Tripp SMX5000XLRT3U User Manual

Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA
Customer Support: +1.773.869.1234 • www.tripplite.com
Important Safety Instructions
2
Mounting
3
Quick Installation
4
7
Storage and Service
11
Español
Copyright ©2008 Tripp Lite. All rights reserved. SmartPro®is a registered trademark of Tripp Lite.
SmartPro®3U Rackmount
(5000VA)
Intelligent, Line-Interactive UPS Systems
• 230V Input/Output
• Extended-Run Options
Not suitable for mobile applications.
13
Battery Replacement
12
Français
25
Optional Installation
5
Pусски
é
37
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 1
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these warnings will void your warranty.
UPS Location Warnings
• Use caution when lifting your UPS. Because of the considerable weight of all rackmount UPS systems, at least two people should assist in lifting and installing them.
• Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight.
• For best performance, the ambient temperature near your UPS should be between 0° C and 40° C (between 32° F and 104° F).
• Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents or fan openings.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this
manner will seriously inhibit the unit's internal cooling, eventually causing product damage not covered under warranty.
UPS Connection Warnings
• The UPS contains its own energy source (battery). The output terminals may be live even when the UPS is not connected to an AC supply.
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reason­ably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
• Do not connect surge suppressors or extension cords to the output of your UPS. This might overload the UPS and will void the surge suppressor and UPS warranties.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement should be performed only by authorized service personnel using the same number and type of batteries (sealed Lead-Acid). The batteries are recyclable. Refer to your local codes for disposal requirements. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges (R.B.C.). Visit Tripp Lite on the Web at www.tripplite.com to locate the specific replacement battery for your UPS.
• During hot-swap battery replacement, the UPS will not provide backup power in the event of a blackout or other power interruptions.
• Do not operate UPS without batteries.
• When adding external battery packs connect only Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS is operating on battery power.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 2
3
Mounting
Mount your equipment in either a 4-post or 2-post rack or rack enclosure. The user must determine the fitness of hardware and procedures before mounting. If hardware and procedures are not suit­able for your application, contact the manufacturer of your rack or rack enclosure. The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
4-Post Rack Mounting
Loosen the wingnuts on each of the two adjustable side supports ; adjust the length of the supports to match the depth of your rack; tighten wingnuts. Mount both side supports in the lowest space of your rack on the inside surfaces of the rails with user-supplied #10­32 rack bolts and washers . Note: Both support ledges should face inward. The side supports’ front and back holes are threaded and do not require nuts to secure rack bolts.
Attach mounting ears to the front mounting holes of your UPS using the screws provided . The ears should face forward.
Using an assistant if necessary, lift your UPS and slide it onto the mounting shelves (if your model includes the shelves). Attach your UPS to the rack by using the appropriate hardware through its mounting ears and into the rack rails.
G
FE
D
C
B
A
1
2
3
E
D
F
G
2
3
1
C
B
C
A
2-Post Rack (Telecom) Mounting
If you mount 3U UPS models in 2-post racks, they require the addition of a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKITWM, sold separately). See Installation Kit owner’s manual for installation procedure for 3U UPS models.
Tower Mounting
If you tower mount this UPS, it requires the addition of a Tripp Lite 2U to 9U tower stand (model: 2-9USTAND, sold separately). See owner's manual for installation procedure.
Rotate the power module’s Control Panel to view it easier while the UPS is tower mounted. Insert a small screwdriver, or other tool, in the slots on either side of the Control Panel. Pop the panel out; rotate it; and pop the panel back into place.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 3
C
A
C
B
4
Hardwire the UPS System's input terminals to a utility power source.
DANGER!
HIGH VOLTAGE! RISK OF SERIOUS INJURY OR
DEATH! FOR QUALIFIED ELECTRICIANS ONLY!
ELECTRICIANS MUST READ WARNINGS BELOW
AND IN SAFETY SECTION PRIOR TO INSTALLATION.
1
Quick Installation
1
HARDWIRE WARNINGS!
• Wiring must be done by a qualified electrician.
• When making wiring connections, observe the cable connection regulations appropriate to your area at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS's AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 10 inch-pounds (1.1 NM).
• Make sure that your equipment is properly grounded.
• Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to make wiring connections (Ground conductors must be the same size and type as the power conductors used).
A
B
Input and Output Ratings
Input Maximum Rated Maximum Rated Typical Model Voltage Input Current Output Current Wire Size SMX5000XLRT3U 230V 27A 30A 10 AWG
Before hardwiring, switch OFF the facility's circuit breaker which is supplying power to the circuit the UPS System will be connected to. Using a screwdriv­er, remove the top of the box covering the UPS System's input terminals. Pass user-supplied cable through the opening in the box and attach it to the terminals. After hardwiring is complete, switch ON the facility's circuit breaker which is supplying power to the circuit the UPS System is connected to. Note! after the UPS System is connected to a live utility power source, the UPS (in “Standby” mode) will automatical­ly charge its batteries,* but will not supply power to its outlets until it is turned ON (see Step 3 below).
* The BATTERY CHARGE LED will be the only LED illuminated.
B
A
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 4
5
3
2
Plug your equipment into the UPS.*
Plug your equipment into the UPS using the addition­al power cord(s) that came with the UPS.
Note: Additional interconnection cords (C13 to C14) are available from Tripp Lite. Call +1.773.869.1234 (Part # P004-006).
* Your UPS is designed to support only electronic equipment. You will overload the UPS if the total VA ratings for all the equipment you connect exceeds the UPS's Output Capacity. To find your equipment's VA rat­ings, look on their nameplates. If the equipment is listed in amps, mul­tiply the number of amps by 230 to determine VA. (Example: 1 amp × 230 = 230 VA). If you are unsure if you have overloaded the UPS’s outlets, see “OUTPUT LOAD LEVEL” LED description.
Turn the UPS ON.
Press and hold the “ON/OFF/STANDBY” button for one second. The alarm will beep once briefly after one second has passed. Release the button.
3
2
Quick Installation
continued
Optional Installation
These connections are optional. Your UPS will function properly without these connections.
USB and RS-232 Serial Communications
Use the included USB cable (see ) and/or DB9 serial cable (see ) to connect the communication port on your computer to the communication port of your UPS. Install on your computer the Tripp Lite PowerAlert software appropriate to your computer’s operating system. Consult your PowerAlert manual for more information.
1b
1a
1
1b
1a
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 5
6
3b
4a
4b
3a
Optional Installation
continued
Relay Contact-Closure Connection
Use the included DB9 cable (see ) to connect spe­cialized electronic equipment to the relay contact-clo­sure port on your UPS System. See diagram and chart below to determine signals carried by this port.
Relay Contact Closure Chart
2b
2a
3
4
LINE FAIL
K1A
LO BATT
K10A
1
2
3
4
5
6
7
8
9
OPENS ON LI NE FAI L
CLOSES ON LI NE FAIL
CLOSE S BELOW LOW BATT ERY
TOP OF DUAL DB9 (J5/J34)
NO TE :
CLOS ES BE LO W MI D BA TTE RY
J5 REMOT E CONTAC TS
COM
MID BA T
K4A
COM
COM
OPENS BELOW MID BATTERY
RELAYS SHOWN D E -ENE RG IZED
OPENS BELOW LOW BATTERY
2b
2
2a
EPO Port Connection
This optional feature is only for those applications which require connection to a facility’s Emergency Power Off (EPO) circuit. When the UPS is connected to this circuit, it enables emergency shutdown of the UPS’s inverter.
Using the cable provided, connect the EPO port of your UPS (see ) to a user-supplied normally closed or normally open switch according to the circuit diagram (see ). The EPO port is not a phone line surge sup­pressor; do not connect a phone line to this port.
External Battery Connection
All UPS models come with a robust internal battery system; select models feature connectors (see ) that accept optional external battery packs (sold separately from Tripp Lite) to provide additional runtime. Adding external batteries will increase recharge time as well as runtime. See battery pack owner’s manual for complete installation instructions. Make sure cables are fully inserted into their connectors. Small sparks may result during battery connection; this is normal. Do not connect or disconnect battery packs when the UPS is running on battery power.
If you connect any
external batteries, set the Battery Charge Level Switch (see ) to the down position. This will increase your UPS’s charger output so the addi­tional batteries charge faster. Note: the switch to the right of the Battery Charge Level Switch is inactive and will not affect UPS operation regardless of its position.
CAUTION! DO NOT set the Battery Charge Level Switch to the down position without an external battery connected. There is a risk of damaging the UPS’s internal battery system.
4b
4a
3b
3a
Line Fail Mid Battery Low Battery
Indication Indication Indication UPS Operating Pins 1 Pins 2 Pins 7 Pins 8 Pins 4 Pins 5 Conditions & 6 & 6 & 3 & 3 & 9 & 9
AC Input Voltage OK CLOSED OPEN — AC Input Out of Range OPEN CLOSED — Battery More than 3 Min. OPEN CLOSED — Remaining Charge* Battery Less than 3 Min. CLOSED OPEN — Remaining Charge* Battery More than 2 Min. OPEN CLOSED Remaining Charge* Battery Less than 2 Min. CLOSED OPEN Remaining Charge*
Open on Close on Close Open Close Open
Line Line Below Below Below Below
Contact Action Failure Failure Mid Mid Low Mid
Battery Battery Battery Battery Battery
* Times are approximate, at full load.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 6
4-5
7
Buttons (Front Panel)
“ON/OFF/STANDBY” Button
When the UPS system is connected to a live AC utility power source, the UPS
System will operate in one of three modes: ON, OFF or STANDBY. Refer to
the chart below for UPS System operating characteristics within each mode.
UPS Charges Battery UPS Supplies Power to Outlets
Mode (when utility is present) (when utility is present or absent*) UPS Displays LEDs ON Yes Yes Yes (variety of LEDs,
depending on conditions) OFF No No No STANDBY Yes No Yes ("BATTERY CHARGE"
LED only)
To place the UPS in the ON mode: First, have a qualified electrician connect the UPS System to a utility power source as outlined in the Quick Installation section. Once the utility power source is live, the UPS System will automati­cally enter STANDBY mode. Press and hold the “ON/OFF/STANDBY” button for one second** and then release it to switch the UPS System from STAND­BY mode to ON mode.
OPTIONAL: If the utility power source is not live, you can “cold-start” the UPS System (i.e.: switch it directly from the OFF mode to the ON mode by supplying power for a limited time from its batteries*) by pressing and hold­ing the “ON/OFF/STANDBY” button for one second** and then releasing it.
To place the UPS in the OFF mode: With the UPS System in the ON mode and receiving utility power, press and hold the “ON/OFF/STANDBY” button for one second** and then release it to switch the UPS System from ON mode to STANDBY mode. Switch OFF the facility's circuit breaker which is supply­ing power to the circuit the UPS System is connected to.
* If batteries are fully charged. ** The alarm will beep once briefly after the interval has passed.
“MUTE/TEST” Button To Silence (or “Mute”) UPS Alarms: briefly press and release the
MUTE/TEST button.* To Run a Self-Test: with your UPS connected to a live utility power source and
turned ON, press and hold the MUTE/TEST button for two seconds.* Continue holding the button until the alarm beeps several times and the UPS performs a self test. See “Results of a Self-Test” below. Note: you can leave connected equip­ment on during a self-test. Your UPS, however, will not perform a self-test if the UPS is not turned on (see “ON/OFF/STANDBY” Button description).
Results of a Self-Test: the test will last approximately 10 seconds as the UPS switches to battery to test its load capacity and battery charge.
• If the “OUTPUT LOAD LEVEL” LED remains lit red and the alarm continues to sound after the test, the UPS’s outlets are overloaded. To clear the overload, unplug some of your equipment and run the self-test repeatedly until the “OUTPUT LOAD LEVEL” LED is no longer lit red and the alarm is no longer sounding.
CAUTION! Any overload that is not corrected by the user immediately following a self-test may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.
• If the “BATTERY WARNING” LED remains lit and the alarm continues to sound after the test, the UPS batteries need to be recharged or replaced. Allow the UPS to recharge continuously for 12 hours, and repeat the self-test. If the LED remains lit, contact Tripp Lite for service. If your UPS requires battery replacement, visit www.tripplite.com to locate the specific Tripp Lite replacement battery for your UPS.
* The alarm will beep once briefly after the indicated interval has passed.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 7
8
Basic Operation
continued
Indicator Lights (Front Panel)
All Indicator Light descriptions apply when the UPS is connected to a live utility power source and turned ON.
“POWER” LED: this green LED lights continuously when the UPS is ON and supplying connected equipment with AC power from a utility source. The LED flashes and an alarm sounds (4 short beeps followed by a pause) to indicate the UPS is operating from its internal batteries during a blackout or severe brownout. If the blackout or severe brownout is prolonged, you should save files and shut down your equipment since internal battery power will eventual­ly be depleted. See “BATTERY CHARGE” LED description below.
“VOLTAGE CORRECTION” LED: this green LED lights continuously whenever the UPS is automatically correcting high or low AC voltage on the utility line without the assistance of battery power. The UPS will also emit a slight clicking noise. These are normal, automatic operations of the UPS, no action is required on your part.
“OUTPUT LOAD LEVEL” LED: this multicolored LED indicates the approximate electrical load of equipment connected to the UPS's AC outlets. It will turn from green (light load) to yellow (medium load) to red (overload). If the LED is red (either illuminated continuously or flashing), clear the overload immediately by unplugging some of your equipment from the outlets until the LED changes from red to yellow (or green). CAUTION! Any overload that is not corrected by the user immediately may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.
“BATTERY CHARGE” LED: when the UPS is operating from utility power, this LED indicates the approximate charge state of the UPS's internal batteries: red indicates the batteries are beginning to charge; yellow indicates the batteries are roughly midway through charging; and green indicates the batteries are fully charged. When the UPS is operating from battery power during a blackout or severe brownout, this LED indicates the approximate amount of energy (ulti­mately affecting runtime) which the UPS’s batteries will provide: red indicates a low level of energy; yellow indicates a medium level of energy; and green indicates a high level of energy. Since the runtime performance of all UPS bat­teries will gradually deplete over time, it is recommended that you periodically perform a self-test (see MUTE/TEST Button description) to determine the energy level of your UPS batteries BEFORE a blackout or severe brownout occurs. During a prolonged blackout or severe brownout, you should save files and shut down your equipment since battery power will eventually be depleted. When the LED turns red and an alarm sounds continuously, it indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.
“BATTERY WARNING” LED: this LED lights red and an alarm sounds intermittently after you complete a self test (See “MUTE/TEST” Button descrip­tion) to indicate the UPS batteries need to be recharged or replaced. Allow the UPS to recharge continuously for 12 hours, and repeat the self-test. If the LED continues to light, contact Tripp Lite for service. If your UPS requires battery replacement, visit www.tripplite.com to locate the specific Tripp Lite replacement battery for your UPS.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 8
9
Basic Operation
continued
Other UPS Features (Rear Panel)
AC Receptacles: Your UPS features C13 outlets, and select models also fea­ture C19 outlets. These output receptacles provide your connected equipment with AC line power during normal operation and battery power during blackouts and brownouts. The UPS protects equipment connected to these receptacles against damaging surges and line noise. If you have a serial or USB connection to your UPS, you can remotely reboot connected equipment by turning the recep­tacles OFF and ON using Tripp Lite's PowerAlert software.
Input Terminal block: Use these terminals to connect the UPS System to utility power. Unscrew and remove the cover over the block for access.
Communications Ports (USB or RS-232): These ports connect your UPS to any workstation or server. Use with Tripp Lite’s PowerAlert software and included cables to enable your computer to automatically save open files and shut down equipment during a blackout. Also use PowerAlert software to monitor a wide variety of AC line power and UPS operating conditions. Consult your PowerAlert software manual or contact Tripp Lite Customer Support for more information. See “USB and RS-232 Serial Communications” in the “Optional Installation” section for installation instructions.
Relay Contact Interface Port: This female DB9 port sends contact-closure signals to indicate line-fail and low battery status. See “Optional Installation” section for installation instructions.
EPO (Emergency Power Off) Port: Your UPS features a EPO port that may be used to connect the UPS to a contact closure switch to enable emergency inverter shutdown. See Optional Connection.
C13/230V
C19/230V
Charge Rate Setting
(when External Batteries
are not connected)
Charge Rate Setting (when
External Batteries are
connected)
Battery Charge Level Switch: Controls the UPS system’s battery charge rate. If you connect any external batteries, set the Battery Charge Level Switch to the down position. This will increase your UPS’s charger output so the additional bat­teries charge faster. Note: the switch to the right of the Battery Charge Level Switch is inactive and will not affect UPS operation regardless of its position.
CAUTION! DO NOT set the Battery Charge Level Switch to the down position without an external battery connected. There is a risk of damaging the UPS’s internal battery system.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 9
10
Basic Operation
continued
Accessory Slot: Remove the small cover panel from this slot to install optional accessories to remotely monitor and control your UPS. Refer to your accessory’s manual for installation instructions. Contact Tripp Lite Customer Support at +1.773.869.1234 for more information, including a list of available SNMP, network management and connectivity products.
Power Sensitivity Adjustment: This dial is normally set fully counter-clockwise, which enables the UPS to provide maximum protection against waveform distortions in its AC input. When such distortion occurs, the UPS will normally switch to providing sine wave power from its battery reserves for as long as the distortion is present. In areas with poor utility power or where the UPS’s input power comes from a backup generator, chronic waveform distortion could cause the UPS to switch to battery too frequently, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to moderate waveform distortion by experimenting with different settings for this dial. As the dial is turned clockwise, the UPS becomes more tolerant of variations in its input power’s AC waveform. NOTE: The further the dial is adjusted clockwise, the greater the degree of waveform distortion the UPS will allow to pass to connected equip­ment. When experimenting with different settings for this dial, operate connect­ed equipment in a safe test mode so that the effect on the equipment of any wave­form distortions in the UPS’s output can be evaluated without disrupting criti­cal operations.
External Battery Connector: Use to connect Tripp Lite external battery packs for additional runtime. Refer to instructions available with the battery pack for complete connection information and safety warnings.
Output Breaker(s): Protect your UPS from output overload. If one or more breakers trip, remove some of the load on the circuit(s), then reset them by pressing the breaker switch(es) in.
Ground Screw: Use this to connect any equipment that requires a chassis ground.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 10
11
Storage and Service
Storage
Before storing your UPS, turn it completely OFF. If you store your UPS for an extended period of time, recharge the UPS batteries for 4 to 6 hours once every three months. Note: after you connect the UPS to utility power, it will automatically begin charging its batteries. If you leave your UPS batteries dis­charged for an extended period of time, they will suffer a permanent loss of capacity.
Service
Before returning your UPS for service, follow these steps:
1. Review the installation and operation instructions in this manual to ensure that the service problem does not originate from a misreading of the instructions. Also, check that the UPS System’s circuit breaker(s) are not tripped. This is the most common cause of service inquiries which can be easily remedied by following the resetting instructions in this manual.
2. If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp Lite at +1.773.869.1233. A service technician will ask for the UPS's model number, serial number and purchase date and will attempt to correct the problem over the phone.
3. If the problem requires service, the technician will issue you a Returned Material Authorization (RMA) number, which is required for service. If you require packaging, the technician can arrange to send you proper packaging. Securely pack the UPS to avoid damage during shipping. Do not use Styrofoam beads for packaging. Any damages (direct, indirect, special, incidental or consequential) to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty. UPS Systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the RMA number on the outside of the package. If the UPS System is within the 2-year warranty period, enclose a copy of your sales receipt. Return the UPS for service using an insured carrier to the address given to you by the Tripp Lite service technician.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 11
12
Battery Replacement
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Made in China.
Note on Labeling
Two symbols are used on the label. V~ : AC Voltage
V : DC Voltage
Battery replacement should be performed only by authorized service personnel using the same num­ber and type of batteries (sealed Lead-Acid). Under normal conditions, the original batteries in your UPS will last many years. See Safety section before replacing batteries. The batteries are designed for hot-swap replacement (i.e. leaving the UPS in ON mode), but some qualified service personnel may wish to put the UPS in the OFF mode and disconnect equipment before proceeding.
Procedure
Remove Front Panel and Battery Holding Plate
Disconnect Batteries
Remove/Dispose of Batteries
Add Batteries
Connect Batteries
Attach connectors: black-to-black and red-to-red.
Replace
Front Panel
WARNING!
Batteries can present a risk of electrical shock and burn
from high short-circuit current resulting in serious injury or death. Battery terminals are in close proximity to UPS cabinet and special care must be taken to avoid
shorting the batteries including not touching metal
cabinet and battery terminals simultaneously.
6
5
4
3
2
1
S
MART
P
RO
®
UPS
1
6
2
5
3
4
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and elec­tronic equipment from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 12
Manual del propietario
1111 W. 35th Street, Chicago, IL 60609 USA
Soporte al cliente: +1.773.869.1234 • www.tripplite.com
Instrucciones de seguridad importantes
14
Montaje
15
Instalación rápida
16
Operación básica
19
Almacenamiento y servicio
23
English
Copyright ©2008 Tripp Lite. Todos los derechos reservados. SmartPro®es una marca comercial registrada de Tripp Lite.
SmartPro®3U Rackmount
(5000VA)
Sistemas de UPS Inteligentes e Interactivos en Línea
• 230V Entrada/Salida
• Opciones de Operación Extendidas
No conveniente para los usos móviles.
1
Reemplazo de batería
24
Français
25
Instalación opcional
17
Pусски
é
37
13
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 13
14
Instrucciones de seguridad importantes
GUARDE ESTAS INSTRUCCIONES
Este manual contiene importantes instrucciones que deben seguirse durante la instalación, operación y el almacenamiento de todos los UPS de Tripp Lite. La no observancia de estas advertencias anulará su garantía.
Advertencias sobre la ubicación del UPS
• Tenga cuidado al levantar el UPS. Debido al gran peso de los UPS para montaje en bastidor, se requieren por lo menos dos personas para que le ayuden a levantarlos e instalarlos.
• Instale su UPS bajo techo, lejos de la humedad, el calor, el polvo o la luz solar directa.
• Para un mejor funcionamiento, la temperatura ambiente cerca de su UPS debe estar entre 0° C y 40° C (32° F - 104° F)
• Deje una cantidad adecuada de espacio alrededor de todos los lados del UPS para sua adecuada ventilación. No obstruya sus respiraderos ni las aberturas de ventilación.
• No monte esta unidad con el panel frontal o con el panel trasero hacia abajo (Bajo ningún ángulo o
inclinación). Si lo monta de esta manera, inhibirá seriamente el sistema de enfriamiento interno de la unidad; lo que finalmente causará daños al producto que no están cubiertos por la garantía.
Advertencias sobre la conexión del UPS
• El UPS contiene su propia fuente de energía (batería). Los terminales de salida pueden estar con energía incluso cuando el UPS no está conectado a un suministro de corriente alterna.
Advertencias sobre la conexión de equipos
• El uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda razonable­mente hacer suponer que causará fallas en el equipo de soporte de vida o afecte significativamente su seguridad o efectividad, no está recomendado. No use este equipo en la presencia de una mezcla anestési­ca inflamable con aire, oxigeno u óxido nitroso.
• No conecte supresores de sobretensiones ni cordones de extensión a la salida de su UPS. Esto puede sobrecargarlo y anular su garantía y la del supresor de sobretensiones.
Advertencias sobre la batería
• Las baterías presentan un peligro de choque eléctrico y quemaduras debido a las altas corrientes de corto­circuito. Observe las precauciones apropiadas. No deseche las baterías en un incinerador. No abra el UPS ni las baterías. No ponga los terminales de la batería en corto o en puente con ningún objeto. Apague y desconecte el UPS antes de reemplazar la batería. Use herramientas con mangos aislados. No hay piezas que el usuario pueda reparar dentro del UPS. El reemplazo de baterías debe ser realizado solamente por personal de servicio autorizado usando el mismo número y tipo de baterías (plomo-ácido, selladas). Las baterías son reciclables. Consulte la reglamentación local para los requisitos de disposición de desechos. Tripp Lite ofrece una línea completa de cartuchos de reemplazo de batería para UPS (R.B.C.) Visite la página web de Tripp Lite en www.tripplite.com para localizar la batería de reemplazo específica para su UPS.
• Durante el reemplazo de baterías en operación (hot-swap), el UPS no proporcionará energía de respaldo en el caso de una falla del servicio eléctrico u otras interrupciones de energía.
• No opere el UPS sin baterías.
• Al agregar bancos de baterías externas, sólo emplee bancos recomendados por Tripp Lite del voltaje y tipo correctos. No conecte ni desconecte bancos de baterías cuando el UPS esté funcionando con energía de las baterías.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 14
15
Montaje
Monte su equipo en un bastidor de 2 o 4 postes. El usuario debe determinar la idoneidad de los materiales y acce­sorios, así como de los procedimientos antes del montaje. Si los materiales y procedimientos no son adecuados para su aplicación, contacte con el fabricante de su bastidor. Los procedimientos descritos en este manual son para bastidores comunes y de tipo caja y podrían no ser apropiados para todas las aplicaciones.
Montaje en bastidor de 4 postes
Afloje las tuercas de mariposa en los dos soportes lat­erales ajustables ; ajuste la longitud de los soportes para que sea igual a la profundidad de su bastidor; apriete las tuer­cas de mariposa. Monte ambos soportes laterales en el espa­cio más bajo de su bastidor en la superficie interna de los rieles, con los pernos para bastidor #10-32 y las arandelas suministrados por el usuario . Nota: Ambos bordes de apoyo deben mirar hacia adentro. Los agujeros delantero y posterior de los soportes laterales son roscados y no necesi­tan tuercas para asegurar los pernos del bastidor.
Fije las orejas de montaje a los agujeros de montaje de la parte delantera de su UPS usando los tornillos sumin­istrados . Las orejas deben mirar hacia adelante.
Utilizando la ayuda de otra persona, levante su UPS y colóquelo sobre los estantes de apoyo (si su modelo los incluye.) Fije su UPS al bastidor usando los accesorios sum­inistrados a través de las orejas de montaje y dentro de los rieles del bastidor.
F
E
D
C
C
B
A
1
2
3
D
C
E
F
2
3
1
C
B
C
A
Montaje en bastidor de 2 postes
Si monta un modelo de UPS de 3U en bastidores de 2 postes, necesi­tará agregar un kit de instalación para montaje en bastidor de 2 postes de Tripp Lite (modelo: 2POSTRMKITWM, vendido por separado) Vea el manual del propietario del kit para conocer el procedimien­to de instalación en los modelos de 3U.
Montaje de torre
Si monta en torre este UPS, debe agregar un pedestal de torre Tripp Lite de 2U a 9U (modelo: 2-9USTAND, vendido por separado). Consulte el procedimiento de instalación en el manual del propi­etario.
Gire el panel de control del módulo de potencia para obtener mejor visibilidad mientras el UPS esté montado en torre. Introduzca un pequeño destornillador u otra herramienta en las ranuras en cualquier lado del panel de control. Saque el panel, gírelo y colóquelo en posición nuevamente.
200807051 93-2460 Smart 3U 230V OM.qxd 8/8/2008 10:10 AM Page 15
C
A
C
B
Loading...
+ 33 hidden pages