Please read these instructions carefully for
trouble free operation and to get the most out of
your purchase. For further information
concerning this project, contact your local Trion
representative.
The Trion MP 600M air cleaner is designed to capture
machine tool fluids, metal dust and smoke for clean air
filtration. It can be mounted to a wall, frame, platform, or
directly on the machine tool. Mist, dust, and smoke are
drawn from each machine through an external duct into
the air cleaner. A self-draining Impinger removes the
heavy mist and droplets (including water soluble fluids),
and the remaining contaminates are captured by the prefilter and the primary filter. Clean air is returned to the
plant through the vertical discharge. The air cleaner
operates at 95-99.97% efficiency at the rated 600 CFM
airflow.
NEW UNIT INSPECTION
At the time the unit is received, all shipping containers
and their contents should be examined for damage. Any
damage occurring in shipment must be immediately
reported to the carrier, an inspection report completed
and a claim filed at the receiving point. The unit cabinet
is shipped completely assembled
POSITION AIR CLEANER CABINET
To reduce weight for ease in handling, remove the prefilters, main filters and place them safely aside. Position
the cabinet in the designated location giving
consideration to following points:
(a) Provide sufficient clearance in front of the
access doors for mechanical filter replacement.
A minimum of 26” is required (see figure 2).
(b) Level the cabinet to assure proper drainage from
the drain pan.
(c) Unless specific design features have been
prearranged, the direction of air flow through th
e cabinet may be from any side or upward
through the bottom. When the filters are
reinstalled, the directional arrows on the filters
must concur with airflow through the cabinet. If
mist suppressors have been specified, they are
to be installed on the air entering side of the unit.
After the cabinet has been properly located, it may be
secured into place at the mounting pads either by bolting
or welding.
2
Figure 1 - MP 600M High Static
SPECIFICATIONSSTANDARDOPTIONAL MP600M and High Static
MP 600M
Voltage115208-230208-230/460 575115/230
Phase11331
HZ6060606060
AMPS179.4-8.54.9-4.6/2.31.98.0-4.0
Motor½ hp1 ½ hp1 ½ hp1 ½ hp½ hp
CFM600600600600600
Shipping Weight175 lbs225 lbs.225 lbs.225 lbs. 225 lbs.
3
Figure 2 – Dimension and Access Data
GENERAL SAFETY INFORMATION
WARNING: RISK OF ELECTRIC SHOCK
These serving instructions are for use by qualified
personnel only, To reduce the risk of electric shock, do
not perform any servicing other than that contained in
the operating instructions unless you are qualified to do
so.
1. Read this manual thoroughly before beginning
the installation of this unit.
2. Conference to all local ordinances associated
with building codes and electrical codes is
required prior to beginning installation of this
unit. Authorities having jurisdiction should be
consulted before installation is made. If there are
no local codes, the installation should conform to
the National Electrical Code.
CAUTION:
The weight of the air cleaner is 150 lbs. Any mounting
arrangement must be able to support this weight. Failure
to determine if mounting is sufficient may result in
damage or injury within the area.
INSTALLATION
Prior to beginning installation, select the location for the
air cleaner. The air cleaner should be located as close to
the contaminant source as possible. The air enters the
air cleaner from the bottom (or specified side with inlet
plenum as viewed from the access door side) and
discharges vertically through the grille in the cabinet top
panel. Do not obstruct the air flow from the unit. Maintain
at least 18 inches (45 cm) clearance above the unit.
MOUNTING
WALL OR VERTICAL SUPPORT MOUNTED
1. Four (4) tapped holes are provided in the
cabinet back. Bars may be mounted to the
cabinet with existing hard ware. The MP600M
can then be mounted to the wall or vertical
support stand (not provided) with 3/8” hardware
(not provided).
2. The inlet plenum is equipped with a ½” half
coupling to connect drain piping. Plumbing
should be routed to the collection point to
facilitate drainage.
3. Affix duct(s) or elbow fitting(s) or flex hose(s) to
the inlet plenum flange collar using hose clamps
or other similar connection method. (Clamps,
elbows and/or duct are not provided).
4
CAUTION:
When using flex duct connections with other than
straight runs of duct, 45 degree elbows should be used
to connect ducting to flanged collars to maximize air
flow.
ENCLOSED MACHINING CENTER DIRECT MOUNT
1. When mounting directly to an enclosed
machining center ensure there is 53” (135 cm)
clearance above the enclosure and structure
integrity is sufficient to support the MP 600M.
2. Open the filter access door and remove all the
filtering elements. Set these components aside
until the installation is complete.
3. Prepare an outlet opening on the top of he
enclosed machining center (8” minimum to 20”
maximum diameter opening).
4. Center the MP600M over opening and secure to
the enclosure with self-drilling/self-tapping
screws or other similar method in accordance
with local codes. No additional duct connections
or drain plumbing is required on this type of
installation.
ARM ASSEMBLY (OPTIONAL) MOUNTING
Mount the arm assembly(s) to the arm connection collar
on the inlet plenum in accordance with the mounting
instructions provided in the arm assembly kit.
TRAPEZE MOUNT
1. Four (4) through holes are provided in the inlet
plenum bottom flange to which two (2) mounting
channels are affixed with 3/8” hardware (not
provided).
2. The MP600M can be suspended from overhead
with chains or 3/8” diameter (minimum) rods (not
provided).
3. The inlet plenum is equipped with a ½” half
coupler to connect drain piping. Plumbing should
be routed to the collection point to facilitate
drainage (P – trap not Required).
4. Affix duct(s) or elbow fitting(s) or flex hose(s) to
the inlet plenum flange collar using hose clamps
or other similar connection method (not
provided).
MINI-HELIC GAUGE (Optional Mounting)
1. Gauge may be mounted directly on MP600M
unit or may be remotely mounted for improved
visibility.
2. Gauge may be connected to measure entire
system static pressure or only pressure drop
across filter section.
3. All hardware, components and detailed
installation instructions are included in gauge kit
option.
Figure 3 - MP 600M Wall Mounted with 8” Arm Assembly and Drain Pipe
5
Figure 4 - MP 600M Inlet Plenum and Stand Options
6
Figure 5 – Wiring Diagrams for Model MP 600M
7
Figure 6 – Wiring Diagram
8
Figure 6A – Motor Wiring Diagram
9
The MP600M is wired directly from the power source
with 20 amps minimum, service utilizing 3 wire grounded
cable, (115-208-230-460-575/60/3) for single 208230/60/1, phase service and 4 wire grounded cable for 3
phase service, routed through appropriate conduit (See
figure 5 wiring diagram). All wiring must be connected in
accordance with local electrical codes.
The conduit is connected to the cabinet junction box, or
motor starter enclosure on the top-right front corner of
unit.
OPERATION
To start the air cleaner, close the access door and
activate the ON-OFF control switch to ON. The blower
motor should start.
the pressure reading when the pre-filter is replaced. At
that point, the unit would be allowed to run until 3.1” w.c.
and both filters replaced.
NOTE:
The unit can continue to run beyond the 3.1” w.c.
pressure reading; however, airflow will be reduced
further.
CAUTION:
To check internal components, disconnect power source
to unit to prevent accidental shock.
MAINTENANCE
Blower Rotation (3 phase power only)
By looking down through the MP600M discharge grille
confirm blower rotation agrees with rotation label on
motor mount. If rotation is incorrect reverse two (2) input
power leads connections in the junction box, switch box
or motor starter enclosure. Again verify correct blower
rotation.
Change filter according to the pressure drop across the
filter. A minihelic gauge with a range from 0-5” water
column is optional for reading filter pressure.
Estimated Filter Change Pressure
Main Filter Both Filters Change Pre-filterRecommended Final
95%1.8”w.c.3.1”w.c.
HEPA1.8”w.c.3.1”w.c.
These readings will vary slightly due to altitude and
temperature.
Upon installation of the unit, note the initial pressure
reading and record in the table above. Check daily and
replace pre-filter at the reading shown in the table.
Pressure should return to near the initial pressure
reading. When the pressure reading, with new pre-filter,
shows little improvement (less than 0.1”) allow unit to run
until recommended final pressure is reached. At that
point, both pre-filter and main filter should be replaced.
Impinger models will have greater pressure initially than
standard models.
Estimated Estimated
NOTE:
Precision equipment will require a minimum amount of
maintenance to keep it in operating condition. You can
perform all normal preventative maintenance. If you are
unfamiliar with the terminology used in the in the
following sections, refer to the Parts List (Figure 7-A).
CLEANING AND INSPECTION
Cleaning of Impinger, and inspection and replacement of
pre-filter and main filter.
CAUTION:
Always disconnect the power source before working on
or near any electrical component. If the disconnect point
is out of sight, lock it in the proper position and tag to
prevent unexpected application of power.
1. Turn unit off.
2. Open access door by turning door latches
counter clockwise.
3. Remove filter element, pre-filter and impinger
assembly or pre-filter support.
4. Clean impinger by first rinsing with warm to hot
water, then immerse in a commercial grade
detergent. Trion recommends our specially
formulated Tridex detergent to provide maximum
cleaning efficiency on air cleaning equipment.
For best results, the cleaning solution should be
140ºF to 160ºF. The impinger should be soaked
in the solution for 1½ to 2 hours (longer if
extremely dirty).
NOTE:
Using non-factory approved detergents can cause
damage to the metal surface.
Once a pattern is established, the pre-filters can be
replaced on a calendar basis with the main filter being
replaced when the gauge reads “Recommended Final”
in the Table. For example, if the unit takes 6 weeks to go
from initial reading to 1.8” w.c., the pre-filter would then
be replaced every 6 weeks until no change occurred in
5. While impinger is soaking, make the following
inspections:
10
A.
Thoroughly inspect the main and prefilter for holes, tears or any other
condition that might allow air to leak
through or around the filter. Replace the
filters if any damage is found.
B. Inspect the cabinet. Remove all foreign
debris and dirt accumulation inside the
cabinet.
C. Check for dirt accumulation on the
blower wheel blades and clean if there
is a buildup.
D. Bearings of blower motor should be
checked for signs of unusual wear.
E. If liquids are being collected, check the
drain fittings for proper drainage.
6. When soaking of impinger is complete, rinse
7. Reinstall impinger and filters into the unit.
8. Switch unit on at the control switch. The blower
9. If the air flow is now adequate to draw the
F. Check rubber gasketing and adhesion of
gasketing to cabinet surfaces.
with clean water and allow to dry.
should start.
contaminant being collected off the process, it
will not be necessary to replace the main filter.
If, however, the air flow remains unsatisfactory,
replace the main and pre-filter.
TROUBLESHOOTING CHART
SYMPTOMPOSSIBLE CAUSESCORRECTIVE ACTION
Failure to start
(motor does not start when unit is
turned on
Motor / Blower operates with little or
no air volume
Blow Through / Bypass
1. Proper power not reaching unit
2. Loose electrical connections
3. Defective control switch
4. Defective Motor
1. Dirty or dogged filters
2. Discharge grille obstructed
3. Blower wheel blades loaded with
dirt
4. Blower wheel loose on motor shaft
5. Incorrect voltage
6. Dirty or dogged impinger
7. Motor rotation incorrect
1. Filter ruptured or torn
2. Gasket missing or damaged
3. Filter saturated or damaged
1. Check that unit is connected to live
power line with good fuses, and
that the voltage at the unit is
correct
2. Check; tighten if necessary
3. Replace control switch
4. Replace motor/ blower assembly
1. Replace filters
2. Clean or remove obstruction
3. Clean blower wheel blades
4. Tighten blower wheel on shaft
5. Supply correct line voltage
6. Clean impinger
7. Reverse 2 of the 3 input power
leads (3 Phase only)
** To determine performance with various filter combinations, add total static of filters (from table)
15
WARRANTY
All Trion air cleaners are warranted for component failure and workmanship for a
period of three years after purchase. Do not return defective parts without prior
permission from the factory. Contact your local Trion Distributor or Trion Customer
Service Department at 1-800-884-002 of Fax 1-800-458-2379 to obtain
material return authorizations and service information.