke extract duct
EK-JZ
Suspension
Connecting strips according to instructions by the manufacturer of the smoke extract duct
Angle section made from strips of fire-rated PRO-
⑤ ⑥
Personnel:
TECT®-LS board d = 35 mm or equivalent
MA Fire-resistant smoke extract duct Solid ceiling slab
Steel staples ≥ 63/1
Connecting subframe made from fire-rated PRO-
TECT®-LS board d = 35 mm x 60 mm or equiv-
MA
1.2/1.5 mm
alent (by others)
Cover grille (at the end of a smoke extract duct)
Dry wall screw
Cover of the actuator encasing
Smoke control damper Type EK-JZ26
Installation
Fire-resistant smoke extract ducts > Installation in horizontal smoke ext...
Specialist personnel
Materials:
Fire-rated PROMATECT®-LS board d = 35 mm or equivalent
Steel staples ≥ 63/11.2/1.5 mm
Suspension
Requirements:
Smoke extract duct, fire-resistant, tested to EN 1366-8, gross density ≥ 520 kg/m³, wall thickness ≥ 35 mm
The actuator encasing must remain accessible for maintenance even after installation (cover, Fig. 13/1
Installation
1. Build a connecting subframe (Fig. 13/8) from fire-rated PROMATECT®-LS board (d = 35 mm x 60 mm
equivalent (by others), then fix the subframe with dry wall screws (Fig. 13/10) to the operating side of the smoke control damper.
2. Create and suspend a fire-resistant smoke extract duct according to the manufacturer's instructions.
3.
Place the smoke control damper onto the fire-resistant duct and suspend the damper smoke control damper’ on page 30.
4. Fix an angle section (Fig. 13/4) between the actuator encasing and the smoke extract duct.
5. Connect the fire-resistant smoke extract duct to the smoke control damper with a connecting strip (Fig. 13/3)
Ä
6 ‘Connecting the smoke extract duct’ on page 31.
Be sure to follow the manufacturer's instructions.
Ä
5.6 ‘Suspending the
1).
) or
Smoke control damper Type EK-JZ 27
Installation
Fire-resistant smoke extract ducts > Installation at the end of horizonta...

5.5.4 Installation at the end of horizontal smoke extract ducts

Fig. 14: Installation at the end of a horizontal smoke extract duct
EK-JZ
Suspension
Connecting strips according to instructions by the manufacturer of the smoke extract duct
Angle section made from strips of fire-rated PRO-
TECT®-LS board d = 35 mm or equivalent
MA
Smoke control damper Type EK-JZ28
⑤ ⑥ ⑦ ⑧
Fire-resistant smoke extract duct Solid ceiling slab Steel staples ≥ 63/1 Cover grille
1.2/1.5 mm
Installation
Fire-resistant smoke extract ducts > Installation at the end of horizonta...
Personnel:
Specialist personnel
Materials:
Fire-rated PROMATECT®-LS board d = 35 mm or equivalent
Steel staples ≥ 63/11.2/1.5 mm
Suspension
Requirements:
Smoke extract duct, fire-resistant, tested to EN 1366-8, gross density ≥ 520 kg/m³, wall thickness ≥ 35 mm
Installation
1. Create and suspend a fire-resistant smoke extract duct according to the manufacturer's instructions.
2.
Place the smoke control damper onto the fire-resistant duct and suspend the damper smoke control damper’ on page 30.
3. Fix an angle section (Fig. 14/4) between the actuator encasing and the smoke extract duct.
4. Connect the fire-resistant smoke extract duct to the smoke control damper with a connecting strip (Fig. 14/3)
Ä
6 ‘Connecting the smoke extract duct’ on page 31.
Be sure to follow the manufacturer's instructions.
Ä
5.6 ‘Suspending the
Smoke control damper Type EK-JZ 29
Installation
Suspending the smoke control damper > Suspending the smoke control damper

5.6 Suspending the smoke control damper

5.6.1 General

Smoke control dampers can be suspended from solid ceiling slabs using adequately sized threaded rods. Load the suspension system only with the weight of the smoke control damper.
Ducts must be suspended separately
Suspension systems longer than resistant insulation.
Size of threaded rods
Thread M8 M10 M12 M14 M16 M20
Fmax (N) per threaded rod
Maximum loading [kg] per threaded rod
219 348 505 690 942 1470
22 35 52 70 96 150

5.6.2 Fixing to the ceiling slab

.
1.5 m require fire-

5.6.3 Suspending the smoke control damper

Fig. 16: Suspending the smoke control damper
Smoke control damper
Threaded rod M8M20
Hilti mounting rail MQ 41 × 3 or equivalent
Hilti MQZ-L drilled plate or equivalent
Nut, M8M20, galvanised steel
Fig. 15: Fixing to the ceiling slab
Anchor with certified fire protection qualification
Push through installation
Only steel anchors with certified fire protection qualifica­tion and suitable for the wall or ceiling must be used. Instead of anchors, threaded rods can be used and can be secured using nuts and washers.
Smoke control damper Type EK-JZ30

Connecting the smoke extract duct

Smoke extract ducts
6 Connecting the smoke
extract duct

6.1 Smoke extract ducts

Calcium silicate smoke extract duct
Sheet steel smoke extract duct
Fig. 17: EK-JZ connection to a calcium silicate smoke extract duct
X1Smoke extract duct and EK-JZ flush on the outside X2Smoke extract duct and EK-JZ flush on the inside
EK-JZ
Connecting strips according to instructions by the manufacturer of the smoke extract duct
Calcium silicate smoke extract duct
Steel staples
Connecting subframe for smoke extract duct (by others)
Angle section made from strips of fire-rated PRO-
TECT®-LS board d = 35 mm or equivalent
MA
Fig. 18: EK-JZ with connecting subframe for smoke extract duct made of sheet steel
Connecting subframe (optional)
As ducts may expand and walls may become deformed in the event of a fire, we recommend using flexible con­nectors when connecting the damper to sheet steel smoke extract ducts: The flexible connectors should meet the specifications for the sheet steel smoke extract duct. Be sure to follow the manufacturer's instructions.
Smoke control damper Type EK-JZ 31
Connecting the smoke extract duct

Inspection access

6.2 Cover grille

Fig. 19: Smoke control damper with cover grille
Cover grille (optional)
Wire mesh (optional)
If no smoke extract duct is connected to the smoke con­trol damper, a cover grille is required to protect that side of the damper.
Cover grilles are available as accessories.
6.3
Inspection access
The interior of the smoke control damper must remain accessible for maintenance. Depending on the installa­tion configuration it may be necessary to provide addi­tional inspection panels in the connecting ducts.
Smoke control damper Type EK-JZ32
Electrical connection

7 Electrical connection

General safety notes
DANGER!
Danger of electric shock! Do not touch any live com­ponents! Electrical equipment carries a dangerous electrical voltage.
Only skilled qualified electricians are allowed to
work on the electrical system.
Switch off the power supply before working on
any electrical equipment.
Wiring and connection to the central BMS
Personnel:
Skilled qualified electrician
24 V actuators with AS-i module
The connecting cables of the AS-i module are fitted with wire end ferrules.
Electric cables and system
For manual release (MA), the electric cables and system must have at least 30 minutes circuit integrity.
For manual release (MA) we recommend using a ceramic terminal to connect the AS-i cable to the actuator cable or to the cable of the AS-i module.
Note: Feeding the electric connecting cable through the actuator encasing requires a drilled hole of the exact
cable + 1 mm). Note that the cable must not be
size ( fed through the cover. A wire clamping bracket is required.
Fig. 20: Wiring example, BE actuator
Switch for opening and closing, to be provided by others
Indicator light for CLOSED position, to be provided by others
Indicator light for OPEN position, to be provided by others
The smoke control damper may be equipped with a
230 V AC or a 24 V AC/DC actuator. See the per­formance data on the rating plate.
The actuator must be connected according to the
wiring example shown. Several actuators can be connected in parallel as long as the performance specifications are taken into consideration.
Ä
Technical data, see
Actuators with 24 V AC/DC
Safety transformers must be used. The connecting cables are fitted with plugs. This ensures quick and easy connection to the TROX AS-i bus system. For con­nection to the terminals, shorten the connecting cable.
10
Smoke control damper Type EK-JZ 33
14 13 12 11
BC24
X
Electrical connection
SLC module
Socket for an actuator
Sockets for limit switches
Terminal for a thermoelectric release mechanism or any other safety-related release mechanism
THC/SLC two-wire connection, 2 x 1.5 mm², 300 m max., exchangeable wires
Fig. 22: Terminals 11 to 14
11 Reserved 12 GND 13 +24 VDC (25 mA max.) 14 IN
If you use terminals 13 and 14, remove the wire link.
You may use terminals 13 and 14 to connect a smoke detector or any other volt-free control contact, e.g. a fire alarm system. When the contact opens, the damper blades move to the defined safe position. For this case the terminals 13 and 14 of several BC24 can be switched in parallel.
Fig. 21: BC24
Screw terminal to connect a smoke detector
'Test' push button
LEDs (red = malfunction or self test, green = com­munication in progress)
Socket for a BAE thermoelectric release mechanism (supplied with wire link, can be removed)
Cable feed-through for TROX or Belimo actuators (­ST)
Connection data
Supply voltage Provided by the SLC con-
trol module
Power consumption 1 W
Contact load, terminals
25 mA max.
12/13
IEC protection class III (protective extra-low
voltage)
Smoke control damper Type EK-JZ34
Bus modules
M
LO HI
24V
GND
A B
24V GND A B
1 2 3 4 5 6 7 8 9 10
17
S1 1 32S2 S3 S4 S5 S6
18 19 20 21 22 29 30 31
BRM-10-F
BUS in BUS out
L
N
L N
11 12 15 1613 14
PE
PE
ZU AUF
B(L)E
M
LO HI
24V
GND
A B
24V GND A B
1 2 3 4 5 6 7 8 9 10
BRM-10-F-ST
BUS in BUS out
L
N
L N
11 12 15 1613 14
PE
PE
B(L)E
Fig. 23: Connection example BRM-10-F
Electrical connection
Fig. 24: Connection example BRM-10-F-ST
Check during commissioning whether the blades of the damper move correctly from OPEN to CLOSED.
The mode switch allows you to choose one of the following operating modes:
Automatic (damper is controlled via the bus; status LEDs are not active) Revision (damper is controlled via the bus; status LEDs are not active) NC contact, manual (bus commands are overridden) NO contact, manual (bus commands are overridden)
Technical data
Electrical data Supply voltage 18 – 32 V DC (typically 24 V)
Construction Digital inputs 2 for feedback from limit switches (volt-free)
Outputs Voltage supply to the
Current consumption 5 mA (typically), 26 mA max. (for 100 ms when relays close)
Protection level IP 20 (EN 60529)
IEC protection class II
Digital outputs 1 for signalling to the fire damper
24 / 230 V AC 24 V DC
damper
Permanent current,
AC 5 A DC 5 A
max.
Smoke control damper Type EK-JZ 35
Electrical connection
Technical data
Switch-on current, max. (< 15 ms)
Switch rating 1250 VA / 150 W
Terminals for damper input
Terminals for bus, feed­back, damper output
Ambient conditions Ambient temperature 0 – 45 °C
Max. cross-sectional area of conductors
Max. current, terminals 10A
Pre fuse MCB, 10 A, characteristic B
Cross-sectional areas of conductors
Ambient humidity 0 – 90%
AC 8 A DC 8 A
Solid core: 0.08 – 2.5 mm²
Multi-strand (without ferrule): 0.08 – 2.5 mm²
Multi-strand (insulated ferrule): 0.25 – 1.5 mm²
Multi-strand (non-insulated ferrule): 0.25 – 2.5 mm²
Solid core: 0.2 – 1.5 mm²
Multi-strand (without ferrule): 0.2 – 1.5 mm²
Multi-strand (insulated ferrule): 0.25 – 1.5 mm²
Multi-strand (non-insulated ferrule): 0.25 – 1.5 mm²
Smoke control damper Type EK-JZ36
8 Commissioning/functional
test

8.1 Commissioning

Before commissioning, each smoke control damper must be inspected to determine and assess its actual
Ä
condition. ures’ on page 39.

8.2 Functional test

General
Smoke control dampers must be checked regularly. A functional test involves closing the smoke control damper and opening it again. This is typically done with an input signal from the central fire alarm system.
‘Inspection, maintenance and repair meas-

Commissioning/functional test

Functional test
Smoke control damper Type EK-JZ 37
Maintenance

9 Maintenance

General safety notes
DANGER!
Danger of electric shock! Do not touch any live com­ponents! Electrical equipment carries a dangerous electrical voltage.
Only skilled qualified electricians are allowed to
work on the electrical system.
Switch off the power supply before working on
any electrical equipment.
CAUTION!
Danger due to inadvertently actuating the smoke control damper. Inadvertent actuation of the damper blade or other parts can lead to injuries.
Make sure that the damper blade cannot be released inadvertently.
Regular care and maintenance ensure operational read­iness, functional reliability, and long service life of the smoke control dampers.
The owner or operator of the system is responsible for the maintenance of the smoke control damper. The operator is responsible for creating a maintenance plan, for defining the maintenance objectives, and for the functional reliability of the damper
Functional test
The functional reliability of the smoke control damper must be tested at least every six months; this has to be arranged by the system owner. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
The functional test must be carried out in compliance with the basic maintenance principles of the following standards:
.
Maintenance
The smoke control damper and the actuator are mainte­nance-free with regard to wear but smoke control dampers must still be included in the regular cleaning of the smoke extract system.
Inspection
Smoke control dampers must be inspected before com­missioning. After commissioning, the function has to be tested in regular intervals. Local requirements and building regulations must be complied with.
The inspection measures to be taken are listed under
Ä
‘Inspection, maintenance and repair measures’
on page 39.
The test of each smoke control damper must be docu­mented and evaluated. If the requirements are not fully met, suitable remedial action must be taken.
Repair
For safety reasons, repair work must only be carried out by expert qualified personnel or the manufacturer. Only original replacement parts are to be used. A functional
Ä
test is required after any repair work sioning/functional test’ on page 37.
Any repair must be documented.
Cleaning
All surfaces of TROX components and systems, with the exception of electronic parts, may be wiped with a dry or damp cloth. Do not use cleaning agents that con­tain chlorine. All surfaces may also be cleaned with an industrial vacuum cleaner. To avoid any scratches, a soft brush should be used on the suction inlet. Equip­ment for removing stubborn contamination, e.g. scrub­bing sponges or scouring cream, may damage the sur­faces and must not be used.
8 ‘Commis-
EN 12101-8 EN 13306 EN 15423 Depending on where dampers are installed, country-
specific regulations may apply
.
Smoke control damper Type EK-JZ38
Inspection, maintenance and repair measures
Interval Maintenance work Personnel
Maintenance
A Accessibility of the smoke control damper
Internal and external accessibility
Provide access
Installation of the smoke control damper
Installation according to the operating manual
on page 14
Install the smoke control damper correctly
Connection of smoke extract ducts/cover grille/flexible connector
Ä
6 ‘Connecting the smoke extract duct’ on page 31
Connection according to this manual
Establish correct connection
Supply voltage for the actuator
Power supply according to the actuator rating plate
Provide correct power supply
A / B Check of the smoke control damper for damage
Smoke control damper
Repair or replace the smoke control damper
Functional test of the smoke control damper
on page 37
Actuator function OK Damper blade closes Damper blade opens
Determine and eliminate the cause of the fault – Replace actuator
Repair or replace the smoke control damper
, damper blade and seal must be intact
Ä
Ä
5 ‘Installation’
8.2 ‘Functional test’
Specialist personnel
Specialist personnel
Specialist personnel
Skilled qualified electrician
Specialist personnel
Specialist personnel
C Cleaning the smoke control damper
No contamination in the interior or on the exterior of the smoke con-
trol damper – Remove contamination
Interval
A = Commissioning
B = Regularly
The functional reliability of smoke control dampers must be tested at least every six months. If two consecu­tive tests are successful, the next test can be conducted one year later.
C = As required, depending on the degree of contamination
Maintenance work
Item to be checked
Required condition
Remedial action if necessary
Specialist personnel
Smoke control damper Type EK-JZ 39

Decommissioning, removal and disposal

10 Decommissioning,
removal and disposal
Final decommissioning
Switch off the ventilation system. Switch off the power supply
Removal
DANGER!
Danger of electric shock! Do not touch any live com­ponents! Electrical equipment carries a dangerous electrical voltage.
Only skilled qualified electricians are allowed to
work on the electrical system.
Switch off the power supply before working on
any electrical equipment.
.
1. Disconnect the wiring.
2. Remove the smoke extract duct.
3. Remove the smoke control damper.
Disposal
ENVIRONMENT!
Risk of harm to the environment due to incorrect disposal of packaging.
Incorrect disposal can harm the environment.
Have electronic waste and electronic components disposed of by an approved specialist disposal com­pany.
For disposal the smoke control damper must be com­pletely disassembled.
Smoke control damper Type EK-JZ40

11 Index

Index
A
Actuator................................................................ 13, 33
Actuator encasing......................................................
AS-i............................................................................ 33
13
B
Blades........................................................................ 13
C
Calcium silicate smoke extract duct........................... 31
Casing........................................................................ 13
Central BMS............................................................... 33
Commissioning........................................................... 37
Copyright...................................................................... 3
Correct use................................................................... 6
Cover.......................................................................... 13
Cover grille................................................................. 32
D
Decommissioning....................................................... 40
Defects liability............................................................. 3
Dimensions.............................................................. 8, 9
Disposal..................................................................... 40
F
Functional test............................................................ 37
H
Hotline.......................................................................... 3
I
Inspection............................................................. 38, 39
Inspection access....................................................... 32
Installation
at the end of a horizontal smoke extract duct....... 28
in a horizontal smoke extract duct......................... 26
in solid shaft walls................................................. 16
in solid walls.......................................................... 18
on a horizontal smoke extract duct....................... 24
on solid shaft walls................................................ 20
on vertical smoke extract ducts............................. 22
Installation position..................................................... 14
Installation situations.................................................. 14
L
Limitation of liability
Linkage....................................................................... 13
...................................................... 3
M
Maintenance............................................................... 38
O
Open/Close actuator.................................................. 10
P
Packaging.................................................................. 12
R
Rating plate............................................................ 7, 13
Removal..................................................................... 40
Repair................................................................... 38, 39
S
Seal............................................................................ 13
Service......................................................................... 3
Sheet steel smoke extract duct.................................. 31
Staff.............................................................................. 6
Storage....................................................................... 12
Supply voltage............................................................ 33
Suspension................................................................ 30
Symbols....................................................................... 4
T
Technical data.............................................................. 7
Technical service.......................................................... 3
Threaded rods............................................................ 30
Transport.................................................................... 11
Transport damage...................................................... 11
Travel stop.................................................................. 13
W
Weights.................................................................... 8, 9
Wiring......................................................................... 33
Smoke control damper Type EK-JZ 41
Smoke control damper Type EK-JZ42
Smoke control damper Type EK-JZ 43
TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany
Phone: +49 (0) 2845 2020 +49 (0) 2845 202-265 E-mail: trox@trox.de http://www.troxtechnik.com
© 2017
Loading...