Tripp Lite OMNISMART450HG User Manual

OmniSmart UPS System
Line-interactive battery backup and network power
DESCRIPTION
in line interactive voltage regulation, intelligent monitoring and unattended
shutdown capability. 450VA power handling capacity supports computers, internetworking equipment and other critical loads during
commercial power failures. Line interactive voltage regulation corrects brownouts as low as 75V and overvoltages as high as 147V back to
normal 120V levels, saving battery reserves for use only during complete power failures. Includes 4 hospital grade outlets, diagnostic LEDs
in DB9 communications port that works with web downloadable PowerAlert Software and cabling to provide automatic unattended
KEY BUYING POINTS
Line interactive voltage regulation corrects brownouts and overvoltages from 75 to 147 volts back to usable 120V output levels, without
TYPICAL APPLICATIONS
OPTIONS & ACCESSORIES
PACKAGE INCLUDES
management with hospital grade plug and receptacles
Model #: OMNISMART450HG
450VA line interactive tower UPS Hospital grade plug and 4 NEMA5-15R hospital grade output receptacles Corrects brownouts as low as 75V and overvoltages to 147V without using battery power DB9 communications port
Tripp Lite's OMNISMART450HG offers UPS protection, built-
and built­shutdown of connected network and PC applications.
Ideal UPS protection for mission critical equipment and computers where hospital-grade input/output connections are required Provides connected equipment with continuous power duuring short and long duration loss of commercial power
using battery power
Hospital-grade plug and outlets offer added degree of safety to input/output connections Supports loads up to 450VA /280 watts 17 minutes half load runtime (with 225VA load), 5 minutes full load runtime (with 450VA load) Hospital grade input plug and 4 NEMA5-15R hospital grade output receptacles 1 DB9 serial port for network interface; SNMP compatible Surge portection and EMI/RFI noise filtering PowerAlert UPS monitoring and auto-shutdown software available for free download from www.tripplite.com Includes complete cabling for remote monitoring via PowerAlert software 4 diagnostic LEDs indicate AC present, on battery, voltage correction & battery low/replace Battery replacement door 2 year product warranty
Ideal UPS protection for network workstations, small office fileservers and PC systems
SNMP accessories: SNMPWEBSOLO, ENVIROSENSEDataline protectors: DNET1, DTEL2, DCATVWallmount Bracket: UPSWMCircuit Tester: CT120Extended warranties: 3 Year WEXT3-OMNI, 5 Year WEXT5-OMNI
COMPLETE SPECIFICATIONS
OmniSmart 450 Hospital-Grade UPS System
RS-232 remote monitoring cable
Instruction manual with warranty information
SYSTEM OVERVIEW
System overview:
Voltage compatibility: Frequency compatibility:
OUTPUT
Output volt amp capacity (VA): Output watt capacity (watts): Output nominal voltage: Output voltage regulation:
Output frequency regulation:
Outlet quantity / type:
INPUT
Maximum input amps: Input connection type: Input cord length: Recommended electrical service:
Line Interactive UPS system with hospital grade plug and outlets, meets, line interactive voltage regulation, AC surge suppression and DB9 communications port
120 V AC 60 Hz
450 280 120V nominal LINE MODE: Sine wave line voltage 120V (-18% / +8%)
BATTERY MODE: PWM sine wave output 120V +/-5% LINE MODE: Passes line frequency of 60Hz. +/-10%
BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz 4 NEMA5-15R Hospital Grade Output Receptacles
2.8A / 320 watts NEMA 5-15P Hospital-Grade 6 ft, 14 gauge 15A 120V
BATTERY
Full load runtime: Half load runtime: DC system voltage: Typical battery lifespan: Battery recharge rate:
VOLTAGE REGULATION
Voltage regulation description:
Overvoltage correction: Direct pass through:
Brownout correction: Severe brownout correction:
LEDS ALARMS & SWITCHES
Front panel LEDs:
5 minutes (450VA) 17 minutes (225VA) 12 VDC 3-6 years, depending on usage 2-4 hours to 90%
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 75V and overvoltages to 147V
Input voltages between 128 and 147V AC are reduced by 12% Input voltages between 108 and 127V AC are passed on to connected equipment
unchanged Input voltages between 93 and 107V AC are boosted by 14% Input voltages between 75 and 92V AC are boosted by 30%
4 front-panel indicator LEDs show line power status, battery power status, battery low/replace status and voltage regulation operation
Alarms:
Audible alarm indicates power failure conditions, silenceable via alarm cancel switch. Once cancelled, alarm will resume when approximately 2 minutes of battery operation remain
(assuming full load).
PowerAlert UPS monitoring software available via web download for all common network and
Switches:
SURGE / NOISE SUPPRESSION
AC surge suppression: AC suppression response time: EMI / RFI AC noise suppression:
PHYSICAL
Shipping weight (lbs): Shipping weight (kg): Unit weight (lbs): Unit weight (kg): Unit Dimensions (HWD/in): Unit Dimensions (HWD/cm): Material of construction: Form factors supported: Cooling method: Battery Access:
Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
Conforms to IEEE 587 / ANSI C62.41 specifications Instantaneous Yes
23
10.4 21
9.5
10.75 x 5.25 x 7.25
27.3 x 13.3 x 18.4 PVC Tower, wall mountable with optional UPSWM accessory Convection Battery access door allows hot swap battery replacement without powering connected
equipment off
ENVIRONMENTAL
Operating Temperature:
Storage Temperature:
Relative Humidity:
COMMUNICATIONS
Network monitoring port: Software and cabling included:
SNMP compatibility:
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode:
Low voltage transfer to battery power: High voltage transfer to battery power:
CERTIFICATIONS
Certifications:
+32 to +104 degrees Fahrenheit 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit
-15 to +50 degrees Celsius 0 to 95%, non-condensing
Includes built-in basic DB9 monitoring port
standalone operating systems. Ships with 1 cable. External accessory "SNMP-SOLO" SNMP / Web adapter available
2-4 milliseconds
75V (resets to line power as voltage increases to 79V) 147V (resets to line power as voltage decreases to 143V)
UL1778 (USA, Series AGOM700KSR61), cUL (Canada), FCC Class A (emissions)
WARRANTY
Optional coverage: Product warranty:
3 year, 5 year, next day and on-site warranty coverage available 2 year product warranty
SPECIAL FEATURES
Cold Start: Appearance:
Yes, inverter can be "cold started" to enable temporary AC output during a power failure Attractive gray tower UPS
The policy of Tripp Lite is one of continuous improvement.
Specifications are subject to change without notice.
Therefore, your product may vary slightly from what is currently listed.
Tripp Lite World Headquarters
1111 W. 35th Street
Chicago, IL 60609 USA
Customer Support
(773) 869-1234
© 2004 Tripp Lite. All Rights Reserved.