Owner’s Manual
1111 W. 35th Street Chicago, IL 60609 USA
Customer Support: (773) 869-1234 • www.tripplite.com
Important Safety Instructions
2
Quick Installation
3
Basic Operation
5
Storage & Service
8
Specifications
9
Copyright © 2003 Tripp Lite. All rights reserved. SmartPro®is a registered trademark of Tripp Lite.
Español
10
Français
20
UL 1778
SmartPro® & SmartPro®XL
Intelligent, Line-Interactive UPS Systems (Tower Configuration)
• 120V Input/Output • 700 - 1500VA Capacities • Extended-Run Options
Optional Installation
4
Register on-line today for a chance to win a FREE Tripp LIte product! www.tripplite.com/warranty
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the
installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these
warnings will void your warranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, conductive contaminants,
dust or direct sunlight.
• For best performance, keep the indoor temperature between between 32º F and 104º F
(0º C and 40º C).
• Leave adequate space around all sides of the UPS for proper ventilation.
UPS Connection Warnings
• Connect your UPS directly to a properly grounded AC power outlet. Do not plug the
UPS into itself; this will damage the UPS.
• Do not modify the UPS's plug, and do not use an adapter that would eliminate the UPS’s
ground connection.
• Do not use extension cords to connect the UPS to an AC outlet. Your warranty will be
voided if anything other than Tripp Lite surge suppressors are used to connect your UPS
to an outlet.
• If the UPS receives power from a motor-powered AC generator, the generator must
provide clean, filtered, computer-grade output.
Equipment Connection Warnings
• Do not use Tripp Lite UPS Systems for life-support applications in which a malfunction
or failure of a Tripp Lite UPS System could cause failure or significantly alter the
performance of a life-support device.
• Do not connect surge suppressors or extension cords to the output of your UPS. This
might damage the UPS and will void the surge suppressor and UPS warranties.
Quick Installation
1
Plug the UPS into an outlet
on a dedicated circuit.*
NOTE! after you plug the UPS into a live AC
outlet, the UPS will automatically charge its
batteries,** but will not supply power to its
outlets until it is turned ON (see Step 3
below).
* See Specifications for circuit amperage requirements.
Select models include an additional plug which can be
switched by a qualified electrician. See Specifications for
details. ** The BATTERY CHARGE LED will be the only
LED illuminated
2
Plug your equipment into
the UPS.
Note: Your UPS is designed to only support computer
equipment. You will overload the UPS if the total VA ratings for all the equipment you connect exceeds the UPS's
Output Capacity (see Specifications). To find your equipment's VA ratings, look on their nameplates. If the equipment is listed in amps, multiply the number of amps by 120
to determine VA. (Example: 1 amp × 120 = 120 VA). If you
are unsure if you have overloaded the UPS's outlets, see
“OUTPUT LOAD LEVEL” LED description.
3
Turn the UPS ON.
Press and hold the “POWER” button for one
second. The alarm will beep once briefly after
one second has passed. Release the button.
1
EXTERNAL
BATTERY
NORM DELAY
SEE MANUAL FOR
PROPER CONNECTION
2
Battery Warnings
• Your UPS does not require routine maintenance. Do not open your UPS for any reason
except battery replacement. There are no user-serviceable parts inside.
• Because the batteries present a risk of electrical shock and burn from high short-circuit
current, observe proper precautions. Unplug and turn off the UPS before performing
battery replacement. Use tools with insulated handles, and replace the existing batteries
with the same number and type of new batteries (Sealed Lead-Acid). Do not open the
batteries. Do not short or bridge the battery terminals with any object. Tripp Lite offers a
complete line of UPS System Replacement Battery Cartridges (R.B.C.). Visit Tripp Lite
on the Web at www.tripplite.com/support/battery/index.cfm to locate the specific
replacement battery for your UPS.
• The UPS batteries are recyclable. Refer to local codes for disposal requirements, or in
the USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-8-228-8379) or visit
www.rbrc.com for recycling information. Do not dispose of the batteries in a fire.
• (Select models only) If your UPS model is equipped with an external battery connector,
only connect Tripp Lite battery packs of the appropriate type and correct voltage. Do not
connect or disconnect external batteries while the UPS is operating from battery power.
• Do not attempt to connect external batteries to your UPS system if it does not include an
external battery connector.
2
3
3