Tripp Lite OMNIVSX450 User Manual

Line Interactive UPS, C13 Outlets (4) - 230V, 450VA, 240W, Ultra-Compact Design
MODEL NUMBER: OMNIVSX450
OMNIVSX450 provides voltage regulation, surge suppression and battery backup support for computers and other sensitive electronics.
Features
Protect Your Electronics with Voltage Regulation, Surge Suppression and Battery Backup
Operate Your Connected Equipment During Short-Term Outages
This UPS supports an entry-level PC consuming 60W continuous up to 32 minutes during power failure condition and a 50% load of 120W for 7 minutes. It also enables users to operate connected equipment during short-duration outages without interruption and shut down without data loss during longer outages. All the UPS C13 outlets receive battery backup.
Highlights
Correct brownouts as low as 170V and overvoltages as high as 280V without using battery
450VA capacity supports a variety of desktop and networking devices
Fused C14 inlet accepts user­supplied AC power cord with country-specific plug
Ultra-compact design saves space
Applications
Protect your PC and other sensitive electronics against power surges, brownouts and blackouts
Operate your connected equipment during short-term power outages
Shut down equipment during longer power outages without data loss
Provide battery backup and power protection in locations with limited space
Support small business phone systems, POS (point-of-sale) systems, kiosks and ATMs
Package Includes
OMNIVSX450 line-interactive UPS
(2) C13 to C14 1.5m power cables
Owner's manual
1 / 4
Specifications
OVERVIEW
UPC Code 037332217905 UPS Type Line-Interactive
INPUT
Rated input current (Maximum Load) 2A Nominal Input Voltage(s) Supported 230V AC UPS Input Connection Type C14 inlet UPS Input Connection Description The C14 inlet accepts included or user-supplied AC power cords Input Phase Single-Phase
OUTPUT
Output Volt Amp Capacity (VA) 450 Output Watt Capacity (Watts) 240 Nominal Voltage Details 230V nominal output in battery mode Frequency Compatibility 50 / 60 Hz Frequency Compatibility Details Automatic frequency selection Output Voltage Regulation (Line
Mode) Output Voltage Regulation (Battery
Mode) Included Output Power Cables Includes 2 C13 to C14 power cables Output AC Waveform (AC Mode) Sine wave Output AC Waveform (Battery
Mode) Nominal Output Voltage(s)
Supported Output Receptacles (4) C13 Individually Controllable Load Banks No
BATTERY
Battery Type Valve Regulated Lead Acid (VRLA) Half Load Runtime (min.) 7 min. (120w) Expandable Runtime No DC System Voltage (VDC) 12
230V (±9.5%)
±10%
PWM sine wave
220V; 230V; 240V
Battery Recharge Rate (Included Batteries)
8 hours from 10% to 90%
2 / 4
Battery Replacement Description See manual for battery replacement information
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with input voltage as low as 170 and as high as
280 Overvoltage Correction Input voltages between 253 and 280 are reduced by 15% Undervoltage Correction Input voltages between 170 and 207 are boosted by 18%
USER INTERFACE, ALERTS & CONTROLS
Switches 1 Switch controls off/on power status Audible Alarm Audible alarm with distinct tone patterns indicates low-battery, overload, replace-battery and fault-mode LED Indicators 3 front panel LEDs indicate off/on power status, line power availability, battery mode operation, overload, replace-
battery and fault-mode
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 312 UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Installation Form Factors Supported with Included Accessories
Tower
Primary Form Factor Tower Primary UPS Depth (mm) 300 Primary UPS Height (mm) 142 Primary UPS Width (mm) 102 Shipping Dimensions (hwd / in.) 8.70 x 5.60 x 13.60 Shipping Weight (kg) 3.99 UPS Housing Material PVC UPS Power Module Dimensions
(hwd, in.)
5.6 x 4 x 11.8
UPS Power Module Weight (kg) 3.72 UPS Power Module Weight (lbs.) 8.2
ENVIRONMENTAL
Operating Temperature Range 0 to 40°C Storage Temperature Range -15 to 45°C Relative Humidity Up to 90%, non-condensing AC Mode BTU / Hr. (Full Load) 17
3 / 4
AC Mode Efficiency Rating (100% Load)
Operating Elevation (m) 0-2000m
COMMUNICATIONS
Communications Interface None
LINE / BATTERY TRANSFER
Transfer Time 6 milliseconds
95%
Low Voltage Transfer to Battery Power (Setpoint)
High Voltage Transfer to Battery Power (Setpoint)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode During a Power Failure)
High Availability UPS Features Automatic Voltage Regulation (AVR); Surge/noise protection
STANDARDS & COMPLIANCE
UPS Certifications CE Certification Details IEC 62040-1:2008+A1:2013; EN62040-2, 2006, C2
WARRANTY
Product Warranty Period (International)
Product Warranty Period (Mexico) 2-year limited warranty Product Warranty Period (Puerto
Rico)
170
280
Yes
2-year limited warranty
2-year limited warranty
© 2021 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: https://www.tripplite.com/products/product-certification-agencies