Trion Herrmidifier Herrtronic 6000 Series Installation, Operation & Maintenance Manual

Page 1
READ AND SAVE THESE INSTRUCTIONS
Herrtronic® 6000 Series
Electrode Steam Humidiers
TRION® | www.trioniaq.com
Page 2
Installation, Operation, & Maintenance Manual
TABLE OF CONTENTS
SECTION I WARRANTY
Preface ...........................................................................................................................................................3
SECTION II UNIT OPERATION
Basic Operation .............................................................................................................................................. 4
Key Features .................................................................................................................................................. 5
Engineering & Application............................................................................................................................... 6
SECTION III INSTALLATION INSTRUCTIONS
Mounting ......................................................................................................................................................... 6
Plumbing.........................................................................................................................................................7
Steam Distribution .......................................................................................................................................... 7
Wiring .............................................................................................................................................................7
Supply Power .................................................................................................................................................7
Control Circuit Connections ............................................................................................................................ 8
SECTION IV OPERATING INSTRUCTIONS
Start-up Instructions .......................................................................................................................................8
Checklist ......................................................................................................................................................... 9
Maintenance ................................................................................................................................................... 10
SECTION V TROUBLESHOOTING GUIDE
Board Test Points ........................................................................................................................................... 11
Unit Detected Faults: (Red Service Light On) ................................................................................................12
Non-fault Activated Problems ......................................................................................................................... 13
Wiring Diagram ............................................................................................................................................... 15
Exploded View ................................................................................................................................................ 16
Parts List.........................................................................................................................................................17
2 www.trioniaq.com
Herrtronic® Model 6000
Page 3
Installation, Operation, & Maintenance Manual
SECTION I WARRANTY
Warranty
1. TRION/HERRMIDIFIER warrants to the buyer or any user during the duration of the Warranty that the
humidier described in this manual will be free from
defects of material and workmanship for a period of two (2) years from the date of shipment.
2. For this Warranty to be effective, this humidier must be installed, operated and maintained in accordance with the Installation Instructions, Operations and
Maintenance Manual(s) supplied with the humidier.
3. In the event of a defect or malfunction in this product during the Warranty Period, user may contact the Customer Service Department or their TRION/HERRMIDIFIER Representative for a Customer Relations Management (CRM) number. Items tagged (on the outside of the box) with this number may be returned to TRION/ HERRMIDIFIER for replacement. Incidental expenses
such as cost of transporting the humidier to TRION/
HERRMIDIFIER or labor associated with removal/ replacement of the parts shall be paid by the user. Upon
completion of the reconditioning, the humidier will be
returned at no cost to the user. Items returned without a CRM number will not be accepted!
4. Every 6000 series steam generating humidier contains a plastic steam generating cylinder which is to be considered a routinely disposable part to be changed at regular maintenance intervals at the user’s expense. This steam generating cylinder is not covered by this
Warranty. If, after the installation of your 6000 humidier,
you feel the steam generating cylinder is not operating normally, you should contact TRION/HERRMIDIFIER with an explanation of the problem. However, in the
continuing operation of the humidier, replacements
of this part are your responsibility as part of routine maintenance.
5. This Warranty does not cover eld labor for repairs to this humidier or any special, indirect or consequential damages. Some states do not allow
the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
6. If, after a reasonable number of attempts to do so, TRION/HERRMIDIFIER is unable to remedy any
defects or malfunctions in this humidier, then the user
may elect either a replacement of such product or part which may be defective without charge or a refund of the buyer’s original purchase price.
7. This Warranty gives you specic legal rights, and you
may also have other rights which vary from state to state.
NOTE
Water quality plays a vital role in the performance and maintenance requirement of any humidier. Adjust- ments to the circuit board may be necessary based on the incoming water quality. See pages: 11-14.
Performance problems associated with water quality are not warranty issues!
Herrtronic® Model 6000
www.trioniaq.com
3
Page 4
SECTION II UNIT OPERATION
Water Level
Output
Basic Operation
Installation, Operation, & Maintenance Manual
Controlled humidication requires a very precise control
system. The 6000 utilizes a solid state control to monitor
performance and maintain humidity. The humidier evaluates
the operation and alerts the operator to problem conditions and prevents undesirable operation.
On initial start-up or a call for humidity, the humidier will attempt to ll to its full load amp rating. The unit will not
necessarily have a full cylinder of water. Water level depends on the conductivity of the water. The more conductive the water, the more current that can be passed through the same volume of water.
If the water is not conductive enough to allow the unit
to reach full load amps (full capacity) on the initial ll, the
cylinder full light will indicate a full cylinder condition. The
unit will operate in this mode with repetitive ll and boil cycles
until the unit has concentrated enough minerals in the water to reach the rated amp level.
Once full load amp (FLA) has been reached, the ll valve will
shut off. The unit will now compare the rate of change of amp draw to a time cycle.
If the water in the cylinder is mineral laden and hence very conductive, a drain cycle will be initiated.
After the drain cycle and/or the time cycle is completed, the
unit will rell and start the process over.
These cycles will repeat until:
•The call for humidity is satised.
•The cylinder is used up.
•A fault condition occurs.
On initial start-up, if the water is not conductive enough for
the unit to reach FLA, the water will stop lling when the
water reaches the cylinder full electrode. Once the unit has
entered a cylinder full condition it will operate with ll and
boil cycles only. By eliminating the drain cycle, the water conductivity will be increased by producing pure steam and leaving the minerals behind. The increased mineral levels
will raise the conductivity allowing the humidier to draw sufcient amperage to achieve FLA. Normal operation will
then commence.
As the electrodes in the cylinder are coated with minerals, the water level will slowly increase to the cylinder full level. Concentration of coating on electrodes will no longer allow the unit to reach FLA. After a period of time, the unit will display the red “Service” light indicating the need to change the cylinder.
High Drain
Threshold
Capacity Set Point
Low Drain Threshold
Cylinder
Full
1. 2.
General Time of Operation
3.
Steadily Increase
Water Level
4 www.trioniaq.com
Herrtronic® Model 6000
Page 5
Key Features
Installation, Operation, & Maintenance Manual
Adjustable Setpoints (See Figure 7, Page 11)
Capacity
• Range = 50-100%
• Preset at 100% for 6000-1
• Preset at 50% for 6000-2
Low Drain Threshold
• Range = 50-100%
• Preset at 90%
Cycle Time
• Range = 30-180 seconds
• Preset at 60 seconds
ADJUSTABLE LOUVER
Faults:
Overcurrent
• 138% of Rated Current
• System Shutdown
Fill System
• Fill valve open for 6 hours without achieving capacity setpoint or cylinder full
• System Shutdown
End of Cylinder Life
• 6 hours of operation while on cylinder full without achieving capacity setpoint.
• System Shutdown
Operation using water of less than 100 micromho is not recommended.
Typically 500-2000 hours of cylinder operation can
be obtained. Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.
INTEGRAL, QUIET OPERATING FAN
"CYLINDER FULL" ELECTRODE (RED WIRE)
CYLINDER - REPLACEABLE GLASS FILLED POLYPROPYLENE
DRAIN SYSTEM (SEALED DRAIN VALVE, ADJUSTABLE DRAIN THRESHOLD AND CYCLE TIME PROVIDE EXTENDED LIFE.)
HERRMIDIFIER
FILL SYSTEM (INTEGRAL 1" AIR GAP PREVENTS REVERSE SIPHONING TO POTABLE WATER SUPPLY; "ADJUSTABLE METERING VALVE ACCOMODATES WATER PRESSURES UP TO 100 PSI."
INTERNAL CIRCUIT BREAKER
INTEGRAL HUMIDISTAT
ISOLATED CONTROL COMPARTMENT WITH SOLID STATE CONTROLS
POWER, CYLINDER FULL, AND SERVICE INDICATOR LIGHTS
ON/OFF/DRAIN SWITCH
COVER INTERLOCK SWITCH (PREVENTS UNIT OPERATION WITH COVER OFF)
CONCEALED FILL AND DRAIN CONNECTIONS
Herrtronic® Model 6000
www.trioniaq.com
5
Page 6
Installation, Operation, & Maintenance Manual
Note: Duct liner may be used with a maximum thickness of 1".
5 FEET MINIMUM
5 FEET MINIMUM
Engineering and Application
The Herrtronic 6000 Series Steam Humidiers can be applied in
a variety of applications. The simplest application is to utilize the model with the built-in blower package. The steam generated by the unit is distributed into the conditioned space by the built-in blower package (Figure 1).
18 INCHES MINIMUM
5 FEET MINIMUM
SECTION III INSTALLATION INSTRUCTIONS
Mounting
The cabinet is designed to safely contain the working components
of the Herrtronic 6000 series humidier and dissipate heat to protect the electronics. Locate humidier in a manner to allow
routine inspection and any necessary maintenance. DO NOT install the unit above false ceilings or around valuable property, where a malfunction could cause damage. Correct positioning of
the humidier is important to allow for proper operation and easy
maintenance. Minimum clearance around the cabinet should be maintained as follows:
Minimum Clearances
Around Cabinet
Left 6”
Right 12”
Top 18”
Bottom 12”
Remove foam packing from top of cylinder. Four lag bolts, (2) 5/16” and (2) 1/4”, are supplied with the 6000 unit. Install the top two lag bolts (5/16”) according to the dimensions in Figure
2. Hang the unit on the wall, and then install the bottom two lag bolts (1/4”) and secure all four bolts. Be sure the unit is level and mounted directly to the wall to wood studs at least 2” thick (or equivalent). Operating weight: 35 lbs.
Figure 1
Allowable Operating Conditions:
Ambient Temperature: 40°F (4°C) to 120°F (50°C) Ambient Relative Humidity: 0% to 90% (non-condensing) Line Voltage: -15% to +10% of Nominal Frequency: 50/60 HZ. Water Supply Pressure: 20 psi – 100 psi.
1"
Back View
16 1/2"
1 1/2"
5/16" DIA.
4 1/4"
5/16 x 5/8 DIA. KEYHOLE MOUNTING SLOT
1/2"
9"
Figure 2
WARNING!
Do not mount any controls inside the unit or tap power from any location in the unit, except as stated in these instructions. Do not place objects near the cabinet. Do not attach to dry wall without studs. At least one 5/16” and one 1/4” lag bolt must be located on a stud.
6 www.trioniaq.com
Herrtronic® Model 6000
Page 7
Installation, Operation, & Maintenance Manual
Plumbing
To make the necessary connections for water ll and drain, the
following steps are required: (refer to Figure 3 for locations)
1. Install external shutoff valve between the water supply and
the humidier for ease in servicing the unit.
2. Connect water supply to the 1/4’ compression tting on the bottom of the cabinet.
CAUTION!
Do not use reverse osmosis or demineralized water treatment without rst consulting the factory. This water may not be sufciently conductive to allow proper operation. Consult factory if water is outside the range of allowable conductivities. Do not use hot water.
3. Connect the 3/4” tube from the accessory pack to the drain reservoir. Cut the tube to the length necessary to reach the drain.
4. Insert the other end of the tube into a minimum 6” vertical length of the 1-1/4” minimum I.D. drain line. The balance of the drain line should be 1” I.D. minimum with a minimum 1/8” per foot slope. (See Figure 3.)
WARNING!
If the drain line is exposed, it is recommended that it be insulated for safety. Do not use PVC drain line unless “Drain Tempering” is enabled.
NOTE: Inlet water pressure must be in the range of 20-100 psig. Consult the factory if you are outside this range. Softened water may be used but requires that the low drain threshold be adjusted. Drain water can be tempered to lower its temperature.
Steam Distribution
The 6000 Series Steam Humidier with the built-in blower pack
should be mounted a minimum of 18” from the ceiling. There should also be 5 feet of horizontal clearance in front of the unit to prevent steam from condensing on obstructions (See Figure
1). There is an adjustable louver to adjust the direction of the steam plume.
WARNING! Do not adjust this louver to extreme angles as it will restrict the airow causing condensation to form around the steam distribution manifold.
WARNING! Locate away from areas where people can walk into the
steam path.
Wiring
All eld wiring should be routed up through the knockout in the
bottom panel or in the back of the unit.
7/8" KNOCKOUT
2" KNOCKOUT
1 1/2"
BOTTOM VIEW
1"
1 3/8"
3 3/4"
FIgure 4
DRAIN RESERVOIR
1/4" O.D. COPPER OR POLY TUBE WATER FILL LINE
BOTTOM COVER
Figure 3
Herrtronic® Model 6000
DRAIN LINE TO BE 1" MIN. I.D. TERMINATING AT THE UNIT WITH 6" OF 1 1/4" I.D. VERTICAL PLUMBING.
THIS ALLOWS AN AIR GAP BETWEEN THE 1" O.D. DRAIN TUBE FROM THE UNIT AND THE DRAIN.
UNIT HOUSING
FILL CONNECTION
3/4" I.D./1" MAX. O.D. FLEXIBLE DRAIN HOSE
1 1/4" I.D. COPPER OR PVC DRAIN PIPE
1" I.D. COPPER OR PVC DRAIN PIPE
Supply Power
1. Ensure that minimum circuit ampacity is 15 amps.
2. Terminals are provided in the electrical compartment for
eld connection of the main power supply legs (single
phase) and a ground wire.
3. Install external overcurrent protection and provide wiring in accordance with the NEC, state and local codes.
4. Power supply must be “clean”: free of spikes, surges and sags: -15% to +10% of nominal.
Electrical Characteristics
Capacity Steam Output
Lbs. / hr 4 8
Kg / hr 1.8 3.6
Input KW
1.33 2.66
Volts/Ph: Amps
120/1 11.8 N/A
230/1 5.9 11.8
www.trioniaq.com
7
Page 8
Installation, Operation, & Maintenance Manual
Control Circuit Connections
WARNING!
Do not install any controls inside the Herrtronic 6000 cabinet. Installations of any extraneous devices inside the electrical compartment may cause erratic behavior of the circuitry and will VOID the warranty.
The 6000 units with built-in blowers require no external control wiring since the humidistat is built-in.
SECTION IV OPERATING INSTRUCTIONS
Start-up Instructions
1. Check that the humidier is properly mounted and level.
2. Check that the water ll and drain are properly connected.
3. Check that the correct voltage and amperage service are supplied.
4. With power off, double check all electrical connections and plumbing connections to ensure that they did not loosen during shipment.
5. With the “on-off-drain” switch in the “off” position, and the control humidistat at its lowest setting, turn on the main disconnect. The contactor should remain deenergized and the power light should remain “off”. Place the “on-off­drain” switch in the “on” position and the power light should illuminate.
6. Turn the control humidistat up to its highest setting. The contactor should pull in.
7. After approximately a 5 second delay, the ll valve energizes
and water begins to ll the cylinder to the preset amp level
or cylinder full condition, depending on the incoming water supply. When starting up the unit, it is best to put an amp clamp on the power leg that passes through the toroid
transformer. Ensure that the humidier lls to “cylinder full”
(approximately 1.5” from the top of the cylinder), or that
the amperage reaches the data plate maximum and the ll
valve de-energizes.
8. All units are equipped with a drain tempering feature which
mixes cold ll water with the hot drain water to protect drain piping. Depending on your ll water pressure, some adjustment of the ll metering valve may be necessary to
ensure drain water of less than 140°F. (See Figure 5.) To deactivate, remove diode from socket CRI8 from circuit board. (See Figure 7.)
9. Reset control humidistat to its desired settings. Typical control humidistat settings are 30-40%.
NOTE:
The capacity of the humidier can be adjusted between 50% and 100% of the maximum level by adjusting the capacity adjustment potentiometer (labeled R39) on the main circuit board. All units are set from the factory to produce 4 lbs/hr. If the psychrometric conditions permit, the 6000—2 may be increased to 8 lbs/hr by adjusting R39 from 50% to 100% capacity. Refer to Figure 7.
CAUTION!
Inadequate airow may allow humidity to collect in areas causing condensation.
RELAY
FILL VALVE
CYLINDER FULL INTERFACE
L2
L1
TERMINAL BLOCK
TRANSFORMER
MOUNTING SCREWS
FILL VALVE ADJUSTING SCREW
NOTE:
If upon initial start-up of this humidier the cylinder is slow in heating and/or the service light continues to come on, drain the cylinder to 1/4 full. Turn off power at break­er, obtain some Alka-Seltzer tablets and crumble 1/2 of one tablet (Alka-Seltzer) into the grey ll tee. Change the middle blue dial on the left side of the circuit board, R18, from 90% to 87%. Then turn the breaker on and run the unit. If you have had to use these this step on a 240V unit (6000-2,4), it is advisable that you order a GT-176-1 re­placement cylinder rather than the standard replacement cylinder in the future so this procedure will not need to be repeated. Upon receipt of the GT-176-1 cylinder, adjust the dial, R18, on the circuit board back to 90%.
8 www.trioniaq.com
VIEW IN FROM RIGHTSIDE OF UNIT
Figure 5
Herrtronic® Model 6000
Page 9
Installation, Operation, & Maintenance Manual
MAKE SURE LOUVER IS ADJUSTED TO PREVENT STEAM FROM CONDENSING ON COVER.
MAKE SURE ALL HIGH VOLTAGE ELECTRICAL CONNECTIONS ON STEAM CYLINDER ARE TIGHT.
MAKE SURE ALL HIGH VOLTAGE ELECTRICAL CONNECTIONS ARE TIGHT, 15-20 IN-LBS.
Installation Checklist
FILL VALVE
POWER SUPPLY:
1. MATCHES DATA PLATE
2. IS PROPERLY GROUNDED
3. CAN CARRY AT LEAST 15 AMPS
4. EXTERNAL FUSED DISCONNECT PROVIDED BY OTHERS.
3/4" MIN. I.D./ 1" MAX. O.D. FLEXIBLE DRAIN CONNECTION
DRAIN RESERVOIR
DURING FILL CYCLE, CHECK TO SEE IF ANY WATER IS DRAINING FROM UNIT. A LOT OF WATER FLOWING OUT OF THE UNIT WOULD INDICATE EXCESSIVE WATER PRESSURE. TURN OFF POWER AND REDUCE THROUGH METERING FILL SOLENOID OR SUPPLY VALVE TO HUMIDIFIER. A SMALL AMOUNT OF WATER IS NOT UNCOMMON.
6" MIN. LENGTH OF 1 1/4" MIN. I.D. VERTICAL COPPER LINE. IF PVC IS USED, ADD DRAIN TEMPERING.
BALANCE OF DRAIN LINE TO BE 1" MIN. I.D.
DRAIN WATER TEMPERATURE IS SUITABLE FOR PLUMBING.
NOTE:
The Herrtronic 6000 Humidier checklist is provided to help the installer ensure a successful installation. If further assis­tance is needed from the TRION/HERRMIDIFIER representative or the factory, the checklist is expected to be completed. If a job site visit is required from the TRION/HERRMIDIFIER representative or the factory, and the checklist has not been ac­curately completed, additional charges may be applied by the individual(s) representing TRION/HERRMIDIFIER. If the visit uncovers a component malfunction, the parts will be replaced under warranty.
_____________________________________________ ____________________________________________ Project Name Checklist completed by
_____________________________________________ ____________________________________________
Humidier Installer (Company) Checklist completion date
Herrtronic® Model 6000
www.trioniaq.com
9
Page 10
Installation, Operation, & Maintenance Manual
Maintenance
To maintain output, the water level in the cylinder will slowly move upwards, exposing new electrode to the water as the electrodes become coated with minerals. Eventually, all of the usable electrode surfaces will be coated and the cylinder will be full of water. At this point, the output will begin to drop and the red “service” light will come on. The unit will shutdown. This indicates the need to change the cylinder, typically 500-2000 hours of
operation, depending on the quality of the ll water supply.
To replace the cylinder
1. Drain cylinder completely using the ‘on-off- drain” switch.
2. Turn off power to the unit at the external disconnect. Disconnect electrode power wires (#38 & #39) and cylinder full electrode wire (#29) from the cylinder. These connections are 1/4” quick connects. (See Figure 6B, 6C, & 6D.)
3. Disconnect 1” hose at top of cylinder.
4. Remove cylinder, clean out the drain cup and insert the new
cylinder. Be sure that “o” ring is in place on the cylinder ll/
drain port prior to installation. (See Figure 6A.) New o-ring is included with each replacement cylinder.
5. Clean and check both the ll and drain valves while servicing
the unit.
6. Check the strainer. If it is dirty or restricting the water­replace it.
7. Install cylinder in unit by pushing downward with a slight twisting motion, while ensuring proper orientation of cylinder within cabinet.
8. Reconnect electrode power wires (#38 & #39) and cylinder full electrode, wire (#29). Make sure that all electrical connections are securely tightened. (See Figures 6B, 6C, & 6D.)
9. Follow cold start-up instructions on page 8. Monitor amp draw for several cycles. .
Extended Shutdown
Always drain cylinder completely if unit will be off for an extended period of time. This will preserve the life of the cylinder.
CYLINDER FILL/DRAIN PORT
EST-1060-3 O-RING
Figure 6A
CYLINDER FULL ELECTRODE CONNECTION
PROTECTIVE BOOT
(SHOWN TRANSPARENT FOR CLARITY)
POWER WIRE CONNECTIONS
CYLINDER FULL ELECTRODE WIRE #29
POWER WIRE #38
ELECTRODE CONNECTION
PROTECTIVE BOOT
(SHOWN TRANSPARENT FOR CLARITY)
Figure 6B
POWER WIRE #39
RED POWER WIRE
1/4" MALE QUICK CONNECT
Figure 6C
10 www.trioniaq.com
1/4"-20 NUT
1/4" LOCK WASHER
GROMMET
BLACK POWER WIRE
1/4" MALE QUICK CONNECT
1/4"-20 NUT
1/4" LOCK WASHER
Figure 6D
Herrtronic® Model 6000
Page 11
Installation, Operation, & Maintenance Manual
SECTION V TROUBLESHOOTING GUIDE
All Herrtronic 6000 Series Humidiers are manufactured under
strict quality control and are subjected to a complete operational test before shipment. All circuit board adjustments are made at the factory and should not be adjusted beyond the guidelines
set in this troubleshooting guide without rst consulting a factory
representative. The following information is for your help and
reference. If you still experience difculty after trying these
remedies, contact your TRION/HERRMIDIFIER representative.
WARNING!
The Herrtronic 6000 Series Electronic Steam Humidier cabinet was designed to house and shield the components from outside interference. Absolutely NO other components may be mounted inside or be electrically tapped into the humidier without TRION/ HERRMIDIFIER’s express written permission. Failure to heed this warning will void your warranty.
TEST POINTS
Each circuit board (See Figure 7) features three test points to aid in the troubleshooting process. Each of these test points works on a 0-4 VDC scale. “0 VDC” = 0%. “4 VDC” = 100%. All readings are between the test point and ground (Molex J1, terminal 11 [far right of molex connector, wire #11).
Test Point #1:
Provides exact reading of drain threshold setting.
Test Point #2:
Provides circuit board reference voltage. Should always
read 4 VDC +/-2%. Test Point #3: Provides actual percentage of output. For example, a unit running at 80% of maximum output would have a Test Point #3 to ground reading of 3.2 VDC.
Maximum Capacity Setpoint
The potentiometer labeled “R39” located in the top left-hand corner of the board allows adjustment of the unit’s capacity in the range of 50-100% of maximum.
Circuit Board Settings
Models Time Cycle
R23
Low Drain Setting, R18
Capacity, R39
Standard Settings
All 60 sec 90% at 3.6V 100% at 4V
High Conductivity Settings (> 1000 micromho)
All 84 sec 93% at 3.72V 90% at 3.6V
Softened Water Settings (750-1000 micromho)
All 60 sec 92% at 3.68V 95% at 3.8V
Low Conductivity Settings (<100 micromho)
All 60 sec 85% at 3.4V 100% at 4V
Capacity adjustment R39
Test point #3
(Output capacity)
R4 Capacity
resistor socket
Low drain threshold R18 (50-100%)
Test point #1
(Drain threshold reading)
(Equilibrium voltage reading)
Test point #2
Cycle timer R23 (30-180%)
copyright 1986 HERRMIDIFIER CO, INC.
CAP ADJ
TP3
PROP DISPLAY
%
TP1
R18
TP2
SEC R23
CR17 LED - overamp condition indicator if illuminated
CR17
CR18
R4
J1
J1 Connector
CR18 diode drain tempering socket
Herrtronic® Model 6000
Figure 7
www.trioniaq.com
11
Page 12
Installation, Operation, & Maintenance Manual
Unit Detected Faults: (Red Service Light is ON)
Problem / Symptom Probable Cause Reason - Correction
Overcurrent
The alarm condition occurs when an overcurrent situation (>138% of rated
current) has occurred and the humidier
has shut down to prevent any damage. This alarm indicates that there has been a signicant reduction in resistance be­tween the main legs of the supply power
and the humidier has been shut down to
prevent damage and should be serviced before it is restarted. Overcurrent LED CR 17 (Figure 7) is illuminated.
End of Cylinder
This alarm condition occurs if the humidi-
er is unable to reach full output over a 6
hour timeframe. It is constantly switching
between “ll” and “cylinder full” modes.
This alarm indicates a need to change the cylinder, that the water supply is low in conductivity, or that a foaming condi­tion exists:
Fill System Fault
This alarm condition occurs when the ll
valve has been energized for a 6 hour
timeframe. The humidier has been
shutdown to prevent any damage.
Dead short between electrodes. Replace the steam cylinder. Check re-
sistance between electrodes with power “off”
Restricted or blocked drain. Clean and inspect drain system.
Restricted ll system Clean and inspect the ll system. Check
for restriction or loss of supply pressure.
Incoming water conductivity is outside the range of normal circuit board settings.
Check amp draw to unit during start-up. If amp draw greatly exceeds rated amp draw, the drain threshold pot, labeled “% adj.” (R18), must be increased 2% to increase the frequency and duration of drains to reduce the conductivity inside the cylinder.
End of cylinder life – Cylinder life is typically between 500 and 2000 hours, depending on incoming water supply.
If incoming water supply is less than 100 micromho, the unit may not be able to pass the rated current through the water.
Foaming condition exists. Flush and ll the steam cylinder several
Loss of or restricted water supply Check ll system.
Leaking drain system. Check drain system.
Defective drain valve. Repair and replace as required.
Defective ll valve. Repair and replace as required.
Consult the factory for options.
Manually drain the unit and restart.
For emergency use, you may restart the
humidier with the capacity setpoint,
R39, at a lower level to allow operation until a replacement steam cylinder can be obtained. To clear the fault, turn the main disconnect to the unit “off” and then back “on”.
See – NON-FAULT ACTIVATED PROB-
LEMS GUIDE – “Unit lls to the cylinder
full condition and remains cold”
times and restart. If it persists, you must
lter or treat the water to remove the
foaming agent. See circuit board settings on previous page if supply water is soft­ened. See NON – FAULT ACTIVATED PROBLEMS GUIDE – “Water foaming inside the cylinder”
NOTE: The three fault conditions outlined above will cause the humidier to shut down and the service light on the front of the unit to illuminate. To clear these faults, the main power must be turned “off” and back “on” again.
12 www.trioniaq.com
Herrtronic® Model 6000
Page 13
Installation, Operation, & Maintenance Manual
Non-Fault Activated Problems:
Problem / Symptom Reason - Correction
24 VAC circuit breaker trips as soon as power switch is turned “on”.
24 VAC circuit breaker trips after the unit is turned on for about 15 seconds.
24 VAC Circuit breaker trips when­ever the drain valve activates
Humidier turned on but will not
operate. Power lamp is “off”.
Unit turned “on”. Contactor pulled in, but no water is entering the cylinder.
Excessive arcing in cylinder Check drain valve and ensure that when it activates it drains freely. Clean if necessary.
Unit lls to the cylinder full condi­tion and remains cold.
Unit turned on and cycles for a short period of time. Then it stops
in the middle of a ll cycle and
won’t reset until boiling stops.
Check the wiring at the 24 VAC breaker for a short or loose connection.
Disconnect the contactor coil from the circuit and repeat. If 24 volt breaker doesn’t blow, replace the contactor.
Replace the main circuit board.
Disconnect ll valve from electrical circuit. If circuit breaker doesn’t trip, replace the ll
valve.
Replace the main circuit board
Disconnect drain valve from electrical circuit. If circuit breaker doesn’t trip, replace the drain valve.
Remove the drain valve and ensure that it is clean and free of any obstructing mineral deposits.
Replace the main circuit board.
Check power supply.
Check circuit breaker.
Check connector J1 on the circuit board and ensure that it is plugged into the circuit board properly and that no wires are loose.
Ensure that there is 24 VAC between pole #9 and #11 connector J1. If not, check wiring.
Check door interlock.
Check external shutoff valves and open if closed.
Check strainer and ll valve for clogs. Turn adjusting screw (Figure 5, page 8).
Check ll valve coil to determine if it is receiving 24 VAC. If so, replace the valve.
Check for break in wiring.
Replace valve if defective.
Check water supply. If it is softened, increase the drain threshold pot, “% adj.” (R18), up to 92% at 3.68VDC. (See Figure 7, page 11.)
Use high conductivity settings if water supply is very hard, >750 micromho.
Unit lling slower or at the same rate as the water is boiling, causing over concentration and foaming. Check restriction in ll line. Adjust the metering ll valve to allow greater ow of
water. (See Figure 5.)
Have water analyzed. If iron content is greater than .1 mg/liter, a lter will have to be used.
Consult factory with water analysis
Check between Test Point #3 and ground with a multimeter set on VDC scale. Conrm the circuit board is seeing low current ow (<2.8 VDC). Proceed to next step.
If on initial ll, unit reaches less than 70% of rated capacity (2.8 VDC on Test Point #3),
adjust the drain threshold pot, “% adj.” (R18), down 2-3%. Manually drain the unit down
completely and add ½ Alka Seltzer tablet via the ll tee(GT-120). Restart the unit while
monitoring the amp draw. Fill unit ¼ full and turn “off” for several minutes to allow tablets to dissolve. Restart unit. If amperage rises rapidly, it may be necessary to dilute the water. If amperage rises slowly, add another Alka-Seltzer tablet.
Check that drain valve is sealing properly.
Check the water conductivity and consult the factory.
Check cylinder ll interface connections.
Check cylinder connections. (See Figures 6A-6D, page 10.)
Check items in next troubleshooting tip concerning foaming.
Check amperage between cylinder full electrode and cylinder full interface terminal #1. If it
is greater than 7.0 mA AC, take a ll water sample and consult the factory.
Herrtronic® Model 6000
www.trioniaq.com
13
Page 14
Installation, Operation, & Maintenance Manual
Problem/Symptom Reason - Correction
Water “foaming” inside the cylin­der.
Cylinder lls and overows Check cylinder wiring. (See Figures 6A-6D, page 10.)
Unit turned on, lls to full amp draw, stops lling, and after a
delay, the circuit breaker trips and the service light comes on.
Unit cycle “on” and “off” rapidly Check location and setting of high limit humidistat
Cabinet leaks Check for loose connections
Check drain valve and ensure that water drains freely. If necessary, clean or replace valve if defective.
Check water supply. If it is commercially softened, either increase the drain threshold (R18) to 92% or reconnect the unit to raw water. Drain and restart the unit. If the unit is connect­ed to a hot water line, reconnect to the cold water line. (3.68VDC)
If steam line is hard copper, drain cylinder and test unit operation disconnected from steam
line to ensure ux from solder joints is not causing foaming.
Observe the ll tee(GT-120). If water is going down the overow and the water level is low: Check to ensure that static pressure in the duct is not forcing water down the overow
instead of allowing water to enter the cylinder.
Adjust the ll metering valve to regulate the water ow to the cylinder. (Figure 5.) Unit lling slower or at the same rate as it is boiling off, causing over concentration and
foaming. Fill rate must be increased. Open metering valve.
If the ll valve is already fully open, get a water analysis and consult the factory.
Check wiring of cylinder full interface.
If more than 1.9 mA AC is passing between the cylinder full electrode and interface termi­nal #1, and when placing multimeter between terminal #3 and ground yields approximately negative 11 VDC, replace the interface.
Replace the circuit board.
Consult the factory after obtaining a water analysis
Use the “On-Off Drain” switch to drain the cylinder. Turn the capacity adjustment pot(R39)
on the main circuit board to 80% and restart the humidier. (3.2VDC)
Check the drain valve and clean or replace if necessary.
If the drain valve doesn’t come on before the service light illuminates, replace the main circuit board.
Fill tube out of ll tee
Steam cylinder out of drain cup
Cabinet drain backing up, kink in drain line
14 www.trioniaq.com
Herrtronic® Model 6000
Page 15
Installation, Operation, & Maintenance Manual
POWER
TERMINAL BLOCK
POWER INPUT (120 VAC FOR 6000-1 AND 6000-3)
BLK
16
2A BREAKER
BLK
23
(24 VAC)
HUMIDISTAT
DOOR
RED
27
BLUE
28
INTERLOCK
BLUE
BLK
24
10
RED
25
BLK
ORG
SWITCH
1
3
2
4
5
6
BLK
ORG
9
5
15
12
87
16 PIN DIP PLUG
WIRING DIAGRAM
POWER
CYLINDER
FULL IND.
237
53
27
RED
2
8
9
RELAY/TIMER
BLK
BLK
30
34
15
BLK
WHT
22
(24 RET)
WHT
BLK
16
19
20
WHT
CYLINDER FULL
INTERFACE
2
BLK
35
1
RED
29
3
ORG
3
8
BLK
4
OHM
RED
BLK
14
RED
WHT
20
LIGHT
RED
25
18
WHT
FILL
VALVE
WHT
WHT
6
22
21
WHT
SERVICE
LIGHT
17
WHT
RED
WHT
11
7
DRAIN
VALVE
ORG
12
TRANSFORMER
BLK
31
L2
L1
(240 VAC FOR 6000-2 AND 6000-4)
GND
11
J1
WHT
BLK
BLK
BLK
RED
WHT
ORG
ORG
RED
RED
11
10
9
8
765
MOLEX
4
3
2
1
CYLINDER
FULL
BLK
BLK
(240V)
(240V)
40
BLK (120V)
32
32
(120V)
BLK
32
(240V)
BLK
BLK
31
32
33
BLK
35
BLK
GRN
GROUNDED
TO CHASSIS
ELECTRODE
19
WHT
BLK
13
BLK
13
BLK
BLK
36
34
BLK
37
RELAY
WHT
BLK
BLK
18
38
39
BLK
30
FAN
RED
RED
TOROID
POWER ELECTRODES
10
9
8
7
6
5
3
2
1
Herrtronic® Model 6000
www.trioniaq.com
15
Page 16
Installation, Operation, & Maintenance Manual
CYLINDER ASSEMBLY
EST-1405
EST-1409
EST-1517-1 (120V)
121800-004
EST-1518-1 (240V)
EST-1514
EST-1409
EST-1512
EST-1530
EST-003PA
EST-105A
EST-207
EST-353
EST-353
EST-1519
EST-1001B
EST-1136
1860
EST-177
EST-353
8260R
EST-1407
EST-1142
EST-1141
1845
EST-1143
EST-1516
EST-1513
EST-1415
GT-116
4060
EST-1415
GT-262
1095
DRAIN SUB-ASSEMBLY
GT-122
GT-120
(6000-1)
GT-176-1
CYLINDER ASSEMBLY
(6000-2)
GT-202
EST-207
GT-262
EST-1522A
FILL SUB-ASSEMBLY
GT-196-KIT
EST-207
GT-116
GT-153
EST-1501
EST-1012
EST-1533-3
EST-1225-KIT
16 www.trioniaq.com
Herrtronic® Model 6000
Page 17
Installation, Operation, & Maintenance Manual
Parts List
1095 Hose Clamp SS 1845 Door Interlock 1860 KEP Nut, 6-32 4060 Fitting, 1/4” Bulkhead 8620R Humidistat Element 121800-004 KEP Nut, 8-32 EST-003 PA Cylinder Full Interface EST-105A Toroid Transformer EST-177 Nylon Spacer EST-207 Clamp EST-353 Bushing EST-1001B Main Circuit Board EST-1136 Nylon Washer EST-1141 Red Lamp EST-1142 Green Lamp (2) EST-1143 On Off Drain Switch EST-1225-KIT Drain Reservoir Kit EST-1405 Timer/Relay EST-1407 Knob EST-1409 Universal Bushing EST-1415 Tubing EST-1501 Steam Manifold EST-1512 Transformer 120/240 to 24 VAC EST-1513 Distribution Louver EST-1514 Relay, 2 pole, 20 A EST-1516 Steam Hose EST-1517-1 Fan, 120V EST-1518-1 Fan, 240V EST-1519 Circuit Breaker, 2A EST-1522A Fill Assembly EST-1530 Terminal Block EST-1533-3 Drain Valve Kit EST-1542 Power Wire Assembly (Not Shown) GT-116 Celcon Compression Nuts GT-120 Fill Tee GT-122 Nylon Clamp GT-153 Strainer SS GT-176-1 Low Conductivity Steam Cylinder Assembly (Standard 120V Units) GT-196-KIT Fill Valve Replacement Kit GT-202 Steam Cylinder Assembly (Standard 240V Units)
GT-262 Hose, 1/2” I.D. Overow
Herrtronic® Model 6000
www.trioniaq.com
17
Page 18
TRION
®
101 McNeill Rd. | Sanford, NC 27330
P: 800.884.0002 | F: 800.458.2379 | www.trioniaq.com | customerservice@trioniaq.com
Form No. OM-273 Rev. 01/18
© 2018 TRION. All Rights Reserved.
Loading...