Highlights
6 outlets (3 UPS/surge, 3 surge-only)
Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages
Larger scale battery produces significantly longer runtimes
Serial port works with software to facilitate unattended shutdown
$200,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
Description
Tripp Lite's TE600 UPS System provides line-interactive voltage regulation and long lasting battery support for small business telephone systems,
voicemail systems, personal computers and other communications, network and telecom applications. 600VA power handling capacity and large
capacity battery system maintains continuous operation through power interruptions with over 1 hour runtime for many phone systems. Line
interactive voltage regulation maintains normal 120 volt output levels during brownouts as low as 75 and overvoltages as high as 147, saving battery
reserves for use only during complete power failures. Unique design features 6 protected outlets (3 UPS supported & 3 surge-suppression only),
diagnostic LEDs and a built-in serial port that works with PowerAlert Software and cabling to provide automatic unattended shutdown of network and
PC applications (part# 75-0195). $200,000 Ultimate Lifetime Insurance (USA & Canada Only).
Applications
Small business telephone systems, voicemail systems, hubs, routers, bridges, concentrators, IP telephony, desktop PCs, small network fileservers and more.
Package Includes
TE600 UPS System Warranty information Instruction manual
Features
Provides connected equipment with continuous power during short and long duration loss of commercial power Line-interactive voltage regulation corrects brownouts and overvoltages from 75 to 147 volts back to usable 120V output levels, without using battery power Supports loads up to 600VA/425 watts 22 minutes half load runtime (300VA/210 watts), 7 minutes full load runtime (600VA/425 watts) 6 protected outlets total (3 UPS Supported & 3 surge-suppression only); 6-ft. cord DB9 serial network interface Complete surge protection and EMI/RFI noise filtering $200,000 Ultimate Lifetime Insurance (USA & Canada Only) — 2 year product warranty — No warranty cards required for coverage! 4 diagnostic LEDs indicate AC present, on battery, voltage correction & battery low/replace Battery replacement door
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V AC
Frequency compatibility
60Hz
OUTPUT
Output VA 600
Output watts 425
Output nominal voltage
120V AC
Output voltage regulation
LINE MODE: Sine wave line voltage 120V (-18% / +8%) BATTERY MODE: PWM sine wave output 120V +/-5%
Output frequency regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 6 NEMA 5-15R
INPUT
Maximum input amps 12A / 1440 watts
Input connection type NEMA 5-15P, right-angle plug
Input cord length 6 ft., 14 gauge
Recommended Electrical Service
15A 120V
BATTERY
Full load runtime 9 minutes (600VA)
Half load runtime 22 minutes (300VA)
DC system voltage 12 VDC
Typical battery lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
Replacement Battery Cartridge
RBC52 (quantity 2)
VOLTAGE REGULATION
Voltage regulation description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 75V and overvoltages to 147V
Overvoltage correction
Input voltages between 128 and 147V AC are reduced by 12%
Direct pass through Input voltages between 108 and 127V AC are passed on to connected equipment unchanged
Brownout correction Input voltages between 93 and 107V AC are boosted by 14%
Severe brownout correction
Input voltages between 75 and 92V AC are boosted by 30%
LEDS ALARMS & SWITCHES
Front panel LEDs 4 front panel LEDs indicate line power status, battery power status, battery low/replace status and voltage regulation
operation
Alarms Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches Includes 2 front panel switches — one main on/off power switch and one dual function "alarm cancel" / "self test" button
SURGE / NOISE SUPPRESSION
AC surge suppression 480 joules
Loading...
+ 2 hidden pages