Tripp Lite AVRX500UD, AVRX650UD, AVRX800UD, AVRX1000UD Owner’s Manual

Owner’s Manual
AVRX Series UPS Systems
AVRX500UD, AVRX650UD, AVRX800UD, AVRX1000UD
(Series Numbers: AG-0541, AG-0542, AG-0543, AG-0544)
Not suitable for mobile applications.
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Copyright © 2020 Tripp Lite. All rights reserved.
1
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation and storage of this product. Failure to heed these warnings may affect the warranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight.
• For best performance, keep the indoor temperature between 0º C and 40º C.
• Leave adequate space around all sides of the UPS for proper ventilation.
• Only set the UPS upright on a sturdy flat surface.
UPS Connection Warnings
• Connect your UPS directly to a properly grounded AC power outlet. Do not plug the UPS into itself; this will damage the UPS.
• Do not modify the UPS plug, and do not use an adapter that would eliminate the UPS ground connection.
• Do not use extension cords to connect the UPS to an AC outlet.
• If the UPS receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer­grade output.
• The mains socket outlet that supplies the UPS should be easily accessible and located near the UPS.
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
• Do not connect surge protectors or extension cords to the output of your UPS. This might damage the UPS and may affect the surge protector and UPS warranties.
• Connect the UPS to an outlet that is adequately protected against excess currents, short circuits and earth faults as part of the building installation.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. There are no user-serviceable parts inside the UPS. Do not open batteries. Do not short or bridge the battery terminals with any object. Do not dispose of batteries in a fire. The batteries may explode. Released material is harmful to the skin and eyes. It may be toxic. Unplug and turn off the UPS before performing battery replacement. Use tools with insulated handles. Battery replacement should be performed only by authorized service personnel using the same number and type of batteries (sealed lead-acid).
CAUTION, RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
CAUTION: A battery can present a risk of electrical shock and high short circuit current. The following precautions
should be observed when working on batteries.
a) Remove watches, rings or other metal objects. b) Use tools with insulated handles. c) Wear rubber gloves and boots. d) Do not lay tools or metal parts on top of batteries. e) Disconnect the charging source prior to connecting or disconnecting battery terminals.
2
Important Safety Instructions
f) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with
any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
UPS and Battery Recycling
Please recycle Tripp Lite products. The batteries used in Tripp Lite products are sealed lead-acid batteries. These batteries are recyclable. Please refer to local codes for disposal requirements.
Go to the Tripp Lite website for up-to-date information on recycling the batteries or any Tripp Lite product. Please follow this link: http://www.tripplite.com/support/recycling-program/
3
Features
4
5
1 2
Power Switch with Status Indicator:
1
• To turn the UPS ON, press the POWER SWITCH when the UPS is turned off. The switch LED will turn ON to confirm the UPS is ON.
• To turn the UPS OFF, press the POWER SWITCH when the UPS is turned on. The switch LED will turn OFF to confirm the UPS is OFF.
AC Input Cable: Connects to a SCHUKO-type AC input power source.
2
AC Input Circuit Breaker: Built-in circuit breaker protects the UPS from overload conditions.
3
Schuko CEE 7 Outlets: Provide both battery backup and surge protection. Plug your computer, monitor and other
4
critical equipment into these outlets.
Do not plug laser printers into these outlets.
Grounding Lug: Use this to connect any equipment that requires a chassis ground.
5
Automatic Voltage Regulation (Internal, Not Shown): Automatically adjusts fluctuations to incoming voltage (under/
over voltages) to supply connected equipment with 230V computer-grade output power. Automatic voltage regulation functions separately from battery power (will not drain battery).
Keyhole Mounting Tabs (Bottom Panel, Not Shown): Use the bottom-panel mounting tabs to mount the UPS on any flat surface.
3
4
Features
Status LED and Audible Alarm Notifications
The status LED and audible alarm report UPS off/on status, battery mode operation, low battery condition and UPS fault. See chart for a complete description.
LED Alarm UPS Status
Off The mains is normal and UPS is operating normally. Sounding every 10 seconds Power failure occurs and UPS is in battery mode. Sounding every second Low battery. Off UPS is off. Continuously sounding UPS fault, the LED will be Off.
LED On LED Off LED Flashing
Troubleshooting
Problem Possible Cause Solutions
LED not lit.
The UPS stays in battery mode. The UPS continuously beeps.
Backup power time is too short.
The UPS is not on. Press the power switch again to turn on the UPS. Battery voltage is too low. Charge the battery at least 6 hours. Battery fault. Replace the battery. Power cord loose. Re-plug the power cord. UPS may have been damaged. Shut down UPS and disconnect all loads on UPS,
then restart it. If the issue persists please contact
a qualified professional for maintenance. Battery voltage is too low. Charge the battery at least 6 hours. Overload. Remove some unnecessary loads. Before recon-
necting equipment, please verify that the load
matches the UPS capability specified in the specs. Battery defect. Replace the battery.
5
Specifications
Model AVRX500UD AVRX650UD AVRX800UD AVRX1000UD
VA / Watts 500VA / 300W 650VA / 375W 800VA / 450W 1000VA / 600W Input Voltage 230V Nominal 230V Nominal 230V Nominal 230V Nominal Input Voltage Range 159-282V 159-282V 159-282V 159-282V Input Breaker 5A, 250V AC 5A, 250V AC 7A, 250V AC 7A, 250V AC Transfer Time 2 - 6 ms Typical, 10 ms Max. Waveform PWM Sine Wave Battery Rating 12V 4.5Ah 12V 6Ah 12V 7Ah 12V 9Ah Charging Time 8 Hours at 90% Dimensions (H x W x D) 9.1 x 16.3 x 24.5 cm 9.1 x 16.3 x 24.5 cm 9.1 x 19 x 28 cm 9.1 x 19 x 28 cm Net Weight 3.64 kg 4.44 kg 5.29 kg 5.69 kg Humidity 0% - 95% Non-condensing Audible Noise 40 dB at 1 m Distance Runtime at 50% Load 4 min. 6 min. 3 min. 1.2 min.
Regulatory Compliance
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marketing name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products.
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
6
20-07-199 93-3CD5_RevA
Manual del Propietario
Sistemas UPS Serie AVRX
AVRX500UD, AVRX650UD, AVRX800UD, AVRX1000UD
(Números de serie: AG-0541, AG-0542, AG-0543, AG-0544)
No es adecuado para aplicaciones móviles.
English 1 • Русский 13 • Deutsch 19
1111 W. 35th Street, Chicago, IL 60609, EE UU • tripplite.com/support
Copyright © 2020 Tripp Lite. Todos los derechos reservados.
7
Instrucciones de Seguridad Importantes
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse durante la instalación, operación y almacenamiento de este producto. La omisión en la observancia de estas advertencias puede afectar la garantía.
Advertencias para la Ubicación del UPS
Instale su UPS en interiores, alejado de humedad o calor excesivos, contaminantes conductores, polvo o luz solar directa.
• Para mejor desempeño, mantenga la temperatura interior entre 0 ºC y 40 ºC.
• Deje suficiente espacio alrededor de todos los lados del UPS para una ventilación adecuada.
• Sólo ponga el UPS en posición vertical sobre una superficie plana sólida.
Advertencias para la Conexión del UPS
• Conecte su UPS directamente a un tomacorrientes de CA conectado correctamente a tierra. No enchufe el UPS en sí mismo; esto dañará al UPS.
• No modifique la clavija del UPS y no use un adaptador que pueda eliminar la conexión a tierra del UPS.
• No use cables de extensión para conectar el UPS a un tomacorriente de CA.
• Si el UPS recibe alimentación de un generador de CA accionado por motor, debe probarse que el generador proporciona una salida de grado computadora, limpia y filtrada.
• El tomacorrientes que alimenta al UPS debe ser fácilmente accesible y estar cerca del UPS.
Advertencias en relación con la Conexión del Equipo
• No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde razonablemente se pueda esperar que la falla de este equipo cause la falla del equipo de soporte de vida o afecte significativamente su seguridad o efectividad.
• No conecte supresores de sobretensiones o cables de extensión a la salida de su UPS. Esto puede dañar al UPS y afectar las garantías del supresor de sobretensiones y del UPS.
• Conecte el UPS a un tomacorrientes que esté adecuadamente protegido contra corrientes excesivas, cortocircuitos, y fallas de conexión a tierra como parte de la instalación del edificio.
Advertencias de la Batería
Las baterías pueden presentar un riesgo de descarga eléctrica y quemaduras por la corriente de cortocircuito elevada. Observe las precauciones apropiadas. No hay partes dentro del UPS a las que el usuario pueda dar servicio. No abra las baterías. No ponga en corto o puentee las terminales de la batería con ningún objeto. No deseche las baterías en el fuego. Las baterías pueden explotar. El material liberado es dañino a la piel y ojos. Puede ser tóxico. Desenchufe y apague el UPS antes de reemplazar la batería. Use herramientas con mangos aislados. El reemplazo de la batería debe realizarlo solo el personal de servicio autorizado usando el mismo número y tipo de baterías (plomo-ácido selladas).
PRECAUCIÓN, SI SE REEMPLAZA LA BATERÍA CON UN TIPO INCORRECTO, EXISTE UN RIESGO DE EXPLOSIÓN. DESECHE LAS BATERÍAS USADAS DE ACUERDO CON LAS INSTRUCCIONES.
PRECAUCIÓN: Una batería puede presentar un riesgo de descarga eléctrica y alta corriente de cortocircuito. Deben
observarse las siguientes precauciones al trabajar con baterías.
a) Retire relojes, anillos u otros objetos metálicos. b) Use herramientas con mangos aislados. c) Use guantes y botas de hule. d) No coloque herramientas o partes metálicas sobre la parte superior de las baterías. e) Desconecte la fuente de carga antes de conectar o desconectar las terminales de la batería.
8
Loading...
+ 16 hidden pages