Tripp Lite APSX User Manual

Owner’s Manual
®
PowerVerter
APSX Series
DC-to-AC Inverter/Chargers
Input Output
Invert: 12 or 24 VDC 230V, 50 Hz. AC Charge: 230V, 50 Hz. AC 12 or 24 VDC
Reliable Emergency Backup Power
Congratulations! You’ve purchased the most advanced, feature-rich Inverter/Charger designed as an alternative energy source during utility power failures. Tripp Lite APS Inverter/Chargers keep your equipment constantly up and productive through all utility power problems (blackouts, brownouts and high voltages) by inverting DC power from user-supplied batteries into AC power. Built-in surge suppression provides an additional level of equipment protection. When utility power is present, APS Inverter/Chargers automatically pass through power to your equipment while simultaneously recharging your connected battery bank. APS Inverter/Chargers are the quiet alternative to gas generators during emergency backup applications—with no fumes, fuel or noise to deal with! You get AC electricity anywhere and anytime you need it.
• Built-In Isobar Surge Protection
• Automatic Overload Protection
1111 W. 35th Street, Chicago, IL 60609 USA
Customer Support: (773) 869-1212
www.tripplite.com
Ideal Output for All Loads (including computers)
• Frequency-Controlled Output
• Fast Load Switching
• Balanced Load Sharing
Better for Your Batteries Faster Battery Recharge
• High-Amp, 3-Stage Battery Charger (adjustable)
Critical Battery Protection
• Battery Charge Conserver (Load Sense)*
• High-Efficiency DC-to-AC Inversion
Better for You Simple, Maintenance-Free Operation
• Multi-Function Lights & Switches
• Dead Battery Startup
• Moisture-Resistant Construction**
Contents
Safety 2 Warranty 2 Feature Identification 3
Battery Connection 9 AC Input/Output Connection 10
Service/Maintenance/Troubleshooting 11 Operation 4 Configuration 5-6 Battery Selection 7 Mounting 8
* Available on all models except 750 and 1250 models. ** Inverter/Chargers are moisture-resistant, not waterproof.
Copyright © 2005. PowerVerter
Español 12 Français 23
Pyсский 34
®
is a registered trademark of Tripp Lite. All rights reserved.
Important Safety Instructions
SAVE THESE INSTRUCTIONS!
This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite Inverter/Chargers.
Location Warnings
• Install your Inverter/Charger (whether for a mobile or stationary application) in a location or compartment that minimizes exposure to heat, dust, direct sunlight and moisture.
• Although your Inverter/Charger is moisture resistant, it is NOT waterproof. Flooding the unit with water will cause it to short circuit and could cause personal injury due to electric shock. Never immerse the unit, and avoid any area where standing water might accumulate. Mounting should be in the driest location available.
• Leave a minimum of 5cm clearance at front and back of the Inverter/Charger for proper ventilation. The heavier the load of connected equipment, the more heat will be generated by the unit.
• Do not install the Inverter/Charger directly near magnetic storage media, as this may result in data corruption.
• Do not install near flammable materials, fuel or chemicals.
Battery Connection Warnings
• Multiple battery systems must be comprised of batteries of identical voltage, age, amp-hour capacity and type.
• Because explosive hydrogen gas can accumulate near batteries if they are not kept well ventilated, your batteries should not be installed (whether for a mobile or stationary application) in a “dead air” compartment. Ideally, any compartment would have some ventilation to outside air.
• Sparks may result during final battery connection. Always observe proper polarity as batteries are connected.
• Do not allow objects to contact the two DC input terminals. Do not short or bridge these terminals together. Serious personal injury or property damage could result.
Equipment Connection Warnings
Do not use a Tripp Lite APS Inverter/Charger in life support or healthcare applications where a malfunction or failure of a Tripp Lite APS Inverter/Charger could cause failure of or significantly alter the performance of, a life support device or medical equipment.
• Corded models: Do not modify the Inverter/Charger’s plug or receptacle in a way that eliminates its ground connection. Do not use power adapters that will eliminate the plug’s ground connection.
• Connect your Inverter/Charger only to a properly grounded AC power outlet or hardwired source. Do not plug the unit into itself; this will damage the device and void your warranty.
• You may experience uneven performance results if you connect a surge suppressor, line conditioner or UPS system to the output of the Inverter/Charger.
Operation Warnings
• Your Inverter/Charger does not require routine maintenance. Do not open the device for any reason. There are no user serviceable parts inside.
• Potentially lethal voltages exist within the Inverter/Charger as long as the battery supply and/or AC input are connected. During any service work, the battery supply and AC input connection should therefore be disconnected.
• Do not connect or disconnect batteries while the Inverter/Charger is operating in either inverting or charging mode. Operating Mode Switch should be in the OFF position. Dangerous arcing may result.
Limited Warranty
Tripp Lite warrants its Inverter/Chargers to be free from defects in materials and workmanship for a period of one year (except for outside of U.S.A., Canada and Mexico—120 days) from the date of retail purchase by end user Tripp Lite’s obligation under this warranty is limited to repairing or replacing (at its sole option) any such defective products.To obtain service under this warranty you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an authorized
Tripp Lite service center.Products must be returned to Tripp Lite or an authorized Tripp Lite service center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of pur­chase. This warranty does not apply to equipment which has been damaged by accident, negligence or misapplication or has been altered or modified in any way, including opening of the unit’s casing for any reason. This warranty applies only to the orig­inal purchaser who must have properly registered the product within 10 days of retail purchase.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclu­sion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POS­SIBILITY OF SUCH DAMAGE. Specifically, Tripp Lite is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
2A
Feature Identification
Identify the premium features on your specific model and quickly locate instructions on how to maximize their use.
Configuration DIP Switches: optimize Inverter/Charger
1
operation depending on your application. See Configuration Section for setting instructions.
Operating Mode Switch: controls Inverter/Charger operation.
2
The “AUTO/REMOTE” setting ensures your equipment receives constant, uninterrupted AC power. It also enables the Inverter/Charger to be remotely monitored and controlled with an optional remote module (Tripp Lite model APSRM4, sold separately). The “CHARGE ONLY” setting allows your batter­ies to return to full charge faster by turning the inverter off which halts battery discharging. See Operation Section for set­ting instructions.
3
Operation Indicator Lights: intuitive “traffic light” signals
show whether the Inverter/Charger is operating from AC line power or DC battery power. It also warns you if the connected equipment load is too high. See Operation Section for instruc­tions on reading indicator lights.
4
Battery Indicator Lights: intuitive “traffic light” signals show
approximate charge level of your battery. See Operation Section for instructions on reading indicator lights.
5
DC Power Terminals: connect to your battery terminals. See
Battery Connection Section for connection instructions.
AC Output Receptacles (not on hardwire models): IEC-320
6
output receptacle(s) allow you to connect equipment that you would normally plug into a utility outlet. Select models also include a Universal AC Output Adapter which allows you to connect equipment with a wide variety of plug styles.
AC Input Receptacle (not on hardwire models): IEC-320
7
input receptacle connects the Inverter/Charger to any source of utility or generator-supplied AC power when used with a user­supplied cable with country-specific plug.
Hardwire AC Input/Output Terminal Strip (not on corded
8
models): securely connects the Inverter/Charger to facility or
vehicle electrical system. See Input/Output Connection Section for connection instructions.
Resettable Circuit Breakers: protect your Inverter/Charger
9
against damage due to overload. See Operation Section for resetting instructions.
10
Remote Control Module Connector: allows remote monitoring
and control with an optional module (Tripp Lite model APSRM4, sold separately). See remote module owner’s manu­al for connection instructions.
11
Battery Charge Conserver (Load Sense) Control (available on select models): conserves battery power by setting the
low-load level at which the Inverter/Charger’s inverter automati­cally shuts off. See Configuration Section for setting instructions.
12
Main Ground Lug: properly grounds the Inverter/Charger to
earth ground or to vehicle or boat grounding system. See Battery Connection Section for connection instructions.
13
Thermostatically-Controlled Cooling Fan: quiet, efficient fan
regulates internal temperature and prolongs equipment service life. Fan runs intermittently depending on temperature and load.
14
DC Power Terminal Cover Plate
15
Hardwire AC Input/Output Cover Plate Dead Battery Startup Feature (for all models, internal, not
shown): internal circuitry allows you to start up the
Inverter/Charger even with a dead battery connected to the unit. As long as the Inverter/Charger is connected to a live utility- or generator-supplied AC power source, the Inverter/Charger will pass through AC power to connected equipment and charge con­nected batteries.
1 24 3
5
Front View (750 & 1250 Corded Model)
1013
9
6
12
7
Front View (2012 & 2424 Hardwire Models).
1
5
10 111314
“FOR USE WITH COPPER WIRE ONLY”
HOT IN
NEUTRAL IN
GROUND IN
GROUND OUT
HOT OUT
NEUTRAL OUT
8 15
24 3
16 12
9
Side Mounted, Not Shown
Rear Mounted, Not Shown
3A
Operation
Switch Modes
After configuring, mounting and connecting your Inverter/Charger, you are able to operate it by switching between the following operating modes as appropriate to your situation:
AUTO/REMOTE: Switch to this mode when you need constant, uninterrupted AC power for connected appliances and equipment. The Inverter/Charger will continue to supply AC power to connected equipment and to charge your connected batteries while utility­or generator-supplied AC power is present. Since the inverter is ON (but in Standby) in this mode, it will automatically switch to your battery system to supply AC power to connected equipment in the absence of a utility/generator source or in over/under voltage situations. “AUTO/REMOTE” also enables an optional remote control module (Tripp Lite model APSRM4, sold separately) to function when connected to the unit.
CHARGE ONLY: Switch to this mode when you are not using connected appliances and equipment in order to conserve battery power by disabling the inverter. The Inverter/Charger will continue to supply AC power to connected equipment and charge con­nected batteries while utility- or generator-supplied AC power is present. However, since the inverter is OFF in this mode, it WILL NOT supply AC power to connected equipment in the absence of a utility/generator source or in over/under voltage situations.
OFF: Switch to this mode to shut down the Inverter/Charger completely, preventing the inverter from drawing power from the batteries, and preventing utility AC from passing through to connected equipment or charging the batteries. Use this switch to automatically reset the unit if it shuts down due to overload or overheating. First remove the excessive load or allow the unit to sufficiently cool (applicable to your situation). Switch to “OFF”, then back to “AUTO/REMOTE” or “CHARGE ONLY” as desired. If unit fails to reset, remove more load or allow unit to cool further and retry. Use an optional remote control mod­ule (Tripp Lite model APSRM4, sold separately) to reset unit due to overload only.
Indicator Lights
Your Inverter/Charger (as well as an optional Tripp Lite Remote Control Module, sold separately) is equipped with a simple, intuitive, user-friendly set of indicator lights. These easily-remembered “traffic light” signals will allow you, shortly after first use, to tell at a glance the charge condition of your batteries, as well as ascertain operating details and fault conditions.
LINE Green Indicator: If the operating mode switch is set to “AUTO/REMOTE,” this light will ILLUMINATE CONTINUOUSLY when your con­nected equipment is receiving continuous AC power supplied from a utility/generator source.
If the operating mode switch is set to “CHARGE ONLY,” this light will FLASH to alert you that the unit’s inverter is OFF and will NOT supply AC power in the absence of a utility/generator source or in over/under voltage situations.
INV (Inverting) Yellow Indicator: This light will ILLUMINATE CONTINUOUSLY whenever connected equipment is receiving battery-supplied, inverted AC power (in the absence of a utility/generator source or in over/under voltage situations). This light will be off when AC power is supplying the load. This light will FLASH to alert you if the load is less than the Battery Charge Conserver (Load Sense) setting.
LOAD Red Indicator: This red light will ILLUMI­NATE CONTINUOUSLY whenever the inverter is functioning and the power demanded by connected appliances and equipment exceeds 100% of load capacity. The light will FLASH to alert you when the inverter shuts down due to a severe overload or over­heating. If this happens, turn the operating mode switch “OFF”; remove the overload and let the unit cool. You may then turn the operating mode switch to either “AUTO/REMOTE” or “CHARGE ONLY” after it has adequately cooled. This light will be off when AC power is supplying the load.
BATTERY Indicator Lights: These three lights will illuminate in several sequences to show the approximate charge level of your con­nected battery bank and alert you to two fault conditions:
Approximate Battery Charge Level*
Indicator Illuminated Battery Capacity
Green 91%–Full
1
Green & Yellow 81%–90%
2
Yellow 61%–80%
3
Yellow & Red 41%–60%
4
Red 21%–40%
5
All three lights off 1%–20%
6
Flashing red 0% (Inverter
7
(Charging/Discharging)
1
2 3
4
6
5
shutdown)
* Charge levels listed are approximate. Actual conditions vary depending on battery condition and load.
7
Fault Condition
Indicator Illuminated Fault Condition
All three lights Excessive discharge
1
flash slowly* (Inverter shutdown) All three lights Overcharge (Charger
2
1
2
flash quickly** shutdown)
*Approximately ½ second on, ½ second off. See Troubleshooting section. ** Approximately ¼ sec­ond on, ¼ second off. May also indicate a battery charger fault exists. See Troubleshooting sec­tion.
Resetting Your Inverter/Charger to Restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your elec­trical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to “OFF” and remove some of the connected electrical load (ie: turn off some of the AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to either “AUTO/REMOTE” or “CHARGE ONLY.”
Output Circuit Breaker Reset: Alternatively, check output circuit breaker(s) on the unit’s front panel. If tripped, remove some of the elec­trical load, then wait one minute to allow components to cool before resetting the circuit breaker. See Troubleshooting for other possible reasons AC output may be absent.
4A
Configuration
INPUT C/B 10A
OUTPUT C/B 12A
B4 B3 B2 B1
A4 A3 A2 A1
Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger operation depending on your application.
Group B Dip Switches
Group A Dip Switches
Group A DIP Switches
Select Battery Type—REQUIRED
A1
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,” for more information.
Battery Type Switch Position
Gel Cell (Sealed) Battery Up Wet Cell (Vented) Battery Down (factory setting)
A2
Select High AC Input Voltage Point for Switching to Battery—OPTIONAL* APSX2424 models
Voltage Switch Position
278V Up 259V Down (factory setting) .
A4
A3
Select Low AC Input Voltage Point for Switching to Battery—OPTIONAL*
Voltage Switch Position
201V #A4 Up & #A3 Up 182V #A4 Up & #A3 Down 163V #A4 Down & #A3 Up 144V #A4 Down & #A3 Down
(factory setting)
* Most of your connected appliances and equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage Point is left in the factory setting and its Low AC Voltage Input Point is set to 182V. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.
A1A2A3A4
Charger Inhibit—OPTIONAL
A2
APSX750, APSX1250, APSX2012 models
Charger Switch Position
Inhibit Up Enable Down (factory setting)
Group B DIP Switches
B1
B2
Select Load Sharing—OPTIONAL
Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or generator when charging at its maximum rate. If your unit is supplying its full AC power rating to its connected heavy electrical loads at the same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility power.
To reduce the chance of tripping this breaker, Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum of the unit’s AC load and charge power within the circuit breaker rating. This charger-limiting function has four settings, allowing you to reduce the charger’s draw lower and lower, as needed, if the AC input circuit breaker keeps tripping under the normal AC loads of devices you have connected downline from the unit. The figures on the next page show how to set your DIP Switches to determine how heavy the connected load can be on your Inverter/Charger before charger-limiting begins.
5A
Configuration
B1B2B3B4
B1B2B3B4
B1B2B3B4
B1B2B3B4
"
(continued)
Select Battery Charger-Limiting Points—OPTIONAL
Most Limiting (#B1 & #B2 Up, factory
setting): Charger-limiting takes effect the moment any 230V AC load is applied; charger output falls gradually from full output at no 230V load passing through to no output at full load.
Less Limiting (#B1 Down & #B2 Up): Charger-limiting begins when the Inverter/Charger’s load reaches 33% of the Inverter/Charger’s load rating. Charger output falls gradually from full output at 33% of the Inverter/Charger’s load rating to about 33% of full output at full load.
Select Equalize Battery Charge—OPTIONAL
B3
This DIP Switch is momentarily engaged to begin the process of equal-
B1B2B3B4
"Reset"
izing the charge state of your battery’s cells by time-limited overcharge of all cells. This can extend the useful life of
"Equalize
certain types of batteries; consult with your battery’s manufac­turer to determine if your batteries could benefit from this process. The charge equalization process is automatic; once started, it can only be stopped by removing the input power.
Least Limiting (#B1 Up & #B2 Down): Charger-limiting begins at when the Inverter/Charger’s load reaches 66% of the Inverter/Charger’s load rating. Charger output falls gradually from full output at 66% of the Inverter/Charger’s load rating to about 66% of full output at full load.
No Limiting (#B1 & #B2 Down): No charger-limiting occurs at any load size.
Setting Procedure
• Move to “Equalize” (DOWN) position for three seconds.
• Move to “Reset” (UP) position and leave it there. This is the factory default setting.
CAUTION: Do not leave DIP switch #3 in the down position after beginning process. Battery charge equalization should only be performed in strict accordance with the battery manufacturer’s instructions and specifications.
Battery Charge Switch Position
Reset Up (factory setting) Equalize Down—momentarily
Set Battery Charging Amps—OPTIONAL
B4
Check specifications for your unit’s high­and low-charging amp options. By setting
B1B2B3B4
Battery Charger Switch Position
Low Charge Amps Up (factory setting)
High Charge Amps Down on high charging, your batteries will charge at maximum speed. When setting on low charging, you lengthen the life of your batteries (especially smaller ones).
CAUTION: When switching to the High Charge Amp setting, the user must ensure that the amp
hour capacity of their battery system exceeds the amperage of the High Charge Amp setting or
the batteries may be damaged or degraded.
Set Battery Charge Conserver (Load Sense) Control—OPTIONAL (Not on 750 or 1250 models)
In order to save battery power, the unit's inverter automatically shuts off in the absence of any power demand from connected equipment or appliances (the electrical load). When the Inverter/Charger detects a load, it automatical­ly turns its inverter function on. Users may choose the minimum load the Inverter/Charger will detect by adjusting the Battery Charge Conserver Control (see diagram). Using a small tool, turn the control clockwise to lower the minimum load that will be detected, causing the inverter to turn on for smaller loads. When the control is turned
MAX
(GREATER
LOAD
ON)
OFF
(LESSER
LOAD
ON)
fully clockwise, the inverter will operate even when there is no load. Turn the control counterclockwise to increase the minimum load that will be detected, causing the inverter to stay off until the new minimum load is reached.
NOTE: The factory setting for the control is fully clockwise. However, based on the threshold load to which you’d like the inverter to respond, you should adjust the control counterclockwise to reduce its sensitivity until the inverter is active only when connected equipment or appliances are actually in use.
Connect Remote Control—Optional
All models feature an 8-conductor telephone style receptacle on the front panel for use with an optional remote control module (Tripp Lite model APSRM4, sold separately). The remote module allows the Inverter/Charger to be mounted in a compartment or cabinet out of sight, while operated conveniently from a remote location. See instructions packed with the remote control module.
6A
Battery Selection
Select Battery Type
Select “Deep Cycle” batteries to enjoy optimum performance from your Inverter/Charger. Batteries of either Wet-Cell (vented) or Gel-Cell /Absorbed Glass Mat (sealed) construction are ideal. 6-volt “golf cart,” Marine Deep-Cycle or 8D Deep-Cycle batteries are also acceptable. You must set the Inverter/Charger’s Battery Type DIP Switch (see Configuration section for more information) to match the type of batteries you connect or your batteries may be degraded or damaged over an extended period of time.
Match Battery Amp-Hour Capacity to Your Application
Select a battery or system of batteries that will provide your Inverter/Charger with proper DC voltage and an adequate amp-hour capacity to power your application. Even though Tripp Lite Inverter/Chargers are highly-efficient at DC-to-AC inversion, their rated output capacities are limited by the total amp-hour capacity of connected batteries plus the output of an alternator when one is used.
Example
• STEP 1) Determine Total Wattage Required
Add the wattage ratings of all equipment you will connect to your Inverter/Charger. Wattage ratings are usually listed in equipment manuals or on nameplates. If your equipment is rated in amps, multiply that number times AC utility voltage to estimate watts. (Example: a drill requires 1.3 amps. 1.3 amps × 230 volts = 300 watts.)
NOTE: Your Inverter/Charger will operate at higher efficiencies at about 75% - 80% of nameplate rating.
Drill Orbital Sander Cordless Tool Charger
300W + 220W + 20W = 540W
Tools
• STEP 2) Determine DC Battery Amps Required
Divide the total wattage required (from step 1, above) by the battery voltage (i.e. 12 or 24) to determine the DC amps required.
• STEP 3) Estimate Battery Amp-Hours Required
Multiply the DC amps required (from step 2, above) by the number of hours you estimate you will operate your equipment exclusively from battery power before you have to recharge your batteries with utility- or genera­tor-supplied AC power. Compensate for inefficiency by multiplying this number by 1.2. This will give you a rough estimate of how many amp-hours of battery power (from one or several batteries) you should connect to your Inverter/Charger.
NOTE: Battery amp-hour ratings are usually given for a 20-hour discharge rate. Actual amp-hour capacities are less when batteries are discharged at faster rates. For example, batteries discharged in 55 minutes provide only 50% of their listed amp-hour ratings, while batteries discharged in 9 minutes provide as little as 30% of their amp-hour ratings.
• STEP 4) Estimate Battery Recharge Required, Given YourApplication
You must allow your batteries to recharge long enough to replace the charge lost during inverter operation or else you will eventually run down your batteries. To estimate the minimum amount of time you need to recharge your batteries given your application, divide your required battery amp-hours (from step 3, above) by your Inverter/Charger’s rated charging amps (see Specifications section).
NOTE: For Tripp Lite Inverter/Chargers providing 1000 watts or less of continuous AC power, a full-size battery will normally allow sufficient power for many applications before recharging is necessary. For mobile applications, if a single battery is continuously fed by an alternator at high idle or faster, then recharging from utility or generator power may not be necessary. For Tripp Lite Inverter/Chargers over 1000 watts used in mobile applications, Tripp Lite recommends you use at least two batteries, if possible fed by a heavy-duty alternator anytime the vehicle is running. Tripp Lite Inverter/Chargers will provide adequate power for ordinary usage within limited times without the assistance of utility or generator power. However, when operating extremely heavy electrical loads at their peak in the absence of utility power, you may wish to “assist your batteries” by running an auxiliary generator or vehicle engine, and doing so at faster than normal idling.
7A
Appliances
Blender Color TV Laptop Computer
300W + 140W + 100W = 540W
540 watts ÷ 12V = 45 DC Amps
45 DC Amps × 5 Hrs. Runtime
× 1.2 Inefficiency Rating = 270 Amp-Hours
270 Amp-Hours ÷ 30 Amps
Inverter/Charger Rating = 9 Hours Recharge
Mounting
WARNING! Mount your Inverter/Charger BEFORE DC battery and AC power connection. Failure to follow these instructions may lead to personal injury and/or damage to the Inverter/Charger and connected systems.
Tripp Lite manufactures a variety of different Inverter/Chargers with a variety of different mounting options for use in vehicular or non-vehicular applications. Tripp Lite recommends permanent mounting of your Inverter/Charger in any of the configurations illustrated below. User must supply mounting hardware and is responsible for determining if the hardware and mounting surface are suitable to support the weight of the Inverter/Charger. Contact Tripp Lite if you require further assistance in mounting your Inverter/Charger.
Vehicular and Non-Vehicular Horizontal Mount
(750 and 1250 models only)
Using the measurements from the diagram, install two user-sup-
A
plied ¼" (6 mm) fasteners into a rigid horizontal surface, leaving the heads slightly raised. Slide the Inverter/Charger back over
B
the fasteners to engage the mounting slots molded on the bottom of the Inverter/Charger cabinet. Install and tighten two user-sup-
C
plied ¼" (6 mm) fasteners into the mounting feet molded on the front of the Inverter/Charger cabinet.
C
A
M
11.4 cm
M
M
B
M
20 cm
M
M
M
17.1 cm
Vehicular and Non-Vehicular
(2012 and 2424 models only)
• Horizontal Mount • Vertical Mount • Inverted Mount
Tripp Lite’s Lateral Mounting Bracket (available as an option­al accessory from Tripp Lite*) provides a rigid surface for lat­eral mounting in vehicular or non-vehicular applications. Consult the instructions packed with the Lateral Mounting Bracket for complete mounting information. Note: your Inverter/Charger is not designed nor covered under warranty for vertical or inverted mounting in a vehicular application. Such mounting may be possible, however, when your Inverter/Charger is properly secured to a Lateral Mounting Bracket. As with any mounting, user is responsible for deter­mining if the Inverter/Charger can be mounted safely relative to their application. Since securing an Inverter/Charger to a Lateral Mounting Bracket which is not factory pre-installed will require some modifications to the Inverter/Charger cabi­net, please consult the Lateral Mounting Bracket owner’s man­ual prior to purchasing.
* Contact Tripp Lite for ordering information.
Lateral Mounting Bracket
Vehicular and Non-Vehicular Horizontal Mount and Non-Vehicular Vertical Mount
(2012 and 2424 models only)
Using the measurements from the diagram, install two user-sup-
A
plied ¼" (6 mm) fasteners into a rigid surface, leaving the heads slightly raised. Slide the Inverter/Charger forward over the fasteners to engage the mounting feet molded on the front of the Inverter/Charger cabinet. Install and tighten two user-supplied ¼" (6 mm) fasteners into the mounting feet molded on the rear of the Inverter/Charger cabinet. The rear feet extend beyond the unit’s cabinet to provide for adequate ventilation space behind the cooling fan(s); they should not be removed.
A
Note: APS model cabinets may have different front panel features, but all have identical mounting. Vertical Mount for select models only.
M
B
14.16 cm
C
C
B
M
M
M
38.12 cm
M
C
14.16 cm
M
M
38.12 cm
B
M
M
A
8A
Battery Connection
Connect your Inverter/Charger to your batteries using the following procedures:
• Connect DC Wiring: Though your
Inverter/Charger is a high-efficiency con­verter of electricity, its rated output capacity is limited by the length and gauge
DC Connectors
of the cabling run­ning from the battery to the unit. Use the shortest length and largest diameter cabling (maximum 2/0 gauge) to fit your Inverter/Charger’s DC Input terminals. Shorter and heavier gauge cabling reduces DC voltage drop and allows for maximum transfer of current. Your Inverter/Charger is capable of delivering peak wattage at up to 200% of its rated continuous wattage output
WARNING! • Failure to properly ground your Inverter/Charger to a vehicle’s chassis or earth ground may result in a lethal electrical shock hazard.
• Never attempt to operate your Inverter/Charger by connecting it directly to output from an alternator rather than a battery or battery bank.
• Observe proper polarity with all DC connections.
for brief periods of time. Heavier gauge cabling should be used when continuously operating heavy draw equipment under these conditions. Tighten your Inverter/Charger and battery terminals to approximately 3.5 Newton-meters of torque to create an effi­cient connection and to prevent excessive heating at this connection. Insufficient tight­ening of the terminals could void your war­ranty. See Specifications (included sepa-
rately) page for Minimum Recommended Cable Sizing Chart.
• Connect Ground: Using a #8 AWG wire
or larger directly connect the Main Ground Lug to the vehicle’s chassis or earth ground. See the Feature Identification section to locate
the Main Ground Lug on your specific Inverter/Charger model. All installations must comply with national and local codes and ordinances.
• Connect Fuse: Tripp Lite recommends that you connect all of your Inverter/Charger’s positive DC Terminals directly to a fuse(s) and fuse block(s) within 45 cm (18 inches) of the battery. The fuse’s rating must equal or exceed the Minimum DC Fuse Rating listed in your Inverter/Charger’s specifica­tions. See Specifications for fuse and fuse block recommendations. See diagrams below for proper fuse placement.
Non-Vehicular or Vehicular
Non-vehicular applications include stationary configurations as well as mobile configurations that are not integrated into a vehicle’s electrical system. In a parallel connection, your Inverter/Charger’s Nominal DC Input Voltage (listed in the Specifications section as either 12 or 24) must match the voltage of your battery or batteries (12 or 24). For example, a 12V DC Inverter/Charger would require 12V DC from your battery system.
In a series connection, your Inverter/Charger’s Nominal DC Input Voltage must match the number of batteries multiplied by their voltage. For example, a 24V DC Inverter/Charger would require either two 12V batteries connected in series (24 = 2 × 12) or four 6V batteries connected in series (24 = 4 × 6).
In vehicular applications, your Inverter/Charger’s Nominal DC Input Voltage must match the voltage of your battery or batteries— 12 Volts. Although it is possible to connect your Inverter/Charger to the main battery within your vehicle’s electrical system, in the normal vehicular context, the Inverter/Charger is connected to one or more dedicated auxiliary (house) batteries which are isolated from the drive system to prevent possible draining of the main battery.
Contact Tripp Lite technical support for assistance with additional parallel, series or series/parallel connections.
4
1
X Volts
6 Volts 6 Volts 6 Volts
2
X Volts Inverter/Charger
3
24 Volt Inverter/Charger
Optional connection
for Vehicular
applications only.
Single Battery Connection
1
5
2 2 2 2 4
6 Volts
Multiple Battery Connection (Series)— 24 Volt Shown
3
Note: X=Your Inverter/Charger’s Nominal DC Input Voltage (listed in the specifications section as either 12 or 24)
Earth or Vehicle/Boat Battery Ground Battery UL-Listed Fuse & Fuse Block (mounted within 45 cm of the battery) Large Diameter
Cabling, Maximum 2/0 Gauge to Fit Terminals Alternator (for vehicle or boat connection only)
5
9A
4321
AC Input/Output Connection
To avoid overloading your Inverter/Charger, be sure to match the power requirements of the equipment you plan to run at any one time (add their total watts) with the output wattage capacity of your Inverter/Charger model. When figuring the power requirements of your equipment, do not confuse “continuous” wattage with “peak” wattage ratings. Most electric motors require extra power at start-up (“peak” wattage) than required to run continuously after start-up, sometimes over 100% more. Some motors, such as in refrigerators and pumps, start and stop intermittently according to demand, requiring “peak” wattage at multiple, unpredictable times during operation.
• DoubleBoost™Feature
Tripp Lite Inverter/Chargers deliver up to twice their nameplate rated wattage for up to 10 seconds,* providing the extra power needed to cold start heavy-duty tools and equipment.
• OverPower™Feature
Tripp Lite Inverter/Chargers deliver up to 150% of their name plate rated wattage for up to 1 hour,* providing plenty of reserve power to reliably support tools and equipment longer.
* Actual duration depends on battery age, battery charge level and ambient temperature.
Connection for Models with Cords and Receptacles
With a user-supplied cable and country-specific plug, connect the Inverter/Charger's IEC-320 AC Input Receptacle to your utility wall out­let. Connect your equipment directly to the Inverter/Charger's IEC-320 AC Output Receptacle(s). Select models also include a Universal AC Output Adapter which allows you to connect equipment with a wide variety of plug styles.
Warning! Consult a qualified electrician and follow all applicable electrical codes and requirements for hardwire connection. Disconnect both DC input and AC utility supply before attempting hardwiring.
Connection for Models with Hardwire Terminals
Remove the screws and cover plate over the hardwire terminal box. Remove the knockout covers closest to the desired electrical source and to your equipment. Attach 1.28 cm diameter conduits (user-supplied) to the knockouts and thread wires through. Connect the conduits to each other with the ground bond connection supplied.
Ground*
• Connect the incoming and outgoing ground wires to the ground (green) terminals .
1
AC Input
“FOR USE WITH COPPER WIRE ONLY”
HOT IN
2 3 1 4 5
NEUTRAL IN
GROUND IN
GROUND OUT
HOT OUT
NEUTRAL OUT
• Connect the incoming hot wire to the input hot (brown) terminals .
2
• Connect the incoming neutral wire to the input neutral (blue) terminal .
3
AC Output
• Connect the outgoing hot wire to the output hot (black) terminal .
4
• Connect the outgoing neutral wire to the output neutral (white) terminal .
Replace cover plate and tighten screws.* If the incoming conduit only contains two wires (hot and neutral), the incoming conduit must be bonded to the main ground lug on the unit. In any case, the incoming conduit must be bonded to earth or vehicle ground, and the incoming con­duit must be bonded to the outgoing conduit.
5
10A
Service
If you are returning your Inverter/Charger to Tripp Lite, please pack it carefully, using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the Inverter/Charger is within the warranty period, enclose a copy of your sales receipt. To obtain service you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an author­ized Tripp Lite service center.
Maintenance
Your Inverter/Charger requires no maintenance and contains no user-serviceable or replaceable parts, but should be kept dry at all times. Periodically check, clean and tighten all cable connections as necessary, both at the unit and at the battery.
Troubleshooting
Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service before returning your unit for service.
Battery Indicator Lights
Operating Mode Switch
Operation Indicator Lights
SYMPTOM PROBLEMS CORRECTIONS
No AC Output Unit is not properly connected to utility power. Connect unit to utility power. (All Indicator Lights Are OFF)
Battery Not Recharging Connected batteries are dead. Check and replace old batteries. (AC Input Present)
All Three Battery Indicator Lights Battery is excessively discharged. Use an auxiliary charger* to raise battery voltage. Check external Are Slowly Flashing battery connections and fuse. Unit automatically resets when (½ Second Flashes) condition is cleared.
All Three Battery Indicator Lights Battery is overcharged. Unit will shut down to prevent Disconnect any auxiliary chargers. Reset by moving Operating Mode Are Rapidly Flashing battery damage. The problem may be with connected Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” (¼ Second Flashes) auxiliary chargers, if any, or with the unit’s charger. or “CHARGE ONLY.” If unit remains in shutdown mode after several
Red “LOW” Battery Battery voltage is low. Unit will automatically shut down Make sure that AC power is present in order to recharge batteries. Indicator Light is Flashing after 5 seconds to protect battery from damage. Reset by moving Operating Mode Switch to “OFF then to
Red “LOAD” Operation Inverter is overloaded. Unit will automatically shut down Reduce load. Reset by moving Operating Mode Switch to “OFF.” Indicator Light Flashing after 5 seconds. Wait 1minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”
* User-supplied.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.
Operating Mode Switch is set to “OFF” and Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY.” AC input is present.
This is normal when the Operating Mode Switch No correction is required. AC output will return when AC input is set to “CHARGE ONLY” and AC input is absent. returns. Set Operating Mode Switch to “AUTO/REMOTE” if you
Circuit breaker is tripped. Reset circuit breaker. Unit has shut down due to battery overcharge (preventing Disconnect any auxiliary chargers. Reset by moving Operating
battery damage). The problem may be with connected Mode Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” auxiliary chargers, if any, or with the unit’s charger. or “CHARGE ONLY.” If unit remains in shutdown mode after several
Unit has shut down due to excessive battery discharge. Use an auxiliary charger* to raise battery voltage. Check external
Unit has shut down due to overload. Reduce load. Reset by moving Operating Mode Switch to “OFF.”
Battery fuse* is blown. Check and replace fuse.* Battery cabling* is loose. Check and tighten or replace cabling.* Unit has shut down due to battery overcharge (preventing Disconnect any auxiliary chargers. Reset by moving Operating Mode
battery damage). The problem may be with connected Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” or auxiliary chargers, if any, or with the unit’s charger. “CHARGE ONLY.” If unit remains in shutdown mode after several
Input circuit breaker is tripped. Reset circuit breaker.
False reading due to undersized or insufficiently connected Use sufficient size DC cable sufficiently connected to the DC cabling. Inverter/Charger.
11A
require AC output.
attempts to reset, contact Tripp Lite Customer Service for assistance.
battery connections and fuse. Unit automatically resets when condition is cleared.
Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”
attempts to reset, contact Tripp Lite Customer Service for assistance.
attempts to reset, contact Tripp Lite Customer Service for assistance.
“AUTO/REMOTE” or “CHARGE ONLY.”
Manual del propietario
PowerVerter
®
Serie APSX
Inversores/cargadores de corriente
continua a corriente alterna
Entrada Salida
Inversión: 12 o 24 VCC 230V, 50 Hz. CA Carga: 230 V, 50 Hz. CA 12 o 24 VCC
Confiable energía de respaldo de emergencia
¡Felicitaciones! Ha adquirido el inversor/cargador más avanzado y con más funciones, diseñado como una fuente alternativa de energía durante fallas del suministro de energía de la red. Los inversores/cargadores Tripp Lite APS mantienen sus equipos constantemente en operación y pro­ductivos durante cualquier problema de energía de la red (fallas del servicio eléctrico, bajas de voltaje y voltajes altos) convirtiendo la energía de corriente continua de baterías suministradas por el usuario, en energía de corriente alterna. La supresión de sobretensiones integrada propor­ciona un nivel adicional de protección al equipo. Cuando hay energía de la red, los inversores/cargadores APS pasan automáticamente la energía a sus equipos, y recargan simultáneamente el banco de baterías conectado. Los inversores/cargadores APS son la alternativa silenciosa a los gen­eradores de gasolina durante aplicaciones de respaldo de emergencia—¡sin humo, combustible ni ruido! Usted obtiene energía de corriente alter­na en cualquier lugar y en cualquier momento en que la necesite.
Mejor para su equipo Niveles de protección Premium
• Protección contra sobretensiones integrada Isobar
• Protección automática contra sobrecarga
1111 W. 35th Street, Chicago, IL 60609 USA
Soporte al cliente: (773) 869-1212
www.tripplite.com
Salida ideal para cualquier carga (incluyendo computadoras)
• Salida controlada por frecuencia
• Rápida conmutación de carga
• Reparto de carga balanceada
Mejor para sus baterías Recarga de baterías más rápida
• Cargador de baterías de 3 etapas de alta capacidad (ajustable)
Protección crítica de batería
• Conservador de carga de batería (Detección de carga)*
• Inversión de CC a CA de alta eficiencia
Mejor para usted Operación simple y sin mantenimiento
• Luces y conmutadores multifunción
• Arranque con batería agotada
• Fabricación resistente a la humedad**
Contenido
Seguridad 13 Garantía 13 Identificación de funciones 14
Conexión de la batería 20 Conexión de entrada/salida de corriente alterna Servicio/Mantenimiento/Solución de problemas
21
22
Operación 15 Configuración 16-17 Selección de baterías 18 Montaje 19
* Disponible en todos los modelos, excepto el 750 y el 1250. ** Los inversores/cargadores son resistentes a la humedad, pero no son impermeables.
Copyright © 2005. PowerVerter
®
es una marca comercial registrada de Tripp Lite. Todos los derechos reservados.
English 1 Français 23
Pyсский 34
Instrucciones de seguridad importantes
¡GUARDE ESTAS INSTRUCCIONES!
Este manual contiene instrucciones y advertencias importantes que deben seguirse durante la instalación, operación y almacenamiento de todos los inversores/cargadores de Tripp Lite.
Advertencias de ubicación
• Instale su inversor/cargador (ya sea para una aplicación móvil o estacionaria) en un lugar o compartimiento que minimice la exposición al calor, al polvo, a la luz solar directa y a la humedad.
• Aunque su inversor/cargador es resistente a la humedad, NO es impermeable. Llenar la unidad con agua causará un cortocircuito y podría causar lesiones personales por choque eléctrico. Nunca sumerja la unidad, y evite toda área donde pueda acumularse agua. El montaje debe realizarse en la ubicación más seca disponible.
• Deje una luz mínima de 5 cm en la parte frontal y posterior del inversor/cargador para una adecuada ventilación. A mayor carga del equipo conectado, la unidad generará más calor.
• No instale el inversor/cargador directamente cerca de medios de almacenamiento magnético, ya que puede dañar los datos.
• No lo instale cerca de materiales inflamables, combustibles o productos químicos.
Advertencias de conexión de batería
• Los sistemas de baterías múltiples deben estar conformados por baterías con un voltaje, una antigüedad, una capacidad en amperios hora y un tipo idénticos.
• Debido a que puede acumularse gas hidrógeno explosivo cerca de las baterías si no están bien ventiladas, no debe instalar baterías (ya sea para una aplicación móvil o estacionaria) en un compartimiento sin circulación de aire. En forma ideal, cualquier compartimiento tendría cierta ventilación al exterior.
• Pueden producirse chispas durante la conexión final de la batería. Siempre observe la correcta polaridad al conectar las baterías.
• No permita que ningún objeto entre en contacto con los dos terminales de entrada de corriente continua. No ponga en cortocircuito ni en puente estos terminales. Podrían producirse serias lesiones personales o daños a la propiedad.
Advertencias sobre la conexión de equipos
No use un inversor/cargador Tripp Lite APS para aplicaciones de soporte de vida o cuidado de la salud, en las que un fun­cionamiento defectuoso o una falla del inversor/cargador Tripp Lite pueda causar la falla o una alteración importante en el funcionamiento del dispositivo médico o de soporte de vida
• Modelos con cordón: No modifique el enchufe del inversor/cargador ni la toma en una forma en que elimine su conexión a tierra. No use adaptadores de potencia que eliminen la conexión a tierra del enchufe.
• Conecte su inversor/cargador sólo a una salida de corriente alterna o a una fuente cableada adecuadamente puesta a tierra. No conecte la unidad a si misma; esto dañará el dispositivo y anulará su garantía.
• Puede experimentar un funcionamiento irregular si conecta un supresor de sobretensiones, un acondicionador de línea o un UPS a la salida del inversor/cargador.
Advertencias de operación
• Su inversor/cargador no requiere un mantenimiento de rutina. No abra el dispositivo por ninguna razón. No hay partes en su interior que requieran mantenimiento por parte del usuario.
• Mientras la alimentación de baterías y/o la entrada de corriente alterna estén conectadas, hay voltajes potencialmente letales dentro del inversor/cargador. En consecuencia, durante cualquier trabajo de mantenimiento, deben desconectarse la alimentación de baterías y la entrada de corriente alterna.
• No conecte ni desconecte las baterías mientras el inversor/cargador está operando en modo de inversión o de carga. El conmutador del modo de operación debe estar en la posición apagado. Puede producirse un arco peligroso.
Garantía limitada
Tripp Lite garantiza que su inversor/cargador no tiene defectos en materiales ni mano de obra por un período de un año (excepto fuera de EE.UU., Canadá y México-120 días) desde la fecha de compra por parte del usuario final. Bajo esta garantía, la obligación de Tripp Lite se limita a reparar o reemplazar (a su exclusiva elección) cualquier producto defectuoso. Para obtener servicio bajo esta garantía, debe conseguir un número de Autorización de devolución de mercadería (RMA) de Tripp Lite o de un centro de ser­vicio autorizado de Tripp Lite. Los productos deben ser devueltos a Tripp Lite o a un centro de servicio autorizado de Tripp Lite con los cargos de transporte pagados por adelantado, acompañados de una breve descripción del problema y un comprobante de la fecha y el lugar de compra.
Esta garantía no se aplica al equipo que ha sido dañado por accidente, negligencia o uso inadecuado, o que ha sido alterado o modificado en cualquier forma, incluyendo la abertura de la caja de la unidad por cualquier motivo.Esta garantía solamente se apli­ca al comprador original que debe haber registrado correctamente el producto dentro de los 10 días de la compra.
SALVO POR LO ESTABLECIDO EN ESTE DOCUMENTO, TRIPP LITE NO ESTABLECE NINGUNA GARANTÍA, EXPRESA O IMPLÍCITA, INCLUYENDO GARANTÍAS DE COMERCIABILIDAD O IDONEIDAD PARA UN PROPÓSITO PARTICULAR.Algunos estados no permiten limitaciones o exclusiones de las garantías implícitas; por lo tanto, las limitaciones o exclusiones mencionadas anteriormente pueden no aplicarse al comprador.
SALVO POR LO ESTABLECIDO ANTERIORMENTE, EN NINGÚN CASO TRIPP LITE SERÁ RESPONSABLE POR DAÑOS DIRECTOS, INDIRECTOS, ESPECIALES, INCIDENTALES O EMERGENTES, RESULTANTES DEL USO DE ESTE PRODUCTO, AUN EN EL CASO DE HABERSE INFORMADO DE LA POSIBILIDAD DE DICHOS DAÑOS. Específicamente, Tripp Lite no es responsable por ningún costo, como pérdida de ingresos o beneficios, pérdida de equipos, pérdida de uso de equipos, pérdida de software, pérdida de datos, costos por reemplazos, reclamaciones de terceras partes, o lo que corresponda.
Tripp Lite tiene una política de mejoramiento continuo. Las especificaciones están sujetas a cambio sin previo aviso.
13A
Identificación de funciones
Identifica las funciones Premium en su modelo específico y ubica rápidamente las instrucciones para optimizar su utilización.
Conmutadores DIP de configuración: Optimizan la operación
1
de su inversor/cargador en función de su aplicación. Consulte la Sección Configuración para instrucciones de ajuste.
Conmutador de modo de operación: Controla la operación del
2
inversor/cargador. El ajuste “AUTO/REMOTE” (AUTOMÁTICO/REMOTO) asegura que su equipo recibe una energía constante e ininterrumpida de corriente alterna. También permite monitorear y controlar el inversor/cargador en forma remota con un módulo opcional remoto (Tripp Lite modelo APSRM4, vendido por separado). El ajuste “CHARGE ONLY” (SOLO RECARGA) permite a sus baterías regresar a carga completa más rápidamente mediante el apagado del inversor, lo que detiene la descarga de la batería. Consulte la Sección Operación para instrucciones de ajuste.
Luces indicadoras de operación: Luces tipo “semáforo” indi-
3
can si el inversor/cargador está operando desde una línea de cor­riente alterna o con energía de corriente continua de baterías. También le advierte si la carga del equipo conectado es demasi­ado alta. Consulte la Sección Operación para instrucciones sobre la lectura de las luces indicadoras.
4
Luces indicadoras de batería: Luces tipo “semáforo” indican
el nivel aproximado de carga de su batería. Consulte la Sección Operación para instrucciones sobre la lectura de las luces indi­cadoras.
5
Terminales de potencia de corriente continua: Se conectan a
los terminales de su batería. Consulte la Sección Conexión de batería para instrucciones de conexión.
6
Tomas de salida de CA (no en modelos cableados):
Receptáculos IEC-320 de salida le permiten conectar equipos que usted normalmente conectaría en una toma de la red. Los modelos exclusivos también incluyen un adaptador universal de salida de CA que permite conectar equipos con una gran var­iedad de tipos de enchufe.
7
Receptáculo de entrada de CA (no en modelos cableados): El
receptáculo IEC-320 de entrada conecta el inversor/cargador a cualquier fuente de energía de CA de la red o suministrada por un generador cuando se emplea con un cable suministrado por el usuario con algún enchufe de uso local especial.
Regleta cableada de terminales de entrada/salida de corri-
8
ente alterna (no en modelos con cordón): Conecta firmemente
el inversor/cargador al sistema eléctrico de la red o del vehícu­lo. Consulte las instrucciones de conexión en la Sección Conexión de entrada/salida.
9
Interruptores automáticos restaurables: Protegen su inver-
sor/cargador contra daños por sobrecarga. Consulte las instruc­ciones de reajuste en la Sección Operación.
10
Conector del módulo de control remoto: Permite el monitoreo
y control en forma remota con un módulo opcional (Tripp Lite modelo APSRM4, vendido por separado). Vea el Manual del propietario del módulo remoto para obtener instrucciones de conexión.
11
Control del conservador de carga de batería (Detección de carga) (disponible en modelos exclusivos): Conserva la
energía de batería ajustando el nivel de carga baja al que el inversor/cargador se apaga automáticamente. Consulte la Sección Configuración para las instrucciones de ajuste.
Oreja principal de tierra: Conecta adecuadamente el inver-
12
sor/cargador a tierra o al sistema de tierra del vehículo o del barco. Consulte la Sección Conexión de batería para las instruc­ciones de conexión.
Ventilador de enfriamiento controlado por termostato:
13
Ventilador silencioso y eficiente que regula la temperatura inter­na y prolonga la vida de servicio del equipo. El ventilador opera en forma intermitentemente dependiendo de la temperatura y la carga.
14
Placa de cubierta de terminales de energía CC Placa de cubierta de entrada/salida de CA cableada
15
Función Arranque con batería agotada (para todos los mod­elos, interna, no mostrada): Un circuito interno le permite
arrancar el inversor/cargador incluso con una batería agotada conectada a la unidad. En tanto el inversor/cargador esté conec­tado a una fuente de energía de CA de la red o suministrada por un generador, pasará energía de CA al equipo conectado y car­gará las baterías conectadas.
1 24 3
5
Vista frontal (Modelos con cordón 750 y 1250).
1013
7
1
9
6
12
Vista frontal (Modelos cableados 2012 y 2424).
14A
5
10 111314
“FOR USE WITH COPPER WIRE ONLY”
HOT IN
NEUTRAL IN
GROUND IN
GROUND OUT
HOT OUT
NEUTRAL OUT
8 15
24 3
16
Montaje lateral, no mostrado
Montaje posterior, no mostrado
12
9