Tripp SU40KX Product Data Sheet

SmartOnline 40kVA Modular 3-Phase UPS System, On-line Double-Conversion International UPS
MODEL NUMBER: SU40KX
Description
Tripp Lite's SU40KX (40kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line UPS System provides
100% system availability with N+1 modular architecture and 1+1 parallel capability. In N+1 configuration, the
SU40KX provides two self-contained, redundant 20kVA power modules that can be hot-swapped (load remaining
provide fail-safe redundancy (two 40kVA models supporting a 40kVA load) or increased capacity (two 40kVA
models supporting an 80kVA load). Large capacity 40,000VA/32,000W UPS continually converts incoming AC
power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly
regulated, continuous sine wave output with zero transfer time assures compatibility with all equipment types.
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology
produce less than 3% input total harmonic distortion (THDi). With low THDi, generators run cooler and last longer, allowing managers to save installation costs
by installing a generator with a capacity equal to the equipment load (1:1 ratio). Extremely efficient operation (up to 97%) saves money by lowering electricity
consumption. Hardwire input and output connections support a variety of permanent or PDU-style power connections. Frequency is 50 or 60 Hz
(auto-selectable). The SU40KX combines internal power and battery modules in a single small-footprint tower compartment. Typical half-load/full-load runtimes
are 13 min./5.5 min. Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C,
available separately). A manual bypass breaker and an automatic bypass function ensure 100% availability of connected equipment by safely passing through
AC power if the UPS requires maintenance.
Features
N+1 configuration: If maintenance is required, two self-contained, redundant 20kVA power modules can be hot-swapped with the load remaining powered
1+1 configuration: Two SU40KX can be connected in parallel to provide either fail-safe redundancy or increased capacity
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce low input total harmonic distortion
(THDi)
Low THDi (less than 3%) reduces installation costs by allowing 1:1 generator sizing
Extremely efficient operation (up to 97%) saves money by reducing electricity consumption
True on-line, double-conversion UPS with IGBT technology provides pure sine wave AC output at all times
Highlights
40,000 VA (40kVA) 3-phase
tower UPS
N+1 redundant modular
architecture helps assure 100%
availability
1+1 parallel capability allows for
system redundancy or increased
capacity
Low THDi reduces installation
costs by permitting 1:1 generator
sizing
3-phase hardwire (220/380V,
230/400V or 240/415V AC,
3-phase, 4-wire + ground, wye)
input/output
IGBT technology and zero
transfer time, on-line
double-conversion operation
Runtime is expandable via
external battery cabinet options
Package Includes
SU40KX UPS System
PowerAlert Software
Instruction manual
Warranty information
1 / 5
Maintains continuous operation with zero transfer time through blackouts, voltage fluctuations and surges
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
40,000VA/32,000W power capacity with 3-phase, hardwire input/output connections
Wide input voltage correction range: 173-300V/276-477V AC
Precision +/-1% output voltage regulation
Internal power and battery modules are combined in a single small-footprint tower compartment. Typical half-load/full-load runtimes are 13 min./5.5 min.
Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C, available
separately)
Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed
Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS
Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server
Accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns, reboots and more
Emergency Power Off button turns UPS output OFF and disables Bypass output
Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities
Specifications
SELECTOR
Selector Type UPS SYSTEMS
General Info
Product Group UPS SYSTEMS
TAA Compliant No
OVERVIEW
UPS Family SmartOnline
UPS Type On-Line
OUTPUT
Output Volt Amp Capacity (VA) 40000
Output kVA Capacity (kVA) 40
Output Watt Capacity (Watts) 32000
Output kW Capacity (kW) 32
Power Factor 0.8
Crest Factor 3:1
Nominal Output Voltage(s) Supported
220/380V; 230/400V; 240/415V; 3-Phase Wye
Frequency Compatibility 50 / 60 Hz
Output Voltage Regulation (Line Mode)
+/- 1%
2 / 5