Tripp PDUMV20HVNETLX Product Data Sheet

3.2–3.8kW Single-Phase Switched PDU with LX Platform Interface, 200–240V Outlets (20 C13 & 4 C19), C20/L6-20P, 0U, TAA
MODEL NUMBER: PDUMV20HVNETLX
Description
The PDUMV20HVNETLX 3.2–3.8kW Single-Phase Switched PDU provides advanced network control and remote power monitoring with the ability to turn on, turn off, reboot or lock out power to each outlet. Recommended for any IT or industrial application, it features 24 switched outlets (20 C13 and 4 C19) with included plug-lock insert sleeves to prevent cables from becoming accidentally disconnected. A 10-foot cord with NEMA L6-20P plug connects the PDU’s C20 inlet to a compatible AC power source, generator or protected UPS.
The built-in Java-free HTML5-based LX Platform network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
A digital ammeter allows you to monitor each bank’s load in real time to ensure it remains well below maximum capacity with no danger of overload. The vertical PDU mounts in 0U of space in EIA-standard 19-inch racks using the included toolless mounting buttons or the included rack-mounting brackets. Use the included PDUMVROTATEBRKT kit to install the unit with outlets facing the rear for better airflow or equipment access.
Features
Distributes Network-Grade Single-Phase Power
3.2–3.8kW 200/208/230/240V switched PDU Recommended for network applications requiring individual outlet control, load shedding and remote monitoring of critical network components Includes detachable NEMA L6-20P plug with 10 ft. cord; C20 inlet supports user-supplied international input cabling Firmware upgrades support future product enhancements
24 Switched Outlets Distribute AC Power
20 C13 and 4 C19 outlets split into 2 separately breakered load banks
Highlights
3.2–3.8kW 200/208/230/240V switched PDU 24 individually controllable outlets—20 C13, 4 C19 Built-in LX Platform interface for 24/7 remote access Digital ammeter for on-site load monitoring in real time C20 inlet with 10ft NEMA L6-20P AC power cord
Package Includes
PDUMV20HVNETLX 3.2–3.8kW Single-Phase Switched PDU Built-in LX Platform interface Detachable NEMA L6-20P to C19 power cord, 10 ft. Configuration cable (24) Plug-lock inserts Rack-mounting hardware
PDUMVROTATEBRKT mounting
bracket accessory Owner’s manual
1 / 4
Individual outlets can be remotely controlled to power up, power down, reboot or lock out devices Plug-lock inserts prevent cables from becoming accidentally disconnected
Digital Ammeter
Reports load level on each bank and total PDU output Supports IP-address self-ID Rotates 180° for easy reading at either angle
Built-In LX Platform Interface
Allows full remote access for power monitoring with email notifications via secure web browser, SNMP, telnet or SSH Supports 10/100 Mbps auto-sensing for communication with an Ethernet network Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities No Java required
Broad Communications Compatibility
Supports HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP Supports automatic and manual assignment of IP address
Easy 0U Installation in EIA-Standard 19 in. Racks
Mounts vertically using included toolless buttons or rack-mounting brackets Included PDUMVROTATEBRKT allows mounting with rear-facing outlets
TAA-Compliant
Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
Specifications
OVERVIEW
PDU Type Switched
OUTPUT
Output Capacity Details
3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V) / 16A total capacity; 16A max per
C19 outlet; 12A (10A CE) max per C13 outlet Frequency Compatibility 50 / 60 Hz Output Receptacles (20) C13; (4) C19 Output Nominal Voltage 200; 208; 220; 230; 240 Overload Protection n/a Customized Load Management
Receptacles
Each outlet is individually controllable via remote interface
INPUT
PDU Input Voltage 200; 208; 220; 230; 240