Tripp Lite 1400VA User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMART2600RM2U
Highlights
2600VA / 2.6kVA high efficiency line interactive, extended-run 2U rack / tower
UPS
Maintains sine-wave 120V nominal output over an input range of 83 to 145V
Network communications supported via HID enabled USB port, DB9 serial
port, SNMP/Web card slot and EPO interface
Current monitoring and switched PDU control via 3 individually controllable
load banks
Input: NEMA 5-20P (120V 20A) / Output: 1 L5-20R, 4 NEMA 5-15/20R, 4
NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto
Rico & Canada only)
Description
2600VA line interactive UPS system for server, network and telecommunications equipment. 2U rackmount or tower form factor with an installed
depth of only 19 inches. High 96% line-power efficiency rating reduces energy consumption and BTU heat output. Expandable battery runtime with
optional BP48V24-2U and BP48V60RT-3U external battery packs. Uninterruptible Power Supply (UPS) switches to battery-derived AC output during
power failures and extreme voltage variations. Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during
brownouts and one level of voltage cut during overvoltages to maintain regulated 120v output over an input range of 83-145V. Includes 5-20P input
plug and 5-15R, 5-15/20R and L5-20R output receptacles. Network-grade AC surge and noise suppression. Network management interfaces
support communications via USB, DB9 serial and SNMPWEBCARD slot. HID-compliant USB interface enables full integration with built-in power
management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test
data and utility power conditions via all 3 network interfaces at once. Includes PowerAlert monitoring software and complete cabling. Emergency
Power Off (EPO) interface. Integrated 3-bank PDU switching supports load shedding and remote-reboot of connected equipment. 3-stage metered
current monitoring and battery charge status LEDs. Utility power and voltage regulation LEDs. Audible alarm. Self-test. 4-post rackmount
accessories included; 2-9USTAND tower kit and 2POSTRMKITWM two post rack & wallmount accessories available. Field-replaceable,
hot-swappable internal batteries and external battery packs. Attractive all-black color scheme. 2-year warranty and $250,000 connected equipment
insurance; extended warranty and service contracts available.
Applications
Ideal for protection of critical 120V equipment in server rooms, internetworking closets and telecommunications systems in rackmount or tower applications. Common applications include corporate or departmental servers, workstations, hubs, routers, bridges, CAD/CAM workstations, concentrators, IP telephony and traditional PBX switching systems.
Package Includes
SMART2600RM2U UPS System, PowerAlert Software and cabling, 4-post rackmount installation hardware, Warranty information, Instruction manual
Features
SmartPro line interactive UPS system is ideal for voice, data, medical and industrial networking applications High 96% line-power efficiency rating reduces energy consumption and BTU heat output Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during brownouts and one level of voltage cut during overvoltages Maintains continuous operation through blackouts, voltage fluctuations and surges Corrects line voltage conditions as low as 83V and as high as 145 back to 120V nominal values Standard internal battery set offers 12 minutes at full load and 4 minutes at full load Optional BP48V24-2U and BP48V60RT3U external rack/tower battery packs enable extended runtime operation Compact form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 inches Ships with all mounting accessories for 4 post rackmount installation Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation Optional 2-9USTAND accessory enables small-footprint upright tower placement Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, with the built-in ability to shutdown any number of additional servers over IP UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter sutoff, activate self-test, load bank output power control and remote reboot Built-in Emergency Power Off (EPO) interface with cable Factory installed NEMA 5-20P input plug; user configurable L5-20P or L5-30P input plug-in connections supported NEMA 5-15R, NEMA 5-15/20R and L5-20R output receptacles Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (1 outlet per load bank) Front panel LEDs offer current monitoring and battery charge level information UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required 2 year manufacturer's product warranty, $250,000 ULtimate Lifetime Insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120 VAC
Frequency compatibility
60 Hz
OUTPUT
Output VA 2600
Output watts 2100
Output nominal voltage
120V AC
Output voltage regulation
LINE MODE: Sine wave line voltage 120V (-18% / +8%), BATTERY MODE: Sine wave output 120V +/-5%
Output frequency regulation
LINE MODE: Passes line frequency of 60Hz +/-10%, BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 4 5-15R, 4 5-15/20R and 1 L5-20R
Customized load management receptacles
3 individually controllable outlets support load shedding and remote reboot on demand of locked network devices. Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers and other critical devices
Overload protection Resettable circuit breaker
INPUT
Maximum input amps 16A with 5-20P or user installed L5-20P input plug / 24A with L5-30P user installed input plug
Input connection type 5-20P (user installed L5-20P and L5-30P input plugs supported)
Input cord length 10 ft., 10 gauge
Recommended Electrical Service
20-30A 120V