Tripp SMX3000XLRT2UA Product Data Sheet

Page 1
SmartPro 230V 3kVA 2.7kW Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9
MODEL NUMBER: SMX3000XLRT2UA
Description
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for
with built-in Auto-Voltage Regulation(AVR) actively corrects brownouts and overvoltages back to usable levels
while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in
exceptionally poor-power environments with two separate levels of voltage boost to correct both slight
undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed
UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover
from line to battery power occurs within milliseconds to maintain operation of connected equipment without
interruption or reboot. 98% line-mode efficiency offers reduced heat emissions and operating costs. Network management interfaces support communications
via USB, RS-232 and slot for network management card options, such as Tripp Lite's SNMPWEBCARD network interface. HID-compliant USB interface
enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Network communications ports enable detailed
monitoring of equipment load levels, self-test data and utility power conditions. Includes PowerAlert monitoring software and complete cabling. Switched output
load banks enable scheduled and real-time remote reboot and load shedding of select outlets. Emergency Power Off(EPO) interface. LCD display panel easily
rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options.
Programmable self-test. Field-replaceable, hot-swappable battery modules.
Features
Tripp Lite SMX3000XLRT2UA line interactive 2U rack/tower UPS with 3000VA / 3kVA capacity and extended runtime options
Line interactive UPS with Automatic Voltage Regulation(AVR) corrects brownouts and overvoltages from 158 to 278V
C20 AC power inlet; 8 C13 and 1 C19 output receptacles, Two independently switchable output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages
High 98% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
Internal batteries offer 11.1 minutes at 50% load(1350W) and 3.9 minutes at 100% load(2700W)
Extended runtime is available with optional external battery packs BP48V24-2U(limit 1), BP48V60RT-3U(multi-pack compatible) and
Highlights
3kVA / 3000VA / 2700W line
interactive 2U rack/tower UPS,
Sine Wave
230V output, Corrects brownouts
and overvoltages from 158V to
278V
0.9 Power Factor, Interactive
LCD interface
Extended runtime options up to
2700W
4 post compatible mounting
accessories
98% line-mode efficiency, 2
switched load banks
USB, RS232, EPO and slot for
Network Management Card
options
230V C20 inlet, 8 C13 & 1 C19
outlets
Package Includes
SMX3000XLRT2UA UPS system
PowerAlert Software with USB,
Serial & EPO cabling
4 post rackmount installation kit
Set of 3 C13/C14 power cables
Instruction manual
1 / 5
Page 2
BP48V27-2US(multi-pack compatible)
External battery configurations require the use of Tripp Lite's External Battery Configuration Software(see manual)
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no disruption to connected equipment
Intelligent battery management system extends battery life
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens
of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post rackmount/wallmount installation; Optional 2-9USTAND
enables tower placement
Built-in USB, RS-232 and slot for optional network management card options, such as Tripp Lite's SNMPWEBCARD network interface
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software; Built-in Emergency Power Off(EPO) interface with cable
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2700
Output kW Capacity (kW) 2.7
Power Factor .9
Nominal Output Voltage(s) Supported
220V; 230V; 240V
Nominal Voltage Details 230v nominal inverter output voltage
Frequency Compatibility 50 / 60 Hz
Output Voltage Regulation (Line Mode)
+6%, -15%
Output Voltage Regulation (Battery Mode)
+/-5%
Output Receptacles (8) C13; (1) C19
Included Output Power Cables Set of 3 C13 to C14 power cables included
Load Management Receptacles Two switchable single outlet C13 load banks
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 14.1A
Nominal Input Voltage(s) Supported 230V AC
UPS Input Connection Type C20 inlet
2 / 5
Page 3
UPS Input Connection Description
IEC320-C20 input connection accepts a variety of user supplied detachable C19 output cordsets to match country or site specific power sources
Input Circuit Breakers 20A
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 3.9 min. (2700w)
Half Load Runtime (min.) 11.1 min. (1350w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V24-2U
(limit 1);
BP48V60RT-3U
(multi-pack compatible);
BP48V27-2US
(multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included Batteries)
Less than 5 hours from 10 to 90% (typical, full load discharge)
Internal UPS Replacement Battery Cartridge
RBC58-2U
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
Overvoltage Correction Input voltages between 244 and 278 are reduced by 12%
Undervoltage Correction Input voltages between 206 and 183 are boosted by 12%
Severe Undervoltage Correction Input voltages between 158 and 183 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 350
EMI / RFI AC Noise Suppression Yes
AC Suppression Response Time Instantaneous
3 / 5
Page 4
PHYSICAL
Included Mounting Accessory Description
4 post rackmount installation hardware included
Installation Form Factors Supported with Optional Accessories
2 post rackmount(
2POSTRMKITWM
); Wallmount(
2POSTRMKITWM
); Tower(
2-9USTAND
)
Primary Form Factor Rackmount
UPS Power Module Dimensions (hwd, in.)
3.5 x 17.5 x 19.5
UPS Power Module Dimensions (hwd, cm)
8.9 x 44.4 x 49.5
Rack Height (U Spaces) 2
Minimum Required Rack Depth (inches)
26.5
Minimum Required Rack Depth (cm) 67.3
UPS Power Module Weight (lbs.) 62.8
UPS Power Module Weight (kg) 28.5
UPS Shipping Dimensions (hwd / in.) 9 x 23.75 x 20.5
UPS Shipping Dimensions (hwd / cm)
22.9 x 60.3 x 52.1
Shipping Weight (lbs.) 72.6
Shipping Weight (kg) 33
Cooling Method Fan
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 158
AC Mode Efficiency Rating (100% Load)
98%
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software Included
Communications Cable USB, DB9 and EPO cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
4 / 5
Page 5
LINE / BATTERY TRANSFER
Transfer Time 6 milliseconds (AC to battery mode), 1 millisecond (Battery to AC mode)
Low Voltage Transfer to Battery Power (Setpoint)
158
High Voltage Transfer to Battery Power (Setpoint)
278
SPECIAL FEATURES
Cold Start (Startup in Battery Mode During a Power Failure)
Cold-start operation supported
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications CE; ROHS (Restriction of Hazardous Substances)
UPS Certification Details IEC 62040-1, IEC 62040-2 Class A EMI, GOST
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
© 2016 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
5 / 5