Tripp-Lite SV20KS1P0B Data Sheet

Tripp-Lite SV20KS1P0B Data Sheet

SmartOnline SV Series 20kVA Small-Frame Modular Scalable 3-Phase On-Line DoubleConversion 208/120V 50/60 Hz UPS System, No SVBM Battery Module

MODEL NUMBER: SV20KS1P0B

3-phase 20kVA UPS system offers network-grade power protection in a highly configurable, modular and scalable small-chassis rack-width frame. External batteries required to operate.

Description

The SV20KS1P0B SmartOnline® SV Series 20kVA Small-Frame 3-Phase On-Line Double-Conversion UPS System delivers true scalability and offers the highest level of secure, uninterrupted power protection. Featuring a modular, scalable design with high-efficiency voltage and frequency independent

(VFI) operation, this on-line UPS system with a high 0.9 power factor is ideal for protecting a variety of critical IT systems.

The SV20KS1P0B includes pre-installed input, bypass and output breakers, as well as a static transfer switch (STS) and one 20kVA SV20PM power module. Space is included for up to two additional userinstallable SV20PM power modules. External ±120VDC battery options, such as BP240V370 or EBP240VXXX series battery cabinets, are available from Tripp Lite for extended runtime.

The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or

SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network.

With up to 92% efficiency in standard mode and up to 98% efficiency in optional economy mode, this 20kVA UPS system helps you reduce operating and cooling costs. Automatic and manual bypass options keep connected equipment operational during routine maintenance or critical power module failure. Frontpanel display offers full UPS condition and status reporting.

Features

20kVA 18kW 3-Phase Small-Chassis UPS SystemSupports 208/120V or 220/127V AC 50/60Hz Wye 4- wire plus Earth hardwire input and output wiringDual hardwire input design enables operation from up to 2 power sourcesNetwork-grade sine-wave AC output with 1% output voltage regulation and less than 2% output total harmonic distortionTested to UL 1778 (U.S.), CSA (Canada) and NOM (Mexico) standardsHigh 0.9 power factor offers higher kW output than lower-rated competing legacy designs

Pre-Installed WEBCARDLX Network InterfaceAllows full remote access for power monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or SSHSupports 10/100 Mbps auto-sensing for communication with an Ethernet networkOptional EnviroSense2 sensors

Highlights

Scalable capacity up to 60kVA (or 40kVA with N+1 fault tolerance)

Economy mode option helps reduce operating and cooling costs

Pre-installed WEBCARDLX network interface for 24/7 remote access

DSP/IGBT technology and 1% output voltage regulation

No internal batteries and requires external batteries to operate

Package Includes

SV20KS1P0B SmartOnline SV Series 20kVA Small-Frame 3- Phase On-Line DoubleConversion UPS System

Pre-installed WEBCARDLX network interface

(1) SV20PM 20kVA power module (shipped separately)

Owner’s manual

1 / 6

(sold separately) enable site monitoring of temperature, humidity and contact-closure statusNo Java required

Modular, Scalable Design for Maximum FlexibilityModular configuration with hot-swappable power and battery modules enables easy, fast maintenance with zero downtimeOpen slots for up to 2 additional 20kVA SV20PM power modules accommodate increased capacity up to 60kVA (or 40kVA with N+1 fault tolerance)External battery pack options available for even more extended runtimeSupports external

±120VDC battery options for extended runtimes

Optional Economy ModeUp to 98% efficient in optional economy mode to lower operating and cooling costs

Wide Input/Narrow Output Voltage Operating RangeEnables full continuous online operation during brownouts as low as 121V and overvoltages up to 253VRegulates output voltage within 1% of the selected nominal output voltage in on-line double-conversion mode

Advanced IGBT Inverter with Digital Signal Processor (DSP) TechnologyProvides for less than 3% input total harmonic distortion (THDi) to support 1:1 generator sizing and prevent the need to oversize generator systems relative to UPS capacity

Automatic and Manual Bypass OptionsKeep connected equipment operational during routine maintenance or critical power module failure

Specifications

OVERVIEW

UPC Code

037332237422

 

 

UPS Type

On-Line

 

 

INPUT

 

Rated input current (Maximum Load)

SV20KS1P0B 20kVA Configuration: 60A; Maximum 60kVA Configuration: 180A; 132.5A maximum inrush current

 

 

Nominal Input Voltage(s) Supported

120/208V 3-PH Wye; 127/220V 3-PH Wye

 

 

Nominal Input Voltage Description

Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, E) inputs from two separate power

 

sources

 

 

UPS Input Connection Type

Hardwire

 

 

Input Circuit Breakers

MAIN and ALTERNATE AC inputs are each protected by 250A 3 pole magnetic breakers

 

 

Input Phase

3-Phase

 

 

Input Frequency

40 to 70Hz (online mode); 50/60Hz Auto-selectable

 

 

Power Factor (Input)

Greater than 0.99 (full load)

 

 

THDi

Less than 3% (full linear load)

 

 

OUTPUT

 

Output Volt Amp Capacity (VA)

20000

 

 

Output kVA Capacity (kVA)

20

 

 

Output Watt Capacity (Watts)

18000

 

 

Output kW Capacity (kW)

18

 

 

Output Capacity Details

OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1

 

minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to

 

100% or less

 

 

Power Factor

0.9

 

 