Tripp Lite SMART2200RMXL2U Product Description

Page 1
Smart Pro 2U Rack/Tower Extended Run UPS
Line interactive, sine wave UPS with integrated switched PDU and current monitoring
DESCRIPTION
2200VA line interactive UPS system for server, network and telecommunications equipment. 2U rackmount or tower form factor with an
3U external battery packs.
derived AC output during power failures and extreme voltage variations. Line
interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during brownouts and one level of voltage cut during
20P input plug (with
grade AC surge and noise suppression. Network
compliant USB
in power management and auto shutdown features of Windows and Mac OS X. Supports
test data and utility power conditions via all 3 network interfaces. Includes
bank PDU switching supports load
stage metered current monitoring and battery charge status LEDs. Utility power and
9USTAND tower kit and 2POSTRMKITWM two
KEY BUYING POINTS
Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during brownouts and one level of voltage cut
in power management and auto shutdown features of Windows and Mac
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers,
voltage, output current monitoring, battery charge
15/20R output
Model #: SMART2200RMXL2U
2200VA / 2.2kVA line interactive, extended-run 2U rack / tower UPS Maintains sine-wave 100/110/120V nominal output over an input range of 83 to 145V Network communications supported via HID enabled USB port, DB9 serial port, SNMP/Web
card slot and EPO interface Current monitoring and switched PDU control via 3 individually controllable load banks
Input: NEMA 5-20P (120V 20A / includes 5-15P plug 120V 15A) / Output: 4 NEMA 5­15/20R, 4 NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
installed depth of only 19 inches. Expandable battery runtime with optional BP48V24-2U and BP48V60RT­Uninterruptible Power Supply (UPS) switches to battery-
overvoltages to maintain regulated 100, 110, 120v selectable output over an input range of 83-145V. Includes NEMA 5­NEMA 5-15P plug option) and both NEMA 5-15R and 5-15/20R output receptacles. Network­management interfaces support simultaneous communications via USB port, DB9 serial port and SNMPWEBCARD slot. HID­interface enables full integration with built­simultaneous detailed monitoring of equipment load levels, self­PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Integrated 3­shedding and remote-reboot of connected equipment. 3­voltage regulation LEDs. Audible alarm. Self-test. 4-post rackmount accessories included; 2­post rack & wallmount accessories available. Field-replaceable, hot-swappable internal batteries and external battery packs. Attractive all­black color scheme. 2-year warranty and $250,000 connected equipment insurance; extended warranty and service contracts available
SmartPro line interactive UPS system is ideal for voice, data, medical and industrial networking applications
during overvoltages
Maintaints continuous operation through blackouts, voltage fluctuations and surgesCorrects line voltage conditions as low as 83V and as high as 145 back to selectable 100/110/120V nominal valuesStandard internal battery set offers 16 minutes at half load (800w) and 6 minutes at full load (1600w)Optional BP48V24-2U and BP48V60RT3U external rack/tower battery packs enable extended runtime operationCompact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 inchesShips with all mounting accessories for 4 post rackmount installationOptional 2POSTRMKITWM enables 2 post rackmount or wallmount installationOptional 2-9USTAND accessory enables small-footprint upright tower placementNetwork interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slotHID compliant USB interface enables integration with built-
OS X
with the built-in ability to shutdown any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-
current, battery capacity, AC line frequency, timed inverter sutoff, activate self-test, load bank output power control and remote reboot
Built-in Emergency Power Off (EPO) interface with cableNEMA 5-20P input plug (user-installable NEMA 5-15P replacement plug included) / NEMA 5-15R & NEMA 5-
receptacles
Page 2
Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (Each
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user
TYPICAL APPLICATIONS
Ideal for protection of critical 120V equipment in server rooms, internetworking closets and telecommunications systems in rackmount
or tower applications. Common applications include corporate or departmental servers, workstations, hubs, routers, bridges, CAD/CAM
OPTIONS & ACCESSORIES
PACKAGE INCLUDES
COMPLETE SPECIFICATIONS
bank controls 1 outlet per load bank)
Front panel LEDs offer current monitoring and battery charge level information
required
2 year manufacturer's product warranty, $250,000 ULtimate Lifetime Insurance
workstations, concentrators, IP telephony and traditional PBX switching systems.
External battery pack: BP48V60RT-3U or BP48V24-2U
SNMP accessories: SNMPWEBCARD, ENVIROSENSE
Watchdog software: WATCHDOGSW
USB Hubs-accessories: U202-004-R, U205-004-R, U022-010Dataline protectors: DNET1, DTEL2, DCATVRack enclosures: Rack SystemsCircuit Tester: CT120Power distribution: PDU1220, PS7224-20Tower Stands: 2-9USTANDTwo Post Rackmount / Wallmount Kit:2POSTRMKITWMExtended warranties: 3 Year WEXT3-2200-3000, 5 Year WEXT5-2200-3000
SMART2200RMXL2U UPS systemPowerAlert software CD-ROMUSB, serial and EPO cablingOwner's manual with warranty information
SYSTEM OVERVIEW
System overview: 2200VA Line-interactive UPS system with controllable load banks and user selectable input
voltages
Voltage compatibility: 120V factory default (110V, 100V user selectable) Frequency compatibility: 50 / 60 Hz
OUTPUT
Output volt amp capacity (VA): 2200 Output watt capacity (watts): 1600 Output nominal voltage: 120V (110V, 100V) VAC Output voltage regulation: LINE MODE: Sine wave line voltage 120V (-18% / +8%) Output frequency regulation: LINE MODE: Passes line frequency of 60Hz +/-10% Outlet quantity / type: 4 NEMA 5-15R and 4 NEMA 5-15/20R Customized load management receptacles: 3 single outlet load banks
INPUT
Page 3
Maximum input amps: 13.3 (120V)/ 14.6 (110V)/ 16.0 (100V)
alarm cancel functions. Back panel includes voltage selection dip switches for 120 / 110 / 100
Input connection type: NEMA 5-20P (optional, user-installable NEMA 5-15P included in box) Input cord length: 10 ft./ 3m Recommended electrical service: 20A 120V
BATTERY
Full load runtime: 6 Half load runtime: 16 DC system voltage: 48V Typical battery lifespan: 4-6 years typical Replacement Battery Cartridge: RBC94-2U
VOLTAGE REGULATION
Voltage regulation description: Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade
output, without using battery power, during brownouts to 83V and overvoltages to 145V
Overvoltage correction: 120V: Input voltages between 127 and 145 volts AC are reduced by 12% / 110V: Input
voltages between 116 and 133 are reduced by 12% / 100V: Input voltages between 106 and 121 are reduced by 12%
Brownout correction: 120V: Input voltages between 96-108 are boosted by 12% / 110V: Input voltages between 87
and 99 are boosted by 12% / 100V: Input voltages between 83 and 90 are boosted by 12%
Severe brownout correction: 120V only: Input voltages between 83 and 95 are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LEDs: 5 front panel LEDs — Green POWER LED, Green VOLTAGE CORRECTION LED, 3 color
BATTERY CHARGE LED, 3 color OUTPUT LOAD LEVEL LED, red BATTERY WARNING LED.
Alarms: 3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds),
overload (continuous short beeps) and low battery (continuous tone)
Switches: Yes, includes 2 front panel mounted push-button switches for system enable, self-test and
volts nominal
SURGE / NOISE SUPPRESSION
AC surge suppression: 570 AC suppression response time: Instantaneous EMI / RFI AC noise suppression: Yes
PHYSICAL
Shipping weight (lbs): 72 Shipping weight (kg): 32.4 Unit weight (lbs): 64 Unit weight (kg): 28.8 Unit Dimensions (HWD/in): 3.5 x 17.5 x 19 Unit Dimensions (HWD/cm): 8.9 x 44.5 x 48.26 Shipping Dimensions (HWD/in): 9 x 23.5 x 20 Shipping Dimensions (HWD/cm): 23 x 59.7 x 50.8 Material of construction: Steel Form factors supported: Rack (2U) Cooling method: Fan Battery Access: Battery access panel allows hot swap replacement without powering connected equipment
off.
Page 4
ENVIRONMENTAL
Operating Temperature: +32 to +104 degrees Fahrenheit Storage Temperature: +5 to +122 degrees Fahrenheit Relative Humidity: 0 to 95%, non-condensing
COMMUNICATIONS
Network monitoring port: HID-compliant USB port and RS232 Software and cabling included: Includes PowerAlert UPS monitoring software for all common network and standalone
operating systems. Ships with 2 cables, 1-USB to USB & 1-DB9 to DB9
SNMP compatibility: Built-in accessory slot accommodates internal SNMPWEBCARD and other network
accessories
WatchDog compatibility: Yes, compatible with Tripp Lite's WatchDog system service software to restore operation to
locked equipment through soft reboot of application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode:
Low voltage transfer to battery power: Switches to battery power if line voltage decreases to 83 (120V), 87 (110V), or 83 (100V)
High voltage transfer to battery power: Switches to battery power as line voltage increases to 145 (120V), 133 (110V), or 121 (100V)
2-4 milliseconds
volts or less. Resets back to line power as line voltage increases to 87 (120V), 92 (110V), or 87 (100V) volts or higher.
volts or higher. Resets back to line power when line voltage decreases to 141 (120V), 129 (110V), or 118 (100V) volts or less.
CERTIFICATIONS
Certifications: Tested to UL1778 (USA), CSA C22.2 No. 107.3 (Canada), RoHS compliant, Class A
(Emissions), NOM (Mexico)
WARRANTY
Optional coverage: 3 year, 5 year, next day and on-site warranty coverage available for select opportunities Product warranty: 2 year product warranty Connected equipment insurance (USA and
Canada Only):
$250,000 connected equipment insurance (USA / Canada only)
SPECIAL FEATURES
EPO port: Includes RJ11 EPO (emergency power off) port and interconnection cable TVSS grounding: Includes back panel grounding point with thumbscrew for data line surge suppressors and
other network accessories requiring a safe grounding point
Cold Start: Yes, inverter can be "cold started" to enable temporary AC output during a power failure Appearance: Attractive all-black housing
BATTERY PACK ACCESSORY (optional)
Battery Pack Accessory (optional): BP48V242U (limit 1) and BP48V60RT3U (multi-pack compatible)
Page 5
The policy of Tripp Lite is one of continuous improvement.
Specifications are subject to change without notice.
Therefore, your product may vary slightly from what is currently listed.
Tripp Lite World Headquarters