Highlights
6 outlets
Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages
Larger scale battery produces significantly longer runtimes
Serial port works with software to facilitate unattended shutdown
$200,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
Description
Tripp Lite's TE1200 UPS System provides line-interactive voltage regulation and long lasting battery support for mid-size business telephone
systems, voicemail systems, personal computers and other communications, network and telecom applications. 1200VA power handling capacity
and large capacity battery system maintains continuous operation through power interruptions with over 2 hours runtime for many phone systems
and over 1 hour for larger systems. Line interactive voltage regulation maintains normal 120 volt output levels during brownouts as low as 75V and
overvoltages as high as 147V, saving battery reserves for use only during complete power failures. Includes 6 outlets, diagnostic LEDs and a built-in
serial port that works with Free PowerAlert Software and cabling to provide automatic unattended shutdown of network and PC applications.
$200,000 Ultimate Lifetime Insurance (USA & Canada Only).
Package Includes
TE1200 UPS System Warranty information Instruction manual
Features
Provides connected equipment with continuous power during short and long duration loss of commercial power Line-interactive voltage regulation corrects brownouts and overvoltages from 75 to 147 volts back to usable 120V output levels, without using battery power Supports loads up to 1200VA/940 watts 16 minutes half load runtime (600VA/470 watts), 7 minutes full load runtime (1200VA/940 watts) 6 protected outlets; 6-ft. cord DB9 network interface Complete surge protection and EMI/RFI noise filtering $200,000 Ultimate Lifetime Insurance (USA & Canada Only 5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace Battery replacement door
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
1200
Output kVA capacity (kVA) 1.2
Output Watt Capacity (watts)
940
Nominal Output Voltage(s) Supported
115V; 120V
Frequency compatibility 60 Hz
Output voltage regulation (line mode)
-18%, +8%
Output voltage regulation (Battery mode)
115V (+/- 5%)
Built-in UPS output receptacles
6 5-15R outlet(s)
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
PWM sine wave
INPUT
Rated input current (at maximum load)
8.25A
Nominal Input Voltage(s) Supported
120V AC
UPS input connection type 5-15P
UPS Input cord length (ft.) 6
UPS Input cord length (m) 1.8
Recommended Electrical Service
15A 120V
BATTERY
Full load runtime (minutes) 7 min. (940w)
Half load runtime (minutes) 16 min. (470w)
DC system voltage (VDC) 36
Battery recharge rate (included batteries)
Less than 8 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement)
RBC53
Battery Access Battery access door
VOLTAGE REGULATION
Voltage regulation description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage correction Input voltages between 93 and 107 are boosted by 14%