Tripp-Lite SM2200RMDVTAA Specifications

TAA SmartPro 120V 2.2kVA 1.92kW Line-Interactive
Highlights
Federal Trade Agreements Act /
TAA Compliant for GSA
Schedule purchases
2200VA / 2.2kVA / 1920W line
interactive 3U rack/tower UPS;
0.9 power factor
Maintains 120V output with 120V
or 230V input, Sine wave output
USB port, RS232, EPO and
optional SNMP/WEB card slot;
Detailed status LEDs
95% line-mode efficiency, 2
switched load banks
C20 inlet & 4 international input
line cords, 4 5-15R & 4 5-15/20R
outlets
Package Includes
SM2200RMDVTAA UPS system
5 international input power cables
USB, DB9, EPO cabling and
PowerAlert software
2-9USTAND tower stand kit
2POSTRMKITHD two-post
rackmount kit
4POSTRAILKIT
Owner's manual
Sine Wave UPS, 3U, 120/230V input, Network Card Options, USB, DB9
MODEL NUMBER: SM2200RMDVTAA
Description
Tripp Lite's dual input voltage SM2200RMDVTAA line interactive UPS system maintains 120V nominal output
and other sensitive equipment types from blackouts, voltage fluctuations and transient surges. 3U rack / tower
form factor with an installed depth of only 22.5 inches. Expandable battery runtime with optional BP48V24-2U
and BP48V60RT3U external battery packs. Uninterruptible Power Supply(UPS) switches to battery-derived AC
output during power failures and extreme voltage variations. Line interactive Automatic Voltage Regulation(AVR)
offers voltage boost during brownouts and voltage cut during overvoltages to maintain regulated 120v output
over an input range of 89 to 148V or 212 to 286V. Includes C20 power inlet with set of 4 international cord sets
and both NEMA 5-15R and 5-15/20R output receptacles. Network-grade AC surge and noise suppression. Communications interfaces support
communications via USB, DB9 serial and slot for optional network management card options, such as Tripp Lite's SNMPWEBCARD. HID-compliant USB
interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed
monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces. Includes PowerAlert monitoring software and
complete cabling. Emergency Power Off(EPO) interface. Integrated 2-bank programmable PDU switching supports load shedding and remote-reboot of up to
2 individual connected devices. 3-stage metered current monitoring and battery charge status LEDs. 95% efficiency in line power mode reduces energy cost
and BTU emissions. Utility power and voltage regulation LEDs. Audible alarm. Self-test. Installation accessories for rackmount and upright tower form factors
included. Field-replaceable, hot-swappable internal batteries and external battery packs. Attractive all-black color scheme.
Features
SmartPro SM2200RMDVTAA dual-voltage line interactive UPS system maintains 120V nominal output with either 120V or 230V input power
Ideal for voice, data and networking applications requiring 120V output from worldwide power sources
Line interactive Automatic Voltage Regulation(AVR) offers voltage boost during brownouts and voltage cut during overvoltages
Maintains continuous operation through blackouts, voltage fluctuations and surges
Corrects line voltage conditions between 89 to 148V or 212 to 286V to 120V nominal output
Standard internal battery set offers 30 minutes runtime at half load(960 watts) and 12 minutes at full load(1920 watts)
Extended runtime is available with optional BP48V24-2U / BP48V242UTAA(limit 1) OR BP48V60RT3U / BP48V60RT3UTAA(no limit)
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software(see manual)
Includes C20 power inlet with set of 4 international cord sets to support 5-20P, Schuko, CEE 7 / EU1-16P, British BS1363A and Italian CEI 23-16 plug
types
Includes NEMA 5-15R and 5-15/20R output receptacles
Network-grade AC surge and noise suppression
Network management card options, such as Tripp Lite’s SNMPWEBCARD, permit remote management and status alert updates
HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces
Includes PowerAlert monitoring software and complete cabling. Emergency Power Off(EPO) interface
Integrated 2-bank PDU switching supports load shedding and remote-reboot of connected equipment. 3-stage metered current monitoring and battery
charge status LEDs
95% efficiency in line power mode reduces energy cost and BTU emissions
Utility power and voltage regulation LEDs
Installation accessories for rackmount and upright tower form factors included
Field-replaceable, hot-swappable internal batteries and external battery packs
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 2200
Output kVA Capacity (kVA) 2.2
Output Watt Capacity (Watts) 1920
Output kW Capacity (kW) 1.92
Power Factor 0.87
Nominal Output Voltage(s) Supported
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Automatic frequency selection
Output Voltage Regulation (Battery Mode)
Output Receptacles (4) 5-15R; (4) 5-15/20R
Load Management Receptacles Two switchable single-outlet 5-15R load banks
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16A (120V), 10A (230V)
120V
+/- 5%
Nominal Input Voltage(s) Supported 120V AC; 230V AC
UPS Input Connection Type 5-20P; C20 inlet
UPS Input Connection Description C20 inlet and 5 compatible plugsets (5-20P, Schuko CEE7, EU1-16P, British BS1363, Italian CEI 23-16)
Input Circuit Breakers 20A
UPS Input Cord Length (ft.) 6
UPS Input Cord Length (m) 1.8
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 12 minutes (1920 watts)
Half Load Runtime (min.) 30 minutes (960 watts)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
DC System Voltage (VDC) 48
Battery Recharge Rate (Included Batteries)
Internal UPS Replacement Battery Cartridge
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains 120v line power output with input range of 89 to 148 or 170 to 286
Overvoltage Correction Voltage reduction of 12% applies when input is between 127 and 148 (120V)
Undervoltage Correction Voltage boost of 12% applies when input voltage is between 96 and 108 (120V)
USER INTERFACE, ALERTS & CONTROLS
Switches
Alarm Cancel Operation
BP48V24-2U
Less than 4.5 hours from 10% to 90% (internal batteries)
RBC49-DV
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support nominal voltage selection
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
(limit 1);
(quantity 2 required)
BP48V60RT-3U
(multi-pack compatible);
BP48V27-2US
(multi-pack compatible)
Audible Alarm Audible alarm indicates power-failure, overload and low-battery conditions
LED Indicators 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 340
UPS AC Suppression Response Time
EMI / RFI AC Noise Suppression Yes
Instantaneous
PHYSICAL
Included Mounting Accessory Description
Installation Form Factors Supported with Included Accessories
Installation Form Factors Supported with Optional Accessories
Primary Form Factor Rackmount
UPS Power Module Dimensions (hwd, in.)
UPS Power Module Dimensions (hwd, cm)
Rack Height (U Spaces) 3
Minimum Required Rack Depth (inches)
Minimum Required Rack Depth (cm) 81.9
UPS Power Module Weight (lbs.) 104.25
UPS Power Module Weight (kg) 47.3
UPS Shipping Dimensions (hwd / in.) 11.5 x 29.5 x 30.5
UPS Shipping Dimensions (hwd / cm)
Complete installation accessories available for 2 post, 4 post and tower installation
Tower
4 post rackmount(
5.25 x 17.5 x 25.25
13.3 x 44.4 x 64.1
32.3
29.2 x 151.6 x 129
4POSTRAILKIT
)
Shipping Weight (lbs.) 159.5
Shipping Weight (kg) 72.4
Cooling Method Fan
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 347
Battery Mode BTU / Hr. (Full Load) 604.4
AC Mode Efficiency Rating (100% Load)
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software Included
95%
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility
LINE / BATTERY TRANSFER
Transfer Time 2-4 milliseconds
Low Voltage Transfer to Battery Power (Setpoint)
High Voltage Transfer to Battery Power (Setpoint)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode During a Power Failure)
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications
WARRANTY
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
89 (120V), 170 (230V)
148 (120V), 286 (230V)
Cold-start operation supported
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); TAA Compliant
Product Warranty Period (Worldwide) 2-year limited warranty
Loading...