Tripp-Lite OMNIVSINT1500XL Specifications

OmniVS 230V 1500VA 940W Line-Interactive UPS,
Highlights
1500VA / 1.5kVA tower 230V line
interactive extended-run UPS
Corrects brownouts and
overvoltages from 151 to 282V
USB port, TEL/DSL/ethernet
protection, External battery pack
options
C14 input and 8 C13 outlets
Package Includes
OMNIVSINT1500XL line
interactive UPS
2 C13 to C14 interconnection
cables
USB and phone line cables
Owner's manual with warranty
information
Extended Run, Tower, USB port, C13 Outlets
MODEL NUMBER: OMNIVSINT1500XL
Description
Tripp Lite's OMNIVSINT1500XL line interactive UPS system offers voltage regulation, surge suppression and long lasting, expandable battery support for
personal computers, internetworking equipment and other sensitive electronics. Internal UPS circuits support entry level PC systems for up to 75 minutes
during power failures so that connected equipment can be shut down without data loss. Automatic Voltage Regulation(AVR) circuits regulate brownouts as low
black tower configuration. Includes 8 IEC320-C13 outlets with battery support and AC surge suppression. USB port enables optional unattended system
shutdown without data loss in the case of extended power failure, USB cable included. PowerAlert software available via free download from www.tripplite.com.
Built-in single line RJ jacks protect modem, fax machine, Ethernet, cordless phone or other peripheral with a standard dialup/DSL phone connection. Built-in
audible alarm and 4 front panel LEDs indicate line power status, battery power status, battery low/replace status and voltage boost operation. 1500VA power
handling ability supports entry-level PCs, network workstations, point-of-sale equipment, small business phone systems, audio/video equipment and home
theater systems. Offers 4.5 minutes battery runtime with a full load of 1500VA and 13 minutes with a half load of 750VA. Supports hot-swappable battery
replacement via built-in access panel. Extended runtime available with optional BP24V15RT2U or BP24V28-2U external battery packs.
Features
OMNIVSINT1500XL Uninterruptible Power Supply offers voltage regulation, surge suppression and long lasting battery support
Supports entry level PCs up to 75 minutes during blackouts to enable shutdown without data loss, runtime is further expandable by connecting an
external battery pack
Regulates brownouts as low as 151 and overvoltages to 282V back to usable 230V nominal levels without using battery power
8 IEC320 C13 outlets with complete AC surge suppression
C14 inlet accepts user-supplied AC power cord with country-specific plug
USB port and cable enables unattended shutdown in the case of extended power failure
PowerAlert software available via free download from www.tripplite.com
Dataline surge suppression protects standard dialup/DSL or Ethernet line connection
Audible alarm and 4 front panel LEDs offer complete UPS and line power status information
1500VA power handling ability supports a variety of sensitive electronic equipment
4.5 minutes full load runtime(1500VA), 13 minutes half load runtime(750VA)
Runtime is further expandable with the addition of external battery packs
Supports hot swappable battery replacement via built-in access panel
Optional PDUBHV10 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment
Attractive full color retail packaging
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 1500
Output kVA Capacity (kVA) 1.5
Output Watt Capacity (Watts) 940
Nominal Output Voltage(s) Supported
Nominal Voltage Details 230V nominal output in battery mode
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Automatic frequency selection
Output Voltage Regulation (Line Mode)
Output Voltage Regulation (Battery Mode)
Output Receptacles (8) C13
Included Output Power Cables Includes 2 C13 to C14 output power cables
Hot-Swap PDU options PDUBHV10 (2U / 8 C13 outlets)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) PWM sine wave
INPUT
Rated input current (Maximum Load) 5A
Nominal Input Voltage(s) Supported 230V AC
UPS Input Connection Type C14 inlet
220V; 230V; 240V
-18%, +8%
+/- 5%
UPS Input Connection Description
UPS Input Cord Length (ft.) 0.5
UPS Input Cord Length (m) 0.2
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 4.5 min. (940w)
Attached 15cm line cord with C14 inlet. The C14 inlet accepts user-supplied AC power cord with country-specific plug.