Tripp SMX2200XLRT2U Product Data Sheet

SmartPro 230V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9
MODEL NUMBER: SMX2200XLRT2U
Description
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for
with built-in Auto-Voltage Regulation(AVR) actively corrects brownouts and overvoltages back to usable levels
while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in
exceptionally poor-power environments with two separate levels of voltage boost to correct both slight
undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed
UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover
from line to battery power occurs within milliseconds to maintain operation of connected equipment without interruption or reboot. 98% line-mode efficiency
offers reduced heat emissions and operating costs. Network management interfaces support communications via USB, RS-232 and optional network
management card options, such as Tripp Lite's SNMPWEBCARD network interface. HID-compliant USB interface enables integration with built-in power
management and auto shutdown features of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels,
self-test data and utility power conditions. Includes PowerAlert monitoring software and complete cabling. Switched output load banks enable scheduled and
real-time remote reboot and load shedding of select outlets. Emergency Power Off(EPO) interface. LCD display panel easily rotates for viewing in rackmount
or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test.
Field-replaceable, hot-swappable battery modules.
Features
Line interactive UPS with Automatic Voltage Regulation(AVR) corrects brownouts and overvoltages from 158 to 278V
C20 AC power inlet; 8 C13 output receptacles, Two independently switchable output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages
High 98% efficiency rating in line-power mode offers reduced power consumption and BTU emissions
Internal batteries offer 11.9 minutes at 50% load(960W) and 5 minutes at 100% load(1920W)
Extended runtime is available with optional BP48V24-2U(limit 1), BP48V60RT3U(no limit) or BP48V27-2US(no limit) external battery packs(max output is
reduced to 1600w with external battery packs connected)
Highlights
2.2kVA / 2200VA / 1920W line
interactive 2U rack/tower UPS,
Sine Wave
230V output, Corrects brownouts
and overvoltages from 158V to
278V
0.9 Power Factor, Interactive
LCD interface
Extended runtime options up to
1600W
4 post compatible mounting
accessories
98% line-mode efficiency, 2
switched load banks
USB, RS232, EPO and slot for
Network Management Card
options
230V C20 inlet, 8 C13 outlets
Package Includes
SMX2200XLRT2U UPS system
PowerAlert Software with USB,
Serial & EPO cabling
4 post rackmount installation kit
Set of 3 C13/C14 power cables
Instruction manual
1 / 5
External battery configurations require the use of Tripp Lite's External Battery Configuration Software(see manual)
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no disruption to connected equipment
Intelligent battery management system extends battery life
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens
of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post rackmount/wallmount installation; Optional 2-9USTAND
enables tower placement
Built-in USB, RS-232 and optional network management card options, such as Tripp Lite's SNMPWEBCARD network interface
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software; Built-in Emergency Power Off(EPO) interface with cable
Optional PDUBHV20 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 2200
Output kVA Capacity (kVA) 2.2
Output Watt Capacity (Watts) 1920
Output kW Capacity (kW) 1.92
Power Factor 0.87
Nominal Output Voltage(s) Supported
220V; 230V; 240V
Nominal Voltage Details 230V nominal output in battery mode
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Automatic frequency selection
Output Voltage Regulation (Line Mode)
-15%, +6%
Output Voltage Regulation (Battery Mode)
+/- 5%
Output Receptacles (8) C13
Included Output Power Cables Includes 3 C13 to C14 output power cables
Load Management Receptacles Two switchable single-outlet C13 load banks
Hot-Swap PDU options PDUBHV20 (2U / 6 C13, 2 C19 outlets)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 10.7A
2 / 5
Nominal Input Voltage(s) Supported 230V AC
UPS Input Connection Type C20 inlet
UPS Input Connection Description
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
Input Circuit Breakers 15A
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 5 min. (1920w)
Half Load Runtime (min.) 11.9 min. (960w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V24-2U
(limit 1);
BP48V60RT-3U
(multi-pack compatible);
BP48V27-2US
(multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery Cartridge
RBC94-2U
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
Overvoltage Correction Voltage reduction of 12% applies when input is between 244-278V
Undervoltage Correction Voltage boost of 12% applies when input voltage is between 183-206V
Severe Undervoltage Correction Voltage boost of 24% applies when input voltage is between 158-182V
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 350
UPS AC Suppression Response Time
Instantaneous
3 / 5
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory Description
4 post rackmount installation accessories included
Installation Form Factors Supported with Optional Accessories
2 post rackmount(
2POSTRMKITWM
); Wallmount(
2POSTRMKITWM
); Tower(
2-9USTAND
)
Primary Form Factor Rackmount
UPS Power Module Dimensions (hwd, in.)
3.5 x 17.5 x 19.5
UPS Power Module Dimensions (hwd, cm)
8.9 x 44.4 x 49.5
Rack Height (U Spaces) 2
Minimum Required Rack Depth (inches)
26.5
Minimum Required Rack Depth (cm) 67.3
UPS Power Module Weight (lbs.) 68.75
UPS Power Module Weight (kg) 31.2
UPS Shipping Dimensions (hwd / in.) 9.25 x 24.75 x 22.5
UPS Shipping Dimensions (hwd / cm)
23.5 x 62.9 x 57.2
Shipping Weight (lbs.) 82.3
Shipping Weight (kg) 37.3
Cooling Method Fan
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 161
AC Mode Efficiency Rating (100% Load)
98%
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software Included
Communications Cable USB, DB9 and EPO cabling included
4 / 5
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time 6 ms. (AC to DC) / 1 ms. (DC to AC)
Low Voltage Transfer to Battery Power (Setpoint)
158V
High Voltage Transfer to Battery Power (Setpoint)
278V
SPECIAL FEATURES
Grounding Lug Back panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure)
Cold-start operation supported
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications CE
UPS Certification Details IEC 62040-1, IEC 62040-2 Class A EMI, GOST
WARRANTY
Product Warranty Period (International)
2-year limited warranty
Product Warranty Period (Mexico) 2-year limited warranty
Product Warranty Period (Puerto Rico)
2-year limited warranty
© 2016 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
5 / 5
Loading...