Troubleshooting:............................... p. 11
Warranty: .......................................... p. 12
Specifications: .................................. p. 12
Maintenance & Service: ................... p. 12
1
Introduction
Congratulations! You’ve purchased the most advanced, feature-rich integrated inverter/battery
charger on the market. Your APS provides your equipment with utility-supplied AC power, when
present. During a blackout, overvoltage or brownout, your APS automatically switches over to an
external battery source to power connected equipment with voltage and frequency-controlled
AC power.
Multi-Function Indicator Lights
Two sets of indicator lights keep you constantly informed of battery charge levels, fault conditions and
APS operation. One set of multi-function lights displays battery charge conditions and fault warnings.
The second set of multi-function lights displays APS operation conditions.
Multi-Operation Switches
Two control points give you convenient options when operating your APS. Set a variety of voltage
levels at which your APS’s inverter will turn on to maximize equipment protection and minimize battery
drain. Other options include a remote-control setting for greater convenience and a battery type
setting for greater charging efficiency.
Frequency-Controlled Output (Invert Mode)
Your APS controls line frequency so frequency-sensitive equipment can operate properly.
Automatic Overload Protection
If you overload your APS, it will automatically protect itself and your valuable batteries from damage.
2
Bulk
Stage 1
Stage 2
Absorption
Stage 3
Float
Advanced, 3-Stage
Battery Charger
Your APS recharges your battery faster
than conventional chargers because
its three-stage charger profiles (Bulk,
Absorption and Float) are optimized,
regardless of the type of battery you
use (Wet or Gel).* In addition, the
advanced charging system protects
against over-charge and overdischarge to ensure a longer service
life from your battery.
* The Absorption and Float levels vary according to battery
type which is field settable either "Wet" or "Gel" Cell.
High Efficiency Output
Your APS’s advanced circuitry produces
a more efficient DC-to-AC conversion,
minimizing energy loss. This allows you
to run connected equipment longer
between battery charges. The APS will
maintain this highly-efficient output even
as the battery charge decreases.
This manual contains important instructions and warnings that should be followed during the
handling, installation, operation and storage of Tripp Lite APS Automatic Power Systems.
3
APS Installation
Configuration DIP Switch Settings*
(See Diagram 1, p. 46. Note: 1.1 is a closeup of the Configuration Dip Switches. 1.2 is “front”,
1.3 is “rear”).
Using a small tool, set the 4 Configuration DIP Switches (located on the bottom of your APS) to select
battery type and set the voltage range outside of which your APS will switch to battery power.
* Select before permanently mounting your APS.
• Select Battery Type
(DIP Switch #1)
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be degraded or
damaged over an extended period of time. See “Battery Selection,” page 6 for more information.
Battery TypeSwitch Position
Gel Cell (Sealed) Battery ................................. Front
(See Diagram 2, p. 46. Note: 2.1 is the “adjustment resistor” located in the upper right-hand
corner of the component side of the circuit board).
To permanently convert the APS INT 512 to 60 Hz., qualified service personnel should open the APS
case, locate the resistor on the circuit board and remove it.
* Turn your APS OFF and disconnect from the wall outlet before 60 Hz conversion.
Electrical Connection
Plug APS INT 512 models into outlets providing 230V AC, 50 or 60 Hz. power.
4
APS Installation (Optional)
Permanent Mounting*
(See Diagram 3, p. 46).
• Install four 5 mm (#8) fasteners** into a rigid
diagram. (Leave head of fasteners slightly above surface in order to engage keyhole slots molded
into the bottom of the APS's feet.)
• Place the APS's four keyhole slots over the four fasteners and slide APS forward or back to secure.
Install “L”-shaped bracket* to permanently hold APS in position.
* Recommended for vehicular installation or other application requiring permanent, secure mounting.
** All fasteners and brackets are user-supplied. Turn your APS OFF and disconnect from the wall outlet before
mounting.
Splash Guard Installation*
(See Diagram 4, p. 46).
Thread four 4 mm (#8) sheet metal screws through four holes in a rigid
measuring 175 mm x 225 mm, through four 25 mm long hollow spacers and into the four blind holes
in the top panel of your APS.
* Recommended for use in wet locations. All sheet metal screws, splash guard and hollow spacers are user-supplied. Turn your APS OFF
and disconnect from wall outlet before installation.
APS INSTALLATION
SAFETY WARNINGS
• Install your APS indoors, away from excess moisture or heat, dust or direct sunlight.
• Leave adequate space around all sides of the APS for proper ventilation. The heavier
the load of your connected equipment, the more heat will be generated.
• Do not remove or modify the ground pin of the APS's plug. Do not use two-prong
adapters with the APS's plug.
• Connect your APS to a three-wire, grounded AC power outlet. Do not plug your APS
into itself; this will damage the APS and void your warranty.
horizontal
surface using the measurements in the
horizontal
splash guard
5
Battery Selection
Selecting Battery Type
Select a battery or system of batteries that will provide your APS with 12V DC and your equipment
with an adequate amp hour capacity.*
* Even though APS models are high-efficiency converters of electricity, their rated output capacities are limited by the amp-hour size
of the external batteries.
Select ‘Deep-Cycle’ batteries to enjoy optimum performance from your APS. Select batteries of
either Wet-Cell (vented) or Gel-Cell/Absorbed Glass Mat (sealed) construction. 6 Volt “golf-cart,”
Marine Deep-Cycle or 8D Deep-Cycle batteries are also acceptable.**
** You must set Configuration DIP Switch #1 (Battery Type) to match the type of batteries you connect or your batteries
may be degraded or damaged over an extended period of time. See “APS Installation,” for more information.
Selecting Battery Amp Hour Capacity
Step 1:
Add the Wattage Ratings of your connected equipment to determine the Total Wattage Required.*
* The wattage rating is usually stated in the equipment's manuals or on their nameplates. If your equipment is rated in
amperes, convert to watts by multiplying the ampere rating by your nominal AC line voltage (230).
Step 2:
Divide the Total Wattage Required (from Step 1) by 12 to determine the DC Amperes Required.
Step 3:
Multiply the DC Amperes Required (from Step 2) by the Number of Hours Between Battery
Charging to determine the Battery Amp-Hour Rough Estimate.
Step 4:
Battery Amp-Hour ratings are usually given for a 20 hour discharge rate. Actual Amp-Hour capacity
is less when discharged at a faster rate. To compensate for this discrepency, multiply the Battery
Amp-Hour Rough Estimate (from Step 3) by 1.2 to determine the optimum battery amp-hour size
you should connect to your APS.**
** Your charging amps multiplied by the charging hours must exceed the discharge amp-hours taken from the batteries
between charges or you will eventually rundown your battery bank.
Battery Connection
SAFETY WARNINGS
• You must connect batteries in order for APS models to operate.
• Multiple battery systems must be made up of batteries of the same voltage, age, amp hour
capacity and type.
• Keep battery location well-ventilated. Explosive hydrogen gas can accumulate near the
battery if it is not kept well ventilated. Sparks may result during final battery connection.
• Do not allow objects to contact the two DC input terminals. Do not short or bridge them
together. Serious injury to person and/or property could result.
6
Battery Connection (Standard)
Single 12V Battery Connection
(See Diagram 5, p. 46. Note: 5.1 is the fuse.)
Multiple 12V Battery System Connection (in Parallel)
(See Diagram 6, p. 47. Note: 6.1 is the fuse.)
Multiple 6V Battery System Connection (in Series)
(See Diagram 7, p. 47. Note: 7.1 is the fuse. Also, the connection will combine to provide
12V DC).
• Connect your APS's positive DC Terminal directly to a fuse near
your battery.
UL recommends that you install a recognized UL component fuse block and fuse within 18 inches of
the battery. The fuse should be rated a minimum of 100 amps. (See Figures 5, 6 and 7 for
recommended connection).
• Use the SHORTEST and HEAVIEST GAUGE battery cabling.
Use #4 cabling for DC cable lengths up to 10 feet. Use #2 cabling for lengths up to 16 feet. Shorter
and heavier gauge cabling limits DC voltage drop and allows for maximum transfer of current.*
* APS models are capable of delivering a much higher wattage output for brief periods of time. Therefore the wiring should
be configured to handle this brief high-current potential draw. Even though APS models are high-efficiency converters of
electricity, their rated output capacities are limited by the length and gauge of the wires running from the battery to the APS.
Battery Connection (Vehicular)
Choose the Basic Connection if you are running light hand tools or other small appliances for a brief
period of time (see Diagram 8, p. 47. Note: 8.1 is the alternator; 8.2 is the vehicle battery ground;
8.3 is a 12V vehicle battery; and 8.4 is the fuse). Choose the Advanced Connection if you are using
your APS to power heavy loads for extended periods of time (see Diagram 9, p. 47. Note: 9.1 is the
alternator; 9.2 is a battery isolator; 9.3 is the vehicle battery ground; 9.4 is a 12V vehicle battery;
and 9.5 is the fuse). This connection incorporates a battery isolator and separate battery system to
provide battery power to your APS while preventing it from draining your vehicle's battery. Note:
Depending on your application, you may require more than one 12V Deep Cycle Battery.
Caution: Never operate your APS from an alternator without a battery connected as show in Diagrams 8 and 9, p.47
7
Equipment Connection
Match the power requirements of your equipment with the power
output of your APS to avoid overload.
When figuring the power requirements of your equipment, do not confuse “Continuous” power
ratings with “Peak” power ratings. Electric motors require more power to turn ON (“peak power”)
than they require to run continuously. “Peak” power ratings are usually 2 to 5 times “Continuous”
ratings. Most electric motors require “peak power” only once when they initially start. However, the
electric motors found in equipment such as refrigerators and sump pumps constantly cycle ON and
OFF in relation to demand. These motors require “peak power” at multiple, unpredictable times
during their operation.*
* After the APS has started an electric motor, it will have reserve power while the motor is running to dedicate to other
devices. Increase the APS load at your discretion. Note: If your batteries are low or the motor is very inefficient, worn or
old, the battery fuses may blow.
Connect your equipment to the APS's receptacles.*
• computers• kitchen appliances• CD players
• microwaves• refrigerators• VCRs
• sump pumps• electric motors (up to 1/6 hp)• lights
• power tools• tape recorders• turntables
• and more!
* All APS models feature Frequency Controlled Inverter Output which allows devices dependent on AC line frequency to operate
properly. Devices that are dependent on line frequency include computers, VCRs, CD players, tape recorders, clocks and turntables.
Set “Operating Mode” Switch
• Switch to “AUTO” when you are using connected equipment. ADVANTAGE: Provides battery
backup power during blackouts or brownouts.
• Switch to “CHARGE ONLY/REMOTE” when you are not using connected equipment.
(WARNING! UPS will not provide battery backup!) ADVANTAGES: A) Continues to charge battery
when power is present, and B) Turns OFF the APS’s inverter, preventing battery drain during
blackouts or brownouts.
Note: When the switch is in the “CHARGE ONLY/REMOTE” position, you can operate a
user-supplied 2-position switch to transfer between the “CHARGE ONLY” and “AUTO”
modes. (See Remote Connector description on page 10.)
• Switch to “OFF” to completely turn off the APS and connected equipment or to reset the APS after
it has shut down due to overload or overheating.
Equipment Connection
SAFETY WARNINGS
• Tripp Lite does not recommend the use of any of its APS series auto-switching emergency
power sources in any life support application when a malfunction or failure of a Tripp Lite
APS unit could cause failure or significantly alter the performance of the life support device.
Contact Tripp Lite for further information on this subject.
• Do not plug a surge suppressor, line conditioner or UPS into the AC output receptacles
of the unit.
• Do not plug your APS into itself; this will damage the APS and void your warranty.
8
Switches, Indicator Lights
& Other Features
(See Diagram 10, p. 48 to locate the following switches, indicator lights and other features. 10.1
shows the UniPlug Universal Plug Adaptor [included with APS INT 512 models] which accepts
most worldwide plug configurations; 10.2 shows the plug and cordset. Note: 10.21=ground,
10.22=neutral, 10.23=line 1, 10.24=detachable line cord. 10.3 shows the “Configuration Dip
Switches” located on the bottom of the unit.)
Switches
1. “Operating Mode” Switch
This switch selects the APS operating mode (either “CHARGE ONLY/REMOTE”, “AUTO”, or
“OFF”. See “Equipment Connection” for the optimum switch setting.
2. “CONFIGURATION” DIP Switches
These four switches must be set for the type of battery your APS will be connected to and the voltage
range outside of which your APS will switch to battery power. The Battery Type DIP Switch #1 setting
must match the type of batteries you connect or your batteries may be degraded or damaged over
an extended period of time. Most loads will perform adequately when your APS’s High AC Voltage
Point DIP Switch #2 is set to 257V and its Low AC Voltage Point DIP Switches #3 and #4 are set to
181V. Set your APS above or below these points, however, to minimize frequent battery operation
caused by momentary high/low line voltage swings which have little effect on equipment operation.
(See “APS Installation” and Diagram 1 on page 46.)
Indicator Lights
3. “LINE”
This green light will turn continuously ON whenever connected equipment is receiving utility-supplied
AC power. It will flash intermittently when utility power is present and your APS's Operating Mode
Switch is set to “Charge Only/Remote” to warn you that the APS's inverter is OFF and that the APS
WILL NOT provide battery backup during blackouts, brownouts or overvoltages.
4. “INV”
This red light will turn continuously ON whenever connected equipment is receiving battery-supplied
AC power (during a blackout, brownout or overvoltage while connected to utility power or when
connected to batteries during vehicular operation).
5. “LOAD”
This red light will turn continuously ON when the APS’s load is between 80% and 110% of capacity.
The light will flash intermittently when the APS's inverter shuts down due to a severe overload or
overheating. If this happens, turn Operating Mode Switch OFF. Remove overload. Let the unit cool.
You may then turn the APS ON again.
9
6. “BATTERY HI/MED/LO”
These three lights will turn ON in several sequences to show the approximate charge level and
voltage of your connected battery bank and alert you to several fault conditions:
All lights “Slow” Flash*Excessive discharge<8.0
All lights “Rapid” Flash**Overcharge>16.0
* Approximately 1/2 second on, 1/2 second off. See Troubleshooting section.
** Approximately 1/4 second on, 1/4 second off. May also indicate a battery charger fault exists. See Troubleshooting section.
Other Features
7. DC Input Terminals
The terminals' wing nuts secure the wires leading from your external battery. Connect a battery or
system of batteries that will ultimately combine to provide your APS with 12V DC and your equipment
with an adequate amp hour capacity. For best connection, use soldered lugs on your battery cable.
See Battery Selection section for more information.
8. AC Receptacles (NEMA 5-15R)
These receptacles allow connection of equipment designed to run on 230 VAC 50/60 Hz. power.
APS INT 512 models may require receptacle adapters (Universal Adapter included see Diagram
10.1, p. 48) to connect equipment to the APS.
9. AC Line Cord (NEMA 5-15P fixed or detachable)
Plug the cord into a 230V, 50/60 Hz. outlet. DO NOT plug the cord into the APS’s AC receptacles.
The APS INT 512 features an IEC-320 male plug and a detachable IEC-320 female to NEMA 5-15P
male cord set. Note the polarity of the plug in Diagram 10.2, p. 48.
10. Resettable Circuit Breaker
The circuit breaker protects your APS against damage due to output overload. Remove overload.
Wait 1 minute. Reset circuit breaker.
11. Remote “ON/OFF” Connector
This allows for remote APS control using user-supplied wire and 2-position switch. The connector
accepts a 3.5 mm 2-wire miniature phone plug. Note: The user-supplied remote switch can only
control APS operation when the APS “OPERATING MODE” switch is in the “CHARGE-ONLY”
position. The remote switch can only transfer between the “CHARGE-ONLY” and “AUTO” modes.
After completing a remote connection, determine which position is the “CHARGE-ONLY” mode and
which position is the “AUTO” mode for your particular switch. The position on your remote switch
that causes the green “LINE” indicator light to flash intermittently is the “CHARGE-ONLY” mode
position.
10
Troubleshooting
Before sending your APS in for service, always check the following first. Call Tripp Lite Customer Service before
sending in your APS
SYMPTOMPROBLEMSCORRECTIONS
APS receptacles do not provide APS not properly connected toConnect APS to wall receptacle.
AC output (AC input present)wall receptacle.
Circuit breaker is tripped.Reset circuit breaker.
APS shutdown due to excessiveTurn APS OFF. Wait 1 minute and
battery voltage (> 16V DC), indicat-switch to “AUTO”.
ing possible charger failure. Line
disconnected to prevent permanent
battery damage.
APS is set to “OFF”Set APS to “AUTO” or “CHARGE-
APS receptacles do not provide Circuit breaker is tripped.Reset circuit breaker.
AC output (AC input absent)
Operating Mode Switch is setSet Operating Mode Switch to “AUTO.”
to “Charge Only.”
Load or High temperature fault.Turn APS OFF. Wait 1 minute.
APS will not charge theConnected batteries are dead.Check and replace old batteries.
battery (AC input present)
Battery fuse* is blown.Check and replace fuse.
Battery cabling* is loose or degraded. Check and tighten or replace cabling.
APS charger failure.Turn APS OFF. Wait 1 minute and
All APS Indicator Lights areThis is normal if the APS is set—
OFF (AC input absent)to “CHARGE-ONLY”
All APS Indicator Lights areExcessive battery discharge.Use an auxiliary charger to raise
OFF (AC input is present orbattery voltage to at least 9V DC.
absent)Check external Battery connections
All APS Battery IndicatorExcessive battery discharge.Use an auxiliary charger to raise
Lights are slowly flashing.battery voltage to at least 9V DC.
APS “LO” Battery LightInverter shutdown because batteryReset by cycling control switch to
flashingvoltage less than 10V DC for moreOFF position then ON.
than 5 seconds. Protects battery
from permanent damage.
All APS Battery Lights areHigh battery voltage shutdownCheck all charging sources.
rapidly flashingduring Charge mode.Reset by cycling control switch to
APS “LOAD” Indicator LightInverter overload caused byReset by reducing load and cycling conis rapidly flashingexcessive load or short circuit.trol switch to OFF position then ON.
If sustained for more then 5
seconds the Inverter is shutdown.
*User supplied
ONLY”.
Remove overload. Switch to “AUTO.”
switch to “AUTO”. If automatic shutdown occurs, call Tripp Lite
Customer Service.
and fuse. Automatically resets when
condition is cleared.
Automatically resets when condition
is cleared.
OFF position then ON.
11
Limited Warranty
Tripp Lite warrants its products to be free from defects in materials and workmanship for a period of one year (domestic) or 120 days
(export) from the date of initial purchase. Tripp Lite’s obligation under this warranty is limited to repairing or replacing (at its sole option)
any such defective products. To obtain service under this warranty you must obtain a Returned Material Authorization (RMA) number
from Tripp Lite or an authorized Tripp Lite service center. Products must be returned to Tripp Lite or an authorized Tripp Lite service
center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of
date and place of purchase. This warranty does not apply to equipment which has been damaged by accident, negligence or
misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied
warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL
OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY
OF SUCH DAMAGE. Specifically, Tripp Lite is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use
of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
Specifications
INVERTERAPS INT 512
Continuous power 20° C:500 Watts
Surge power (5 seconds):1200 Watts
Efficiency (Full Load):90%
DC Input Current @ 12V DC -Full Load:52 Amps
-No Load:1 Amp
Nominal Input Volts:12 VDC
DC Input Voltage Range:10 to 15.5 V DC
Nominal Output Volts:230 VAC +/- 5%
Nominal Output Frequency:50/60Hz +/- .3%
Waveform:Modified Sine
Minimum Input AC Volts:Selectable 144, 162, 181 or 200 VAC
Maximum Input AC Volts:Selectable 257 or 276 VAC
Maximum Input Current:11 Amps
Input Frequency:50/60Hz +/-10%
Maximum Output AC:5 Amps
Automatic Transfer Time:6 milliseconds nominal
Dimensions (H x W x D):17.4 x 17.4 x 25.4 cm
Weight:8.2 kg.
Maintenance & Service
Maintenance
The APS series requires no maintenance but should be kept dry at all times. Periodically check all
cable connections both at the unit and at the battery. Clean and tighten as necessary.
Service
If returning your APS to Tripp Lite, please carefully pack the APS using the ORIGINAL PACKING
MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the
UPS is within the warranty period, enclose a copy of your sales receipt.
12
Introducción
¡Enhorabuena! Acaba de adquirir el ondulador/cargador de baterías más avanzado y con el mayor
número de funciones del mercado. Su nuevo APS suministra CA a los equipamientos cuando la
energía eléctrica está presente. Que haya un corte de electricidad, una subida de tensión o una
reducción de intensidad, su APS se conecta automáticamente a un banco externo de baterías para
suministrar a los equipos conectados CA con una tensión y una frecuencia controladas.
Indicadores visuales para Funciones Múltiples
Dos barras de indicadores visuales le informan constantemente de los niveles de carga de la batería,
de las condiciones de fallo y del funcionamiento del APS. Una barra de indicadores visuales para
funciones múltiples le informa de las condiciones de carga de la batería y enciende las luces de
advertencia en caso de fallo. La otra barra de indicadores visuales para funciones múltiples le informa
de las condiciones de funcionamiento del APS.
Interruptores para Operaciones Múltiples
Las opciones de funcionamiento del sistema APS están agrupados en dos puntos de mando.
Permiten ajustar un amplio abanico de tensiones con las que desea que su APS funcione de manera
a optimizar la protección de su equipo y evitar que la batería se vacíe. Existen otras opciones que
incluyen el ajuste con un mando a distancia, mucho más cómodo, y el ajuste del tipo de baterías para
que cargar sea más eficaz .
Potencia de salida con Regulador de Frecuencia (Modo Ondulador)
Puesto que su APS controla la frecuencia de la línea, los aparatos sensibles a las frecuencias pueden
funcionar correctamente.
Protección Automática en caso de Sobrecarga
Si hay sobrecarga en el APS, el aparato se protegerá automáticamente y protegerá también las
baterías.
13
Etapa 2
Absorción
Etapa 1
A granel
TENSIÓN DE LA BATERÍA
CURVA DE CARGA EN
FUNCIÓN DEL TIEMPO
Etapa 3
Estabilización
Cargador de Batería Avanzado
en 3 Etapas
Su APS permite volver a cargar las baterías
mucho más rápido que los cargadores
convencionales puesto que se han llegado a
optimizar las tres fases de carga (A granel,
Absorción y Estabilización) cualquiera que sea
el tipo de batería que usted utiliza (Batería
líquida o Batería Gel)*. Además, gracias al
sistema de carga avanzado, las baterías están
protegidas contra el exceso de carga o de
descarga, y tienen una duración de vida mucho
más larga.
* Los niveles de Absorción y de Estabilización pueden variar
según el tipo de batería, que el usuario puede ajustar, bien en la
posición Wet (Batería líquida) bien en la posición Gel (Batería
de gel).
Potencia de salida de Alto
Rendimiento
Los circuitos avanzados de su APS producen
una conversión de CC en CA mucho más
eficaz, por lo que se reducen las pérdidas de
energía y se puede hacer funcionar cualquier
equipo conectado durante más tiempo entre
carga y carga. El APS mantendrá una potencia
de salida de alto rendimiento incluso si la carga
de las baterías disminuye.
RENDIMIENTO (en %)
POTENCIA EN VOLTIOS
Este manual contiene instrucciones y advertencias importantes que deben seguirse durante la
instalación, operación y almacenaje de los Sistemas Automáticos de Energía APS de Tripp Lite
14
Instalación del APS
Ajustar los Conmutadores DIP de Configuración*
(Véase el esquema 1, p. 46, Nota: 1.1 muestra una vista detallada de los Conmutadores DIP de
Configuración, 1.2 corresponde a la posición parte delantera, 1.3 a la posición parte trasera).
Con la ayuda de una pequeña herramienta, ajuste los 4 Conmutadores DIP de Configuración (situados
en el panel de abajo de su APS) y seleccione el tipo de batería. Ajuste luego el nivel de tensión puesto
que en la salida el APS se conectará automáticamente a la batería que suministra la energía.
* Selecciónelos antes de montar definitivamente el APS.
• Seleccionar el Tipo de Batería
(Conmutador DIP n° 1)
CUIDADO: Cuando ajusta el Conmutador DIP para elegir el Tipo de Batería tiene que tener en cuenta el tipo de baterías que conecta
o sino dañará o degradará las baterías a largo plazo. Véase “Elegir la Batería” en la página 17 para más información.
Tipo de BateríaPosición del Conmutador
Batería Gel (Hermética) ................................... Parte Delantera
Batería Líquida (Abierta) .................................. Parte Trasera**
• Seleccionar Conmutador de conversión en la
Batería cuando la CA está en Alta Tensión
(Conmutador DIP n° 2)
TensiónPosición del Conmutador
276V ................................................................. Parte Delantera
257V ................................................................. Parte Trasera**
• Seleccionar Conmutador de conversión en la Batería cuando la
CA está en Baja Tensión (Conmutadores DIP n° 3 & n° 4)
Parte Trasera
Parte Trasera
Parte Trasera
Parte Trasera
Parte Delantera
Parte Trasera
Parte Delantera
Parte Trasera
Batería
Líquida
Batería
Gel
257V
276V
Parte Delantera
200V
n°4 Parte Delantera &
n°3 Parte Delantera
** Ajustes por defecto realizados en fábrica
Parte Delantera
181V
n°4 Parte Delantera &
n°3 Parte Trasera
Parte Delantera
162V
n°4 Parte Trasera &
n°3 Parte Delantera
Parte Delantera
144V
n°4 Parte Trasera &
n°3 Parte Trasera**
Conversión de la del APS INT 512 de 50 a 60 Hz.
Sólo para personal cualificado autorizado*
(Véase esquema 2, p. 46. Nota: 2.1 corresponde a la Resistencia de ajuste situada en el
ángulo superior derecho de la parte de los componentes del circuito impreso).
Si se desea convertir la frecuencia del APS INT 512 a 60 Hz de manera permanente, se recomienda
que sólo el personal cualificado abra la unidad APS, localice la resistencia en el circuito impreso y la quite.
* Desconecte y desenchufe el APS antes de realizar la conversión.
Conexión Eléctrica
Conecte los modelos APS INT 512 a tomas que suministren 230V y de 50 ó 60 Hz.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.