Tripp SU20KRTG Product Data Sheet

SmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 12U Rack/Tower, 200-240V C19 outlets
MODEL NUMBER: SU20KRTG
Description
Tripp Lite SU20KRTG 20,000VA / 20kVA / 18,000 watt online, double-conversion UPS system offers complete
power protection for critical server, network and telecommunications equipment in a 12U rack/tower
non-redundant operation at loads between 10 and 20kVA. Fault-tolerant auto-bypass prevents unexpected
service interruptions during UPS overload or internal fault conditions. Included parallel PDU with manual bypass
switching enables hot-swappable replacement of all major UPS system components in both N+1 and combined
operating modes. Enhanced availability, fault tolerance and simple hot-swap replacement options make this UPS
ideal for advanced networking applications in data centers, computer rooms, network closets and rugged
industrial locations.
Features
Tripp Lite SU20KRTG 20kVA, 20,000VA / 18,000 watt on-line, double-conversion UPS system in 12U total rack/tower configuration
Unique configuration offers 20kVA non-redundant operation and automatic N+1 redundancy at load levels of 10kVA and under
Included Parallel PDU with manual bypass switch enables hot-swap replacement power modules at any supported load level
Hardwire input; 8 C19 outlets
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal
Supports 50/60Hz operation for worldwide frequency compatibility
Expandable runtime with optional external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Battery independent restart
Highly efficient economy mode option
Optional SNMPWEBCARD, RELAYIOCARD and RELAYIOMINI interface modules available (RELAYIOMINI requires removal of USB interface module)
Applications utilizing the optional network communications card require two SNMPWEBCARD accessories (install one per included power module)
HID-compliant USB interface
Includes Free PowerAlert monitoring software; PowerAlert LOCAL, PowerAlert NSA and PowerAlert NMS for monitoring up to 250 SNMP-enabled UPS,
Highlights
20kVA / 20,000VA / 18,000W
on-line double-conversion UPS;
0.9 power factor
200/208/220/230/240V 50/60Hz
output; Economy mode option
Hot-swap power and battery
modules, N+1 fault tolerance at
loads up to 10kVA
USB, RS232 & EPO ports;
support for SNMP/WEB and
contact-closure card options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
Hardwire input (3 wire); C19
outlets
Package Includes
Two SU10000RT3UPM UPS
power modules
Two BP240V10RT3U battery
packs
SUPDMB20KIEC PDU with
Bypass switch
4-post rackmount installation rails
PowerAlert software and cabling
1 / 6
PDU and other networking devices
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (4 required)
Optional 2-9USTAND supports upright tower placement (2 required)
Supports Emergency Power Off (EPO) via built-in interface
Front panel LEDs and LCD readout with scroll controls
LED / LCD display panel rotates for viewing in rackmount or tower configurations
External battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Specifications
SELECTOR
Selector Type UPS SYSTEMS
General Info
Product Group UPS SYSTEMS
TAA Compliant No
OVERVIEW
UPS Family SmartOnline
UPS Type On-Line
OUTPUT
Output Capacity Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less
Output Volt Amp Capacity (VA) 20000
Output kVA Capacity (kVA) 20
Output Watt Capacity (Watts) 18000
Output kW Capacity (kW) 18
Power Factor 0.9
Nominal Output Voltage(s) Supported
200V; 208V; 220V; 230V; 240V
Nominal Voltage Details Voltage selection via front panel LCD interface
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Output Voltage Regulation (Line Mode)
+/- 2%
Output Voltage Regulation (Economy Line Mode)
+/- 10%