TripleAqua 3FS11, 3FS15, 3PL11, 3PL15, 3PL20 Installation & Maintenance Manual

...
Installation & Maintenance manual - Indoor unit
3FS Fan Coil Series
MODELS: 3FS11-3PL11 3FS15-3PL15 3FS20-3PL20 3FS25-3PL25 3FS32-3PL32 3FS40-3PL40 3FS50-3PL50 3FS60
Features and benets
Heating, cooling and energy storage in one!
• Up to 50% lower energy consumption
• Passive, free heat and cold storage
• Independent heating and cooling
• Natural refrigerant, no green house F-gas
• Energy exchange between rooms
• Simple control panel
Congratulations with your personal climate!
Your climate will now be controlled by this modern heat pump system. It will provide you exceptional benefits and no compromises on comfort or energy use.
Please read this user guide with care and keep it to obtain the most benefit of this advanced system. Huge benefit not only for the climate, but also in your building For many buildings, heating and cooling the indoor climate is a huge cost factor. For that reason alone, there is much to be gained. The TripleAqua climate system enables you to independently heat and cool different rooms as required, but using up to 50% less energy. This makes it one of the most efficient systems in the world. Aim: to bring your building to energy label
+++
A
level!
High quality system, low water temperature
A heating system is, in fact, a huge energy consumer. TripleAqua utilizes a heat pump combined with high efficiency indoor units. Thanks to the system’s unprecedented heat transfer, a much lower water temperature suffices, with huge savings and minimal losses as a result.
Smart storage and energy exchange
Cooling with a heat pump during the day creates waste heat, while heating creates waste cold. Other systems reject surplus energy immediately. What a waste! TripleAqua exchanges this energy between rooms and passively stores the surplus heat and cold and uses them for free heating and cooling. This results in spectacular energy savings, particularly during the spring and autumn.
Table of contents
1 Intro 4
1.1 Introduction 4
1.2 Emergency stop / Normal operation / External stop 4
1.3 Read this manual 4
2 Safety 5
2.1 Foreword and safety labels 5
2.2 Definitions 6
2.3 Safety devices 6
2.4 Scope of authorization – safe working 6
2.5 Limited Access to the unit 6
2.6 Warnings and precautions against risks 6
3 Transport, storage, handling and positioning 8
3.1 Transportation 8
3.2 Storage 8
3.3 Receiving and Inspecting 8
3.4 Lifting and handling 8
3.5 Anchoring and positioning 8
3.6 About the Installation Site 9
4 Unit structure 10
4.1 Basic unit (illustration) Fan coil, 10
4.2 Drain pan, 11
4.3 Ultra efficient EU5 / M5 air filter 12
4.4 EC-fan 13
4.5 Room Controller 13
4.6 Optional Plenum 14
5 Unit details 16
5.1 Dimensional drawings 16
5.2 Space requirements 18
5.3 Technical specifications 19
5.4 Water side pressure loss 20
5.5 Corrections for glycol 21
6 Installation 22
6.1 Hydraulic connections 22
6.2 Mounting Unit to wall / ceiling (Anti Vibration mounting) 23
6.3 Installation piping 23
6.4 Frost protection 23
6.5 Cold / warm / return / condensate water connections 23
6.6 External components 24
6.6.1 Expansion vessel 25
6.6.2 Water filter 26
6.6.3 Electric bypass valves 26
6.6.4 Optional bypass valves 26
6.7 Condensate drainage 27
6.8 Duct work 27
6.9 Remote Controller 28
7 Electrical connections 29
7.1 Power supply / Electrical data 29
7.2 Warnings 30
7.3 Wiring sizing/ Local CE+ CE- bus / more room controlers 31
7.4 Wiring diagram 32
7.5.1 Detailed optional connections 34
7.5.2 Input D2 forced gate / commissioning / self test 34
7.5.3 X6 external mode on / off or co2 level input 35
7.5.4 Output Q1 35
7.5.5 Output DO2 extra booster fan / louver 36
7.5.6 Output Q3 alarm relay 36
7.5.7 Output Q4 internal or external condensate pump 37
7.5.8 HMI - Control Panel 37
7.5.9 Modbus / BacNet Building Management 38
8 Commissioning 38
8.1 Preliminary checks 38
8.2 Venting / flushing / pressurize 38
8.3 Water balancing 39
8.4 Air balancing 40
8.5 Equipment start up checklist 40
8.6 Delivery to the customer 41
9 Controls 42
10 Maintenance 43
10.1 General 43
10.2 Planned maintenance 43
10.3 Filter replacement 44
10.4 Additional maintenance 44
10.5 Water treatment 44
10.6 Drain pan cleaning 44
11 Service 45
11.1 Exploded view 45
11.2 Spare parts list 46
12 Warranty 47
13 Dismantling and scrapping 48
1 Intro
1 Intro
This document contains the instructions for the installation and maintenance of TripleAqua indoor units.
1.1 Introduction
The TripleAqua system is a human climate comfort system, operating with lukewarm heated and chilled pure water, or water/glycol. The system is build up by central heat pump systems and local terminal fan coil products. They can be combined with other hydraulic systems operating at similar water temperature conditions. TripleAqua is a three pipe water based heat pump operating with natural refrigerant. Operating these products for other applications as human comfort control is not specified and may be unfit for any other purpose other than specified in this manual.
This installation and maintenance manual includes all the information required for a proper installation of the units, This TripleAqua unit is designed and manufactured to state-of-the-art and implementation standards. This climate system will ensure top performance, the highest level of comfort, low operation and maintenance costs in your climate.
We strongly recommend to read this manual carefully before installation or any operation of the products. The TripleAqua installation and maintenance must be carried out by skilled personnel only.
The manufacturer is not liable for any damage to people or property caused by improper installation, operation by non­qualified or trained staff, incorrect start-up and/or improper use of the unit and/or failure to follow and to implement the procedures and instructions included in this manual.
1.2 Emergency stop / Normal operation / external stop
As a factory standard, every indoor unit is equipped with individual, voltage free input. They can be used for an emergency stop (fire command), normal on /off (VING card or occupancy detector) and for external stop (window contact or equivalent). All functions are integrated in the controls. Usually, if more than one unit in a room is present, only the GATE unit needs to be wired to this input. See the CONTROLS MANUAL for further details, wiring and setting up all functions.
1.3 Read this manual
Improper use may cause serious accidents or even death. Thus, for safety reasons, it is mandatory to follow all the instructions given in this manual. The manufacturer is not liable to any direct and consequential damage caused by non-compliance with these instructions.
This documentation, drawings and appendix, as well as the additional documents which accompanies the delivery, are and remain the property of manufacturer, which reserves any and all rights thereon. The manufacturer remains the right to modify and update documentation at any moment. Please check for the most recent version.
This documentation may not be copied in any way or means, partially or in whole, without the written manufacturer’s authorization.
Images and all content in all publications (as well as our websites) are subject to change. No rights can be derived from them.
The DANGER sign recalls your attention to a certain procedure or practice which, if not followed, may result in serious damage to people and property.
The WARNING sign precedes those procedures that, if not followed, may result in serious damage to the appliance.
The NOTE contain important observations.
The USEFUL TIPS provide valuable information that optimises the efficiency of the appliance.
2 Safety
2 Safety
This installation and maintenance manual is for horizontal and vertical TripleAqua Fan Coil units. Fan coils are hydronic terminal units designed for year-round cooling or cooling/ heating. This manual should be thoroughly reviewed prior to the installation, start-up or maintenance of the equipment. If any questions arise, please contact your local sales representative or the factory before proceeding any further.
There are some options and accessories available with the equipment covered in this manual. For more specific details, refer to the documentation.
The installation of TripleAqua Fan Coil units and all related components, parts and accessories which make up the delivery of installation, shall be in accordance with the regulations of all authorities having jurisdiction and must conform to all applicable codes. Only trained and qualified service personnel using good judgment and safe practices should install, repair and/or service. Untrained personnel may only perform basic maintenance functions such as cleaning coils and cleaning or replacing filters. All other operations should be performed by trained service personnel. When working on our equipment, observe precautions in the literature, tags and labels attached to the equipment and all other safety precautions that may apply.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other hazardous conditions which may cause serious personal injury and/ or property damage. Consult a qualified installer, service agency, or your sales representative for information or assistance.
The equipment must always be properly mounted by lifting equipment. Temporary supports used during installation or repairs need to be designed to adequately hold the equipment in place until the unit is permanently fastened and set in its final location. Supports must meet applicable local codes and ordinances.
Electric heating elements must be disconnected prior to servicing to avoid burns.
Never pressurize equipment beyond specified pressures as shown on unit rating plate. Always pressure test with an inert fluid such as water or dry nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing. Please follow all standard safe practices regarding the handling, installing or servicing of mechanical equipment.
2.1 Safety labels
These units must be installed in conformity with the provisions of Electromagnetic Interference Directive 2004/108/EC, Machinery Directive 2006/42/EC, as well as with all other national, local and international regulations applicable in the country of installation. Only if all of these provisions are complied with, the unit is allowed to be operated.
All equipment is to be grounded to earth properly. Any installation and/or maintenance
operation may only be carried out if the main power supply and/or the mains switch has been turn off, fuses have been taken out, thus deenergising the electrical panel of the unit.
All fans are NOT equipped with guards on the fans
They must be only operated if all panels of the
unit are mounted and are not allowed to be removed before fully de-energising the appliance. Fans may start at any sudden moment causing serious human accidents.
It must be noted that it is the OWNER’s only
responsibility to ensure that the unit is fit for the
conditions of intended use and that both installation and maintenance are carried out by trained and experienced personnel, who are capable of respecting all the recommendations provided by this manual.
It is important that the unit is adequately supported/ fixed to a dedicated structure, Noncompliance with these recommendations may create hazardous situations for the personnel and damage to the equipment or surroundings.
The unit has a galvanized frame and panel casing,
which is not designed to withstand loads and/or
stress that may be transmitted by other components, parts, structures or units, connections, piping and/or other mechanical objects.
Each and any external load or stress transmitted to the unit may break or cause breakdowns in the unit’s structure, as well as serious dangers to the internal components of the machine and the personnel. Obviously, in case of damage caused by external load or structures, any form of warranty will automatically become null and void.
The packaging material must not be disposed of
in the surrounding environment or burnt.
Failure to respect these safety precautions as mentioned above may likely result in electrocution hazard and fire in the presence of any short-circuits.
2.2 Definitions
INSTALLER: = the legal representative of the company who has been given by the owner the job of positioning and performing the hydraulic, electric and other connections of unit to the plant: he/she is responsible for handling and properly installing the appliance, as specified in this manual and according to the national regulations in force.
ENGINEER: = skilled and trained person authorised directly by manufacturer or TripleAqua distributor in all EC countries, to perform any routine work, service checks, maintenance operations, control and the replacement of pieces, as may be necessary during the life of the unit.
OWNER: the legal representative of the company, body or individual who owns the plant where unit has been installed; having the responsibility of making sure that all the safety regulations specified in this manual are complied with, along with the national laws in force.
OPERATOR: means a person authorised by the owner to do on unit all the regulation and control settings expressly described in the owner’s manual, or this manual, that must be strictly complied with, without exceeding the scope of the tasks entrusted to him or where he is skilled for.
2.3 Safety devices
All units are equipped with internal fuse. See the unit label for the correct type. Never replace a blown fuse before identifying the cause. Only use the same fuse rating. Transformer and fans are internally thermally protected. Refer to the safety instructions for electric heating elements if applied.
2.4 Scope of authorization – safe working
This installation and maintenance manual is for TripleAqua fan coil units, designed for year-round cooling and heating. This manual should be thoroughly reviewed prior to the installation, start-up or main- tenance of the equipment. Keep the manual with care for future information. If any questions arise, please contact your local sales representative or TripleAqua distributor or the factory before proceeding.
The USER and OPERATOR must simply use the controls of the unit; he must not open any panel, other than the filter support panel.
The INSTALLER can work on the external connections between plant and units; and he must not enable any control, unless trained as ENGINEER. All staff working on the unit must follow the precautions listed below:
• Avoid loose clothing or jewellery or any other accessory that may be caught in moving parts
• Always wear suitable personal protective equipment (gloves, glasses, goggles etc.) when you have to work in the presence of the equipment
• Beware of sharp objects and hot or cold surface. Risk of injury
• Only use tools in a good state
• Be sure to have understood the installation and maintenance and warning instructions
• Be sure to have removed all objects, materials and electrical cables before closing and starting the unit again
The installation of TripleAqua components, parts and accessories assembled to a total working installation, shall be in accordance with local regulations of all authorities having jurisdiction and is to be conform to all applicable codes. Only regularly trained and qualified service personnel using safe practices shall install, repair and service this product. Other personnel may perform under surveillance only basic maintenance functions such as cleaning and replacement of air filters.
Always pay good attention to the literature, tags and labels as indicated on the equipment and all other safety precautions that may apply. Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other hazardous conditions which may cause serious personal injury and/ or property damage. Consult a qualified installer, service agency, or your sales representative for information or assistance.
2.5 Limited Access to the unit
Dedicated service panels are provided protecting the internal parts. They are service friendly, easy removable, though only by using with special tools. No access is permitted to OPERATORS.
2.6 Warnings and Precautions against risks
Prevention of mechanical risks
• All coils have sharp edges and are sensitive to bending. do not touch air finned coils rotective gloves
• At all times, periodical maintenance operations must be carried out as is prescribed by this manual
• Before opening any panelling of the unit, make sure the power has been switched off
• The unit shall only be installed according to the instructions provided in this manual
• Do not remove the panels from the fan coil unit(s) while the unit is powered
2 Safety
Prevention of risks caused by the control system
• start the unit only after you have double checked its perfect condition and good connection to the plant
• be sure to have perfectly understood the operating instructions before carrying out any operation on the control panel
• promptly inform the ENGINEER about any alarm involving the unit
• when working on the control panel, keep always the electrical diagrams and controls manual in your neighbourhood
• do not replace fuses unless you have identified and removed their cause
Prevention of electrical risks
• check the proper grounding to earth of the unit before start-up
• Only connect the unit to the correct mains and earth as is written on the unit label
• periodically carry out all checks on the electrical connections and the maintenance operations specified by this manual
• regularly check all connections, the cables, and in particular the insulation; replace if needed
• disconnect the unit from the mains before opening the electrical board
• do not use cables having an inadequate quality or flying connections, even for limited periods of time or in an emergency
• periodically check the unit’s internal wiring
Prevention of other risks
• check properly if the connections to the unit are built conform to the national and manufacturer’s instructions provided in this manual and the material supplied on site
• before restarting the unit, make sure that panels are properly fitted back into position, if you have to disassemble a piece it has been properly mounted again
• remove any leak of fluid inside and outside the unit
• No smoking or open fire in the direct neighbourhood
• Never pressurize equipment above the specified pressures as shown on unit. Always perform a pressure test with an inert fluid such as water or dry nitrogen to avoid possible damage or injury in the event of a leak or a serious component failure during testing.
• do not bend/hit pipes containing fluids under pressure
• weld only empty pipes; do not approach flames or other sources of heat to refrigerant pipes
Maintenance operations are only to be carried out by authorised and trained technicians, certified to these systems.
• place a warning sign “do not turn on - maintenance in progress” on the external disconnecting switch
• disconnect the unit from the mains
• wear suitable personal protective equipment (helmet, safety glasses, safety gloves, goggles and shoes etc.)
• use only original spare parts purchased from manufacturer or the official retailers of the companies on the recommended spare parts list
Sometimes it cannot be avoided to carry out measurements / checks requiring the activation of the machine:
• do not carry out any work in dangerous climatic conditions (open buildings, heavy wind, rain, snow, mist etc.)
• close the electrical box as soon as the measurement or check has been completed
• work with the electrical box open only for the necessary time
2 Safety
3 Transport, storage, handling
and positioning
from the pallet, to be taken directly to its’ assigned space for immediate installation.
It is the sole responsibility of the customer to provide the protection necessary to prevent vandalism and weather deterioration of the equipment. Under no condition should the units be left unprotected from the elements. If the equipment is not needed immediately at the job site, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse.
DO NOT place units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce system performance, reliability and overall life.
The equipment is NOT suitable for outdoor installations. Before installing any of the system components, be sure to examine each pipe, fitting and valve, and remove any dirt or foreign material found in or on these components. Manufacturer’s warranties are void if foreign material is allowed to be deposited in the drain pan, valves, pipework, or on the motor or fan wheels.
3.4 Lifting and Handling
Coils and some parts are sharp. Avoid touching these parts while handling the unit. Large units may be heavy. Move them with two persons.
Although TripleAqua is designed for durability and fabricated with heavy gauge materials and have a robust appearance, care must be taken to assure that no undue force is applied to the casework, coil, piping, drain connection or other components such as control boards during handling. Wherever possible, all units should be handled by the cabinet, or as close as possible to the mounting points. In the case of a fully exposed cabinet unit, the unit must obviously be handled by the exterior casing. Gloves should be worn when handling finished, painted units and should never be set down on unclean, hard surfaces. There is a risk of scratching the painted or finished surface.
3.5 Anchoring and positioning
Anchoring
In all cases, the steel structure of the unit needs anchoring. Suitable holes (4 to 6 pcs) are foreseen at both sides and suitable for this purpose.
Sufficient clearance must be provided for service and removal of the parts. See 5.2 drawings.
3.1 Transportation
TripleAqua units are supplied fully assembled and tested (except for accessories supplied loose). They are ready to be installed, commissioned and operated in the field.
3.2 Storage
If, on site, the unit must be stored out of operation, before commissioning, the installer is to follow the following precautions to prevent frost, damage, corrosion and/ or deterioration:
• Keep the unit packed in the box as long as possible
• Check if all openings, such as for electrics and water connections, are plugged and sealed.
• Never store the unit where temperature may rise above 50 °C
• Minimum storage temperature is -25 °C, only if the unit is properly drained, no water inside
• It is recommended to leave the finned coils covered with the transportation cover to protect them against any risk of damage which is likely to occur on construction sites.
• Never use steam to clean the unit.
• Check the unit on a regular basis for visual damage
• Remove the tools required to access all the panels and secure them well on site.
3.3 Receiving and Inspecting
Directly upon receipt, the INSTALLER shall immediately inspect the unit for any damage since it has been delivered ex works and transported at the customer’s risk. Also, check if all the goods and parts have arrived as specified on the delivery note. Check all goods carefully. Damage should be reported immediately (within 4 hours) in writing to the carrier and the distributor. Even if the damage is only on the surface or box, please notify the local TripleAqua dealer as well.
The manufacturer disclaims all responsibility for the shipment even if it has organized the transport.
All units are carefully inspected at the factory throughout the entire fabrication and assembly processes. All components such as motors, coils, controls, valve packages and more, are carefully tested for proper operation, visually inspected and verified for full compliance with factory standards. Operational testing for all components has been performed.
Units are usually shipped on pallets of up to 5 units. Single units are packed in boxes. Each unit is factory tagged according to the label. This allows the unit, upon removal
Filters can be removed from the back or bottom on horizontal mounted units and from the front on vertically mounted units. Do not handle unit by coil- or piping connections as damage may occur. Anchoring the equipment in place is accomplished by using the mounting points provided, and positioning the unit on a LEVEL horizontal plane. The positioning is correct if the drain pan is pitched horizontally to provide proper drainage when the unit is installed level.
Units can be installed horizontally and vertically.
Units are designed to be bolted to the wall structure through the slotted wall mounting holes in the chassis, used for anchoring to pre-installed studs.
Fixing is provided with the identical mounting slots in the top panels with hanging rod and field supplied rubber-in­shear insulators. They can be used for proper suspension and vibration isolation only in very critical applications. The type of mounting device is a matter of choice, however the mounting point should always be at the 4 to 6 points of the cabinet.
Check that your lifting equipment can safely support the unit assembly and component weights. See technical data for unit weights.
All supports must be designed to meet applicable local codes and ordinances. All fastening devices must be designed to mechanically lock the assembly in place without the capability of loosening or breaking away due to system operation and vibration.
After mounting the unit, it is ready for the connections such as water, drain and electrical.
3.6 About the Installation Site
When installing the unit, make sure that the
building structure and/or the supporting surface
can withstand the weight of the device. The weights of the units are detailed in the technical data.
These units have been designed to be installed on the floor, a wall or a ceiling. Normally rubber vibration damping supports and internal flexible pipe work are not required.
When the unit is to be installed on the ground, provide for a concrete supporting plate which shall assure a uniform distribution of the weights. A special subbase / feet is generally required. When selecting the installation site, follow these guidelines:
• The unit must not be installed in the proximity of open fire or greasy environments: the discharge of boiler flue gases.
• The unit is installed level on an even surface
• The unit is not allowed to be installed near sources of contaminated air, like chimneys or exhaust pipes and the outlets of large-kitchen extractors. Grease might build up on the fins of air exchangers and filter.
• Although the unit is extremely silent, the valves actuators and fan(s) may generate a few dB(A) more sound than the background noise level. In very sensitive situations, please insulate the unit acoustically in the most beneficial way.
• Contact an acoustical engineer for obtaining the most beneficial acoustical results.
• The total experienced sound pressure level in a room is greatly affected by the room merits.
• Never install in areas exposed to flooding or beneath drip stones, etc.
• The installation site is suitable for the space required for air circulation and for the performance of maintenance operations
3 Transport, storage, handling
and positioning
4 Unit structure
4.1 Basic unit Fan Coil
1 Air inlet (return) 2 Replaceable air filter(s) 3 Ultra efficient EC fan(s) 4 Electro- and controls cabinet 5 Mini-pipe TripleAqua heat exchanger 6 Warm water inlet 7 Return water outlet 8 Cold water inlet 9 Cold valve and actuator 10 Warm valve and actuator 11 Filter box latch for filter removal 12 Air outlet (discharge) 13 3PL.. Plenum box (separate supply) 14 Condensate drain pan
4
10
13
12
5
1
2
3
9
8
7
6
11
14
10
4 Unit structure
4.2 Drain pan
The condensate drip tray and the external connection are made of full stainless steel AISI 304 with outer insulation against condensation. In case of cleaning service, the drip tray is easy to remove. Due to a POSITIVE discharge pressure in the drain tray section, condensate water is additionally driven away into the drain pipe. This positive pressure reassures that condensate water cannot be staggered or sucked inside the drain tray. Also, the positive Pressure in the drain tray makes it almost impossible that odours of the drain system can enter the TripleAqua unit. This design is more costly, but avoiding contamination, cleaning, complicated service and hygienic issues in the life time of the system matter too. Equipped as standard with close cellular expanded synthetic insulation. The connection from the condensate tray to the external pipework is by a strong ½”BSP thread. This solid connection avoids any leaks.
11
4.3 Ultra efficient EU5 / M5 air filter
Clean air means healthy air! The most important merit of indoor air quality is the cleanliness. Air contamination consist of small particles that may reduce the well­being and health of humans. Unlike other dx-units and fan coils, this is why the TripleAqua is equipped with special (M5 to EN779) ultra-efficient micro-filtration cassettes filters, able to filter out these particles, polls and fine dust even as small as 5μ. (0.005mm) throughout the filter’s lifetime ensuring you clean air! Close pleats ensure lowest energy consumption, an excessive large filter area and high efficien­cy and life span.
IMPORTANT
Only the original filters will fit and may be used.
Filters cannot be cleaned.
Filter material is enclosed by a stong, water-resistant ABS casing.
It is made of recyclable synthetic material.
Filters must be replaced by original TripleAqua spare parts. Other types are not allowed.
Used filters shall be disposed according to local regulations, not in unsorted municipal waste.
Filter replacement interval : The average usable time is 6 to 12 months. However, if the white colour of the filter turns dark, please replace.
The filter use is always counted and checked by the controller, both in terms of running hours as well as air volume filtered. When the FI:LT sign is shown shortly, it is a pre-warning as it is about time to schedule a filter change soon. Meanwhile, the unit may operate normally. Due to the extended 60mm thickness, long life and convenient service intervals are possible. The filters can be replaced without any tools. Clips on both side of the unit casing provide easy replacement, even in tight surroundings. Filters come in four standard TripleAqua sizes, suitable to service all models, limiting the number of service components. If the filter warning is ignored, FI:LT is to be shown permanent and the unit capacity is reduced significantly, also internal contamination will occur.
4 Unit structure
Clean air lter
Used air lter
12
4 Unit structure
4.4 EC-fan
The Motor-Ventilator is a double suction, dynamically balanced radial forward curved with direct driven controls. Only available with the most efficient EC Motors, mainte­nance free bearings for long life. Unlike other fans using plastics, our motor, the casing and the fan wheel is fully made of strong metal parts. EC-Ventilators can operate step­less with intelligent electronics at the lowest possible speed. It makes them up to 75% more economic than AC fans. Ultra low speeds are the best choice in silent applications such as hotels. Unit may operate even lower than the human ear threshold value!
A remarkable feature is the intelligent Motor management. Within the operational range and external pressure, the air volume of the fan is kept constant, regardless the change of external pressure or operating condition. The fan just maintains the air volume as demanded by the 0-10 V signal! This is an important move towards full thermal control of the unit output.
An internal thermal overload protection is as standard. These fans set the new standard in modern fan coil applications!
As a standard, these radial ultra-low noise and low speed EC fan(s) with extra-large wheel diameter (146mm) and forward bended shaped blades in full metal. The fans are double balanced and coupled directly to a very energy efficient DC single phase electric rotor motor with internal thermal protection incorporated in version IP 44. Fans are housed in a metal scroll casing, aerodynamically shaped to increase aerodynamic efficiency and minimize noise levels. The fans are produced in best European factories. The efficiency is by far exceeding criteria as set in the ErP2015 directive: Even at full power, the fan(s) used in the TripleAqua consume less than 0,095kW!
Not sensitive to external pressure
Unlike other radial fans, the TripleAqua fans have full internal compensation for change of external pressure, reassuring the air volume delivered at the desired level as given by the 0-10V controls. This feature enables the system to keep the heat transfer performance independent of external variations, such as filter contamination, external pressure and unforeseen conditions. Having total control over the air volume delivered is an essential to guarantee the performance of the indoor unit in terms of capacity and return temperature.
4.5 Room controller
Mostly, in a room, Room Controller(s) (RC) shall be mounted. The wired RC model is known as 3RC866.
In large (open plan) rooms, more RC of this type may be present. It facilitates the controls and the room temperature is measured at more locations. Maximum 6 RC can be connected to the local bus. Each RC has a local temperature sensor. TripleAqua calculates the average temperature of all sensors, which will become the average room temperature.
Consumption: 7mA Max. 0.31 VA Internal sensor: 5 .. 40 °C Quick Time constant: 15 s Protection class: IP30 (to EN60529) Weight: 108 g Color: RAL 9003 Signal White Dimensions: 120.0 mm x 85.9 mm
13
4 Unit structure
1000
203
203
200
Supply air outlet
Return Air inlet
- Fits on discharge and suction
- Plenums are thermally and acoustically insulated
We strongly recommend to use all discharge spigots.
Diameter 200 mm O.D.
4.6 Optional Plenum (separate supplied)
3PL11 3PL15 3PL20 3PL25 3PL32 3PL40 3PL50
14
4 Unit structure
3PL11 for 3FS11
3PL15 for 3FS15
3PL20 for 3FS20
3PL25 for 3FS25
3PL32 for 3FS32
3PL40 for 3FS40
3PL50 for 3FS50 & 3FS60
15
INDOOR UNIT
3FS11 3FS15 3FS20 3FS25 3FS32 3FS40 3FS50 3FS60
A
530 680 830 1130 1280 1430 1580 1580
B
634 783 933 1233 1383 1533 1683 1683
C
505 655 805 1105 1255 1405 1555 1555
217
591
1
2
3
AIR INLET
AIR OUTLET
7
8
LEFT VERSION IS SHOWN
AIR INLET
AIR OUTLET
BACK VIEW
TOP VIEW
FRONT VIEW
TOP VIEW
WARM INLET 15mm Cu
1. RETURN 15mm Cu
2. COLD INLET 15mm Cu - INSULATED
3. AIR INLET
4. FILTER SECTION
5. AIR OUTLET
6. ELECTRICAL BOX
7. CONDENSATE 1/2``BSP O.D. thread
8.
64
BACK VIEW
5 Unit details
5.1 Dimensional drawings
AIR INLET
AIR OUTLET
BACK VIEW
TOP VIEW
AIR INLET
AIR OUTLET
7
8
LEFT VERSION IS SHOWN
AIR INLET
AIR OUTLET
BACK VIEW
TOP VIEW
FRONT VIEW
TOP VIEW
16
B
FRONT VIEW
595
217
181
CONDENSATE 1/2" BSP O.D
233
C
A
FIXING POINTSM8
UNIT 3FS
ELECTRICAL BOX
TOP VIEW
5 Unit details
17
5 Unit details
5.2 Space requirements
For proper operation and maintenance access, a free area around the unit has to be observed. Do not place any objects in this area. The area is intended for free air inlet and access to all internal parts of the unit. In the unlikely event of a se­rious defect, large components such as air heat exchangers, compressors or similar, need space to be able to replace.
220 mm 220 mm
250 mm
Unit
250 mm
18
5 Unit details
5.3 Technical specifications
TECHNICAL DATA INDOOR UNITS SERIES 3FS
Silent series
MODEL 3FS 11 3FS 15 3FS 20 3FS 25 3FS 32 3FS 40 3FS 50 3FS 60
Capacity heating & cooling
1,1 1,5 2,0 2,5 3,2 4,0 5,0 5,8 kW
AIR
Lowest speed ECO
90 120 160 100 125 115 135 160 m3/h
Low speed LOW 90 120 160 200 250 340 400 480 m3/h
Nominal & high speed HIGH 220 310 400 500 630 830 1000 1180 m3/h
Boost peak BOOST 270 370 460 600 760 960 1200 1330 m3/h
SIZE
Length
mm
Height mm
Width 634 783 933 1233 1383 1533 1683 1683 mm
Fixing width 505 655 805 1105 1255 1405 1555 1555 mm
FILTER
Class
EN 779
Depth x Height mm
Filter width 475 625 775 1075 1225 1375 1525 1525 mm
FAN
Scrolls / motors
#
Type
Nom external pressure
Pa
Max external pressure Pa
Motor rating kW
WATER
dT
8 8 8 8 8 9 9 9 K
Valves preset 83 115 81 95 80 90 105 120 %
Valves type Danfoss
Waterflow max. 0,035 0,048 0,062 0,073 0,100 0,113 0,132 0,150 l/s
COIL
Tube diameter
mm
Water dP max 12 9 15 12 13 17 10 12 kPa
Air dP nom 15 15 16 13 15 19 32 33 Pa
Coil rows #
Max pressure bar
External connections Cu
Condensate O.D. AISI 304
SOUND
LOW
28,1 29,7 32,5 27,2 31,1 31,4 33,9 36,5 dB(A)
HIGH 43,1 45,7 46,5 46,2 49,9 47,5 49,8 51,3 dB(A) ECO 14 19 16 11 14 15 18 20 dB(A) LOW 14 19 16 13 16 19 22 25 dB(A) HIGH 29 32 33 33 35 35 37 38 dB(A)
ELECTRICAL
Eco mode
5 6 5 4 5 5 6 7 W
Min speed 5 6 5 8 9 15 17 22 W Nom @ 50 Pa 28 33 38 46 56 82 110 146 W Max @ 100 Pa 46 58 66 81 89 138 190 235 W
Supply V
WEIGHT 23 27 31 37 42 48 54 54 kg
OPTIONS
SUPPLY / RETURN PLENUM(S)
3PL11 3PL15 3PL20 3PL25 3PL32 3PL40 3PL50 3PL50
Spigots 1 2 2 3 4 4 5 5 #
Diameter mm
Air/spigot/grille 220 155 200 167 158 208 200 236 m3/h
issued : jan 2016
198
100
1/2" BSP O.D.
10
3/8"
7
DN10LF DN15LF
230 - 1f - 50Hz
Lp pressure ducted @ 1m
radiated ducted
3 x 15mm O.D.
50
DN15
4
595
217
Lw power ducted casing
free radiated
0,095
M5 / EU5
60 x 178
EC brushless inverter centrifugal direct driven - auto adjustment to any ext. pressure
123
19
5 Unit details
Controller dimensions
5.4 Water side pressure loss
Note: the minimum pressure difference Δpmin for proper linear operation of a control valve is 16 kPa. You must add this valve pressure difference to the coil pressure difference to obtain the unit pressure difference.
20
5 Unit details
5.5 Corrections for glycol
All components placed outside in the central unit, are protected against frost by applying insulation, frost resistant materials and additional tracing on the heat exchangers. As option, tracing on piping is available. Tanks and piping are frost resistant. Pipe material is even resistant to fracture up to temperatures as low as minus 30 degrees. Water as a transport medium will be suitable, generally in all European applications. However, the use of ethylene glycol is a recommendation in case of very cold Nordic climate operation (i.e. Scandinavia) as frost inside the hydraulic unit components is likely to occur in the hydraulic system at a winter stop due to power break down. The addition of ethylene glycol will change the thermal and physical properties of the water in a negative way and thus will consequently reduce the unit performances. In case glycol is to be used, please order the Nordic option N. The Nordic option has lower pressure drop on the condenser and stronger circulation pump to partially compensate the performance loss.
The glycol percentage to be used can be obtained from the lowest operation conditions foreseen and found in the table below. Also the multipliers are shown to obtain the changes of the unit per­formances according to the added percentages of ethylene glycol.
% glycol in weight 20 25 30 35 40
Freezing temperature °C -10 -13 -16 -20 -25 cf G 1,04 1,064 1,08 1,116 1,153 cf w 1,184 1,237 1,316 1,421 1,5 cf Q 0,982 0,978 0,974 0,97 0,965 cf P 0,989 0,987 0,985 0,983 0,982
cf G = correction factor indicating the increase of the glycol&water flow to be circulated cf w = correction factor indicating the increase of the pressure drops through the condensor, evaporator and other components cf Q = correction factor indicating the decrease of the cooling / heating capacity fc P = correction factor indicating the decrease of the total absorbed power consumption
Note: The units equipped with option N (Nordic) are mostly compensated for glycol losses thanks to over-dimensioned condenser and circulation pump with added power and head. See option specs.
Check the table above to check the considerable differences between glycol and normal water, regarding to performance, pressure drop and volume flow.
When choosing ethylene glycol (e.g. Antifrogen N) or propylene glycol (e.g. Antifrogen L), it should be considered that the physical properties of ethylene glycol offer more benefits for the design and energy consumption of the system.
• However, Propylene glycol, which is food safe, must be used where the heat transfer medium could come into contact with drinking water and/or food.
• The minimum proportion of ethylene glycol is 20% by volume and for propylene glycol, 25% by volume. This is essential as lower concentration leads to poor corrosion protection, it even could contribute to corrosion.
21
6 Installation
The cold valves and piping should be kept thoroughly insulated.
Operation on open loop (non closed systems) is not allowed.
Arrange drain points complete with plugs, clocks, etc. in the proximity of the low points of the water lines.
Design the pipework with the minimum possible difference of level. Automatic or manual vents need to be installed inside on the high points of risers and water piping to allow the outlet of the air in the circuit. Due to variations in water temperature, the system is to be kept at the correct pressure by means of an expansion tank or equivalent device.
All the pipework of the cold water piping must be insulated with suitable vapour seal type diffusion proof insulation. Thickness depending on local humidity. Consult your insulation supplier. Insulation is essential to prevent the condensation on the piping itself.
It is also advised to insulate the warm water piping, avoiding transmission losses.
The weight of the water piping and connections must be supported outside by additional brackets, external of the unit. The connections of the unit itself are not able to support any weight and shall not be stressed. It is usually not necessary to put flexible couplings on the water circuit.
A fine filter water, aerator and magnetic filter, although not included in the supply, must always be fitted as part of the plant components. Their installation is mandatory for warranty. See section 6.6
Be very careful when applying water connections to the indoor unit. You must use TWO wrenches
giving force in opposite clock and anti-clock wise directions, to avoid any torque on the unit couplings. If torque is applied, inner piping will be damaged!
Connect the water pipes with the attachments of the unit whose diameters and positions are given in this manual. Select piping at minimum a similar sizing or larger.
6 Installation
Mount the unit using the fixing slots on the unit and M8/10 drop rods or fixing bolts. Attach the insulated ductwork to the spigots on the discharge plenum (if applicable), and on the return plenum (if applicable)
Original TripleAqua 3PL plenums will fit both on the discharge side as well as on the return side.
IMPORTANT Keep in mind that if our standard plenum 3PLxx is not used or if not all the spigots on our standard plenum are connected to ductwork the performance of the unit will be heavily compromised.
Pipework should be sized to keep water velocity from 0.50 (local) ~ to max 1 m/s (main pipes) to minimize water noise and keep water pressure losses low, as this strongly contributes to low pump energy consumption over the life time of the system and to avoid water transportation noise. Indoor units are extremely silent and the EC Pump is designed for maximum energy savings. High water speeds will obstruct these merits considerably.
Pipework should be fit for purpose and equipped with oxygen barrier (plastic piping)
6.1 Hydraulic connections
Before installation, read the safety regulations in force on the site and in particular for this machine, to obtain a safe and exact design and proper installation. We recommend to apply shut-off / interception ball valves in both supply and return piping down and upstream to isolate the unit from the site if needed. A water pressure gauge is suggested at the return filling point to facilitate the operator checking the system water pressure. This supports user routine control and maintenance of the unit.
TripleAqua recommends to install a SpiroCombi on the suction side towards the pump.
Flow switches are part of the internal system and are not required externally.
Install on/off valves (accessory) on the lines at the inlet and outlet of the main branches to be able to shut off pipework sections in case of system layout changes.
Condensate protection for the chilled water valves and piping must be provided by installer.
22
6 Installation
if all the water has been taken out of the coil, in example by applying compressed air.
It is possible to use anti-freezing solutions (ex. Ethylene Glycol) in the appropriate percentage (see chapter)
Even if the system is drained, unit coils may still hold enough water to cause damage when exposed to temperatures below freezing. It is hardly possible to remove all the water by just turning the coil. Some coil sections will remain water inside.
6.5 Cold / warm / return / condensate water connections
All piping should be properly supported. Do not support piping to unit valves or controls. Factory drip pan is pre­installed and suitable for a ½”O.D. BSP connection After the connections are completed, the system should be tested for leaks. The hydronic systems should be tested with water. Test pressure at the outdoor unit must not exceed 6 barg.
Pressure testing should be completed prior to finishing the construction site, tiles structure, carpet, finished floors, painting, caulking, etc.
h min
warm inlet
return
cold inlet
In the event that leaking or defective components are discovered at the unit components, TripleAqua distributor must be notified before any repairs are attempted. All leaks should be repaired before proceeding with the installation.
6.2 Mounting Unit to wall / ceiling
For proper installation and operation, check each of the followings before mounting the units: Allow adequate space for the unit and free area for service clearances.
h min 65 mm
Remove the appliance from the point of installation, drill the holes where marked on the wall and insert the screw anchors. Place the appliance against the wall and fix it by tightening the screws into the anchors. Carry out the water and electrical connections as described in the relevant paragraphs. To replace the housing, proceed according to instructions given below.
6.3 Installation piping
The clearance between drain pan and ceiling should be enough for drain line pitch with a minimum slope of 2/100. Allow sufficient space for lifting ceiling tiles and unit access.
6.4 Frost protection
Danger of freezing:
If the unit and its water connection are subjected to temperature lower than 0°C, some specific items will be essential to avoid icing in the pipework. You need to verify
23
6 Installation
6.6 External Components
6.6.1 Expansion vessel.
The TripleAqua components are not equipped with an expansion vessel. This item is to be added on site in the suction line. Calculate the expansion vessel according to the total system size, with addition to the water volume externally in the central unit(s). Capable to handle the full expansion of the water content over the full temperature range. As a rule of thumb, Expansion vessel size is 2 - 2 ½ % of the total water system volume.
• A membrane expansion tank complete with a safety valve and a drain facility is mandatory. which shall be visible to inspection by the OPERATOR.
The expansion tank shall be dimensioned in such
a way that it can absorb a 2 - 2 ½ % expansion of
the total volume of the water in the plant (exchanger, pipelines, uses and storage tanks, if available). The expansion tank shall never be insulated when the circulating fluid is not flowing through it. To be placed inside near the unit suction.
Care should be taken to assure that no components in the valve package are subjected to a high temperature which can damage seals or other materials. The electric control valves, are provided with a manual opening handle which can be turned. These valves must be placed in the “open” position during all connecting and filling operations.
In accordance with good soldering and brazing practices, welded pipe connections must always be wrapped with a wet rag to dissipate the heat. If the pipe connection is made with a union, the unit side of the connection must be prevented from torque forces causing twisting during tightening to prevent damage to the coil unit tubing.
Over-tightening must be avoided to prevent distorting the piping and components or joints, ultimately causing a leak. All inlet and return connections are marked at the appropriate spots with symbols and sticker / text. After the quality of the pipe work integrity has been established, piping should be insulated in accordance with the project specifications. At all times, the cold inlet needs total insulations avoiding condensation.
It is recommended, avoiding heat losses, to insulate the warm inlet pipe too. This is the choice of the specifier or the installer contractor.
Water Piping material
Piping should have a fit for purpose oxygen barrier layer. Piping can be aluminium, (stainless) steel, copper, ABS, Kryoclim, PE-Xa or PVC, but must comply with local codes and suitable for closed loop water or water-glycol HVAC systems.
24
6 Installation
100000
10000
1000
100
10
1
0,01 0,1 1 10
100
Pressure
Drop
(Pa/m)
Volume
(l/s)
@ watertemperatuur 10°C
0,1 m/s
0,2 m/s
0,3 m/s
0,4 m/s
0,5 m/s
0,7 m/s
1,0 m/s
1,5 m/s
2,0 m/s
2,5 m/s
3,0 m/s
20x2,3
25x2,3
32x2,4
40x3,0
30x3,7
63x4,7
75x5,6
90x6,7
110x8,1
160x14,6
100
Volume
(l/s)
0,1 m/s
0,2 m/s
0,3 m/s
0,4 m/s
0,5 m/s
0,7 m/s
1,0 m/s
1,5 m/s
2,0 m/s
2,5 m/s
3,0 m/s
63x4,7
75x5,6
90x6,7
110x8,1
160x14,6
100
Volume
(l/s)
0,1 m/s
0,2 m/s
0,3 m/s
0,4 m/s
0,5 m/s
0,7 m/s
1,0 m/s
1,5 m/s
2,0 m/s
2,5 m/s
3,0 m/s
75x5,6
90x6,7
110x8,1
160x14,6
100
Volume
(l/s)
0,1 m/s
0,2 m/s
0,3 m/s
0,4 m/s
0,5 m/s
0,7 m/s
1,0 m/s
1,5 m/s
2,0 m/s
2,5 m/s
3,0 m/s
90x6,7
110x8,1
160x14,6
water temperature 10º C
25
6 Installation
6.6.3 Electric Bypass valves
The TripleAqua is a Variable Water Flow system. Due to ever changing demands of the terminal units, water flow in the cold and warm flow of the system may vary at all times between virtually zero and full flow. The outdoor unit will produce warm and/or cold water depending on a range of settings, average ambient temperature, time of day, water flow, set point lines, economic settings and more. In humid, combined with lower ambient temperature conditions, the outdoor air heat exchanger may operate as evaporator and may build up frost. This needs to be defrosted when the amount of frost has exceeded certain limits. The outdoor unit may start a defrosting cycle automatically. In the meantime, it will be likely, indoor terminal units will still be in need of warm water. The thermal buffer in the outdoor unit (optionally equipped with PCM) will reassure the delivery of water during defrost. Heating operation of indoor units is not disrupted.
However, it is not that likely that enough indoor units are requiring cold water too. In order to perform a rapid and efficient defrost cycle, the outdoor unit will activate additionally internal water flow over the internal evaporator. This flow needs to be thermally supported by external water flow over all the three pipe lines. The installer is to place two (normally closed) water valves located as specified, type and Kv value as specified, with significant distance from the main unit. These two valves are activated during defrost only, and will reassure flow in the piping system. As a result, the defrost cycle can be performed and terminated in just a couple of minutes. The two valves are commanded and energized by the central unit. over a 230V command wiring. The table below specifies the valves to be used and the water content to be activated during a defrost cycle in the pipework.
6.6.2 Water Filter
Water filter and deaerator
Air (oxygen) and dirt in system water are causes of disruption. They cause wear, damage to system components, process disruptions or even failure. TripleAqua recommends to install a SpiroCombi deaerator & dirt separator to reduce these risks to a minimum. This device will remove air bubbles very effectively out of the system and has in built filter for dust particles. In addition, a magnet with a smart cleaning tool picks up metal parts before they may enter the EC Pump (having permanent magnets…). The Spiro Combi shall be installed inside the building, centrally in the return pipe work at the suction side of the system.
26
6 Installation
6.8 Ductwork connections
All ductwork and or supply and return grilles should be installed in accordance with the project plans and specifications, and local codes. All supply and return grilles should be provided as recommended in the engineering manual and plenums: use the full number of supplied spigots. Suction noise transmission will be reduced with loose return air grilles located as far as possible from the unit. Alternatively, an acoustical suction duct section will provide attenuation too. See ENGINEERING MANUAL chapter 17.
TripleAqua may provide plenums for return and/or supply air. The original 3PL and 3PD PLENUM models will fit both on return and supply.
NOTE: TripleAqua strongly recommends to use ALL plenum connections. Blocking some off will compromise the unit performance, sound and thermal outputs in a negative way.
Supply connections for 3PL plenums are 203mm ID flexible, thermally and acoustically flexible or solid duct work. Avoid any strong bends or squeezing of duct work as this has a considerable negative impact on noise and pressure drop. Return connections are 203mm ID flexible, (optional acoustical) flexible or solid duct work. Avoid any strong bends or squeezing of duct work as this has a considerable negative impact on noise and pressure drop.
Plenum models are designed to be connected to ductwork with a restricted amount of external static pressure. Consult the fan graphs in the engineering manual for unit external static pressure limitations. Units provided with outside air should have some form of low temperature protection to prevent coil(s) from freezing. This protection may be a low­temperature thermostat to close the outside air damper, a heat reclaim system, a preheat coil to temper the outside air before it reaches the unit, a local damper, or any other protective method, optionally controlled by the unit itself. It should be noted that none of these methods will adequately protect a coil in the event of power failure and frost. The best method of frost protection is to use glycol in the proper percent solution for the coldest expected air temperature.
exceed the external static pressure rating of the unit: see the fan graphs.
6.6.4 Optional Pre-set bypass valves
If the system should operate in extreme low capacity, the compressors will likely not operate and the buffer tanks will take over delivery of warm and/or cold supply water. Likely, water flows will be extremely low or even zero. In this situation, for large systems, it may take more than 10 min before warm or cold water will arrive at a terminal unit, located far away. The installer may choose to install a small bypass to avoid water flow coming to a full standstill, thus increasing time responses to climate requests. However, it should be noted this bypass creates a minor thermal loss.
6.7 Condensate drainage
The drain pan condensate connection is a ½” inch male pipe thread fitting. Elevate the unit so the condensate lines are pitched at least 20 mm per meter. In some cases it may be necessary to insulate the condensate near the unit with insulation to prevent water from condensing on the outside of the pipe. In some climates or locations it may be necessary to protect trap from freezing in the winter. Connect a ½”ID BSP connector over the stainless steel outlet of the drain pan. This should be a mechanical connection that allows easy removal of the drain pan when servicing the condensate piping. Take precautions the connector thread shall not leak by applying a proper seal. Do not torque the connector.
The condensate drain should always be connected and piped to an acceptable drainage disposal point. For proper condensate flow, the drain piping should be sloped at all points away from the unit at the given 20mm per meter. A odor trap must be supplied to ensure proper drainage and odor containment. Condensate drain lines should be at least the same diameter as the drain connection. Provide points to flush and clean the drainage system.
The drain lines should be supported every 1- 1½ m to prevent bends causing staggered drain water. Make sure the drain line is free of kinks and obstructions .
60 mm
30 mm
pitch (2 cm per m)
Typical Condensate Trap
27
6 Installation
6.9 Mounting the remote controller
The TripleAqua remote controller 3RC866 are designed to be fitted on 1.5 m height from the floor, free accessible, not limited or exposed to internal or external heat sources, not on an outside wall.
For large rooms, a max of 6 remote controllers may be connected. This will facilitate the controls and all temperature sensors of these remote controllers will calculate an average room controller temperature together.
Mount the room thermostat(s) at a location where the actual room temperature can be determined correctly. Avoid influences by objects, draft, transmission, radiation, sun light or internal heat sources.
- +
Room temperature sensorAvoid cold drafts in the conduit pipe.
28
7.1 Power supply / Electrical data
Electrical connections may only be carried out by qualified and certified electricians. Before carrying out any electrical work, you must verify that the electricity supply has been switched off. The mains voltage should correspond the unit name plate. Operation outside the unit voltages may result in serious damage and warranty will be void.
An isolator switch or removable power plug / mains socket must be installed according to EU standard EN60947-3/ Likely, more than one unit may be supplied by a given fuse rating. See the unit’s name plates for maximum current and power absorbed.
Electrical connections are to be made to the terminal block inside the electrical control box. Terminals are marked with L, N and PE and color. See wiring scheme.
7 Electrical connections
The unit has an internal primary FUSE F1 (5 x 20mm).
• 3FS Units: Fuse rating 2A SLOW. MAX 8 units to a 13 / 16A external fuse
• 3FD Units: Fuse rating 3A15 SLOW. MAX 4 units to a 13 / 16A external fuse
• Electric Heater: Units with electrical heater have an additional fuse for this purpose only. See name plate.
Do NOT INSTALL any other fuse. Risk of electrical hazard.
29
7.2 Warnings
All field wiring connecting should be in accordance with the national standards and applicable local codes. All unit­mounted components and electrical heater elements, if ordered as a factory option, are factory wired to the control box. Remote-mounted control components are shipped loose for field installation and are to be wired in strict accordance with the wiring diagram and the TripleAqua controls manual.
Connections should be checked prior to start-up to ensure connections have not come loose during shipment or installation, minimizing problems during commissioning.
Check the hydraulic diagram for the indicated bypass valves as required to guarantee proper defrost operation.
Field power supply wiring should be fed through end pocket openings (rubber grummets) in the supplied junction boxes. Any modification of the unit wiring without factory permission will void the warranty TripleAqua assumes no responsibility for any damages and/or injuries from improper field installation and/or wiring.
Field electrical power connections are made in the electrical box, which is mounted to the side of the chassis opposite the primary coil piping connections. Most connections are made by removable Phoenix connectors. Please observe the diagram and the different unique colors of the connections, avoiding mixing of connectors.
Low voltage wires should be brought separate into the box.
NOTE: Wiring coming through the wall should be sealed to stop cold air infiltration through the wall cavity, which could affect Remote Controller sensor operation. Wiring coming through the floor should be sealed too.
7 Electrical connections
The unit serial label attached to the side of the unit indicates the electrical characteristics such as the required supply voltage, motor and optional heater amperage and required circuit amps capacities. The unit wiring diagram as shown in this manual shows all unit basic and general field wiring. The installer is responsible and must be familiar with the wiring diagram before beginning any wiring as the wiring scheme can change at any time.
Electrical shock can cause personal injury or death. When installing or servicing, always shut off main power. Double check if the power is taken off.
The internal fuse can be lifted acting as additional switch.
SD Card slot for software updates
30
7 Electrical connections
7.3 Wiring sizing / Local CE + CE- bus / more room controllers
Connect the RC(s) to the GATE Unit a shown below.
Cable : 2-wire stranded twisted pair (YCYM 2 x 0.8) Wire: Min.0.8mm Max 1.0mm Max. length of local bus: 350 m Wave resistance: 120 Ω @ 100 kHz Line resistance: 20 to 75 Ω / km Capacity: Max 100 pF/m Shielding: Not required / Only to be used if interference is expected. Terminator resistances: Not required.
31
7 Electrical connections
7.4 Wiring diagram
32
7 Electrical connections
33
7 Electrical connections
7.5.1 Detailed optional connections
Input D1 comfort or eco (occupancy / ving)
The input is intended for the following command functions:
( symbol goes from on to off )
• Responding to a VING card operation for Hotels,
• Respond to an Occupancy detector in offices and public rooms
• Respond to external wired command - voltage free input.
The delay time to instruct the controller to switch between Comfort/Day and Night/Eco mode can be programmed by P75. NOTE: ONLY Connect to the GATE D1 input for this function.
If P75 = 0 : This input is not active. Unit may follow clock function. D1 = NO (normally open)
Comfort to Night/Eco is given by the parameter P75. From Night/Eco back to Day/Comfort, no time delay is needed.
If P75 > 0 : D1 => closed : Mode COMFORT => Mode ECO/Night with P75 min time delay D1 => open : Mode Eco/Night => Mode COMFORT with no time delay
If the mode was standby, the mode does not change into Eco.
Input D1 dew point sensor
If P75 = -1 : D1 is meant for dew point sensor: If D1 is closed: cooling valve is closed too.
The dew sensor will interrupt the cooling process until the D1 input is opened again.
7.5.2 Input D2 forced gate / commissioning / self test
Input D2 is used to force the unit in a special setting, to commission the system, purge/flush with water and addressing, select the gate and start auto addressing. See the controls manual for ad­dressing.
Commissioning: Before any commissioning is started, at the factory, D2 is a closed contact, and no GATE or SAT is assigned. When power is applied, after 5 min, a Self-test is completed.
NOW: BOTH WATER VALVES will open and remain open as long as D2 is closed.
This enables the installer to fill the system with water, circulate, flush and vent the system fully with all indoor unit valves open. A relay Q3 will flash slowly to indicate this status. See also Controls ma­nual chapter 7.2 COMMISSIONING.
Normal status for D2 after commissioning completed: open contact. Valves of indoor unit will close.
34
7 Electrical connections
7.5.3 X6 external mode on / off or co2 level input
Input X6 can be used for an external digital input by a switch or relay. It may alter the ON/OFF mode of the unit or operates as a CO2 sensor input.
NOTE: 24V DC is present on the input. The function for X6 is activated by parameter P76:
P76= 1 function is not active @ NO (default value) and is active when X6 is closed P76= 0 function is not active @ NC and is active when X6 is opened. P76 =2 function as an input for a CO2 level detector delivering an 0-10V signal.
External on/off
Set P76 to 0 or 1 The input is intended for an external wired command to change the MODE from On into OFF An active input will force the unit into OFF: (On off symbol goes off ) Can be used for a Fire command or Open window contact If GATE unit on a process bus face a change of mode through the X6 input, the same command is also transferred and obeyed by SATELLITE units. So this switch, contact or detector must only be connected to GATE unit.
CO2 level input
Set P76 to 2. X6 input is able to measure the CO2 level which can be used to adjust a fan or a damper to control the fresh air valve at output Q1. The CO2 set point level to act is pre-set in a P15 parameter. The CO2 level can be read in P45 (Gate only). If the detected value is higher as pre-set, the output is active. The Sensor range of the CO2 level to be connected shall be 0-2000 ppm corresponding to 0-10 Volts.
7.5.4 Output Q1
REMOTE INDICATON - EXT. COMFORT MODE DETECTION / FRESH AIR / CO2 CONTROL
Output Q1 is a voltage free SPDT Change over contact. It can be used to detect if unit is ON in Day-Comfort Mode or to control (open/close) an external open/close servo motor for fresh air and/or return air damper. If a CO2 measurement device is connected, the output can activate the damper only according to CO2 ppm level.
P76=1: Output Q1 is made active and used to report externally if unit is on and in COMFORT MODE.
P76=0: Output Q1 is made active and used to report externally if unit is STANDBY or OFF
35
7 Electrical connections
P76=2: Only to use if Input X6 is used for CO2 measuring. Q1 is only closed if P45 > P15. P45 = measured level of CO2 in ppm P15 = set point level of CO2 in ppm
Note: The CO2 sensor must be calibrated to 0-2000 ppm corresponding to 0-10Volts.
Output Q1 is also permanently activated during the SELF TEST.
Q1 MAX 230V AC @ 2A / 30V DC @ 3A. DO NOT OVERLOAD. NOT FUSED
7.5.5 Output DO2 extra booster fan / louver
Output DO2 is to be used to feed a (not supplied) relay to control an external fan. Note: If an electric heater is present, the common voltage for DO1 and DO2 shall be 24V AC. So a field supplied added RELAY 24VAC must be fitted too. See controls manual. The output is active if the fan signal X5 is above P77-n . (for extra fan)
The output is active for a fan coil louver motor if the fan is on and P77-n = 1. Not active if P77-n = 0.
7.5.6 Output Q3 alarm relay
Output Q3 is a voltage free SPDT NO contact used for reporting an alarm externally. A parameter P59 will define if this output is: not active @ NO and active when NC or reverse active @ NO. The output is active when an alarm is present.
If the alarm is reset, the output is not active. P59 also instructs if filter alarms are included to the alarm output or not. See alarms table. Most alarms are automatic reset, the alarm disappears if the reason is no longer valid.
Alarms for fan(s) and electric heater are manual reset. Alter P01 from 0000 to 0001 to reset these alarms.
Q3 & Q4 MAX 230V AC @ 2A / 30V DC @ 3A. DO NOT OVERLOAD. NOT
FUSED
36
7 Electrical connections
7.5.7 Output Q4 internal or external condensate pump
The output Q4 controls the optional condensate pump using internal air detection sensors.
The unit will set the pump active and will close Q4 when ALL these following conditions are met together:
• P73 > 0
• Unit is operating in cooling, automatic or in dehumidifying mode.
• Unit has been in cooling or cooling request for more than 3 min.
• Unit cold water inlet temperature B2 is below 22 °C
• The outlet air temperature is P73 degrees lower than the return air temperature. When (one of) these conditions are no longer valid, the pump will stop after another 3 min of operation. The pump is allowed to run dry but may consume 16 Watts. See the 3FS controls manual to understand all wiring and addressing details of the local CE+/CE- bus and the BMS Building Management System bus.
7.5.8 HMI - Control Panel
For service, a Human Manual INterface (HMI) Model POL
895.50/STD as shown below can be connected to a GATE unit and is to be used for service purposes. This will give access to parameters P51 and up. Connect the HMI only to the GATE unit T-HI connector.
7.5.9 Modbus / BacNet Building Management
Functions The TripleAqua GATE controller exchanges information with the other local SAT units and Room Controllers through the local CE+/CE- bus that connects them internally in the same room. This information is either sent to or received from the superior BMS system. Therefore the GATE also acts as an interface to this superior system. The fan coil controllers and Room Controllers are for one room. Every GATE unit connects these over the bus to a system with several rooms. Individual room units may send their heating or cooling demands to a primary plant and can receive operating mode, set-points, air- and water temperature status, etc. from a superior controlling system. The Modbus RTU protocol applied is suitable for residential, commercial and light industry environments.
NOTE: Only the GATE unit shall be directly connected to a BMS system over the on board RS485 terminal connection. Other SATELLITE units in the same room communicate their relevant info through the local Process CE bus to and from the GATE unit connected to the BMS. This principle saves a lot of cabling and adresses.
ModBus RTU and limited BacNet MS/TP are on board as standard. For other BMS platforms i.e. LON, M-Bus, KNX, OPC, WebServer, BacNet Ethernet TCP/IP: select the POL
638.00/ STD, POL 636 or POL 908 converters . Ask your local distributor for advice. The GATE receives external commands for MODE, FUNCTION, CLOCK, SETPOINTS, FRESH AIR etc. The GATE sends out status values, sensors, alarms, energy data etc.
See Control Manual - Indoor unit: 6.4 Wiring information.
37
8 Commisioning
8 Commissioning
8.1 Preliminary checks
Never attempt to try to start the system when you have not
studied fully, and understood the operating instructions. You
need to carry out following pre-start checks:
Check the chilled water circulation pumps, circulation
and pressure of units and all other equipment connected
correctly to the system.
Confirm that all pipe securing fixing points are tight.
Check if the electrical connections are completed and
safe.
The start-up of the external heat pump must be executed
by a qualified refrigeration engineer only.
Operating the unit is only possible when a sufficient flow
and thermal load is applied to the system and water is
circulating in the internal water heat exchangers and
external circuit.
All set point adjustments and control tests must be
carried out before the unit is started up.
Ensure that all safety devices are operational and that
no alarms are active.
The unit must be commissioned for the first time by an ENGINEER suitably trained by the TripleAqua distributor. Failure to meet this will immediately void the warranty.
Before the operations will start, hydraulic and electrical works have to be completed by the
INSTALLER. Work carried out by the authorized ENGINEER for com­missioning is limited to the start-up of the unit, and will never include any other installation action or operation on the plant, such as, for example, electrical and hydrau­lic connections etc.
Check that the components of the external water circuit (pump, user equipment, filters, power supply tank and reservoir, if any) have been installed properly, and according to the manufacturer’s instructions.
Check the filling of the hydraulic circuits, and make sure that the fluid circulation is correct, without any trace of leaks and air bubbles. If you use ethylene glycol as antifreeze, check that its percentage is correct (do not exceed 40% glycol percentage).
Check that the pumps have been circulating for at least 12 hours. Then, clean the SpiroCombi and filters on the suction side of the pump(s).
Check the liquid distribution network in such a way that the flow rate is sufficient.
Check that the water quality is up to the specifications.
Check the pump settings.
Check the controls manual for all the user settings, building manager parameter settings and project settings.
Although the units may operate with variable speed con­trol, variable water flow controls and may be overruled by external Building Management Systems, TripleAqua cannot warranty proper operation when in conjunction with any particular external control.
All EC fan-coil motors have internal thermal cutout. The motors will be de-energized if the internal temperature of a motor exceeds a maximum to protect the motors against over-heating and burning out. The auto-reset function will resume the motor operation when the internal temperature of the motor has dropped.
8.2. Venting / Flushing / Pressurize
FILLING
Fill up the system to the calculated hydraulic working pres­sure with clean drinking water according to the VDI2035 (part 2 nr. 4) / EN 12828 standard, optionally added with pre-mixed glycol mixture. The water supply must be analyzed and of appropriate quality, filtered, if needed with water treatment. Otherwise, damage to the control devices, damage to the protection of the tube and heat exchanger surface is likely to occur if the fluid is polluted, fouling and deterioration of the pump fittings will occur too.
Check that all filling valves and vent cocks are closed. Check if the water side safety devices are installed. Check these devices for proper function. Ensure that water flow through the unit is not obstructed, open all corresponding shut off valves!
Never fill up above the maximum allowed pressures
The max. outdoor unit water pressure is 6 barg. If the outdoor unit is at lowest level, this is also the maximum system pressure.
The max. piping system water pressure is depending on the materials used in site.
The max. indoor unit water pressure is 10 barg.
The operational water pressure is depending on system hy­draulic height, usually preferred is 2-4 bars, though pressure should during operation always remain between 1-5 bars. This value may vary per project.
38
8 Commisioning
NOTE: Limited operating pressure water at outdoor unit
Check the pressure in the expansion vessel according to the calculated hydraulic working pressure.
Start and stop the circulation pump with intermediate breaks to collect all the air and vent them off.
NOTE: The pump should not operate when not filled up with water.
Flushing the water system
Flush the system regularly to drain off impurities which may have entered the pipework during installation
Before filling the installation, remove any impurity, such as sand, crushed stones and welding scales, coating drops and any other
material which might damage the evaporator.
It is advisable to flush with disposable water bypassing the exchanger to avoid clogging. Control accurately the absence of leaks during the filling phase. Purge air regularly at all points.
The water used to fill the circuit shall be treated in such as way that the pH will have the correct value.
VENTING
Vent the system on all vents located in the pipe work. Also the outdoor unit has vents on top of both tanks and venting points are located on top of the internal return header pipe as well as two to three venting points in the compartment between the plate heat exchangers and the internal tanks.
WARNING: If the outdoor unit is not properly vented, high pressure problems on the water plate heat exchanger will occur as air in the water condensor cannot escape. Proper venting may take several attempts.
HINT: Venting of the hydraulic system and indoor unit heat exchangers is advised with all indoor units control valves
both fully open, heating and cooling. This is achieved by energizing all indoor units with power whilst input D2 re­mains closed, setting them in commissioning mode.
When water is first introduced into a coil, air is sometimes trapped in the coil tubing. This trapped air has a tendency to collect at the highest point in the coil.
Most models of coils can be vented manually at the return header using a screw driver. Venting can also be carried out according to the procedure in the controls Manual Ind­oor, section 5.1.2. By opening both valves of indoor units mutually, maximum flow inside the small tubes of the coil is generated, thus forcing the air out of the coil pipes into the return. Therefore, a manual air vent procedure is often not required at each coil installed inside on the coil return header. When there remains to be air trapped in the coil, re­sulting in “bubbling” noises within the unit or no water flow, follow the procedure as described to vent the coil according to 5.1.2 and manually vent the coil at the return header.
8.3 Water balancing
TripleAqua does not require water balancing per unit as all flow in operation may vary per second. This will save a considerable amount of time in commissioning. However, at 100% full load, in case all indoor and terminal units are requiring their capacity, the distribution system, piping network and circulation pump setting will benefit a proper pump setting. The pump(s) need to be able to meet this demand. Pump(s) are self-regulating, as well as the valves of the indoor units. In order to adjust and set the maximum pump power/pressure as proper as possible to the water distribution pressure losses and system values, proceed as follow:
Open all valves of terminal units.: Energize and CLOSE IN­PUTS D2 on all indoor units longer than 5 min
The system will set itself to maximum water flow in a few minutes.
Check with an local flow meter, if sufficient water flow is seen at the terminal units as far away as possible, having the highest distribution pipework pressure loss of the system.
You now may want to alter the default PUMP setting (70% / 7 Volt) to meet the required flow. See Controls Manual.
A total knowledge of the hydronic system, including its components and controls, is essential to correct water commissioning of the system and should only be completed by a qualified expert. The system must be complete, and all components must be in operating condition before begin­ning the water commissioning procedures.
39
The actual balancing of any indoor unit is preset by the dials in the control valves on every warm and cold valve kit. See controls document and technical sheet for settings.
It is advised to install ball valves and water flow measuring valves at main sections on both flow and the return pipes in order to shut off sections of the hydraulic system for later changes of the system and local repairs and verifying correct water flow.
Once the proper system operation is established, the defini­te appropriate operating conditions such as flow rates and pressure drops should be recorded for future reference.
During commissioning, poor operating conditions may exist due to incorrect system pressures, resulting in noti­ceable water noise or undesired valve operation or lack of flow. Once the total system is correct, these conditions will not exist on properly designed systems. If any noticeable water noise or undesired valve operation persist, recheck the system for air that may not have been properly vented during start-up.
8.4 Air balancing
In particular if the unit is connected to external grilles, Tri­pleAqua strongly recommend to install the original 3PL and 3PD plenum boxes. Plenums can be installed on the suction and on the discharge side. Please take good notice not to exceed the maximum external pressure drops as is indicated in the technical specs and the fan graphs.
If plenum boxes are used, TripleAqua strongly recommend to use all round spigots. If some spigots are blocked, proper operation and performance cannot be guaranteed.
Especially if the external duct runs are unequal, additional air dampers should be considered at the shortest duct runs.
Suggested external nominal external pressure is 30-50 Pa.
8.5 Equipment start-up checklist
Receiving and inspection
Unit plenums, controllers and structural support is complete and correct
Unit received undamaged (e.g., dents and paint)
Goods have been received complete as ordered
Unit arrangement, models, options and handing is correct
Handling and installation
All electrical service is provided according to the regulations
Mounting grommets/isolators are used if critical installation applies.
Unit mounted level and square (condensate drainage)
All screws are checked
Good access is provided for unit and accessories
A proper condensate trap avoiding odours
Suitable overcurrent external fuse protection is provided
Proper service switch// power plug or means to disconnect is provided
Proper piping of cold and warm and return piping to unit
All services to unit in code compliance
Unit protected from dirt and other objects
Cooling/heating connections
Protect cold valve package components against condensation
Both valve packages are in good order and shape
Connect field piping to unit
Pressure test unit piping for leaks
Pressure test field piping for leaks
Install drain lines and traps, as required
Insulate cold piping, as required and warm piping as preferred
Ductwork connections
Flexible duct connections at unit as smooth as possible
Ducting is not bended obstructing proper air flow
Proper supply and return grille type and size
Control fresh outside air for freeze protection avoiding frost on the coil
Insulate all supply ductwork
Adjust max fan speed setting as required during air system balancing
Unit start-up
Flush water systems
Vent water systems
All isolation valves are open
Check for water leaks
Vent air from coil if needed
All unit panels and filters in place
Check ductwork and units for air leaks
Balance air systems if required
Record final settings for future reference
Check ductwork and piping for any vibration
Check dampers for proper operation
Verify proper cooling operation
Verify proper heating operation
Test the condensate line by adding water into the drain tray
Set unit to desired position for operation
8 Commisioning
40
8.6 Delivery to the customer
If the start-up checklist and commissioning is complete, hand the system over to the customer.
Instruct the customer how to operate the unit.
A USER GUIDE is available for guidance and user control / maintenance.
8 Commisioning
USER GUIDE
MODELS: 3FS11-3PL11 3FS15-3PL15 3FS20-3PL20 3FS25-3PL25 3FS32-3PL32 3FS40-3PL40 3FS50-3PL50 3FS60-3PL60



CLIMATE System Short User Guide
Button
On / Off
Energy setting : Present / Absent
Setting of time and date
Adjust required temperature steps 0,5°C / 1°F for heating and cooling
Con rm your settings
Adjust the fan speed
low medium high automatic
Adjust the mode
Function
– +
Only cooling
Only heating
Automatic cooling / heating
Dehumidi cation
Fan only
Your TripleAqua climate system is a very economic and ecient system. It delivers heat, cooling, ltration and de-humidication in the most sustainable way. Warm and cold energy is reclaimed all over the building and stored for reuse later. Using this controller, you can adjust your personal climate to your own wishes.
HINT: Please avoid cooling/heating having windows / doors open. In summer, do not cool down more than a few °C below outdoor temperature.
By a week clock, using button or by Building Management System, following energy modes can be selected.
= Stand-by
= Economy/night
= Comfort/day
For a more detailed user description, please refer to User Guide.
CLIMATE System Short User Guide
Room temperature or the set temperature.
Actual time, set time or display of alarms.
Manually setting of the fan speed . Usually, an automatic setting is preferred.
7 days of the week: 1 = Monday
The system is performing a heating or a cooling operation.
Alarm indication. Please report the code A_ _ _ to the building manager.
Allowed range for cooling / heating is preset by building manager.
FunctionSymbol
F I L T
If shown shortly : Replace the air  lters soon If shown permanent : Air  lters must be renewed now !
The  lters are extremely e cient. They even  lter out  ne dust and polls. It is important to keep  lters in a very good shape and to apply only the original TripleAqua air  lters in order to reassure clean air quality. Filters cannot be cleaned. They must be replaced. Please dispose dirty  lters according to the local regulations.
Night setting – The temperature is reduced by i.e. 2°C.
Usually, automatic change-over from cooling to heating vice versa brings the best possible comfort. Under some circumstances, no heating or cooling may be available by the central source: See below:
n o H E n o C O
P - -
At the moment, no heating is available. No malfunction.
At the moment, no cooling is available. No malfunction.
Mode for the technician.
Service mode.
Temperature Range
Further explanation symbols on screen
8000002001-Triple Aqua FS short user guide V1.0 UK
A SHORT USER GUIDE is available for day to day instructions in the local language.
41
Two separate controls manuals are available for the ENGI­NEER to document all functionality on all levels, settings, parameters, Building Management System, wiring and more.



Controls
manual
MODELS 3CA22 3CA65 3CA127 3CA32 3CA83 3CA147 3CA45 3CA97 3CA169 3CA53 3CA113 3CA203
Central Air-
Sourced Liquid Chiller & Heat Pump
9 Controls

Controls manual – Indoor unit
3FS and 3FD Fan Coil Series
MODELS 3FS11 3FS32 3FD63 3FS15 3FS40 3FD80 3FS20 3FS50 3FD100 3FS25 3FS60 3FD125
42
Maintenance Contract
TripleAqua recommends a maintenance contract with your local service agent which provides regular maintenance of your installation by a specialist trained in servicing your equipment.
Regular maintenance ensures that problems are avoided and minimizes the possibility that malfunctions will occur. It also ensures the maximum operating life and efficiency of your equipment.
10.1 General requirements
Each indoor unit may have its own unique operating environment and conditions which indicates a maintenance schedule that may differ from other equipment on the project. A maintenance schedule and an individual unit log should be maintained. This schedule will help maximize the performance and service life of each unit.
The air filter(s) is the main and only maintenance replacement item. In addition, cleaning and checking is needed. All fans and valve actuators have permanently lubricated bearings so no further field lubrication is ever required. Do not lubricate fans or motors.
If the motor/blower assembly ever may require more extensive service, only decide to replace the fan with an original spare part.
10.2 Planned maintenance
Service panels are provided to allow access.
Check fan wheel. Dirt and dust should not be allowed to accumulate on the fan wheel or housing. Failure to keep this part of the unit tidy may result in an unbalanced wheel condition which can lead to a damaged fan wheel or motor. The fan wheel and housing may be cleaned periodically using a brush and vacuum cleaner, taking care not to bend the fan blades and to remove any factory applied balancing weights on the blower wheel blades.
Tighten any set screws that may have loosened due to vibration. Any blower or motor that is not properly maintained will not be covered under the manufacturer’s warranty.
The air filter needs regular replacement. See 10.4 The controller counts the filter usage in running hours and air quantity filtered. If a filter needs replacement, the remote controller will show a warning.
The TripleAqua fan coil has an ultra-efficient air filter, cleaning the air of dust and pollution. It is able to filter out micro particles and polls as small as 5μ (0.005mm)!
The filter use is counted by the controller. When the FI:LT sign is shown shortly, it is a warning as it is time to schedule a filter change soon. Meanwhile, the unit may operate normally. Replace the filter soon by a fresh and original TripleAqua filter to guarantee clean air. The filters cannot be cleaned. It is made of recyclable material. Dispose the filter according to local regulations. If the filter warning is ignored, FI:LT is to be shown permanent and the unit capacity is reduced significant.
After a preset number of revolutions in P41, the unit send out a filter replacement request pre-warning text to the RC. On the time line the text F I : L T will appear shortly every 5 second but the unit(s) will continue to operate normally. Filter warning can be reset by the building manager in parameter P 40 and by pressing for more than 10 sec.
NOTE Once the filter has been replaced, do not forget to reset the filter counter.
Press for more than 10 sec.
10 Maintenance
43
10.3 Filter replacement
Filters must be properly maintained and replaced in order to ensure proper air cleaning efficiency. Dirty filters will reduce the air volume handled by the unit, thus adversely affecting its performance. The length of time between cleaning of filters is dependent upon the environment. A 6 to 12 month interval cycle is normal, different servicing may be required in some cases. Record the time interval in the maintenance log for future reference. Only original TripleAqua M5 filters in replaceable casing are to be used and are fitted as standard and can be replaced by gently removing the clamps on both side of the unit.
1. Turn off the electrical power source. Allow the fan wheel to stop.
2. Loosen two clamps at the rear of return filter section as shown below:
3. Pull out the filter-frame(s)
4. Follow the opposite procedure to re-install the filter and frame.
5. Re-connect the electrical power source. In case of a Return plemum box, this box needs to be removed first. The return plenum box can be removed from the unit casing by unscrewing the plenum box. CAUTION: Due to the dimensions and weights of the return plenum, at least two installers are recommended to do this step for safety.
10.4 Additional maintenance
Brush the finned surface with a soft brush, brushing parallel to the fins, taking care not to bend the fins. Brushing should be followed by a vacuum cleaner. Compressed air can also be used by blowing air through the coil fins from the leaving air side, again followed by vacuuming. If fins are damaged, a fin comb can be used to straighten the fins. For a deeper cleaning, i.e. when unpleasant odors or similar appear, spray the finned surface of the coil with a neutral
cleaning solution and rinse thoroughly. Do not use strong acids and strong base cleaners. Strong alkali cleaners containing sodium, potassium or ammonium hydroxide are not recommended as they corrode aluminum tubes and fins. Strong ammonium hydroxide cleaners will cause stress corrosion cracking of tubes. Cleaners may decompose over time producing organic acids that lead to corrosion. Failure to maintain a clean coil will result in reduced airflow, performance and increased power consumption. Check the coil at every inspection and clean when needed.
10.5 Water treatment
Proper water treatment is a specialized industry and therefore it is recommended to consult an expert in this field to analyze the water for compliance with the water quality parameters and to specify the appropriate water treatment program. The expert may recommend rust inhibitors, scaling preventative, antimicrobial growth agents or algae preventatives. Anti-freeze (glycols) may also be used to lower the freezing point. All TripleAqua coils are constructed of copper tubes and headers and brass and bronze alloys are present in the valve packages. It is the end user’s responsibility to ensure that any of the water delivery components are compatible with the treated water. Failure to provide proper water quality will void the fan coil unit’s warranty. See also section 12 of the engineering manual. Water quality should meet the VDI2035 to obtain the full product warranty.
10.6 Drain pan cleaning
The drain pan is made of stainless steel. It may be required to clean the drain pan. The drain pan can be cleaned with non-aggressive cleaning products. Replace the drain pan as original.
Loosen the connecting screws at both sides of the unit and disconnect the drain connection.
10 Maintenance
44
11.1 Exploded view
Replacement parts
Factory replacement parts should be used wherever possible to maintain unit performance, Replacement parts may be purchased through the local Sales Representative. Contact the local Sales representative or factory before attempting any unit modifications. When ordering parts, the following information should be supplied to ensure proper part identifica­tion which can be found on the unit label:
• Complete unit model number
• Unit serial number
• Complete part description including any numbers on the part
On warranty replacements, it is necessary to return the faulty component to receive credit. Contact the local Sales Representative who will get authorization from the factory Filters come in four sizes, quantity of each is depending on the 3FS or 3FD model
11 Service
45
11.2 Service parts
1 Valves Type depending on model, see technical spec
2 Actuators Danfoss AME110 NL
3 Fan EC Rosenberg N43-A3-1
4 Controllers Siemens Climatix Model POL425.50/STD.
5 Coils Type depending on model, see technical spec
6 Transformer Siemens SEM62.1
7 Sensors NG6PTC TPR 2M TTO2-10KC8-2D
8 Fuse Type depending on model, see technical spec
9 Filter Type depending on model, see technical spec
10 Drain pan Type depending on model
Accessoires
• Condensate pump
• E-Heater Type depending on model, see technical spec
11 Service
46
All equipment is sold pursuant to its standard terms and conditions of sale of TripleAqua, including Limited Product Warranty. Consult your local representative for warranty details. To find your local representative, go to www.tri­pleaqua.com (dealers)
The following misuses or maltreatment of equipment will render all guarantees, as set out, to void.
Damage caused to equipment on site through lack of protection from the elements or misuse by others.
Attempting to operate equipment with an electrical supply other than that designed on the equipment data label, or failing to connect and protect such equipment in accordance with national regulations and local laws.
Failure to notify damaged goods on receipt within 4 hours and confirming in writing.
Modification to units, arrangement or performance without prior written approval.
Failure to install, to set up or to put to work any part of the equipment in line with and as specified in this Installation and Maintenance Manual.
Failure to observe all accepted installation and engineering practices during installation, commissioning and subsequent operation of equipment.
The product supplied are subject to TripleAqua Terms and Conditions of Sale, a copy of which is available on request. If anything set out in these installation, operation and main­tenance instructions conflicts with the terms and conditions then the terms and conditions will apply.
12 Warranty
47
During the draining of the circuits, do not
let glycols overflow in the surrounding
atmosphere. The circuit must be drained using suitable recovery equipment.
For the disposal, contact the competent authority for information.
Unless otherwise specified, the maintenance operations listed below may be carried out by any trained maintenance operator.
Open each line that supplies the unit, including the ones of control circuits. Make sure that all disconnecting switches are secured in the off position. The power cables can be disconnected and disassembled. Refer to Chapter 4 for the position of connection points. Remove all the refrigerant from the refrigeration circuits of the unit and store it in suitable containers, using a recovery unit suitable for flammable refrigerants. If its characteristics have remained the same, the refrigerant can be used again. Contact the competent authority to obtain information about disposal. The oil in each refrigeration circuit must be drained and collected into a suitable container; then it shall be disposes of in conformity with local regulations that apply to the disposal of waste lubricants. Any oil spillage must be recovered and disposed of in like manner.
Isolate the unit’s heat exchangers from the external hydraulic circuits and drain the heat exchange sections of the plant.
If no shutoff valves have been provided, it
may be necessary to drain the whole plant.
If a glycol solution or a similar fluid has been
used in the hydraulic circuits, or if chemical additives have been added to the circulating water, the circulating fluid MUST be drained in a proper way. For NO reason shall a circuit containing glycoled water or a similar solution be discharged directly into the drains or surface waters.
After draining operations, the piping of the hydraulic networks can be disconnected and disassembled. Once they have been disconnected as specified, the packaged units can be disassembled in a single piece. First of all, disassemble the anchoring screws and then lift the unit from the position of installation, and hook it to the lifting points provided, using suitable lifting equipment. To this end, refer to Chapter 4 for the installation of these appliances, to Chapter 9 for their weights and Chapter 3 for handling. The units that, once disconnected, cannot be removed in a single piece, must be dismantled on site; in this case, be very careful with the weight and handling of every single component.
It is always advisable to dismantle the units following the installation steps, but in reverse.
Some residues of oil, glycoled water or similar
solutions may remain in certain parts of the unit. These residues must be recovered and
disposed of according to the procedures specified above.
It is very important to ensure that, while a component of the unit is being removed, all the others are properly supported.
Use only lifting means of adequate capacity.
Once disassembled, the components of the unit can be disposed of in conformity with current regulations.
Your unit was designed to be environment friendly. TripleAqua has complied with the standards for environmental-friendly disposal. This means that you have to dispose of your fan coil unit in accordance with legislation. By ensuring this product is disposed correctly, you help to prevent potential negative consequences for the environment and human health and to recycle internal components and materials.
Your unit is categorized as an electrical and electronic product. It is marked with the symbol illustrated. This symbol means that your unit should be recycled and not disposed of in unsorted municipal waste.
13 Dismantling and scrapping
48
Notes
49
Store
Cool
Heat
For more information,
visit www.tripleaqua.com
Installer / Distributor
8000012001 Triple Aqua CA model A installation/maintenance man. V1.0 UK
Loading...