Trion CB777 Installation, Operation & Maintenance Manual

Page 1
READ AND SAVE THESE INSTRUCTIONS
UNIT NOT FOR COMMERCIAL USE
CB777
Centrifugal Atomizing Humidier
TRION® | www.trioniaq.com
Page 2
Installation, Operation, & Maintenance Manual
READ AND SAVE THESE INSTRUCTIONS
LIRE ET CONSERVER CES INSTRUCTIONS
TABLE OF CONTENTS
1. Warranty Statement .................................................................................................................................3
2. Safety Warnings .......................................................................................................................................3
3. Introduction ..............................................................................................................................................4
3.1. Unit Specications ............................................................................................................................. 4
3.2. Capacity Selection Guide .................................................................................................................. 4
3.3. Operation ........................................................................................................................................... 4
4. Installation ................................................................................................................................................ 5
4.1. Selecting the Unit Location ................................................................................................................ 5
4.2. Physical Installation ........................................................................................................................... 5
4.3. Final Installation .................................................................................................................................6
4.4. Electrical Installation .......................................................................................................................... 6
4.5. Humidistat Installation .......................................................................................................................7
5. Maintenance ............................................................................................................................................7
6. Parts List and Unit Diagram ..................................................................................................................... 8
2 www.trioniaq.com
Page 3
Installation, Operation, & Maintenance Manual
CAUTION
Trion recommends that this humidier be installed by a trained HVAC professional. Do not connect the unit to the power source until the installation is complete. A thorough checkout of the unit installation should be completed before operating the unit. Failure to follow these directions may void the manufacturer’s original warranty.
1. Warranty
This limited warranty covers TRION Residential Type Humidiers, excluding duct work, wiring and installation. TRION warrants that all new TRION humidiers are free from defects in material and workmanship under normal, non-commercial use and service. TRION will remedy any
covered defects if they appear within 24 months from the date of original
installation & subject to the terms and conditions of this Limited 2-Year
Warranty stated below:
1. THIS LIMITED 2-YEAR WARRANTY is granted by TRION Customer
Service, 101 McNeill Road, Sanford, NC 27330.
2. This warranty shall extend only to any non-commercial owner who has purchased the residential humidier other than for purposes of
resale.
3. All components are covered by this limited warranty except
expendable items, such as evaporative pads, media lter pads and
nozzles.
4. If, within the warranty period, any TRION residential humidier unit or component requires service it must be performed by a competent heating and/or air conditioning contractor (preferably the installing
contractor). TRION will not pay shipping charges, or labor charges
to remove or replace such defective parts or components. If the part or component is found by inspection to contain such defective material and workmanship it will be either repaired or exchanged free
of charge at TRION’s option, and returned freight collect.
5. In order to obtain the benets of this limited 2-year warranty, the owner must notify the dealer or distributor of any defect within 30 days of its
discovery. If after reasonable time you have not received an adequate
response from the dealer or distributor, notify in writing to TRION Customer Service 101 McNeill Road, Sanford, NC 27330, or call 1-800-884-0002 or email [email protected] Humidiers
which have been installed or become part of real estate cannot be
returned. TRION will receive, freight prepaid, only removable parts or components of such defective humidiers.
6. This limited warranty does not apply to any part or component that is
damaged in transit or in handling, has been subject to misuse, neglect or accident; has not been installed, operated and serviced according
to TRION’s instructions; has been operated beyond the factory rated capacity; or altered in any such way that its performance is affected.
There is no warranty due to neglect, alteration or ordinary wear and
tear. TRION’s liability is limited to replacement of defective parts or components and does not include the payment of the cost of labor charges to remove or replace such defective components or parts.
7. TRION will not be responsible for loss of use of any product; loss of
time, inconvenience, or any other indirect, incidental or consequential damages with respect to person or property, whether as a result of breach of warranty, neglect or otherwise. SOME STATES DO
NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL
OR CONSEQUENTIAL DAMAGES, SO THE LIMITATION OR EXCLUSION IN THE PRECEDING SENTENCE MAY NOT APPLY TO YOU.
8. THIS WARRANTY GIVES YOU SPECIFIC RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO
STATE.
9. Any warranty by TRION of merchantability, tness for use or any other
warranty (express, implied or statutory), representation or guarantee other than those set forth herein, shall expire at the expiration date
of this express limited warranty. SOME STATES DO NOT ALLOW
LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE LIMITATION IN THE PRECEDING SENTENCE MAY NOT APPLY TO YOU.
10. TRION reserves the right to make changes in the design and material
of its products without incurring any obligation to incorporate such changes in units completed on the effective date of such change.
WARNING: Failure to install an air ow proving switch may result in moisture build-up inside of the ductwork. Leaks, mold growth,
and severe water damage may result.
Humidier 2-Year Limited Warranty
2. Safety & Warnings
DANGER
RISK OF ELECTRIC SHOCK
Before cleaning, servicing, or parts replacement, the unit must
be disconnected from all sources of electricity.
CAUTION
Read these instructions thoroughly before installing this unit.
Check data label and verify electrical specications agree
with those at the point of installation.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance may cause property damage, injury, or death. This
appliance must be installed according to these instructions. Read
these instructions thoroughly before installing or servicing the unit.
WARNING
Failure to install this unit in a position that is level and plumb
may impair the unit’s ability to drain if an overow condition
presents itself. Damage to personal property may also result.
WARNING
Installation in freezing conditions can result in unit failure.
Damage to personal property may also result.
WARNING
This appliance is not intended for use by children or persons
with reduced physical, sensory or mental capabilities, or lack
of experience and knowledge, unless they have been given
supervision or instruction concerning use of the appliance
by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
WARNING
A drain pan should be installed under the unit and any supply
water / drain connections to prevent damage to property in the
event of a water leak or faulty operation.
CAUTION
TRION recommends that this humidier be installed by a
trained HVAC professional. Do not connect the unit to the
power source until the installation is complete. A thorough
checkout of the unit installation should be completed before
operating the unit. Failure to follow these directions may void
the manufacturer’s original warranty.
www.trioniaq.com
3
Page 4
Installation, Operation, & Maintenance Manual
3. Introduction
Congratulations on your choice of a TRION IAQ humidication system. Your family can now look forward to breathing more comfortable air, winter after winter. We are committed to
providing advanced products that improve the quality of the air you breathe. The following information will familiarize you with
the operation of your new humidier and provide helpful tips on
how to obtain maximum performance from your unit.
The benets of a properly humidied environment (40-60%
Relative Humidity) are many. They include both personal comfort
as well as the preservation of furniture, draperies, carpets, wooden oors and cabinets, paintings, pianos, etc.. Your home
will be more comfortable at a lower temperature (i.e.: 68° F)
at 40-60% Relative Humidity (RH) than at 71° to 72° F without
controlled humidity. Since every degree of temperature setback
represents about 3% of your heating costs, this can possibly represent a signicant annual savings. During the heating season, cold air is brought into the home and heated. When heated, this air dries out and greatly increases its capacity to hold more moisture. By using a humidier, a source of water is provided to satisfy this increased moisture holding capability,
rather than having it drawn from our body surface and the surrounding furnishings in the home. A properly maintained and
efciently operating humidier is a source of improved Indoor Air
Quality and personal comfort. We hope you will enjoy the
benets of your humidier.
3.1 Unit Specications
Type of Unit Centrifugal atomizing
Duct Mounting Return
GPD @ 140 ° F 6.0 maximum
GPD @ 120 ° F 6.0 maximum
GPD @ 100 ° F 6.0 maximum
Voltages 120V/ 240V
Unit Dimensions 10 1/2” DIA x 12 1/2” H
Standard Equipment Wall / duct mount humidistat
Features Centrifugal atomizer
Operates on low current, less than a 100w bulb
All brass valve assembly Universal mounting options 2 year warranty
Installation Options: Duct Side Mount Free Standing Wall
Mounts on face of vertical or side of horizontal return duct Includes independent mounting bracket Mounts on wall Includes independent mounting bracket
3.2 Capacity Selection Guide
Sq Ft
Home
1000 .5 5.0 10.0
1500 3.0 10.0 16.5
2000 5.0 14.0 24.0
2500 7.5 19.0 30.5
3000 10.0 23.5 37.5
4000 14.5 33.0 51.5
*GPD = Gallons Per Day (Humidier Capacity)
The above calculations are for reference only and are based on the following:
• Inside temperature 70°F / 50% relative humidity
• Outside Temp 20°F / 70% relative humidity
• 8 foot ceiling height
• Internal moisture gain of one pound per hour
• Furnace on-time of 70%
This chart uses A.R.I. standard designations:
A “Tight Home” is assumed to be well insulated with vapor barriers, tight storm windows and doors, and a dampered replace; air exchange rate of 0.50 changes per hour. An “Average Home” is insulated and has a dampered replace, but there are no vapor barriers, storm doors, or storm windows; air exchange rate of 1.0 change per hour. A “Loose Home” is generally one constructed before 1930, has little or no insulation, no storm doors, storm windows, weather stripping or vapor barriers, and often no effective dampering of replaces; air exchange rate is as high as 1.5 changes per hour.
Tight Home
GPD*
Avg Home
GPD*
Loose Home
GPD*
3.3 Operation
Your centrifugal atomizer type humidier operates on the principle of breaking down water droplets into a ne mist and atomizing the moisture into the air. If applicable, set the humidistat in the recommended range of 40-50% relative humidity for automatic
humidity control during the heating season (a lower setting may be used to control condensation on single pane windows).
During the rst heating season, check the mineral buildup in the humidier every month to establish the proper cleaning schedule. Clean the unit at the end of each heating season, or
whenever mineral deposits appear to be impeding the discharge of the water mist.
When shutting the humidier down for the summer months, start with cleaning any mineral accumulation from the unit. Leave the water turned off and the unit dry. If the furnace fan is to be used for cooling purposes, disconnect power to the humidier or turn the humidistat to the OFF position.
4 www.trioniaq.com
Page 5
Installation, Operation, & Maintenance Manual
4. Installation
Selecting the Unit Location
Mounting on face of vertical return duct or side of horizontal
return duct When mounting your humidier on the face of a horizontal return duct, or on the face of a vertical return duct, certain conditions must be met for its proper operation:
• Mount the humidier on the vertical or horizontal cold air return duct.
• Locate the humidier at least four (4) linear feet upstream of
either the furnace fan and/or lter and any turn in the duct.
This will ensure that condensation does not collect within the duct and cause oxidation (rust).
• Mount the humidier at least six (6) linear feet (preferably
10 feet) upstream from any electronic air cleaner. Failure to
follow this recommendation can cause excessive nuisance arcing and or power supply failure.
• If the duct seams inside the duct are not at, locate the
humidier at least three (3) linear feet upstream from the
seam.
• If the humidication needs of the home require more than
one humidier, each unit should be installed a minimum of
three (3) linear feet apart.
• DO NOT use this humidier on the discharge or warm air supply side of a forced air heating system. This will reduce
the efciency of the humidier and may cause operational
problems.
• DO NOT mount the humidier in a furnace jacket.
• DO NOT install the humidier where freezing conditions could occur.
• DO NOT install on gravity hot air systems.
Physical Installation
CAUTION
Only a trained HVAC servicer or contractor should install
this humidier. Do not connect the unit to the power source
until installation is complete. A thorough checkout of the unit installation should be completed before operation. Failure to follow these directions may void the manufacturer’s original warranty.
Remember to select a location that is readily accessible for
periodic inspection and cleaning of your humidier. Allow a minimum of 2” clearance in front of the humidier and 2” below
the water pan to allow for maintenance and repair.
2. Check the template with a level to ensure proper installation
of the Humidier.
3. Drill (4) 1/8” diameter holes (as shown on the template) for mounting the wire bracket with sheet metal screws and at
washers provided.
4. Cut out the circle marked on the template. Do not cut this
opening over-sized.
5. With a hammer and heavy piece of metal, straighten the metal edges to prevent injury to yourself and damage to the
Humidier.
6. Fit the rubber channel around the cut-out to cover the rough edges of the hole and trim to t.
7. Attach the wire mounting bracket to the duct with (4) #10 sheet metal screws and at washers (provided).
8. Move the side adjusting arms vertically until the shelf of the wire mounting bracket is level.
9. Mark the duct for securing adjusting arms and drill (2) 1/8”
holes. Fasten the arms in this position with (2) #10 sheet metal screws and at washers (provided).
10. The oat and valve assembly have been factory adjusted to maintain 1-1 1/2” of water in the water reservoir pan at normal water pressure. If necessary, bend the oat arm to
the required position to maintain the water level at other water pressures.
11. Before mounting the
humidier in its nal position, carefully rotate the
impeller assembly by hand to ensure it rotates freely.
Position the humidier on
the wire mounting bracket
with the oat and valve
assembly connection facing the most convenient location. Be sure that the water reservoir pan feet do not rest on the wire bracket and that the water reservoir pan is level.
12. The discharge dome should approach the
opening in the duct, however, it should not
extend into the duct. There
will be no heat loss, due
to the negative pressure of the cold air return duct
(the air ow will create a
vacuum in the duct).
Cold air return duct
Wire mounting bracket
Bracket should be level
Rubber channel
Discharge
dome
Prior to installing this product:
• Read the instructions carefully to ensure safe operation. Failure to follow them could damage the product or cause a hazardous condition.
• Check the ratings given on the product to make sure it is suitable for your application.
Mounting on the face of a vertical return duct or side of a horizontal return
1. Mount the installation template on the side of the cold air
return air duct with the center line of the template lined up with the center line of the return air duct. The narrow side of the duct may be used if space permits.
NOTE:
The following items are located in the carton:
• Bottom Pan
• Atomizing Assembly
• Discharge Dome
• Wire Mounting Bracket
The following items are located in the parts bag:
• Template
• (6) #10 x 3/4” screws
• (6) #10 at washers
• Rubber Channel
www.trioniaq.com
5
Page 6
Installation, Operation, & Maintenance Manual
Final installation steps for all mounting locations
• Install a saddle valve (not provided) on the nearest cold water supply pipe (see the instructions on the package). If
applicable, connect the saddle valve upstream of any type
of water softener.
• After the saddle valve has been installed and 1/4” copper
tubing tted to the valve, but before attaching the copper tubing to the oat and valve assembly, turn the saddle valve
to the open position and discharge the water into a bucket or pan. This will allow the water to void the line of any debris that may have accumulated during the installation process.
• Attach 1/4” copper tubing to the oat and valve assembly with the ferrule and compression nut (provided).
Caution:
The oat and valve assembly must not turn when tighten­ing the copper tubing compression ttings to the humidier water reservoir pan tting.
• Turn the water supply on at the saddle valve.
• Check the water level in the water reservoir pan to ensure
it is 1 to 1 1/2” deep.
Failure to follow these instructions may result in improper
installation and therefore, void the manufacturer’s warranty.
1. Remove the cover from the junction box in the furnace jacket.
2. Connect the humidier input leads to the two (2) leads that run to the furnace blower motor. This connection provides
for the automatic operation of the humidier during the
heating season.
3. The humidier will only operate when the furnace blower is in operation.
4. It is recommended to install the in the system to provide optimum performance when continuous air circulation is desired.
5. If a humidistat is not used in the installation, install an ON/
OFF switch in its place. This provides a simple, yet effective, method of turning the humidier off during the summer months when humidication is not desired.
Wiring diagram for humidier installation - return duct
installation
Furnace wiring connection
TO BLOWER
=
INPUT POWER
IMPORTANT:
In installations where accidental overow could cause water damage, connect a drain hose from the humidier water reservoir pan overow tube to a
drain.
Do NOT use a soldered joint because the overow tube
will become heated and warp the water reservoir pan.
Electrical Installation
WARNING:
Improper electrical wiring can cause personal shock, injury,
or property damage. It is required that the unit be installed
by a properly qualied HVAC technician or electrician, following NEC and any other local codes.
Electrical installation:
This humidier is intended to be wired directly to the integrated
control panel on your furnace. The electrical tap will provide
power to the humidier whenever the circulating air blower is
in operation.
INPUT POWER
Wiring diagram for humidier installation - free standing
installation
Dedicated wiring connection
INPUT POWER
Read the instructions in the furnace installation manual carefully
before attempting installation or operation of this humidier.
6 www.trioniaq.com
Page 7
Installation, Operation, & Maintenance Manual
Humidistat Installation
Humidistat:
1. Locate the humidistat in the living area making sure that it
is at least ve (5) feet from a supply register (duct mounted
installation) or discharge nozzle (free standing installation).
2. The humidistat should be installed four and a half (4 1/2)
feet above the oor, out of the direct sun and not subject to damage from trafc within the room.
3. If you would like the ability to cut off the electricity to the
humidier for maintenance, a throw -switch may be installed.
4. Turn the humidistat to the highest level (past 60%) and the humidier should begin to run. The humidier should stop
when the humidistat is turned off.
5. Set the furnace controls and humidistat for the desired
conditions (30-40% RH is recommended). Operation of this
unit is automatic.
6. If condensation occurs on single pane windows, lower the humidistat setting until the condensation has disappeared.
NOTE: It may take several days for the humidity level in
your home to reach comfortable levels.
5. Maintenance
Caution:
Before cleaning or servicing this unit, it is recommended
that the unit be disconnected from any electrical supply outlet.
To enjoy the benets of a properly humidied environment,
periodic cleaning is necessary to control both water and
household impurities. Film or scum, which can contain bacteria or fungi, may appear on the water surface, the sides, or bottom of your humidier. A crusty deposit or scale may also appear
and is composed of minerals that have settled out of the water.
To improve the efciency of your humidier, and to reduce the possibility of a health hazard, it is recommended that you take
the following precautions:
• Follow the manufacturer’s recommended cleaning and maintenance instructions below and on the next page.
• The amount of minerals and other impurities in a water
source can vary greatly, therefore, the frequency of cleaning
the unit also varies.
• During the heating season, check for lm or scale build-up
in the unit, or any moving part. Establish a proper cleaning schedule to ensure the efciency of the humidier.
• An algaecide, such as a humidier cleaning tablet or bacteriostatic liquid/powder, can be used to combat algae build-up, should it become evident.
• At the end of the winter humidication season, drain and thoroughly clean your humidier as part of the summer
shutdown. Like your heating system and air conditioning
unit, periodic maintenance and cleaning are required to ensure the safe and efcient operation of your humidier. Due to the operation cycle of the furnace and humidier, it may require 2 to 5 days to reach the proper humidication
level.
Your humidier is constructed from quality materials to assure
superior performance during normal operation. The motor bearings are permanently lubricated and do not require oiling. The motor is also thermal overload protected against extreme conditions.
To clean the unit:
1. Turn the power to the furnace OFF or turn off the electric
switch to the humidier, if provided.
2. Disconnect the humidier motor leads.
3. Turn off the humidier water supply from the saddle valve
and remove water line from humidier.
4. Remove the humidier from the wire mounting bracket.
5. Remove the discharge dome from the humidier by pressing
on the sides of the dome and lifting upward.
6. Lift the entire atomizing assembly from the water reservoir pan.
7. Remove the pump from the end of the impeller shaft. If the
pump is stuck in the motor drive shaft, run hot water over
the end of the shaft for a few seconds to loosen the pump.
8. Flush water through the impeller tube, ensuring that the six holes at the top of the impeller tube are open and clear of mineral deposits. A pipe cleaner works well for this cleaning operation. Note: The impeller tube and pump can become clogged by algae formations prevalent in certain water
sources. The addition of 10 drops of bleach to the water
reservoir pan each week is advisable.
9. Replace the pump into the impeller shaft.
10. Carefully rotate the impeller to ensure it turns freely. Do not force the impeller shaft to turn or breakage could result.
11. With the atomizing assembly removed, clean the water reservoir pan thoroughly. We suggest either a water/white
vinegar solution or liquid humidier cleaner.
12. Reassemble and remount the humidier by reversing steps 6, 5, and 4.
13. Reconnect the water line and motor leads to the humidier, turn on the water supply from the saddle valve and restore electrical power.
Maintenance instructions for models mounted on the face
of a vertical return duct, side of a horizontal return duct, or mounted behind a wall using discharge extension.
www.trioniaq.com
7
Page 8
Installation, Operation, & Maintenance Manual
6. Parts List and Unit Diagram
1
Model 269450-001 Model CB777
Qty Item Part No Description
1 1 40 Discharge Dome
1 2 252413-001C Motor Cover
1 3 252596-001C Motor
6 4 10-32 Nut #10-32, Brass
4 5 19 Retainer Clip
1 6 352728-001C Motor Base
1 7 45C Diffuser Screen
1 8 D9PC Impeller
1 9 6-32 Set Screw #6-32 x 5/16
1 10 8AC Pump
4 11 90 Bushing
1 12 35PC Center Pan
4 13 23C Center Pan Support
1 14 16 Grommet
1 15 92PC Float & Valve Assembly
1 16 47-BC Bottom Pan
1 17 269529-001 Logo Label
1 18 FV-10 Locknut
1 19 FV-11 Sleeve, Brass, 1/4” Com. (Ferrule)
1 20 FV-12 Nut, Brass, 1/4” Com.
1 21 352680-002C Humidistat (Not Shown)
13
16
12
2
3
4
5
6
7
8
9
10
11
14
15
17
19
TRION
18
®
20
101 McNeill Rd. | Sanford, NC 27330
P: 800.884.0002 | F: 800.458.2379 | www.trioniaq.com | [email protected]
Form No. 269451-001 Rev. 07/17 © TRION 2017. All Rights Reserved.
Loading...