SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and
maintenance of all Tripp Lite SmartOnline Rackmount/Tower UPS Systems and their batteries. Failure to heed these warnings may affect your
wa r ranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
• Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
• Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor
temperatures between 62° F and 84° F (between 17° C and 29° C).
• Leave adequate space around all sides of the UPS for proper ventilation.
• Do not install the UPS near magnetic storage media, as this may result in data corruption.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit's
internal cooling, eventually causing product damage not covered under warranty.
UPS Connection Warnings
• Isolate the UPS before working on this circuit.
• Required Protective Devices and Cable Cross-Sections.
Recommended upstream protection.
UPS Power RatingUpstream Circuit Breaker
8kV
10kVAD curve -83A
curve -63A
External power
distribution unit
Q
L
N
UPS
T
L
N
B
GL1
L2(N)
2 poles circuit breaker
L1
L2(N)
To UPS Normal AC source
• The power supply for this unit must be single-phase rated in accordance with
the equipment nameplate. It also must be suitably grounded.
Legend.
B Contactor solenoid.
Q Mains input thermal-magnetic switch
T Two-pole contactor 100 A AC1; coil voltage: according to the mains input.
Remark: Q needs to use the approved component of Safety Certification.
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
Maintenance Warnings
• Your UPS power module and battery module(s) do not require routine maintenance. Do not open them for any reason. There are no userserviceable parts inside.
Battery Warnings
• Do not operate your UPS without connecting it to an external battery module.
• Connect only Tripp Lite battery modules to your UPS power module’s external battery connector.
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the
batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS
before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement
should be performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). The batteries
are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges
(R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.
• Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
• Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
• Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed
via the transformer. Note that potentially lethal voltages exist within this unit as long as the battery supply
is connected.
• Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the detachable PDU is not in bypass
mode.
• During “hot-swap” battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.
• Only connect compatible battery module(s).
2
201102160 93-2897.indb 23/30/2011 9:30:37 AM
Mounting (Rack)
8
Mount your equipment in either a 4-post or 2-post rack or rack enclosure. The user must determine the fitness of hardware and procedures before
mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure. The procedures
described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
Note: The power module and battery module must be installed in separate shelves.
4-Post Mounting
1 The included plastic pegs
will temporarily support the empty rackmount shelves
A
B
while
you install the permanent mounting hardware. Insert a peg near the center of the front and rear
bracket of each shelf as shown. (Each front bracket has 6 holes and each rear bracket has 3 holes.)
The pegs will snap into place.
After installing the pegs, expand each shelf to match the depth of your rack rails. The pegs will
fit through the square holes in the rack rails to support the shelves. Refer to the rack unit labels to
confirm that the shelves are level in all directions. Note: The support ledge of each shelf must
face inward.
2 Secure the shelves
washers
as shown.
C
to the mounting rails permanently using the included screws and cup
B
• For 2U equipment mounting, place 4 screws total at the front and 4 screws total at the back.
• For 3U equipment mounting, place 6 screws total at the front and 4 screws total at the back.
Tighten all screws before proceeding.
Warning: Do not attempt to install your equipment until you have inserted and tightened
the required screws. The plastic pegs will not support the weight of your equipment.
Attach mounting ears
3
provided
. The ears should face forward.
F
to the front mounting holes of your equipment
D
using the screws
E
B
A
A
B
A
1
B
C
C
B
2
B
C
C
B
2
E
Using an assistant, lift your equipment and slide it onto the mounting shelves. Attach your
4
equipment to the rack by passing the screws, nuts and washers (user-provided)
through its
G
3
D
F
mounting ears and into the rack rails.
G
4
(Optional) Attach 2 PDU hanger brackets to the right-side, rear mounting rail using included
5
screws and cage nuts. Important: determining where to attach your PDU hanger brackets will
7
depend on your rack configuration. Generally it is recommended to mount the top bracket in
the bottom two square holes of the U space that the UPS and PDU are mounted in. The second
6
bracket should be installed 3U measures down and placed in the top two square holes of the U.
(For example: If the PDU and UPS are mounted in 7U, the first bracket will be installed in the
bottom two square holes of 7U. The second bracket would be installed in the top two square holes
Mount Here
5
of 4U.
5
4
2-Post Mounting (Optional)
To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKITWM, sold
separately) for each module installed. See the Installation Kit’s owner’s manual for complete mounting instructions.
3
201102160 93-2897.indb 33/30/2011 9:30:39 AM
Mounting (Tower)
Mount all modules in an upright, tower position using included base stands. The user must determine the fitness of hardware and procedures before
mounting.
The UPS system is shipped with two sets of plastic feet
1
and extensions
A
that can be used
B
to tower mount the UPS’s power module, a battery module and a second battery module (9U
total).
Adjust the feet to a width of 10.25 inches (26 cm) for a UPS power module and battery module,
B
or to a width of 15.375 inches (39 cm) for three units. Align the feet in your installation area,
approximately 10 inches (26 cm) apart. Have one or more assistants help you place the units on
their sides in the feet. The control panel of the UPS should be the UPS’s upper corner and face
outward.
A
1
Rotate the power module’s Control Panel to view it easier while the UPS is tower mounted.
2
Insert a small screwdriver, or other tool, in the slots on either side of the Control Panel. Pop the
panel out; rotate it; and pop the panel back into place.
2
Features
Before installing and operating your UPS, familiarize yourself with the location and function of the features of each component.
Power Module Front Panel Controls
LCD DISPLAY: This backlit (16 × 2 character) dot matrix display indicates a wide range of
1
UPS operating conditions and diagnostic data. It also displays UPS settings and options when
the UPS is in setup mode.
ON/MUTE BUTTON: Press this button and hold it until you hear a beep to turn the UPS
2
system’s inverter ON. If the UPS’s battery alarm is sounding, press this button to silence it.
SCROLL DOWN/EXIT SETUP BUTTON: This button allows you to browse through
3
different options and power readings on the LCD display. Momentarily pressing it causes the
LCD screen to display a different power reading (see “Operation”, pg. 12). Pressing it and the
SCROLL UP Button together puts the UPS in setup mode, where this button is used to scroll
through setup options and to exit setup mode.
SCROLL UP/SELECT BUTTON: This button allows you to browse through different
4
options and power readings on the LCD display. Momentarily pressing it causes the LCD
screen to display a different power reading (see “Operation Section”, pg. 17). Pressing it and
the SCROLL DOWN Button together puts the UPS in setup mode, where this button is used
to select setup options.
OFF BUTTON: Press this button until you hear a beep to turn the UPS system’s inverter
5
OF F.
O/P (OUTPUT) LED: This green light will illuminate to indicate your UPS is supplying AC
6
power to connected equipment.
DC/AC (INVERTER) LED: This green light will illuminate to indicate the UPS’s DC/AC inverter is activated.
7
BYPASS LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or inverter. If
8
this LED is lit, connected equipment will not receive battery power in the event of a blackout, unless the Economy Mode feature is enabled.
AC/DC (Converter) LED: This green light will illuminate to indicate the UPS’s AC/DC converter is charging the connected battery pack(s).
9
BATTERY LED: This green light will illuminate when the UPS is discharging the battery to provide connected equipment with AC power. An
10
alarm will sound which can be silenced by pressing the ON/MUTE Button. This LED will remain lit after the alarm is silenced.
I/P (INPUT) LED: This green light will illuminate to indicate an AC input supply is present.
11
ACCESS SLOTS: To rotate the controls, insert a flathead screwdriver into these slots and gently lever the panel out. Taking care not to
12
excessively twist or yank the cables connecting the controls to the rest of the UPS, turn the controls to the desired orientation and reinsert them.
121211
2
107968
1
345
4
201102160 93-2897.indb 43/30/2011 9:30:40 AM
Features (Rear Panel) See page 6 for feature descriptions
8kVA/10kVA Power Module
1
2 38
4567
Detachable Power Distribution Unit
1210
Battery Module
11131415
9
16
17
5
201102160 93-2897.indb 53/30/2011 9:30:42 AM
Features (Rear Panel)
Power Module Feature Description
Accessory Slot: Remove the small cover panel to install optional accessories to remotely control and monitor your UPS system. Visit Tripp Lite
1
on the Web (www.tripplite.com) to learn about available SNMP, network management and connectivity products that may be installed in this slot.
RS-232 Communication Port: This female DB9 serial port may be used to connect your UPS to a workstation or server. It uses RS-232
2
protocol to communicate with a connected computer. It is used with Tripp Lite software and the included serial cable to monitor and manage the
UPS remotely over a network and to automatically save open files and shut down equipment during a blackout. See “Optional Connection” for
details. An optional Contact-Closure card is available if needed (Tripp Lite part # RELAYIOCARD).
Parallel Connector: For UPS communication in parallel.
3
USB Communication Port: The USB port may be used to connect your UPS to a workstation or server. It is used with Tripp Lite software and
4
the included USB cable to monitor and manage the UPS remotely over a network and to automatically save open files and shut down equipment
during a blackout. See “Optional Connection” for details. For USB communications, both DIP switches must be in the ON position. This will
disable the RS-232 port.
EPO (Emergency Power Off) Port: Used to connect the power module to a contact closure switch to enable emergency power off. See
5
“Optional Connection” section for details.
Exhaust Fan: This cools and ventilates the inside of the power module.
6
External Battery Connector: Use this to connect one or more Tripp Lite battery modules to the power module. Remove the cover for access.
7
The power module will not start without a connection to a charged battery module. Refer to the battery module owner’s manual for connection
instructions and safety warnings.
Input Terminal Block: Use these terminals to connect your power module to the detachable PDU.
8
Detachable Power Distribution Unit Feature Description
AC Output Receptacles: Accept direct plug-in connection of NEMA L6-30P or NEMA L6-20P equipment plugs.
9
AC Output Breakers: Control output power to the PDU’s AC output receptacles.
10
Maintenance Bypass Switch: Permits qualified service personnel to remove the PDU from the power module for routine maintenance without
11
disrupting power to the load. When this switch is set to BYPASS the load will receive unfiltered AC utility power and no battery backup power
will be available in the event of a blackout. See the “Manual Bypass Operation” section for detailed manual bypass procedures. WARN I NG!
For qualified service personnel only. If the complete bypass procedure (see “Manual Bypass Operation,” p. 10) is not followed, the UPS
will not be adequately powered down, presenting a risk of death or serious injury from contact with high voltage.
Utility Input Terminal Block: Use these terminals to connect the PDU to utility power. To access the terminals, unscrew and remove the
12
terminal block cover.
Power Module Input Terminal Box: Use these terminals to connect the PDU to the Power Module.
13
Sliding Cover for Power Module Input Terminals: Slide this cover over the terminals after detaching the PDU from the Power Module during
14
Manual Bypass Operation (p. 10).
Input Terminal Block Cable Access: Located on the left side of the PDU.
15
Battery Module Feature Description
Input Connector: Use this connector to daisy chain additional battery modules onto the first. Remove the cover panel for access. Refer to the
16
battery module owner’s manual for connection instructions and safety warnings.
Output Cable: Use this cable to connect the battery module to the power module or to another battery module. The power module will not start
17
without a connection to a charged battery module. Refer to the battery module owner’s manual for connection instructions and safety warnings.
Connection (continued)
Hardwiring Cautions
• Wiring must be done by a qualified electrician.
• When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC) in the
U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS’s AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a
torque of not less than 24-28 inch-pounds (2.7-3.2 NM).
• Make sure that your equipment is properly grounded.
• Using cables of improper size may damage your equipment and
cause fire hazards. Choose appropriate cabling and protection
circuits to make wiring connections. Ground conductors must be
the same size and type as the power conductors used.
46 A
56 A
40 A
50 A
• Refer to National Electrical Code (NEC) guidelines for proper wire gauge and output protection circuit requirements.
6
201102160 93-2897.indb 63/30/2011 9:30:42 AM
Connection (continued)
Connecting Modules to Each Other and to Utility Power and Equipment
1
Attach the PDU to the Power Module and Battery Module.
Align and connect the PDU’s power module input terminals with the terminals on the back of
the Power Module. Secure the PDU to the Power Module with four screws
ing further, ensure that the Bypass Switch is set to NORMAL. Remove the utility input terminal
block cover
2
Hardwire the PDU to a Utility Power Source.
.
B
Pass a user-supplied cable through the knockout on the left side of the PDU
the PDU’s input terminals
. Replace the terminal block cover. Connect the other end of the
D
cable to a utility power source.
3
Connect the battery module to the power module.
Consult the owner’s manual that came with your battery module. Fully insert the connector on
the end of the battery module’s cable
. Small sparks may occur; this is normal. NOTE: the power module does not contain internal
F
into the connector on the rear panel of the power module
E
batteries and will not start until a battery module is connected. The battery modules are fully
charged prior to shipping. However, before expecting full backup capability (particularly if the
battery module has been stored for an extended period) after the UPS system is connected to a
utility power source, allow the battery module to recharge for 12 hours. Once the UPS system is
in use, it will charge the batteries and maintain the charge level automatically. If needed, connect
additional battery modules in a daisy-chain with each module’s cable inserted into the previous
module’s connector
.
G
. Before proceed-
A
and connect it to
C
B
A
1
C
D
2
F
Contacts on Power/Battery Module
WARNING! High Voltage!
Risk of electrical shock!
Due to the presence of high voltage internal
batteries, even without AC present, these
Do not let these contacts touch any surface!
4
Turn UPS ON
contacts are live!
Contacts on Detachable PDU
WARNING! High voltage!
Risk of electrical shock!
If AC is present and Bypass Switch is set to
"Bypass", these contacts are live!
Do not let these contacts touch any surface!
Note: UPS system will function properly upon initial startup; however, maximum runtime for the
unit’s battery will only be accessible after it has been charged for 24 hours.
1. Turn on the breaker for the UPS system’s utility power source. This will energize the UPS
power module and the control panel’s LCD screen
2. Make sure the PDU module’s manual bypass switch
3. Turn on the PDU output circuit breakers
.
M
will display “BYPASS MODE”.
H
is in the “NORMAL” position.
L
4. Configure the UPS system in SETUP MODE. Enter SETUP MODE by holding down both
scroll buttons
5. Scroll through the setup options (using the scroll buttons
to select the appropriate settings:
I
at the same time.
J
) and press the “SELECT” button
J
Input & Output Voltage: Select 200, 208, 220, 230, or 240V AC.Output Frequency: The UPS system will auto-select 50 or 60 Hz to match the input.Economy Mode: The UPS system can provide on-line operation with zero transfer
time. It can also operate in a more energy-efficient, line-interactive mode. Select
“ECONOMY ON” for line-interactive mode. Select “ECONOMY OFF” for on-line
mode.
6. After configuring the options, exit SETUP MODE with the scroll buttons
7. Press the control panel’s “ON” button
until the UPS system beeps, then release the button.
I
.
J
8. The UPS system will perform a brief self-test and show the results on the control panel
LEDs and LCD screen
. See “Startup Self-Test” in the “Operation” section for the display
H
sequence.
9. After the self-test is complete, the LCD screen
should display “ONLINE MODE” or
H
“ECONOMY MODE”, depending on which option was selected. The UPS system is now
turned on.
G
E
3
H
J
4a
L
M
N
KI
O
4b
7
201102160 93-2897.indb 73/30/2011 9:30:44 AM
Connection (continued)
5
Plug Your Equipment into the PDU’s Outlets
Your UPS is designed to support electronic equipment only. You will overload your UPS if the
total VA rating for all the equipment you connect exceeds the UPS’s output capacity. Do not
connect household appliances or laser printers to the UPS’s outlets. To find your equipment’s VA
ratings, look on their nameplates. If the equipment is listed in amps, multiply the number of amps
by the input voltage (240V or 208V) to determine VA. (Example: 1 amp × 120 = 120 VA).
6
Turn UPS OFF (Optional)
1. Press the control panel’s “OFF” button
LCD screen
will display “BYPASS MODE”. The inverter is now turned off, but the UPS
H
system is not fully deactivated and the load is still energized.
2. Turn off the Output Circuit Breakers
longer be energized and the LCD screen
3. Turn off the breaker for the UPS system’s utility power source. The UPS system is now turned
off and the LCD screen
7
UPS Cold Start (Optional)
will be dark.
H
During a blackout or other input power failure, the UPS system can be “cold started” from
battery. (The battery must be at least partially charged.) Note: The UPS system’s output
settings cannot be configured while operating from battery. It will use the previously
configured output settings.
1. Make sure the PDU modules manual bypass switch
2. Turn on the Output Circuit Breakers on PDU module
3. Press the control panel’s “ON” button
The UPS system’s inverter will begin to operate. Note: Some electronic equipment draws
more current at startup. When starting from battery, consider reducing the initial load.
4. The UPS system will perform a brief self-test and show the results on the control panel
LEDs and LCD screen
. See “Startup Self-Test” in the “Operation” section for the display
H
sequence.
5. After the self-test is complete, the LCD screen
an alarm should sound.
6. The UPS system will now provide power to connected equipment until the battery is
discharged.
until you hear a beep, then release the button. The
K
located on the detachable PDU. The load will no
M
will be dark.
H
is set to the “NORMAL” position.
L
.
M
until the UPS system beeps, then release the button.
I
should display “ON BATTERY MODE” and
H
5
Optional Connection
The following connections are optional. Your UPS system will function properly without these connections.
1
USB and RS-232 Serial Communication Connection
Use the included USB cable
port of your computer to the communication port of your UPS. Install on your computer the
Tripp Lite PowerAlert Software appropriate to your computer’s operating system. Consult your
PowerAlert manual for more information.
USB Communication Port Note: The USB port may be used to connect your UPS to a
workstation or server. It is used with TrippLite software and the included USB cable to monitor
and manage the UPS remotely over a network and to automatically save open files and shut down
equipment during a blackout. See “Optional Connection” for details. For USB communications,
both DIP switches must be in the ON position. This will disable the RS-232 port.
or RS-232 DB9 serial cable
1a
to connect the communication
1b
1a
1b
8
201102160 93-2897.indb 83/30/2011 9:30:45 AM
Optional Connection (continued)
2
EPO Port Connection
This optional feature is only for those applications that require connection to a facility’s
Emergency Power Off (EPO) circuit. When the UPS is connected to this circuit, it enables
emergency shutdown of the UPS’s inverter and inhibits transfer to internal bypass. Using the
cable provided, connect the EPO port of your UPS (see 2a) to a user-supplied normally closed
or normally open switch according to the circuit diagram (see 2b).
Note:
1. If using a cable other than what is supplied, the cable should not exceed 350 feet or
have a resistance of greater than 10 ohms.
2. If a non-latching EPO switch is used, the EPO must be held for a minimum of 1
second. This does not apply to a latching EPO switch.
CAUTION: The EPO port is not a phone line surge suppressor; do not connect a phone
line to this port.
UPS Unit State when asserting EPO with AC line present:
LEDsOutputFansSerialSNMPUSBLCD Screen
OFFOFFOFFOFFOFFOFF“Emergency Stop”
To restart the UPS unit after asserting EPO with AC line present:
1. Verify that the EPO assertion has been removed or cleared.
2. Remove AC line power to the UPS unit.
3. Reapply AC line power. Now the UPS will start back up in Bypass mode and the LCD will
display “BYPASS MODE”.
UPS Unit State when asserting EPO without AC line power:
LEDsOutputFansSerialSNMPUSBLCD Screen
OFFOFFOFFOFFOFFOFF“Emergency Stop”
To restart the UPS unit after asserting EPO without AC line power:
1. Verify that the EPO assertion has been removed or cleared.
2. Reapply AC line power to the UPS unit. Now the UPS will start back up in Bypass mode and
the LCD will display “BYPASS MODE”.
2a
EPO PIN ASSIGNMENT
2b
12V
1K
1
X
2
3
4
5
6
X
3
Internal SNMP/WEB Card Insertion
Remove the small cover panel from the accessory slot to use optional accessories to remotely
monitor and control your UPS. Visit www.tripplite.com/support for more information,
including a list of available SNMP, network management and connectivity products.
3
Manual Bypass Operation (for power module maintenance or replacement)
The UPS system includes a self-contained power/battery module along with an independent, detachable PDU with a bypass switch. This switch
allows qualified service personnel to remove the detachable PDU from the power/battery module for routine maintenance without disrupting power
to connected loads. While this switch is set to “BYPASS”, connected equipment will receive unfiltered AC utility power, but the equipment will not
receive battery power in the event of a blackout.
Note: If desired, an optional hardwire detachable PDU is also available separately from Tripp Lite. Contact Tripp Lite for details.
(Optional: During a hot-swap, the PDU can be housed in the back of the rack configuration using supplied PDU hanger brackets and hardware. See
STEP 5 on page 3 for mounting instructions.)
WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not adequately power down the
UPS power/battery module, resulting in the continued risk of death or injury from potential contact with high voltage. The UPS's power/
battery module and detachable PDU are extremely heavy. This procedure requires several people to perform.
9
201102160 93-2897.indb 93/30/2011 9:30:47 AM
Manual Bypass Operation (for power module maintenance or replacement) (continued)
UPS Power/Battery Module Removal
STEP 1. Disable PowerAlert Software and disconnect communication cables from the
communication ports
STEP 2. Press UPS's “OFF” Button
“BYPASS MODE” message shown in the LCD Display
STEP 3. Turn the detachable PDU's Bypass Switch
STEP 4. If an external battery module is connected to the UPSThe UPS power/battery module is now safely powered down and it can be
detached from the PDU to perform maintenance/replacement.
WARNING! High Voltage! Risk of electrical shock! SEE BELOW.
STEP 5: Remove the four screws that hold the detachable PDU to the power/battery module.
STEP 6: Using several assistants at each end, carefully pull the detachable PDU away from
the power/battery module. During this process, ensure that each section is properly
supported after they are separated. If the sections are detached in a rackmount
application, ensure that each section remains adequately supported by the UPS’s
rackmount rails. Remove the rackmounting hardware from the front panel of the UPS;
slide the power and battery modules forward, and remove. If it is desired to leave the
detached PDU in the rack, hang the unit in the back of the rack on the installed PDU
hangers by the screws used to attach the PDU to the UPS system. (Refer back to page
3 for PDU hanger bracket installation).
If the sections are detached in a tower application, ensure that the PDU is supported
by the UPS’s tower feet. Adjust the tower feet so they are as close together as possible.
on the UPS power/battery module.
A
, if the UPS is powered, until you hear a beep and see a
C
to “BYPASS”.
B
, disconnect it from the UPS.
E
B
A
E
Step 1, 3, 4
D
C
Step 2
STEP 7: Loosen the screws
Tighten the screw
in the contact cover
A
to secure the cover. Warning: Use extreme caution when
D
. Slide the cover over the contacts
B
handling the PDU. Do not allow the contacts to touch any surface.
To reattach the PDU, reverse the process listed above.
WARNING!
High
Voltage!
Risk of
electrical
shock!
SEE
BELOW.
Step 6Step 5
C
See Warning
Statements
.
below!
Step 6
C
D
A
B
Step 7
10
201102160 93-2897.indb 103/30/2011 9:30:49 AM
A
Manual Bypass Operation (for power module maintenance or replacement) (continued)
High Voltage Warnings
Contacts on Power/Battery Module
WARNING! High Voltage!
Risk of electrical shock!
Due to the presence of high voltage internal batteries,
even without AC present, these contacts
Do not let these contacts touch any surface!
are live!
A
If AC is present and Bypass Switch is set to “Bypass”,
Contacts on Detachable PDU
WARNING! High voltage!
Risk of electrical shock!
these contacts
Do not let these contacts touch any surface!
are live!
B
A
B
Specifications
The models listed below include a power module, one or two battery modules, and a PDU module.
Model Information
Model # (S)8kVA10kVA
Input
Input Connection TypeAnderson Power Connector 75A (3 pole)Anderson Power Connector 75A (3 pole)
Input Voltage Range156~280V Single Phase156~280V Single Phase
Module Input Voltage200/208/220/230/240V AC200/208/220/230/240V AC
Input Frequency50/60Hz (40~70Hz)50/60Hz (40~70Hz)
Input Current46.0/44.2/41.8/40.0/38.3 (Max.)56.1/54.0/51.0/48.8/46.8 (Max.)
Inrush Current<200A<200A
Power Factor (Full Load)>0.98>0.98
Efficiency (Full Load/On-Line)90%90%
Power Module Circuit BreakerN/AN/A
Battery ModelBP240V10RT-3U; 20 x 12V9AhBP240V10RT-3U; 20 x 12V9Ah
Output
VA800010000
Watts (Power Factor: 0.9)72009000
Output connection TypeAnderson Power Connector 75A (3 pole)Anderson Power Connector 75A (3 pole)
Waveform (On-Line)SinewaveSinewave
Waveform (On-Battery)SinewaveSinewave
Output Voltage (RMS)200/208(default)/220/230/240Vac (Single Phase)200/208(default)/220/230/240Vac (Single Phase)
Output Frequency50/60Hz ± 0.05Hz50/60Hz ± 0.05Hz
Voltage Regulation±2%±2%
Max. Harmonic Distortion (Linear Full Load)<2%<2%
Max. Harmonic Distortion (NonLinear Full Load)<3%<3%
Overload Capabilities
Short Circuit Capability
Crest Factor2.7:12.7:1
Operation
On-Line Transfer Time (Line to Battery, Battery to Line)0 ms.0 ms.
Audible Noise (Full Load @ 1m)60dBA60dBA
IndicatorsIncludes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (Output)).
CommunicationsIncludes an RS-232, a parallel connector , USB connector, a EPO connector and an accessory slot.
Physical Specifications
Unit Dimensions (H x W x D)25.82 x 17.5 x 5.14 in. [ 665.8 x 444.5 x 130.5 mm]25.82 x 17.5 x 5.14 in. [ 665.8 x 444.5 x 130.5 mm]
Power Module
PDU Module20.54 x 6.96 x 4.49 in. [ 521.8 x 176.8 x 114 mm]20.54 x 6.96 x 4.49 in. [ 521.8 x 176.8 x 114 mm]
AC Mode: AC input voltage in normal range:
156-280V.
IP
AC/DCDC/ACO/P
Cold Start/Battery Mode: With a cold start
in Battery Mode, you will see the following
LED display:
AC/DCDC/ACBATTERYO/P
Bypass Mode: AC input voltage in a range
of: -20 to +15% of the rating voltage; Bypass
Mode is enabled.
Flashing
IPBYPASS
AC/DC
AC Power Start Up: With an AC power start
up, you will see the following LED sequence:
IPBYPASS
IPBYPASS
Economy Mode: AC input voltage in a range
between -10 and +10% of rating voltage;
Economy Mode is enabled.
IPBYPASS
AC/DCO/P
Cold Start: With a cold start, you will see the
following LED sequence.
BATTERY
AC/DC
BATTERY
AC/DCDC/ACO/P
12
201102160 93-2897.indb 123/30/2011 9:30:52 AM
Operation (continued)
Startup Self-Test
When you turn the UPS ON, it will enter Diagnostic Mode and perform a brief self-test lasting about 15 seconds. The results of the self-test are
shown on the LCD screen in the sequence below.
*Note: If the UPS is cold started, its
BATTERY LED will be lit.
STARTED WITH
AC INPUT
DIAGNOSTIC MODE
FREQ OUT = 50Hz
DIAGNOSTIC MODE
INPUT 000V / 00Hz
DIAGNOSTIC MODE
RECTIFIER OK
DIAGNOSTIC MODE
CHARGER OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
DC BUS OK
DIAGNOSTIC MODE
INVERTER TEST
DIAGNOSTIC MODE
INVERTER OK
LOAD LEVEL
00.00KW / 000%
COLD
START*
DIAGNOSTIC MODE
FREQ OUT = 50Hz
DIAGNOSTIC MODE
INPUT 000V / 00Hz
DIAGNOSTIC MODE
RECTIFIER OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
DC BUS OK
DIAGNOSTIC MODE
INVERTER TEST
DIAGNOSTIC MODE
INVERTER OK
LOAD LEVEL
00.00V / 000%
Failed Self-Test
If a problem is detected during the self-test, the LCD will display a error message. If your UPS displays any of the following messages in its LCD,
call Tripp Lite Technical Support at (773) 869-1234 for service.
BAD BATTERY!
CALL FOR SERVICE
CHARGE BATT FAIL!
CALL FOR SERVICE
AC/DC FAILURE!
CALL FOR SERVICE
INVERTER FAILURE!
CALL FOR SERVICE
OUTPUT FAILURE!
CALL FOR SERVICE
FAN FAILURE!
CALL FOR SERVICE
13
201102160 93-2897.indb 133/30/2011 9:30:52 AM
Operation (continued)
Normal Operation
During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online, Economy, On Battery, or Bypass.
Online mode: The UPS provides AC power while utility power is available and switches to On Battery mode instantly (zero transfer time) if AC
power is interrupted.
Economy mode: The UPS provides AC power at high efficiency while utility power is within +/- 10% rated AC input voltage and switches to On
Battery mode (zero transfer time) if AC power is interrupted.
Industrial mode: If the UPS detects an output voltage fluctuation more than 5 ms, the UPS will transfer to Bypass mode, returning to Online mode
when the output is back to normal.
On Battery mode: The UPS provides AC power from battery backup so long as battery power lasts. It switches back to Online or Economy mode
if utility power is available and shuts down if it runs out of battery power.
Bypass mode: The UPS provides AC power while utility power is available. The UPS shuts down if AC power is interrupted.
Parallel mode: The UPS can provide redundancy up to 10K or power up to 20K. Refer to your Paralleling Kit manual for more information.
The second line of the LCD Display shows basic power conditions. Push the SCROLL buttons to browse through these basic power conditions in
the sequence shown below.
LOAD LEVEL
00.00KW / 000%
LOAD LEVEL
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
ON-LINE 10KVA
V00 CV01
BATTERY CAPACITY
000V / 000%
LOAD LEVEL
00.00KW / 000%
LOAD LEVEL
00.00KVA / 000%
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
ON-LINE 10KVA
V00 CV01
UPS Setup Menu
Press the UPh and DOWNi buttons simultaneously for 3 seconds until the SETUP MENU screen appears as seen below:
UPS SETUP
EXIT ENTER
Press the UPh button to enter Set Up Mode.
To enter Set Up Mode, you will be required to enter a password.
PASSWORD : 0000
ENT DOWN UP XX
Numbers increase or decrease by 1 when pressing the UPh and DOWNi buttons (0-9). Scroll to select the first number, then press the ON
button. This saves the first number and moves on to the next in the sequence. The password range is 0000-9999 and should be changed by the
administrator. The DEFAULT password is 1234.
14
201102160 93-2897.indb 143/30/2011 9:30:52 AM
Operation (continued)
Changing the Password
To change the password, scroll DOWNi from the SETUP MENU screen to the BASIS SETTING screen. From here, press ON for the CHANGE
PASSWORD screen. From this screen press ON and follow the previously described actions to set your password. When set, press ON to move to
the SAVING screen. Scroll DOWNi to the SAVING:YES screen and press ON to save. Scrolling back UPh will return you to the SETUP MENU.
SETUP MENU
ENT DOWN UP
Down
BASIS SETTING
ENT DOWN UP
OnOn
CHANGE PASSWORD?
ENT DOWN UP
FOLLOW
SEQUENCE
PAGE14
On
SAVING: NO
ENT DOWN UP
Down
SAVING: YES
ENT DOWN UP
On
Scroll uph back to
SETUP MENU
Selecting Screen Language
To select a screen language, scroll DOWNi to the BASIS SETTING screen. Press ON to get to the CHANGE PASSWORD screen and DOWNi to
get to the LANGUAGE screen. From here, press ON. You can then scroll DOWNi or UPh through languages until you find your desired language.
Press ON to save your selection.
SETUP MENU
ENT DOWN UP
Down
BASIS SETTING
ENT DOWN UP
On
CHANGE PASSWORD?
ENT DOWN UP
ENT DOWN UP
Down
LANGUAGE
On
ENT DOWN UP
ENT DOWN UP
ENGLISH
SCROLL
DOWN or UP
THROUGH
LANGUAGES
ENGLISH
On
15
201102160 93-2897.indb 153/30/2011 9:30:52 AM
Operation (continued)
Start Settings
The UPS can start up through the battery without AC power. The DEFAULT is ENABLE. When the UPS switches to battery it can AUTO
RESTART to work in an On-Line Mode when AC power is restored. DEFAULT is ENABLE.
From the SETUP MENU screen, scroll DOWNi to the START SETTING screen. From here, press the ON button for the BATTERY START
screen. From this screen, pressing ON moves you to a ENABLE screen. Pressing ON will enable, while scrolling DOWNi takes you to a
DISABLE screen. From here, press ON to DISABLE this function.
From the BATTERY START screen, pressing DOWNi will take you to an AUTO RESTART screen. Pressing ON takes you to an ENABLE
screen; press ON to ENABLE. Pressing DOWNi takes you to a DISBALE screen. Press ON to DISBALE this function.
START SETTING
ENT DOWN UP
To ENTER
BATTERY START
ENT DOWN UP
AUTO RESTART
ENT DOWN UP
*ENABLE*
ENT DOWN UP
DISABLE
ENT DOWN UP
*ENABLE*
ENT DOWN UP
DISABLE
ENT DOWN UP
Charger Settings
From the SETUP MENU screen, scroll DOWNi until you reach the CHARGER SETTING screen. From here, press ON to get to the CHARGER
CURRENT screen. Press ON again. From here, you can scroll DOWNi or UPh to select current values between 1.5 and 4.0A. Press ON to save
your desired value.
CHARGER SETTING
ENT DOWN UP
To ENTER
CHARGER CURRENT
ENT DOWN UP
CURRENT = 1.5A
ENT DOWN UP
CURRENT = 2.0A
ENT DOWN UP
CURRENT = 3.0A
ENT DOWN UP
*CURRENT = 4.0A*
ENT DOWN UP
16
201102160 93-2897.indb 163/30/2011 9:30:52 AM
Operation (continued)
Battery Settings
Deep Discharge Test: used to set the time period for deep discharge tests. From the SETUP MENU screen, scroll DOWNi until you reach the
BATTERY SETTING screen. Press ON for the BATTERY LOW ALARM screen and scroll DOWNi until you reach the DEEP DISCH TEST
screen. Here, press ON. Now you can scroll DOWNi or UPh between NO TEST, 30, 60, 90 days and QUICK TEST. When you reach your desired
time length, press ON to save. The DEFAULT is NO TEST.
BATTERY SETTING
ENT DOWN UP
BATTERY LOW ALARM
ENT DOWN UP
To ENTER
DEEP DISCH TEST
ENT DOWN UP
*NO TEST*
ENT DOWN UP
30 DAYS
ENT DOWN UP
60 DAYS
ENT DOWN UP
90 DAYS
ENT DOWN UP
QUICK TEST
ENT DOWN UP
17
201102160 93-2897.indb 173/30/2011 9:30:52 AM
Operation (continued)
Output Settings
Note: Any Output Setting changes require a UPS power cycle.
Output Voltage: used to set the UPS’ output voltage rating. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT
SETTING screen. Press ON to reach an OUTPUT VOLTAGE screen and ON again. You can now scroll DOWNi or UPh between 5 voltage
values: 200/208/220/230/240V. Press ON to save your desired voltage.
DEFAULT: 208V
OUTPUT SETTING
ENT DOWN UP
To ENTER
OUTPUT VOLTAGE
ENT DOWN UP
*230V*
ENT DOWN UP
220V
ENT DOWN UP
208V
ENT DOWN UP
200V
ENT DOWN UP
240V
ENT DOWN UP
Frequency Converter: used to set the Frequency Converter Mode. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT
SETTING screen. Press ENTER for the OUTPUT VOLTAGE screen and DOWNi to access the FREQ CONVERTER screen. Here, press ON.
Now you can scroll DOWNi or UPh between DISABLE, 50 and 60 Hz. Press ON to save your selection. When on DISABLE, the UPS will
automatically detect input frequency and select 50 or 60 Hz accordingly. The DEFAULT selection is DISABLE.
OUTPUT SETTING
ENT DOWN UP
To ENTER
OUTPUT VOLTAGE
ENT DOWN UP
FREQ. CONVERTER
ENT DOWN UP
*DISABLE*
ENT DOWN UP
50Hz
ENT DOWN UP
60Hz
ENT DOWN UP
18
201102160 93-2897.indb 183/30/2011 9:30:52 AM
Operation (continued)
Output Settings
ECO Mode: used to set the UPS’ ability to work in the energy saving Economy Mode. When input voltage is in a + or - range of 10% of the overall
voltage rating, the UPS will transfer into an Economy Mode to improve the efficiency of the UPS. From the SETUP MENU screen, scroll DOWNi
until you reach the OUTPUT SETTING screen. From here, press ON for the OUTPUT VOLTAGE screen, and DOWNi through the FREQ
CONVERTER screen until you reach the ECO MODE screen. From here, press ON and now you can scroll DOWNi or UPh between DISABLE
and ENABLE. Press ON to save your selection. The DEFAULT setting is DISABLE.
OUTPUT SETTING
ENT DOWN UP
To ENTER
OUTPUT VOLTAGE
ENT DOWN UP
FREQ. CONVERTER
ENT DOWN UP
ECO MODE
ENT DOWN UP
*DISABLE*
ENT DOWN UP
ENABLE
ENT DOWN UP
Industrial: used to set the UPS’ voltage protection. If enabled, and receiving AC power with input voltage and frequency within a normal range
the UPS will work in an On-Line mode. If the UPS detects an output voltage fluctuation more than 5 ms, the UPS will transfer to Bypass Mode,
returning to On-Line Mode when the output is back to normal. From the STARTUP MENU screen, scroll DOWNi until you reach the OUTPUT
SETTING screen. From here, press ON to reach the OUTPUT VOLTAGE screen, and DOWNi until you reach the INDUSTRIAL screen. From
here, press ON and you can now scroll DOWNi or UPh for ENABLE or DISABLE. Press ON to save your selection. The DEFAULT is DISABLE.
Scrolling DOWN from the INDUSTRIAL screen will take you to a REDUNDANCY screen. From here, press ON and you can now scroll DOWN
or UP for ENABLE or DISABLE. The DEFAULT setting is DISABLE.
OUTPUT SETTING
ENT DOWN UP
To ENTER
OUTPUT VOLTAGE
ENT DOWN UP
FREQ. CONVERTER
ENT DOWN UP
ECO MODE
ENT DOWN UP
INDUSTRIAL
ENT DOWN UP
REDUNDANCY
ENT DOWN UP
*ENABLE*
ENT DOWN UP
DISABLE
ENT DOWN UP
*ENABLE*
ENT DOWN UP
DISABLE
ENT DOWN UP
19
201102160 93-2897.indb 193/30/2011 9:30:52 AM
Operation (continued)
UPS Alarm Log
UPS ALARM LOG
ENT DOWN UP
To ENTER
READ FROM MEMORY
ENT DOWN UP
1 65535 HH:MM:SS
NO HISTORY
2 65535 HH:MM:SS
NO HISTORY
3 65535 HH:MM:SS
NO HISTORY
4 65535 HH:MM:SS
NO HISTORY
5 65535 HH:MM:SS
NO HISTORY
Read From Memory: records the last 5 fault events from the EEPROM. See the Fail Event List below:
Fail Event List
DC BUS FAILCHARGER BATTERY FAILOUTPUT FUSE FAIL
SHORT CIRCUITBYPASS SCR SHORT FAILDC BUS OVP FAIL
INVERTER FAILINPUT SCR SHORT FAILINPUT HVP RELAY SHORT FAIL
OVER TEMPERATUREDERATE SHUTDOWNINPUT HVP RELAY OPEN FAIL
OUTPUT SCR FAILENERGY SAVINGNTC OPEN FAIL
OVERLOADOUTPUT HAS VOLTAGELOW TEMP FAIL
FAN FAILINPUT FUSE FAIL
From the SETUP MENU screen, scroll DOWNi until you reach the UPS ALARM LOG screen. Press ON to enter the READ FROM MEMORY
screen and ON again. Here, you can scroll DOWNi or UPh to read the last 5 fault events. Press ON to exit this menu.
Erase All: used to clear the Fault Event Log. From the STARTUP MENU, scroll DOWNi until you reach the UPS ALARM LOG screen. From
here, press ON to reach the READ FROM MEMORY screen and press DOWNi for the ERASE ALL screen. From here you can scroll DOWNi
or UPh between Yes and No. Press ON to save your selection. You will now be presented with a SURE? screen. Press ON to save or scroll for more
options.
UPS ALARM LOG
ENT DOWN UP
To ENTER
READ FROM MEMORY
ENT DOWN UP
ERASE ALL
ENT DOWN UP
NO
NO HISTORY
YES
NO HISTORY
20
201102160 93-2897.indb 203/30/2011 9:30:52 AM
Operation (continued)
Self Diagnosis Information
When starting with AC power, you will see the following sequence display:
DIAGNOSTIC MODE
FREQ OUT = 50Hz
DIAGNOSTIC MODE
INPUT 000V / 00Hz
DIAGNOSTIC MODE
RECTIFIER OK
DIAGNOSTIC MODE
CHARGER OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
DC BUS OK
DIAGNOSTIC MODE
INVERTER TEST
DIAGNOSTIC MODE
INVERTER OK
LOAD LEVEL
00.00KW / 000%
When starting on battery power, you will see the following sequence display:
DIAGNOSTIC MODE
FREQ OUT = 50Hz
DIAGNOSTIC MODE
INPUT 000V / 00Hz
DIAGNOSTIC MODE
RECTIFIER OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
DC BUS OK
DIAGNOSTIC MODE
INVERTER TEST
DIAGNOSTIC MODE
INVERTER OK
LOAD LEVEL
00.00V / 000%
21
201102160 93-2897.indb 213/30/2011 9:30:52 AM
Operation (continued)
Display Information-Online Mode
When operating in Online Mode with AC power present, you will see the following sequence display:
LOAD LEVEL
00.00KW / 000%
LOAD LEVEL
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 10KVA
V00 CV01
When operating in Online Mode under battery power, you will see the following sequence display:
REMAINING TIME
0000 MINUTES
BATTERY CAPACITY
000V / 000%
LOAD LEVEL
00.00KW / 000%
LOAD LEVEL
00.00KVA / 000%
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
ON-LINE 10KVA
V00 CV01
22
201102160 93-2897.indb 223/30/2011 9:30:52 AM
Operation (continued)
Display Information-Bypass Mode
When operating in Bypass Mode, you will see the following sequence display:
LOAD LEVEL
00.00KW / 000%
LOAD LEVEL
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 10KVA
V00 CV01
UPS Fault Shutdown Messages
CONDITIONLCD DISPLAY MESSAGES
+BUS >450V+ DC BUS HIGH SHUTDOWN
Load <100%: +BUS < 320V
Load >100%: +BUS <290V
-BUS >450V- DC BUS HIGH SHUTDOWN
Load <100%: -BUS <320V
Load >100%: -BUS <290V
BUS Voltage Over 500BUS OVP FAIL SHUTDOWN
Output ShortOUTPUT SHORT SHUTDOWN
UPS Over TemperatureOVER TEMPERATURE SHUTDOWN
Ouput SCR Open FailureOUTPUT SCR FAIL SHUTDOWN
Output OverloadOVERLOAD SHUTDOWN
Bypass SCR ShortBYPASS SCR FAIL SHUTDOWN
Input SCR Rectifier FailureRECTIFIER FAIL SHUTDOWN
Inverter Output Voltage FailureINVERTER SHUTDOWN
Input Fuse OpenI / P FUSE BROKEN SHUTDOWN
Output Fuse OpenO / P FUSE BROKEN SHUTDOWN
Parallel ID LostPARALLEL FAULT SHUTDOWN
+ DC BUS LOW SHUTDOWN
- DC BUS LOW SHUTDOWN
23
201102160 93-2897.indb 233/30/2011 9:30:52 AM
Operation (continued)
On Battery Alarm
When in the On Battery mode, the UPS power module will beep to inform you that it is using battery power to support connected equipment. If
its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are below half capacity, it will beep
twice a second. If its connected batteries are nearly depleted, the UPS power module will beep continuously.
To silence the On Battery Alarm, press the “ON/MUTE” button.
Overload Messages
When the UPS detects an output overload, its LCD will switch to the following display:
OVERLOAD!
LOAD = XXX% X.XXKW
The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to Bypass Mode to
protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:
Overload Condition Countdown Duration
106% - 125% 1 minute
126% - 150%30 seconds
>150% Immediate
Bypass Messages
While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide
battery backup in Bypass Mode.
If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its
LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and
its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.
BYPASS VOLTAGE
CONDITIONS
>15% Higher
Than Nominal
>20% Lower
Than Nominal
LCD DISPLAY
MESSAGES
BYPS OUT OF VOLT
XXXV / XX.X HZ
BYPS OUT OF VOLT
XXXV / XX.X HZ
24
201102160 93-2897.indb 243/30/2011 9:30:52 AM
Operation (continued)
Shutdown Messages
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these conditions, the
“Input,” “Output” and “Bypass” LEDs will be illuminated.
SHUTDOWN
CONDITIONS
Extended
Overload
Output Short
Circuit
Remote Shutdown
Command (Via DB9)
Remote Shutdown
Command (Via EPO)
Internal
Faults
LCD DISPLAY
MESSAGES
SHUT DOWN
OVERLOAD XXX%
SHUT DOWN
O/P SHORT CIRCUIT
SHUT DOWN
REMOTE COMMAND
SHUT DOWN
EMERGENCY STOP!
SHUT DOWN
+ DC BUS HIGH
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
OVERTEMPERATURE
25
201102160 93-2897.indb 253/30/2011 9:30:52 AM
Storage and Service
Storage
Before storing your UPS, turn it completely OFF. If you store your UPS for an extended period of time, recharge the UPS batteries for 4 to 6 hours
once every three months. Note: after you connect the UPS to utility power, it will automatically begin charging its batteries. If you leave your UPS
batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.
Service
Your SmartOnline UPS is covered by the 2-year limited warranty period described below. A variety of Extended Warranty and On-Site Service
Programs are also available from Tripp Lite. For more information on service, visit www.tripplite.com/support. Before returning your UPS for
service, follow these steps:
1. Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading of the
instructions.
2. If the problem continues, do not contact or return the UPS to the dealer. Instead, visit www.tripplite.com/support
3. If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. From here you can request a Returned
Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit’s model and serial
numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you. Any
damages (direct, indirect, special or consequential) to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center
is not covered under warranty. UPS systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges
prepaid. Mark the RMA number on the outside of the package. If the UPS system is within the 2-year warranty period, enclose a copy of your
sales receipt. Return the UPS for service using an insured carrier to the address given to you when you request the RMA.
Warranty and Warranty Registration
2-Year Limited Warranty
TRIPP LITE warrants its products including batteries to be free from defects in materials and workmanship for a period of two years from the date of initial purchase. After
90 days from the date of purchase, TRIPP LITE’s obligation under this warranty is limited to replacing parts on such defective products. To obtain service under this warranty,
you must call TRIPP LITE or an authorized TRIPP LITE service center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with
transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not
apply to equipment which has been damaged by accident, negligence or misapplication or has been altered or modified in any way. This warranty applies only to the original
purchaser who must have properly registered the product within 10 days of purchase.
The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The warranties of all TRIPP LITE UPS
Systems are null and void if a surge suppressor has been connected to its output receptacles.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply
to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES
ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such
as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You’ll be automatically entered into a drawing for a chance to win a FREE
Tripp Lite product!* * No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
FCC Part 68 Notice (United States Only)
If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily discontinue your service. If possible, they will notify you in
advance. If advance notice isn’t practical, you will be notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone company
may make changes in its facilities, equipment, operations or procedures that could affect the proper operation of your equipment. If it does, you will be given advance notice
to give you an opportunity to maintain uninterrupted service. If you experience trouble with this equipment’s Modem/Fax Protection, please visit www.tripplite.com/support for
repair/warranty information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the
equipment is not malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service
provided by the telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation commission for
information.)
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be
found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to
the series number. The series number should not be confused with the marking name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from
Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
26
201102160 93-2897.indb 263/30/2011 9:30:52 AM
201102160 • 932897-EN
Manual del propietario
SmartOnline™
monofásico de 8 kVA-10 kVA
Sistemas de alimentación ininterrumpida (UPS)
inteligentes realmente en línea (montaje en bastidor/torre)
• Incluye módulo de energía, módulo de batería externa y unidad de distribución de energía (PDU)
• La PDU desmontable incorpora salidas e interruptor de sobrepaso para mantenimiento*
• Apto para montaje en bastidor o torre
* Disponible PDU opcional desmontable con conexión por cable. Para más información, póngase en contacto con Tripp Lite.
No conveniente para los usos móviles.
Advertencias de seguridad importantes 28
Montaje 29
Características 30
Conexión 32
Conexión opcional 34
Procedimiento de derivación manual 35
Especificaciones 37
Funcionamiento 38
Almacenamiento y servicio 52
Garantía 52
CONSERVE ESTAS INSTRUCCIONES. Este manual contiene instrucciones y advertencias importantes que deben seguirse durante la instalación y
el mantenimiento de todos los sistemas UPS SmartOnline de Tripp Lite de montaje en torre o en bastidor, y de sus baterías. La falta de observar estas
advertencias podría afectar su garantía.
Advertencias sobre la ubicación del UPS
• Instale el UPS en interiores, lejos del exceso de humedad o calor, la luz solar directa, el polvo o los contaminantes conductores.
• Instale el UPS en una zona estructuralmente segura. El UPS es muy pesado, por lo que debe tener cuidado al moverlo o levantarlo.
• Haga funcionar el UPS únicamente a temperaturas de interior de entre 0 y 40 °C. Para obtener los mejores resultados, mantenga una temperatura de
interior de entre 17 y 29 ºC.
• Deje suficiente espacio alrededor de todo el UPS para que pueda ventilarse de forma adecuada.
• No instale el UPS cerca de medios de almacenamiento magnéticos, ya que esto podría dañar los datos.
• No monte esta unidad con el panel frontal o con el panel trasero hacia abajo (Bajo ningún ángulo o inclinación). Si lo monta de esta manera,
inhibirá seriamente el sistema de enfriamiento interno de la unidad; lo que finalmente causará daños al producto que no están cubiertos por la
garantía.
Advertencias sobre la conexión del UPS
• Aísle el UPS antes de trabajar en su circuito.
• Dispositivos de protección requeridos y cortes transversales del cable.
Protección recomendada para contra-corriente.
Capacidad de potencia del UPS Interruptor automático de contracorriente
GL1
L2(N)
8kVA
10kVA
Interruptor automático de 2 polos
L1
L2(N)
D curva -63A
D curva -83A
A fuente de CA
normal para UPS
• La fuente de alimentación de esta unidad debe ser monofásica y coincidente con las
especificaciones de la placa de datos del equipo, y estar puesta a tierra adecuadamente.
Advertencias sobre la conexión del equipo
• El uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda razonablemente hacer suponer que causará fallas en el
equipo de soporte de vida o afecte significativamente su seguridad o efectividad, no está recomendado. No use este equipo en la presencia de una mezcla
anestésica inflamable con aire, oxigeno u óxido nitroso.
• Conecte el terminal de tierra del módulo de energía del UPS a un conductor electródico de puesta a tierra.
• El UPS está conectado a una fuente de energía de corriente continua (batería). Los terminales de salida pueden tener corriente cuando el UPS no esté
conectado a una fuente de corriente alterna.
Advertencias de mantenimiento
• Ni el módulo de energía ni los módulos de batería del UPS requieren un mantenimiento de rutina. No los abra bajo ningún concepto. No contienen piezas
reparables por el usuario.
Advertencias sobre la batería
• No haga funcionar el UPS sin conectarlo a un módulo de batería externa.
• Conecte únicamente módulos de batería Tripp Lite al conector de baterías externas del módulo de energía del UPS.
• Tome las precauciones adecuadas, ya que las baterías pueden suponer un peligro de descarga eléctrica y quemaduras por las altas corrientes de
cortocircuito. No arroje las baterías al fuego. No abra el UPS ni las baterías, ni puentee o ponga en derivación los terminales de la batería con ningún
objeto. Apague y desenchufe el UPS antes de sustituir la batería y utilice herramientas con mangos aislados. El UPS no contiene piezas reparables por el
usuario. Las baterías sólo deben ser sustituidas por personal técnico autorizado, utilizando el mismo número y tipo de baterías (plomo-ácido selladas).
Las baterías son reciclables. Consulte la reglamentación local para conocer los requisitos de eliminación de residuos. Si se encuentra en España,
puede llamar al teléfono 915 976 000 del Ministerio de Medio Ambiente y Medio Rural y Marino, o visitar www.mma.es/portal/secciones/calidad_
contaminacion/residuos/ para obtener información relativa al reciclado. Tripp Lite ofrece una línea completa de cartuchos de sustitución para baterías de
sistemas UPS. Visite la página web www.tripplite.com/support/battery/index.cfm para encontrar una batería de sustitución específica para su UPS.
• No abra las baterías ni las mutile. El electrolito liberado es nocivo para la piel y los ojos, y puede ser tóxico.
• Los fusibles sólo deben ser sustituidos por personal autorizado por la fábrica. Los fusibles fundidos sólo deben sustituirse por otros del mismo número y tipo.
• El servicio y la reparación sólo deben llevarse a cabo por personal cualificado. Durante cualquier trabajo por parte del servicio técnico, el UPS debe
apagarse o derivarse de forma manual mediante el transformador. Tenga en cuenta que esta unidad contiene voltajes que podrían causar la muerte
mientras se encuentra conectada la alimentación a la batería.
• No conecte ni desconecte los módulos de batería mientras ésta sea la fuente de alimentación del UPS, o cuando la PDU desmontable no esté en modo
derivación.
• Durante la sustitución de un módulo de batería “en caliente”, el UPS no puede proporcionar una batería de reserva en caso de producirse un fallo en el
servicio eléctrico.
• Conecte únicamente módulos de batería compatibles.
28
Unidad de distribución
de energía externa
Q
L
N
Inscripción
B Solenoide del contactor.
Q Interruptor termomagnético de la entrada de la red eléctrica.
T Contactor de 100 A AC1 de dos polos, voltaje de bobina: conforme con la
entrada de la red eléctrica.
Observación: Q necesita usar el componente aprobado de Safety Certification.
T
B
UPS
L
N
201102160 93-2897.indb 283/30/2011 9:30:53 AM
Montaje (bastidor)
8
Monte su equipo en un bastidor o en una caja de bastidor de 2 ó 4 postes. El usuario debe determinar la idoneidad de los materiales y los
procedimientos antes del montaje. Si los materiales y procedimientos no son adecuados para su aplicación, póngase en contacto con el fabricante del
bastidor o caja de bastidor. Los procedimientos descritos en este manual están indicados para bastidores o cajas de bastidores comunes, y podrían
no ser apropiados para todas las aplicaciones.
Nota: El módulo de energía y el módulo de batería deben instalarse en estantes separados.
Montaje de 4 postes
1 Las espigas de plástico incluidas
en bastidor
mientras instala las piezas de montaje permanentes. Introduzca una espiga cerca
B
sostienen temporalmente los anaqueles vacíos de montaje
A
del centro de las abrazaderas delantera y trasera de cada anaquel, tal como se muestra (las
abrazaderas delanteras tienen 6 orificios y las traseras 3). Las espigas se fijarán en su posición.
Después de instalar las espigas, extienda los anaqueles hasta adecuarlos a la profundidad de
los rieles del bastidor. Las espigas encajarán a través de los orificios cuadrados de los rieles del
bastidor para sostener los anaqueles. Consulte las etiquetas del bastidor para confirmar que los
anaqueles se encuentran nivelados en todas las direcciones. Nota: Los bordes de apoyo de los
anaqueles deben mirar hacia dentro.
2 Fije los anaqueles
acopadas
incluidos, tal como se muestra.
C
de forma permanente a los rieles utilizando los tornillos y las arandelas
B
• Para el montaje de equipos en 2U, coloque 4 tornillos en total en la parte delantera y 4 en total
en la trasera.
• Para el montaje de equipos en 3U, coloque 6 tornillos en total en la parte delantera y 4 en total
en la trasera.
Apriete todos los tornillos antes de continuar.
Advertencia: No intente instalar el equipo hasta que haya introducido y apretado los tornillos necesarios. Las espigas de plástico no están preparadas para soportar el peso del equipo.
Fije las orejas de montaje
3
tornillos suministrados
a los orificios de montaje delanteros del equipo
D
. Las orejas deben mirar hacia delante.
F
utilizando los
E
B
A
A
B
A
1
B
C
C
B
2
B
C
C
B
2
E
Con la ayuda de otra persona, levante el equipo y deslícelo en los anaqueles de montaje. Fije el
4
equipo al bastidor pasando los tornillos, las tuercas y las arandelas (suministrados por el usuario)
a través de las orejas de montaje y dentro de los rieles del bastidor.
G
3
D
G
F
4
(Opcional) Fije 2 abrazaderas de soporte para la PDU en el lateral derecho del riel de montaje
5
trasero utilizando los tornillos y las tuercas de jaula incluidos. Importante: el lugar de fijación de
7
las abrazaderas de soporte para la PDU depende de la configuración del bastidor. En general se
recomienda montar la abrazadera superior en los dos orificios cuadrados inferiores del espacio U
en el que están montados el UPS y la PDU. La segunda abrazadera debe instalarse a 3U menos y
colocarse en los dos orificios cuadrados superiores de la U. Por ejemplo, si la PDU y el UPS están
montados en 7U, la primera abrazadera se instalará en los dos orificios cuadrados inferiores de
Montar aquí
6
5
7U, y la segunda en los dos orificios cuadrados superiores de 4U.
5
4
Montaje de 2 postes (opcional)
Para montar el equipo en un bastidor de 2 postes, debe adquirir un kit de instalación de Tripp Lite para montaje en bastidor de 2 postes (modelo
2POSTRMKITWM, se vende por separado) para cada módulo instalado. Consulte el manual del propietario del kit de instalación para obtener las
instrucciones de montaje completas.
29
201102160 93-2897.indb 293/30/2011 9:30:55 AM
Montaje (torre)
Monte todos los módulos en una posición vertical, de torre, utilizando las plataformas incluidas. El usuario debe determinar la idoneidad de los
materiales y los procedimientos antes del montaje.
El sistema UPS se entrega con dos juegos de patas de plástico A y extensiones
1
que pueden
B
usarse para montar en torre el módulo de energía del UPS, un módulo de batería y un segundo
módulo de batería (total 9U).
Ajuste el pie a una anchura de 26 cm si va a instalar un módulo de energía y un módulo de
B
batería, o bien a una anchura de 39 cm si necesita instalar tres unidades.Alinee las patas en la
zona de instalación, con una distancia de unos 26 cm de separación. Pida a una o más personas
que lo ayuden a colocar de forma adosada las unidades en las patas. El panel de control del UPS
debe estar situado en la esquina superior del mismo, y mirar hacia fuera.
Gire el panel de control del módulo de energía para verlo mejor mientras el UPS esté montado
2
1
A
en torre. Introduzca un pequeño destornillador u otra herramienta en las ranuras de cualquiera de
los lados del panel de control, saque el panel, gírelo y vuelva a colocarlo en su sitio.
2
Características
Antes de instalar y poner en marcha el UPS, familiarícese con la ubicación y el cometido de los elementos de cada componente.
Controles del panel frontal del módulo de energía
PANTALLA LCD: esta pantalla de matriz de puntos retroiluminada (16 x 2 caracteres)
1
indica una amplia gama de condiciones de funcionamiento y datos de diagnóstico del UPS.
También muestra la configuración y las opciones del UPS cuando éste se encuentra en modo
de configuración.
BOTÓN ON/MUTE (encendido/silencio): mantenga este botón pulsado hasta escuchar un
2
pitido para encender el inversor del UPS. Si suena la alarma de la batería del UPS, pulse este
botón para silenciarla.
BOTÓN DESPLAZAR HACIA ABAJO/SALIR DE LA CONFIGURACIÓN: este botón
3
le permite desplazarse por las distintas opciones y lecturas de energía en la pantalla LCD.
Si lo pulsa momentáneamente, la pantalla LCD muestra una lectura de energía diferente
(véase “Funcionamiento”, página 38). Si lo pulsa junto con el botón DESPLAZAR HACIA
ARRIBA, el UPS pasa al modo de configuración, donde este botón se utiliza para desplazarse
por las opciones de configuración y para salir del modo de configuración.
BOTÓN DESPLAZAR HACIA ARRIBA/SELECT (seleccionar): este botón le permite
4
desplazarse por las diferentes opciones y lecturas de energía en la pantalla LCD. Si lo pulsa
momentáneamente, la pantalla LCD muestra una lectura de energía diferente. Si lo pulsa junto
con el botón DESPLAZAR HACIA ABAJO, el UPS pasa al modo de configuración, donde
este botón se utiliza para seleccionar las opciones de configuración.
BOTÓN OFF (apagado): pulse este botón hasta escuchar un pitido para apagar el inversor
5
del UPS.
LED O/P (salida): esta luz verde se ilumina para indicar que el UPS está suministrando energía de corriente alterna al equipo conectado.
6
LED DC/AC (CC/CA - inversor): esta luz verde se ilumina para indicar que el inversor de CC/CA del UPS está activado.
7
LED BYPASS (derivación): esta luz verde se ilumina cuando el UPS está proporcionando alimentación de red filtrada sin comprometer al
8
conversor ni al inversor. Cuando este LED está iluminado, el equipo conectado no recibe energía de la batería en caso de producirse un fallo en
el servicio eléctrico, a menos que el modo ECO se encuentre habilitado.
LED AC/DC (CA/CC - conversor): esta luz verde se ilumina para indicar que el conversor de CA/CC está cargando los grupos de baterías
9
conectados.
LED BATTERY (batería): esta luz verde se ilumina cuando el UPS está descargando la batería para proporcionar energía de corriente
10
alterna al equipo conectado. Suena una alarma que puede silenciarse pulsando el botón ON/MUTE. El LED permanece iluminado después de
silenciarse la alarma.
LED I/P (entrada): esta luz verde se ilumina para indicar que existe un suministro de entrada de corriente alterna.
11
RANURAS DE ACCESO: para girar los controles, introduzca un destornillador de cabeza plana en estas ranuras y extraiga suavemente
12
el panel haciendo palanca. Con cuidado de no torcer o tirar excesivamente de los cables que conectan los controles al resto del UPS, gire los
controles hasta la orientación deseada e introdúzcalos nuevamente.
121211
2
107968
1
345
30
201102160 93-2897.indb 303/30/2011 9:30:56 AM
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.