Tripp Lite SmartOnline SU3000RTXL3U Specifications

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU3000RTXL3U
Highlights
3000VA / 3kVA / 2400 watt on-line double-conversion 3U rack/tower UPS
110/120V +/-2% output at 50/60Hz, high efficiency economy mode option
Expandable runtime, Hot-swap batteries, 26 in. / 66cm installed depth
USB, RS232 & EPO ports; support for SNMP/WEB card options
Front panel status LEDs with detailed load and battery metering
2 independently switchable output load banks
NEMA L5-30P input; L5-30R, 5-15/20R & 5-15R outlets
Description
3000VA on-line, double-conversion UPS system for critical server, network and telecommunications equipment. 3U rackmount form factor with an
installed depth of 26 inches. Expandable battery runtime with optional BP72V15-2U (limit 1) and BP72V28RT-3U (multi-pack compatible) external
battery packs. Full time sine wave 110 or 120V output with +/-2% voltage regulation. Online, double-conversion Uninterruptible Power Supply (UPS)
actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output. Operates continuously
without using battery power during brownouts to 65V and overvoltages to 150V. Highly efficient operation in optional economy mode saves BTU heat
output and energy costs. NEMA L5-30P input plug. NEMA 5-15, NEMA 5-15/20R and NEMA L5-30R output receptacles. Network-grade AC surge
and noise suppression. Zero transfer time between AC and battery operation. Network management interfaces support simultaneous
communications via USB port, DB9 serial port and SNMPWEBCARD slot. Built-in DB9 port offers both enhanced RS-232 enabled monitoring data,
plus contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions
via all 3 network interfaces. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Integrated
two-bank PDU switching supports load shedding and remote reboot of connected equipment. 3-stage metered current monitoring and battery
charge status LEDs. LED display panel easily rotates for viewing in rackmount or tower configurations. Dataline surge suppression for dialup, DSL
or network Ethernet connection. Utility power and voltage regulation LEDs. Audible alarm. Self-test. Fault-tolerant auto-bypass mode. 4-post
rackmount accessories included; 2-9USTAND tower kit and 2POSTRMKITWM 2-post rackmount accessories available. Field-replaceable,
hot-swappable internal batteries and external battery packs. Attractive all-black color scheme. $250,000 connected equipment insurance;
Package Includes
SU3000RTXL3U UPS System PowerAlert Software and Cabling Mounting hardware for 4 post rack enclosures Instruction manual
Features
SmartOnline high performance UPS system is ideal for critical voice, data, medical and industrial network applications True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 110/120V (user selectable) under all usage conditions
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 110/120V (+/-2%) values Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W) Expandable battery runtime with optional BP72V15-2U (limit 1) and BP72V28RT-3U (no limit) external battery packs Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual) Compact rackmount form factor installs using only 3 rack spaces (3U) with a maximum installed depth of 26 inches Ships with all mounting accessories for 4 post rackmount installation Optional 2POSTRMKITWM enables 2 post rackmount installation (not wallmount compatible) Optional 2-9USTAND accessory enables small-footprint upright tower placement Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment and UPS line to battery power voltage setpoints Built-in Emergency Power Off (EPO) interface with cable NEMA L5-30P input plug; NEMA 5-15/20R & L5-30R output receptacles Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each bank has four outlets) Front panel LEDs offer current monitoring and battery charge level information UPS ships fully assembled in full compliance with DOT regulations; no time consuming connection of internal batteries by user required Single line TEL/DSL or network ethernet line surge suppression $250,000 Ultimate Lifetime Insurance
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
3000
Output kVA capacity (kVA)
3
Output Watt Capacity (watts)
2400
Output kW capacity 2.4
Output power factor 0.8
Crest Factor 3:1
Nominal Output Voltage(s) Supported
110V; 120V
Nominal Voltage details
120V default
Frequency compatibility
50 / 60 Hz
Frequency compatibility details
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 2%
Built-in UPS output receptacles
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)
Built-in controllable switched load banks
Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)
Output circuit breaker 15A branch rated (x2) - each breaker protects 4 outlets, L5-30R is unbreakered
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum load)
24A
Nominal Input Voltage(s) Supported
110V AC; 120V AC
UPS input connection type
L5-30P
Input circuit breaker 40A
UPS Input cord length (ft.)
10
UPS Input cord length (m)
3
Recommended Electrical Service
30A 120V
BATTERY
Full load runtime (minutes)
5 min. (2400w)
Half load runtime (minutes)
14 min. (1200w)
Expandable battery runtime
Supports extended runtime with optional external battery packs
External battery pack compatibility
BP72V15-2U (limit 1); BP72V28RT-3U (multi-pack compatible)
DC system voltage (VDC)
72
Battery recharge rate (included batteries)
Less than 6 hours from 10% to 80%
Replacement battery cartridge (internal UPS battery replacement)
RBC96-3U (quantity 1)
Battery Access Front panel battery access door