Tripp Lite SURBC2030 User Manual

Owner’s Manual
1111 W. 35th Street • Chicago, IL 60609 USA
(773) 869-1234 • www.tripplite.com
Copyright ©2007 Tripp Lite. All rights reserved.
SmartOnline™ is a trademark of Tripp Lite.
Internal Battery Packs
For use with Tripp Lite SmartOnline™3-Phase
UPS Systems that accept internal battery pack connection.
Model #: SURBC2030
Warranty
Registration:
register online today for a chance
to win a FREE Tripp Lite product—
www.tripplite.com/warranty
Important Safety Warnings
Adding or Replacing Internal Batteries
Warranty & Warranty Registration
1
2
5
Español
6
11
Important Safety Warnings
SAVE THESE INSTRUCTIONS! This owner's manual contains important instructions and warnings that must be followed during the installation and operation of SURBC2030 Internal Battery Packs. The owner's manuals included with compatible products (UPS systems and battery module compartments) include additional safety instructions that must be followed during installation and operation. Failure to heed these instructions may cause permanent damage to the UPS system (voiding its warranty) and create a potential for serious personal injury or death from lethal high voltage.
• Do not use Tripp Lite UPS Systems or Internal Battery Packs in life support applications in which a malfunction or failure of a Tripp Lite UPS System or Internal Battery Pack could cause failure or significantly alter the performance of a life support device.
• The UPS system contains its own energy source (battery). The output terminals may be live even when the UPS is not connected to an AC supply.
• Your UPS does not require routine maintenance. Do not open the UPS's power module for any reason; there are no user-serviceable parts inside. Because of the risk of electrical shock, only qualified electricians should open the battery module.
• Because the batteries present a risk of electrical shock and burn from high short-circuit current, batteries should be changed only by trained service personnel observing proper precautions. Remove watches, rings, and other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of the batteries. Do not short or bridge the battery terminals with any object.
• Do not dispose of the batteries in a fire. The UPS batteries are recyclable. Refer to local codes for disposal requirements, or in the USA only, refer to these sources for recycling information: 1-800-SAV-LEAD (1-800-728-5323), 1-800-8-BATTERY (1-800-8-228-8379), or www.rbrc.com.
• Internal batteries must be replaced by equivalent batteries available from Tripp Lite.
• Do not operate your UPS without batteries.
• Battery fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
• Potentially lethal voltages exist within this unit as long as the battery supply is connected. Service and repair should be done only by trained personnel. During any service work, the UPS should be turned off or put into manual bypass.
• Do not connect or disconnect the battery modules while the UPS is operating from the battery supply or when the unit is not in bypass mode.
1
2
Adding or Replacing Internal Batteries
DANGER!
POTENTIALLY LETHAL HIGH VOLTAGE! FOR QUALIFIED ELECTRICIANS ONLY!
Follow all safety precautions in the Safety section before adding or replacing internal batteries.
DANGER!
DO NOT REMOVE BATTERY SLEEVE!
Do not remove the plastic sleeve covering the battery strings.The sleeve is designed to prevent accidental contact with the terminals on the individual batteries. Contact with the terminals will create a potential for serious injury or death from lethal high voltage. Do not allow tools or other metal objects to come in contact with the terminals.
CAUTION!
BATTERY PACKS ARE HEAVY!
Use assistants as needed.
WARNING!
CHECK BATTERY PACK VOLTAGE BEFORE COMPLETING INSTALLATION
Do not install battery packs with DC voltages outside the acceptable range. (They may compromise battery backup capabilities).
NOTE!
Each battery pack consists of two strings of batteries: one string with a BLACK cable and one string with a RED cable.
The batteries are designed for hot-swap replacement, which allows connected equipment to continually receive AC mains power (but not battery backup support in the event of a blackout) during the battery installation procedure. See “Operation of Manual Bypass Switch” in the Operation section of the UPS System’s owner’s manual. Although the batteries can be hot-swapped, qualified service personnel may want to completely turn the UPS off during battery installation. See “Turning the UPS Off” in the Operation section of the UPS System’s owner’s manual.
Internal battery packs must be replaced by equivalent batteries available from Tripp Lite. Adding battery packs will increase recharge time. Individual models may vary slightly from diagrams.
INTERNAL BATTERY PACK WIRING DIAGRAM
Qualified service personnel should familiarize themselves with the battery pack wiring diagram prior to adding or replacing batteries. The battery module can accept up to four battery packs (each pack consisting of two strings). The diagram shows all four battery packs connected for illustrative purposes only. The actual number of batteries shipped with the UPS System varies depending on model number.
White wire
Blue wire
Red wire (+)
Black wire (–)
UPS System Battery Back
Connector
UPS System Battery Back
Connector
Fuse Block Bracket
3
Adding or Replacing Internal Batteries
(continued)
Place the UPS System in Bypass Mode or completely turn it off, depending on preference. See “Operation of Manual Bypass Switch” or “Turning the UPS Off” in the Operation section of the UPS System’s owner’s manual.
1
Remove battery access panel, located on the FRONT of the UPS system.
2
Disconnect the RED and BLACK cables attached to each internal battery pack.
3
Remove the battery cartridge fuses from each fuse block. Save the fuses.
4
Disconnect the BLUE and WHITE jumper cables attached to each fuse block.
5
CAUTION!
When disconnecting the jumper cables, pull them straight away from the fuse block with even force. Do not wiggle them side-to-side, as this may damage the connector.
Remove the fuse block bracket.
6
Slide the battery string with the RED cable into an empty slot within the battery compartment as shown. Make sure that the string is oriented as shown in the diagram .
NOTE: If the auxiliary battery connector is in the way, remove its mounting screw and position the cable to allow adequate room to add the battery strings .
7B
7A
7
7A
7B
TERMINALS
4
Slide the battery string with the BLACK cable next to it (on the left) in the empty slot as shown. Make sure that the string is oriented as shown in the diagram .
8A
8
8A
Replace the fuse block bracket. Make sure printing on bracket is oriented so it is readable.
9
TERMINALS
Adding or Replacing Internal Batteries
(continued)
DANGER!
BATTERY CARTRIDGE FUSES MUST BE INSERTED LAST DUE TO THE DANGER OF POTENTIAL ARCING OF CONNECTORS.
FUSE REPLA
CEMENT
The fuses protect against short circuit damage. If a heavy overload or short circuit is encountered, a fuse will blow. A battery pack with a blown fuse will not deliver any output voltage to the UPS system.
DANGER!
The fuses must be replaced by a qualified electrician. To reduce the risk of fire, replace only with fuses of the same type or rating (UL­recognized 30A 600VDC rated cartridge fuses).
Use a voltmeter (user-supplied) to test the voltage of the battery pack. Observe proper polarity: connect the voltmeter's BLACK probe to the battery pack's BLACK connector; connect the voltmeter's RED probe to the battery pack's RED connector. To get a proper reading, make sure the voltmeter's probes touch the metal contacts inside the battery pack's connectors. The battery pack's Acceptable DC Voltage Range is between 220 and 280V DC. If several attempts at voltmeter tests yield results outside this range, contact Tripp Lite for assistance in determining the possible causes of the incorrect voltage reading.
12
Connect the BLUE and WHITE jumper cables on each internal battery pack to its corresponding fuse block. See printing next to fuse block to locate the correct fuse block for each cable.
10
Insert the battery cartridge fuses into each fuse block. The fuses are identical, and can be inserted into any of the blocks. Make sure that the fuses are firmly snapped into place.
11
240
5
Adding or Replacing Internal Batteries
(continued)
Connect the BLACK cable for each internal battery pack to the nearest BLACK connector located inside the UPS system's battery module.
Connect the RED cable for each internal battery pack to the nearest RED connector located inside the UPS system's battery module.
Replace the battery access panel.
Return the UPS System to Normal Mode or completely turn it on, depending on the procedure you followed in step 1. See “Operation of Manual Bypass Switch” or “Turning the UPS On” in the Operation section of the UPS System’s owner’s manual.
15 16
13
14
WARNING!
OBSERVE PROPER POLARITY!
Connect BLACK-to-BLACK and RED-to-RED. Failure to observe proper polarity will cause permanent damage to the UPS System and create a potential for serious personal injury.
Warranty & Warranty Registration
LIMITED WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of 2 years (except U.S., Canada and Mexico: 1 year) from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty includes parts and Tripp Lite service center labor. Onsite service plans are available from Tripp Lite through authorized service partners (in most areas). Contact Tripp Lite Customer Service at (773) 869-1234 for details. International customers should contact Tripp Lite support at intlservice@tripplite.com
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction).
Tripp Lite; 1111 W.35th Street; Chicago IL 60609; USA WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the
manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application.
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product.You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!* * No purchase necessary.Void where prohibited. Some restrictions apply.See website for details.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information.When requesting compliance information for this product, always refer to the series number.The series number should not be confused with the marking name or model number of the product.
Tripp Lite follows a policy of continuous improvement. Product specifications are subject to change without notice.
Loading...
+ 11 hidden pages