Trotec IDS 900 Operating Manual

OPERATING MANUAL
OIL HEATING UNITS
IDS 900
EN
TRT-BA-IDS900-HS-003-EN
Table of contents
02. Description
01. Safety .......................................A - 1
02. Description ...................................A - 1
03. Instructions for the installer .......................A - 2
05. Care and maintenance ..........................A - 6
06. Transport and repositioning .......................A - 7
07. Faults and troubleshooting .......................A - 7
08. Functional diagram and control panel ...............A - 9
09. Circuit diagram ...............................A - 11
10. Technical data ................................A - 12
11. Available accessories ..........................A - 13
This release replaces all previous releases. No part of this publication may be reproduced without written permission. The same applies for electronically processing, duplicating or spreading the publication. Subject to technical changes. All rights reserved. Trademarks are used without guarantee that they may be used freely and primarily following the spelling of the manufacturer. The product names used are registered and should be treated appropriately. The right to make construction changes in the interests of constant product improvement as well as changes to the shape and colour is reserved. The scope of delivery may vary from product images. This document was produced with all due care. We accept no liability whatsoever for mistakes or omissions.
®
© TROTEC
01. Safety
The applicable laws and regulations concerning the use of air heat­ers must be observed for the installation, regulation and use of this device. Please observe the following instructions:
• Strictly adhere to the instructions contained in this operating manual.
• Avoid positioning air heaters in rooms with explosion hazard or where fire is prohibited.
• Do not store combustible materials near the device (minimum distance 3m).
• Take the necessary fire protection measures.
• Provide for sufficient ventilation of the room where the air heater is positioned.
• Position the device near a chimney and an electrical supply control panel complying with the specified parameters.
• Check the device prior to start-up and regularly during operation. In particular, make sure that children or animals cannot approach the device unnoticeably.
• Always remove the plug from the socket after operation. Further­more, pay attention to the operating conditions of the air heater, particularly:
• Do not exceed the maximum thermal output of the heater ("TECHNICAL DATA").
• Make sure that the air supply is not below the nominal air supply. Therefore check that there are no obstacles or obstructions in the inlet and/or outlet pipes, such as cloths or blankets placed on the device, or walls or large objects situated in the immediate vicinity of the device. If the air flow rate is insufficient, the combustion chamber will heat up and the overheating protection thermostat L1 will switch the device on and off continuously ("FAULTS AND TROUBLESHOOTING"). .
The air heaters of the IDS series are designed for heating medium-sized and large rooms requiring a fixed or mobile heating source. They heat the air by emitting the thermal energy generated by combustion via the metal surfaces of the combustion chambers and via the heat exchanger. The air passage duct and the smoke passage duct are hermetically sealed from each other.
The combustion air, i.e. the air required for combustion, is directly sucked in by the integrated burner in the following way:
• from outdoors via the air inlet nozzle (available as accessory) to avoid reducing the oxygen content of the room to be heated or
• directly from the room to be heated. In the latter case the room must be adequately ventilated to guarantee a sufficient air exchange.
The hot air flow is moved by the motor-driven high-performance fan. The fresh air is heated by the combustion gases via the dense metal surface of the combustion chamber. The combustion gases are
directed to an exhaust gas duct so that they can escape via a chimney or chimney pipe with sufficient dimensions to ensure the discharge of the flue gases.
The end piece of the hot air outlet duct can be replaced by the following ducts:
• with 2 or 4 outlet openings, all of which are kept open.
The air heater IDS 900 can be operated with burners running on diesel fuel, natural gas (G20) or liquid gas LPG (butane, G30, and propane, G31) with ON-OFF operating mode.
m
Only the burners selected and supplied by the manufacturer may be used.
The CE label on the device becomes obsolete if the burner is replaced with a non-original burner, even if the latter has similar characteristics.
The IDS900 is equipped with an electronic flame monitoring system and the following equipment:
• Safety equipment (safety thermostat with manual reset, flame monitoring, air pressure switch) responding in case of severe operational disruptions and triggering a safety shutdown: in this case the air heater switches off, the burner display(h) is perma­nently illuminated in red and operation can only be continued after the cause of the failure has been identified and eliminated.
• Control equipment (temperature controller for regulating the air outlet temperature, fan thermostat and burner thermostat, voltage monitoring) triggering in case of minor malfunctions or disruptions in the power supply and causing a temporary shutdown of the air heater. In this case the air heater resumes operation automatically
once the normal operating conditions have been restored.
If one of these safety devices is triggered, always identify the cause and repair the damage before pressing the corresponding restart button to switch the air heater back on ("FAULTS AND TROUBLE­SHOOTING").
In the event of an overheating of the combustion chamber, the over­heating thermostat responds. It switches the device off and switches it back on after the device has cooled down (light (h) turns on and off again).
A - 1 Operating manual – IDS 900 EN
03. Instructions for the installer
m All operations described in this chapter must be carried out
by appropriately qualified personnel.
3.1 POWER CONNECTIONS AND SETTINGS
The standard version of the air heater contains all control and safety equipment required for operating the device. The electric switch panel, burner, fan thermostat, overheating thermostat and safety thermostat with manual restart are already connected.
Connect the power cable to a properly secured socket. On construction sites, there must be an RCD upstream of the socket according to VDE 0100/0105.
Before commissioning the air heater and thus before connecting the device to the electricity grid check that the values of the electricity grid correspond to the specifications on the identification plate.
m All activities listed under this section may only be carried
out by specialists.
3.2 FLOOR OR CEILING INSTALLATION
The air heater can be mounted as follows:
• on the floor in a stable position
• suspended from the ceiling using ropes and/or chains with a suitable size and length fastened to the four suspension points
NO
The minimum distance to walls, to the floor and/ or to the ceiling should be at least 1m.
m Make sure that the angle of the ropes and/or chains to
the vertical axis does not exceed 5°, that the ropes do not cross each other and that a different rope is used for each hook.
3.3 CONNECTION TO THE HOT AIR FEED DUCTS
The air heater is designed for direct air distribution. The hot air opening can be replaced with a 2-way or 4-way distributor head in order to divide the hot air flow by means of flexible channel modification. In such a case, you have to disassemble the original outlet nozzle and replace it with the 2-way or 4-way distributor head.
The equipment mentioned above can be connected to ducts with the corresponding diameter whenever this is required for special applications. In this case or if there are substantial changes in the hot air distribution circuit (change of the length or diameter of the pipe, number of curves etc.), checks and adjustments are required. In any case you have to:
• Check that the power consumption of the fan motor does not exceed the specified value.
• Check that the air flow rate corresponds to the nominal flow rate.
EN Operating manual – IDS 900 A - 2
3.4 CONNECTION TO THE FUEL SUPPLY
Always observe the installation, adjustment and operating regulations stipulated by the local and/or national laws regarding the use of air heaters.
• Before planning the exhaust system, inform the responsible chimney sweep according to DIN18160.
• Risk of injury due to poisoning!
• Improper installation of the exhaust system can cause health problems.
• Have the device installed by an expert technician!
• Have the exhaust emission of the burner checked at regular intervals.
In order to connect the device to the fuel oil pipe, the fuel oil tank can be connected to the burner pump:
• directly using the fuel oil pump of the burner while observing the dimensions and lengths specified in the burner's operating manual included in the annex of this operating manual;
• indirectly using an auxiliary pump for the fuel oil. In this case please contact the technical service for a proper dimensioning of the system.
Connect the end of the air intake pipe with the wall duct. The pipe must be fitted with a protective grid so that small animals or rubble cannot enter it.
3.5 CONNECTION OF THE BURNER'S AIR INLET
The combustion air inlet(3) can be connected to the outdoor area of the room to be heated so that fresh air can be sucked in without reducing the oxygen content of the room.
A pipe must be provided for this purpose to prevent narrowing due to the negative pressure of the intake air. The pipe should have a diameter of at least 100mm and a length not exceeding 6m.
m Shorten pipes which are too long. There must be no kinks
and/or curves which might obstruct the intake of air.
Connecting the air inlet of the burner:
• Remove the cover(1) of the burner housing.
• Remove the end plate(2) of the burner housing.
• Guide the air hose(3) through the hole in the end plate(2) and fasten it to the air intake snorkel(4) of the burner.
• Slide the cover(1) of the burner housing along the air hose(3) and attach it to the burner housing. While doing so, make sure that the air hose(3) does not slip off the air intake snorkel(4).
• Fasten the plate(1) to the air inlet of the burner. It must be rotat­ed so that the air hose(3) is blocked.
m Adjust the burner air according to the "TECHNICAL DATA"
table.
3.6 CONNECTION TO THE SMOKE OUTLET DUCT
The smoke outlet ducts must be made of steel and in accordance with EN1443.
The combustion efficiency and the proper burner operation depend on the chimney draught. For connection to the chimney pipe, the applicable legal regulations and the following provisions must be observed:
• The chimney connection must be as short as possible and ascending (minimum height 1m);
• There must be no sharp curves or reductions in cross-section;
• Always provide a wind shield to prevent the penetration of rain water or clogging of the smoke outlet due to wind;
• The draught of the chimney pipe must not be lower than the nominal value;
• Every air heater must have its own chimney;
The following image shows how to position the chimney:
A - 3 Operating manual – IDS 900 EN
A) Minimum distance 1 m
B) As short as possible
C) Minimum distance 1 m
D) H-shaped chimney cowl
m The use of concentric pipes for smoke outlet or intake of
combustion air is expressly prohibited for these devices. It can severely and permanently affect their functioning.
04. Start-up
m The initial start-up must always be carried out by a
specialist who verifies whether the combustion parameters are correct.
m The burners are preset at the factory. This setting may
deviate from the required setting. It must therefore be checked and, if necessary, corrected during start-up.
The settings (fuel oil pressure of the burner, combustion head position, air regulation) can be found in the "TECHNICAL DATA" table.
The probe used for regular checks of the combustion and exhaust gas temperature must be inserted as follows:
NO
The combustion is stable and clean if the combustion parameters have the following values:
Bacharach index: 0 (white)
CO
: 11 ÷ 12.5 %
2
Oxygen (O
CO
): 4.5 ÷ 6 %
2
max: 500 ppm
Depending on the fuel used and on the installation conditions (height level, combustion air intake with or without air inlet etc.), readjustment of the burner may be required if the combustion parameters are incorrect.
After completion of the acceptance inspections, the hole for inserting the probe must be sealed with a material that is heat-resistant and guarantees tightness of the duct.
4.1 SWITCH-ON
• Lift the panel(n) of the control box.
• Make sure that the switch(a) is set to "0".
• Switch on the air heater using the circuit breaker at the control box. The green power indicator light(b) lights up.
• Turn the switch(a) to "H" or "V+H": the burner starts the starting or pre-purging cycle. Then the flame is ignited. After the combustion chamber has been preheated for several minutes, the main fan switches on.
EN Operating manual – IDS 900 A - 4
m In V+H operating mode, the fan runs continuously. This
also applies when the burner switches off after reaching the predefined room temperature.
m In H operating mode, the fan only operates when the
combustion chamber is sufficiently heated. When the predefined room temperature is reached, the burner switches off and the fan keeps running until the combustion chamber has cooled down completely.
In case of a failure of the air heater during start-up or operation, please refer to the "FAULTS AND TROUBLESHOOTING" chapter to find the cause for the malfunction.
m After a safety shutdown of the burner, the lamp/button
(m) lights up and the burner reset button (m) must be pressed and held for three seconds to be able to restart the air heater.
m After a safety shutdown caused by the safety thermostat
(indicator light h), you have to press the reset button(i) to be able to restart the air heater.
m Never carry out more than two consecutive restarts.
Unburned fuel oil can accumulate in the combustion chamber and might suddenly ignite during the subsequent restart.
4.2SWITCH-OFF
To switch the device off in case of manual operation, set the main switch (a) to "0". For automatically operated devices, the room thermostat must be used.
The burner stops (indicator light h goes out) while the fan keeps running. The fan switches on and off several times until the combustion chamber has cooled down completely.
m The air heater's operation must not be stopped by simply
removing the plug from the supply control panel. The electrical supply may only be interrupted after the fan has come to a standstill.
4.3VENTILATION
If you want to use the air heater for continuous ventilation only, set the switch(a) to "V".
Detection of the air outlet temperature The detected temperature [°C] is shown on the display:
Recording of the operating hours If you press the button (a) twice, the operating time in hours[h] will be displayed:
m The indicated time is not the effective heating time but
the time during which the device has been supplied with current and switched on.
Proceed as follows to reset the counter:
• Turn the device's main switch to "0" (OFF).
• Press and hold the P button of the temperature controller for at least three seconds. The word "PASS" flashes for five seconds.
• Enter the code "-481". To do so, repeatedly press the button(b) until the desired character appears. Then press the P button to confirm and move to the next character.
• Finally, press the U button: The air outlet temperature is displayed again.
4.5 CONTROL OF THE TRIGGER TEMPERATURE OF THE FAN
THERMOSTAT
Control of the trigger temperature of the fan thermostat
4.4TEMPERATURE CONTROLLER
The air heater is equipped with a temperature controller (g) with LCD display that can be used to display and control the following parameters:
• Detection of the air outlet temperature
• Recording of the operating hours
• Control of the trigger temperature of the fan thermostat
• Control of the trigger temperature of the burner thermostat
The temperature controller is programmed in a way that it automatically switches the main fan on or off depending on the temperature set for the combustion chamber. This prevents cold air from being blown out when the burner starts and the combustion chamber is not yet sufficiently heated.
It also guarantees a discharge of the internal residual heat upon switch-off.
The default temperature setting is 35°C with a hysteresis of 5°C.
A - 5 Operating manual – IDS 900 EN
The red "OUT1" LED indicates the operating condition of the fan thermostat:
• When it is illuminated, the fan is running (ON);
• When it is not illuminated, the fan is switched off (OFF).
4.6 CONTROL OF THE TRIGGER TEMPERATURE OF THE BURNER THERMOSTAT
Control of the trigger temperature of the burner thermostat
• Proper operation of the device requires regular maintenance activities. Make sure that you disconnect the air heater from the electrical power supply before starting these activities.
Maintenance
Measure
Check the air heater
Check the fuel oil supply line
Daily Weekly
x
x
Semi-
annually
Annually
The temperature controller is programmed in a way that it automatically switches the burner on or off depending on the maximum temperature set for the combustion chamber. This prevents overheating of the combustion chamber and thus triggering of safety thermostat L2, which would switch off the air heater (see also "Faults and troubleshooting" chapter).
The default thermostat setting for the maximum temperature of the combustion chamber is 95°C with a hysteresis of 5°C.
The red "OUT2" LED indicates the operating condition of the burner thermostat: The LED sequence "- = +" indicates the current temperature compared to the set temperature:
• If the red arrow above the "-" symbol lights up, the temperature is below the set value and thus the thermostat enables operation of the burner.
• If the green LED above the "=" symbol lights up, the temperature equals the set value.
• If the red arrow above the "+" symbol lights up, the temperature is above the set value and thus the thermostat disables operation of the burner.
m The trigger temperatures of the fan thermostat and burner
thermostat can be modified. However, this should only be done if it is absolutely necessary. For this purpose, please contact the Trotec service to obtain the information required for reprogramming the temperature controller.
Clean the outside of the device
Clean the motor and fan
Check the electrical connections
Check and test the burner
Check the thermostats
Clean the inside of the device
Inspect and clean the combustion chamber
x
x
x
x
x
x
x
5.1 CHECKING THE AIR HEATER AND THE FUEL OIL SUPPLY LINE
Please check the following:
• Make sure that the device is not positioned in areas with a high risk of fires or in potentially explosive atmospheres
• Make sure to maintain a safety distance from flammable
• substances
In case of fuel oil leaks:
• Close the fuel oil shut-off valve
• Locate and repair the fuel oil leak
• Do not use the machine until the removed panels have been reattached
• Make sure that the room to be heated is sufficiently ventilated
• Make sure that the air intake and outlet pipes are not blocked in any way
• Make sure that there are no sheets or blankets placed on the device
• Make sure that the device is in a firm and stable position
• Make sure that the air heater is regularly monitored during operation and checked prior to start-up
05. Care and maintenance
For a smooth operation of the device, the following tasks must be performed regularly. Please note that the power supply of the air heater must be interrupted beforehand.
m All operations described in this chapter must be carried out
by appropriately qualified personnel. Before starting work, make the following preparations:
• Switch off the device as described above in the "SWITCH­OFF" section.
• Cut off the power supply using the circuit breaker.
• Wait until the device has cooled down.
5.2 CLEANING THE OUTSIDE OF THE DEVICE
For a failure-free operation, we recommend that you clean the fol­lowing parts:
• Burner:
- Thoroughly remove dirt and residues
- Make sure that the air inlet is not clogged
• Clean the housing, lines, pipes, connectors and joints with a cloth
• Air inlet/outlet:
- Thoroughly remove dirt and residues
- Make sure that the air inlet is not clogged
EN Operating manual – IDS 900 A - 6
5.3 CLEANING THE MOTOR AND THE FAN
To clean the fan wheel and the motor, please proceed as follows:
• Loosen the fastening screws of the fan and remove the fan.
• Clean the motor with compressed air.
• Clean the fan wheel with a hard brush.
• Reinstall the fan.
5.4 CHECKING THE ELECTRICAL CONNECTIONS
After unplugging the power supply cable, check all electrical connections as follows:
• Make sure that the connections are intact and properly seated.
• Remove any dirt and corrosion or replace the connections if necessary
• Replace damaged wires or connectors if necessary
5.5 CHECKING AND TESTING THE BURNER
To access the burner:
5.8 CLEANING THE HEAT EXCHANGER AND THE COMBUSTION CHAMBER
To maintain the device's high efficiency, the cleaning work described here must be performed at least once at the end of each operating season, or several times in case of excessive soot formation. The latter can occur, for instance, if the chimney draught is not ideal, if low quality fuel is used, if the burner is improperly adjusted, or if the device is switched on and off frequently.
06. Transport and repositioning
Hold the front handles when repositioning or transporting the device. The heater will move on its rear wheels.
m Before repositioning the device, make the following prepara-
tions:
• Switch off the device.
• Interrupt the power supply by removing the plug from the socket.
• Wait until the heater has cooled down.
• Unscrew the fastening screw of the burner
• Pull out the burner and perform the inspection and cleaning work according to the instructions in the burner's operating manual
• Reattach the burner unit
• Perform the work steps required to measure the combustion parameters and ensure a stable and clean combustion, which are described in chapter4
5.6 CHECKING THE THERMOSTATS
Proceed as follows to check the thermostats:
• Remove any connection ducts from the air outlet
• Locate the thermostats mounted on the inner wall of the air heater
• Clean the thermostats with a dry cloth and pay attention not to kink or damage the capillary tube
5.7 CLEANING THE INSIDE OF THE DEVICE
For thorough cleaning the air heater can be washed with water both on the inside and on the outside.
However, you have to observe the following:
• The power cable must be removed from the socket
• All inspection panels must be completely closed
• When cleaning with a water jet, the maximum permissible pressure is 70 bar with a distance below 30 cm
• All parts must have dried completely before the power cable is reconnected
Only use the provided lifting gear for lifting the device. Attach ropes or chains to the four lifting points. Before lifting the device make sure that the lifting gear used is actually suited to lift the device. You will find the weight of the device in the technical data table.
m Do not try to lift the device with pure muscle power: The
heavy weight can cause serious physical damage.
07. Fault and troubleshooting
In case of a severe operational disruption, various safety devices can cause a safety shutdown of the device. This is signalised as follows:
• at the control box
This is the block signal indicating that safety thermostatL2 has triggered. The reset button is located inside the burner housing.
• at the burner
Safety shutdown signal indicating that the burner's flame monitoring has triggered.
m In the event of a safety shutdown, do not carry out two
consecutive restarts. Unburned fuel components can ac­cumulate in the combustion chamber and might suddenly ignite during the subsequent restart.
If the inspections and corrective measures do not produce any re­sults, please contact your nearest sales and service centre.
A - 7 Operating manual – IDS 900 EN
Malfunction Cause Troubleshooting
• Device does not start
• No power supply
• Incorrect main switch position
• Room thermostat only functions
sporadically
The safety system (burner, thermostat L2, thermal relay of the fan) was not reset after repair
• Overheating of the combustion chamber
• Tripping of thermostat L2 (warning light (9) lights up)
• Tripping of thermal relay RM (light (10) lights up)
• Overheating of the combustion chamber
• Excessive power consumption of the fan motor
• Check the functioning and position of the switch
• Check the characteristics of the electrical line
• Check the electrical connections
Check whether the fuses are intact
• Set to the right position
• Check and correct the thermostat position
• Check whether the thermostat is operational
• Press the reset button:
• Burner (button on control system)
• Thermostat L2 (button (6))
• Thermal relay of the fan (button (11))
• Check fuel supply• Tripping of thermostat L1
• Check the correct positioning of any flaps, nozzles etc.
• Remove any parts which might be stuck in the air ducts or ventilation grilles
• Check as described above
• If unsuccessful, please contact your supplier
• Heater with axial fan: Remove any obstacles from the air intake. Reduce the lengths of the air ducts
• The burner starts, the flame does not ignite and the reset indicator on the control system is illuminated
• The fan does not start or starts with a delay
• The fan makes noises or vibrates
• Irregular operation of the burner
• No power supply
• Thermostat F damaged
• Motor winding burnt or interrupted
• Motor capacitor burnt (Mod. "M")
• Motor bearing blocked
• Foreign objects on fan blades
• Insufficient air circulation
• Heater with centrifugal fan: Check the fan belt setting as described in the "CONNECTION TO AIR DUCTS" chapter
• In any case check that the power consumption is lower than the value indicated on the nameplate
• Should this situation reoccur after pressing the restart button and starting the device, please contact the technical customer service
• Check whether the fuses are intact
• Check the electrical connections
• Check, adjust or exchange the thermostat
• Exchange fan motor
• Exchange capacitor
• Exchange bearing
• Remove foreign objects
• Remove any obstacles affecting air circulation
• Insufficient heating
• Insufficient heat output of the burner
• Please contact the technical customer service
EN Operating manual – IDS 900 A - 8
08. Functional diagram and control panel
1 USCITA ARIA CALDA SORTIE AIR CHAUD WARMLUFTAUSTRITT HOT AIR OUTFLOW SALIDA DE AIRE CALIENTE
ВЫХОДГОРЯЧЕГОВОЗДУХА
2 CAMINO CHEMINEE SCHORNSTEIN CHIMNEY CHIMENEA
ДЫМОХОД
3 VENTILATORE RAFFREDDAMENTO VENTILATEUR REFROIDISSEMENT KÜHLVENTILATOR COOLING FAN VENTILADOR DE ENFRIAMIENTO
ВЕНТИЛЯТОРОХЛАЖДЕНИЯ
4 CAMERA DI COMBUSTIONE CHAMBRE DE COMBUSTION BRENNKAMMER COMBUSTION CHAMBER CÁMARA DE COMBUSTIÓN
КАМЕРАСГОРАНИЯ
5 BRUCIATORE BRULEUR BRENNER BURNER QUEMADOR
ГОРЕЛКА
6 SCAT OLA TERMOSTATI L2 BOITIER THERMOSTATS L2 THERMOSTATGEHÄUSE L2 THERMOSTATS L2 BOX CAJA DE TERMOSTATOS L2
КОРОБКАТЕРМОВЫКЛЮЧАТЕЛЕЙL2
7 STAFFE DI SOLLEVAMENTO ÉTRIERS DE LEVAGE TRAGWANGEN HOISTING BRACKETS SOPORTES DE ELEVACIÓN
ПОДЪЕМНЫЕКРОНШТЕЙНЫ
8 PIEDE / MANIGLIA SUPPORT/POIGNEE STUTZE/HANDGRIFF SUPPORT/HANDLE AYUDA Y MANIJA
НОЖКА/РУЧКА
9 RUOTA ROUE RAD WHEEL RUEDA
КОЛЕСО
10 SCATOLA BRUCIATORE BOÎTIER BRÛLEUR BRENNERGEHÄUSE BURNER BOX CAJA DEL QUEMADOR
КОЖУХГОРЕЛКИ
11 PARAURTI PARE-CHOCS PUFFER BUFFER PARACHOQUES
АМОРТИЗИРУЮЩИЕПРОКЛАДКИ
12 SCATOLA QUADRO ELETTRICO BOÎTIER TABLEAU ÉLECTRIQUE SCHALTKASTEN ELECTRICAL PANEL BOX CAJA DEL CUADRO ELÉCTRICO
КОЖУХЭЛЕКТРОШКАФА
A - 9 Operating manual – IDS 900 EN
a INTERRUTTORE RISCALDAMENTO-VENTILAZIONE INTERRUPTEUR CHAUFFAGE-VENTILATION SCHALTER HEIZUNG-LÜFTUNG HEATING-VENTILATION SWITCH INTERRUPTOR CALEFACCION/VENTILACION
ПЕРЕКЛЮЧАТЕЛЬНАГРЕВА-ВЕНТИЛЯЦИИ
b LAMPADA TENSIONE TEMOIN TENSION LEUCHTE SPANNUNG VOLTAGE LAMP TESTIGO TENSIÓN
ИНДИКАТОРНАПРЯЖЕНИЯ
c LAMPADA TERMOSTATI DI SICUREZZA L2 TEMOIN THERMOSTATS DE SURCHAUFFE, L2 KONTROLLLEUCHTE SICHERHEITSTHERMOSTATE L2 OVERHEAT THERMOSTATS CONTROL LAMP, L2 TESTIGO TERMOSTATOS DE SEGURIDAD, L2
ИНДИКАТОРПРЕДОХРАНИТЕЛЬНЫХ  ТЕРМОВЫКЛЮЧАТЕЛЕЙL2
d PRESA PER TERMOSTATO AMBIENTE PRISE THERMOSTAT D’AMBIANCE RAUMTHERMOSTAT STECKDOSE ROOM THERMOSTAT PLUG ENCHUFE TERMOSTATO AMBIENTE
РАЗЪЕМДЛЯТЕРМОСТАТАОКРУЖАЮЩЕЙСРЕДЫ
e PRESA PER FILTRO PRERISCALDO PRISE POUR FILTRE PRÉCHAUFFAGE ANSCHLUSS FÜR FILTER VORWÄRMANLAGE INTAKE FOR PRE-HEAT FILTER TOMA PARA FILTRO DE PRECALENTAMIENTO
ГНЕЗДОДЛЯФИЛЬТРАПОДОГРЕВА
f PRESSACAVO PER CAVO ALIMENTAZIONE PRESSE-CÂBLES POUR CÂBLE D‘ALIMENTATION KABELDURCHFÜHRUNG FÜR STROMVERSORGUNGSKABEL CABLE CLAMP FOR POWER CABLE PRENSACABLE PARA CABLE DE ALIMENTACIÓN
КАБЕЛЬНАЯВТУЛКАДЛЯСИЛОВОГОКАБЕЛЯ
g TERMOREGOLATORE THERMORÉGULATEUR TEMPERATURREGLER TEMPERATURE CONTROLLER TERMORREGULADOR
ТЕРМОРЕГУЛЯТОР
h LAMPADA BRUCIATORE VOYANT BRÛLEUR BRENNERANZEIGE BURNER LIGHT TESTIGO DEL QUEMADOR
ИНДИКАТОРГОРЕЛКИ
LAMPKA SYGNALIZACYJNA PALNIKA i PULSANTE DI RIARMO TERMOSTATO DI SICUREZZA, L2
POUSSOIR DE RÉARMEMENT THERMOSTAT DE SÉCURITÉ, L2 ENTSTÖRTASTE DES SICHERHEITSTHERMOSTATEN, L2 SAFETY THERMOSTAT RESET BUTTON, L2 BOTÓN DE REARME DEL TERMOSTATO DE SEGURIDAD, L2
КНОПКАСБРОСАПРЕДОХРАНИТЕЛЬНОГОТЕРМОВЫКЛЮЧАТЕЛЯ,L2
l LAMPADA BLOCCO VENTILATORE (solo per modelli trifase) TÉMOIN BLOCAGE VENTILATEUR (uniquement pour modèles triphasés) KONTROLLLEUCHTE SICHERHEITSABSCHALTUNG DES VENTILATORS (nur Modelle mit 3-Phasen-Betrieb) FAN BLOCK LAMP (for 3-phase models only) TESTIGO BLOQUEO VENTILADOR (sólo para modelos trifásicos)
ИНДИКАТОРБЛОКИРОВКИВЕНТИЛЯТОРА(толькодлятрехфазныхмоделей)
m LAMPADA / PULSANTE DI RIARMO BRUCIATORE TÉMOIN / POUSSOIR DE RÉARMEMENT BRÛLEUR LAMPE / ENTSTÖRTASTE BRENNER BURNER RESET BUTTON / LAMP TESTIGO/BOTÓN DE REARME DEL QUEMADOR
ИНДИКАТОР/КНОПКАСБРОСАГОРЕЛКИ
n PANNELLO SCATOLA QUADRO ELETTRICO PANNEAU BOÎTIER TABLEAU ÉLECTRIQUE ABDECKUNG SCHALTKASTEN ELECTRICAL PANEL BOX PANEL PANEL DE LA CAJA DEL CUADRO ELÉCTRICO
ПАНЕЛЬКОЖУХАЭЛЕКТРОШКАФА
o QUADRO ELETTRICO TABLEAU ÉLECTRIQUE SCHALTKASTEN ELECTRICAL PANEL CUADRO ELÉCTRICO
ЭЛЕКТРОШКАФ
EN Operating manual – IDS 900 A - 10
09. Circuit diagram
C Capacitor M Fan motor F Air controller FB Fuse for burner 6A TM Remote switch for fan RM Thermal relay for fan ST Indicator light SB Fan "OFF" indicator light
A - 11 Operating manual – IDS 900 EN
BR Burner TA Room thermostat PB Burner L1 Overheating protection thermostat, L1 L2 Safety thermostat with manual release, L2 RV Switch heating-stop-ventilation SL Overheating protection indicator light, L1, L2
10. Technical data
Article number Air flow rate
Fan Max. nominal heat input Nominal heat output Temperature increase* (ΔT) Input voltage
Current consumption Max. oil consumption
Air transport hose connector ø Chimney connection ø
Thermostat connection
Tank contents Sound level (distance 1m)
Length
Width
Height
Weight kg
Combustion
1.430.000.160
Type IDS 900
12,500 m³/h
axial fan
235 kW
221 kW (181,427 kcal)
47 °C
230 V / 50 Hz
12 A
21.67 l/h
1 x 700 mm** 2 x 600 mm** 4 x 400 mm**
200 mm
standard
208 l
81.3 dB(A) 2,245 mm
982 mm
1,584 mm
351 kg
indirect
* ΔT indicates the temperature increase. The outlet air temperature is calculated from ΔT + ambient temperature.
** Optionally available accessories required.
EN Operating manual – IDS 900 A - 12
11. Available accessories
Accessory Article number
Hose connector
Two-way hose distributor
Four-way hose distributor
Thermostat with 10 m cable
Connection kit for external oil tank
Oil pre-heating
Filler neck oil filter
1 x ø 700 mm, standard equipment
2 x ø 600 mm, Article no. 6.100.006.174
4 x ø 400 mm, Article no. 6.100.006.175
Article no.
6.100.007.016
Standard equipment
Article no.
6.100.006.177
Article no.
6.100.006.161
Oil tank pedestal IDS900, capacity 208 litres
Exhaust gas pipe rigid, length 1 m
90° arc connection for exhaust gas pipe
Exhaust gas pipe rain cover
Air hose Tronect SP-C³, length 7.6m
Article no.
6.100.006.176
Article no.
6.100.006.214
Article no.
6.100.006.220
Article no.
6.100.006.226
Article no.
6.100.001.273
A - 13 Operating manual – IDS 900 EN
EN Operating manual – IDS 900 A - 14
Trotec GmbH & Co. KG
Grebbener Str. 7 D-52525 Heinsberg
+49 2452 962-400
+49 2452 962-200
info@trotec.com www.trotec.com
Loading...