SmartOnline SV Series 60kVA Medium-Frame
Modular Scalable 3-Phase On-Line DoubleConversion 208/120V 50/60 Hz UPS System, No
SVBM Battery Modules
MODEL NUMBER: SV60KM3P0B
3-phase 60kVA UPS system offers network-grade power protection in a highly configurable, modular and
scalable medium-chassis rack-width frame. External batteries required to operate.
Description
The SV60KM3P0B SmartOnline® SV Series 60kVA 3-Phase On-Line Double-Conversion UPS System
delivers true scalability and offers the highest level of secure, uninterrupted power protection. Featuring a
modular, scalable design with high-efficiency voltage and frequency independent (VFI) operation, this online UPS system is ideal for protecting a variety of critical IT systems.
Highlights
●
Scalable capacity up to 80kVA
(or 60kVA with N+1 fault
tolerance)
●
Economy mode option helps
reduce operating and cooling
costs
●
Pre-installed WEBCARDLX
network interface for 24/7
remote access
●
DSP/IGBT technology and 1%
output voltage regulation
●
External batteries required to
operate
Package Includes
SV60KM3P0B SmartOnline SV
Series 60kVA 3-Phase On-Line
Double-Conversion UPS System
Pre-installed WEBCARDLX
network interface
(3) SV20PM 20kVA power
modules (shipped separately)
Owner’s manual
The SV60KM3P0B includes pre-installed input, bypass and output breakers, as well as a static transfer
switch (STS) and three 20kVA SV20PM power modules. Space is included for one additional userinstallable SV20PM power module. External ±120VDC battery options, such as BP240V370 or
EBP240VXXX series battery cabinets, are available from Tripp Lite for extended runtime.
The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS
status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or
SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network.
With up to 92% efficiency in standard mode and up to 99% efficiency in optional economy mode, this
60kVA UPS system helps you reduce operating and cooling costs. Automatic and manual bypass options
keep connected equipment operational during routine maintenance or critical power module failure. Frontpanel display offers full UPS condition and status reporting.
Features
60kVA 54kW 3-Phase Medium-Chassis UPS SystemSupports 208/120V or 220/127V AC 50/60Hz Wye
4-wire plus Earth hardwire input and output wiringDual hardwire input design enables operation from up to
2 power sourcesNetwork-grade sine-wave AC output with 1% output voltage regulation and less than 1%
output total harmonic distortionTested to UL 1778 (U.S.), CSA (Canada) and NOM (Mexico)
standardsHigh 0.9 power factor for maximum power to the connected load
Pre-Installed WEBCARDLX Network InterfaceAllows full remote access for power monitoring,
configuration, control and email notifications via secure web browser, SNMP, telnet or SSHSupports
10/100 Mbps auto-sensing for communication with an Ethernet networkOptional EnviroSense2 sensors
(sold separately) enable site monitoring of temperature, humidity and contact-closure statusNo Java
1 / 6
required
Modular, Scalable Design for Maximum FlexibilityModular configuration with hot-swappable power
modules and batteries enables easy, fast maintenance with zero downtimeOpen slot for 1 additional
20kVA SV20PM power module accommodates increased capacity up to 80kVA (or 60kVA with N+1 fault
tolerance)Supports external ±120VDC battery options for extended runtimes
Optional Economy ModeUp to 99% efficient in optional economy mode to lower operating and cooling
costs
Wide Input/Narrow Output Voltage Operating RangeEnables full continuous online operation during
brownouts as low as 121V and overvoltages up to 253VRegulates output voltage within 1% of the
selected nominal output voltage in on-line double-conversion mode
Advanced IGBT Inverter with Digital Signal Processor (DSP) TechnologyProvides for less than 2%
input total harmonic distortion (THDi) to support 1:1 generator sizing and prevent the need to oversize
generator systems relative to UPS capacity
Automatic and Manual Bypass OptionsKeep connected equipment operational during routine
maintenance or critical power module failure
Specifications
OVERVIEW
UPC Code 037332237477
UPS Type On-Line
INPUT
Rated input current (Maximum Load) SV60KM3P0B 60kVA Configuration: 180A; Maximum 80kVA Configuration: 240A; 306A maximum inrush current
Nominal Input Voltage(s) Supported 120/208V 3-PH Wye; 127/220V 3-PH Wye
Nominal Input Voltage Description Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power
UPS Input Connection Type Hardwire
Input Circuit Breakers MAIN and ALTERNATE AC inputs are each protected by 300A 3 pole magnetic breakers
Input Phase 3-Phase
Input Frequency 40 to 70Hz (online mode); 50/60Hz Auto-selectable
Power Factor (Input) Greater than 0.99 (full load)
THDi Less than 2% (full linear load)
OUTPUT
Output Volt Amp Capacity (VA) 60000
Output kVA Capacity (kVA) 60
Output Watt Capacity (Watts) 54000
Output kW Capacity (kW) 54
Output Capacity Details OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1
Power Factor 0.9
sources
minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to
100% or less
Crest Factor 3:1