TE Series 120V 600VA 425W Line-Interactive UPS,
Highlights
6 outlets (3 UPS/surge, 3
surge-only)
Automatic Voltage Regulation
(AVR) corrects brownouts and
overvoltages
Larger scale battery produces
significantly longer runtimes
Serial port works with software to
facilitate unattended shutdown
$200,000 Ultimate Lifetime
Insurance (U.S., Canada, and
Puerto Rico only)
Package Includes
TE600 UPS System
Warranty information
Instruction manual
AVR, Tower, DB9 Serial port
MODEL NUMBER: TE600
Description
Tripp Lite's TE600 UPS System provides line-interactive voltage regulation and long lasting battery support for small business telephone systems, voicemail
systems, personal computers and other communications, network and telecom applications. 600VA power handling capacity and large capacity battery
system maintains continuous operation through power interruptions with over 1 hour runtime for many phone systems. Line interactive voltage regulation
maintains normal 120 volt output levels during brownouts as low as 75 and overvoltages as high as 147, saving battery reserves for use only during complete
power failures. Unique design features 6 protected outlets (3 UPS supported & 3 surge-suppression only), diagnostic LEDs and a built-in serial port that works
with PowerAlert Software and cabling to provide automatic unattended shutdown of network and PC applications (part# 75-0195). $200,000 Ultimate Lifetime
Insurance (U.S., Canada, and Puerto Rico only).
Features
Provides connected equipment with continuous power during short and long duration loss of commercial power
Line-interactive voltage regulation corrects brownouts and overvoltages from 75 to 147 volts back to usable 120V output levels, without using battery
power
Supports loads up to 600VA/425 watts
22 minutes half load runtime (300VA/210 watts), 7 minutes full load runtime (600VA/425 watts)
6 protected outlets total (3 UPS Supported & 3 surge-suppression only); 6-ft. cord
DB9 serial network interface
Complete surge protection and EMI/RFI noise filtering
$200,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)
4 diagnostic LEDs indicate AC present, on battery, voltage correction & battery low/replace
Battery replacement door
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 600
Output Watt Capacity (Watts) 425
Nominal Output Voltage(s)
Supported
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles (6) 5-15R
UPS Output Receptacles (Surge
Suppression Only)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) PWM sine wave
INPUT
Rated input current (Maximum Load) 12A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-15P
UPS Input Cord Length (ft.) 6
UPS Input Cord Length (m) 1.8
115V; 120V
-18%, +8%
115V (+/- 5%)
3 UPS outlets, 3 surge-only outlets
Recommended Electrical Service 15A 120V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 9 min. (600w)
Half Load Runtime (min.) 22 min. (300w)
DC System Voltage (VDC) 12
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access Battery access door
Expandable Runtime No
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage Correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage Correction Input voltages between 93 and 107 are boosted by 14%
Less than 6 hours from 10% to 90%
(quantity 2)
RBC52