Trion 600M User Manual

Air Boss MP 600M
Vertical Air Flow Mist Precipitator
Installation
Operation
Service
Please read these instructions carefully for trouble free operation and to get the most out of your purchase. For further information concerning this project, contact your local Trion representative.
Phone: 800-884-0002 Fax: 800-458-2379 Email: sales@trioninc.com
101 McNeill Road Sanford, NC 27330
www.trioninc.com
Manual Part No. 153632-001 June 2002
DESCRIPTION
The Trion MP 600M air cleaner is designed to capture machine tool fluids, metal dust and smoke for clean air filtration. It can be mounted to a wall, frame, platform, or directly on the machine tool. Mist, dust, and smoke are drawn from each machine through an external duct into the air cleaner. A self-draining Impinger removes the heavy mist and droplets (including water soluble fluids), and the remaining contaminates are captured by the pre­filter and the primary filter. Clean air is returned to the plant through the vertical discharge. The air cleaner operates at 95-99.97% efficiency at the rated 600 CFM airflow.

NEW UNIT INSPECTION

At the time the unit is received, all shipping containers and their contents should be examined for damage. Any damage occurring in shipment must be immediately reported to the carrier, an inspection report completed and a claim filed at the receiving point. The unit cabinet is shipped completely assembled

POSITION AIR CLEANER CABINET

To reduce weight for ease in handling, remove the pre­filters, main filters and place them safely aside. Position the cabinet in the designated location giving consideration to following points:
(a) Provide sufficient clearance in front of the
access doors for mechanical filter replacement. A minimum of 26” is required (see figure 2).
(b) Level the cabinet to assure proper drainage from
the drain pan.
(c) Unless specific design features have been
prearranged, the direction of air flow through th e cabinet may be from any side or upward through the bottom. When the filters are reinstalled, the directional arrows on the filters must concur with airflow through the cabinet. If mist suppressors have been specified, they are to be installed on the air entering side of the unit.
After the cabinet has been properly located, it may be secured into place at the mounting pads either by bolting or welding.
2
Figure 1 - MP 600M High Static

SPECIFICATIONS STANDARD OPTIONAL MP600M and High Static

MP 600M
Voltage 115 208-230 208-230/460 575 115/230 Phase 1 1 3 3 1 HZ 60 60 60 60 60 AMPS 17 9.4-8.5 4.9-4.6/2.3 1.9 8.0-4.0 Motor ½ hp 1 ½ hp 1 ½ hp 1 ½ hp ½ hp CFM 600 600 600 600 600 Shipping Weight 175 lbs 225 lbs. 225 lbs. 225 lbs. 225 lbs.
3
Figure 2 – Dimension and Access Data
GENERAL SAFETY INFORMATION
WARNING: RISK OF ELECTRIC SHOCK
These serving instructions are for use by qualified personnel only, To reduce the risk of electric shock, do not perform any servicing other than that contained in the operating instructions unless you are qualified to do so.
1. Read this manual thoroughly before beginning the installation of this unit.
2. Conference to all local ordinances associated with building codes and electrical codes is required prior to beginning installation of this unit. Authorities having jurisdiction should be consulted before installation is made. If there are no local codes, the installation should conform to the National Electrical Code.
CAUTION:
The weight of the air cleaner is 150 lbs. Any mounting arrangement must be able to support this weight. Failure to determine if mounting is sufficient may result in damage or injury within the area.
INSTALLATION
Prior to beginning installation, select the location for the air cleaner. The air cleaner should be located as close to the contaminant source as possible. The air enters the air cleaner from the bottom (or specified side with inlet plenum as viewed from the access door side) and discharges vertically through the grille in the cabinet top panel. Do not obstruct the air flow from the unit. Maintain at least 18 inches (45 cm) clearance above the unit.
MOUNTING
WALL OR VERTICAL SUPPORT MOUNTED
1. Four (4) tapped holes are provided in the cabinet back. Bars may be mounted to the cabinet with existing hard ware. The MP600M can then be mounted to the wall or vertical support stand (not provided) with 3/8” hardware (not provided).
2. The inlet plenum is equipped with a ½” half coupling to connect drain piping. Plumbing should be routed to the collection point to facilitate drainage.
3. Affix duct(s) or elbow fitting(s) or flex hose(s) to the inlet plenum flange collar using hose clamps or other similar connection method. (Clamps, elbows and/or duct are not provided).
4
CAUTION:
When using flex duct connections with other than straight runs of duct, 45 degree elbows should be used to connect ducting to flanged collars to maximize air flow.
ENCLOSED MACHINING CENTER DIRECT MOUNT
1. When mounting directly to an enclosed machining center ensure there is 53” (135 cm) clearance above the enclosure and structure integrity is sufficient to support the MP 600M.
2. Open the filter access door and remove all the filtering elements. Set these components aside until the installation is complete.
3. Prepare an outlet opening on the top of he enclosed machining center (8” minimum to 20” maximum diameter opening).
4. Center the MP600M over opening and secure to the enclosure with self-drilling/self-tapping screws or other similar method in accordance with local codes. No additional duct connections or drain plumbing is required on this type of installation.
ARM ASSEMBLY (OPTIONAL) MOUNTING
Mount the arm assembly(s) to the arm connection collar on the inlet plenum in accordance with the mounting instructions provided in the arm assembly kit.
TRAPEZE MOUNT
1. Four (4) through holes are provided in the inlet plenum bottom flange to which two (2) mounting channels are affixed with 3/8” hardware (not provided).
2. The MP600M can be suspended from overhead with chains or 3/8” diameter (minimum) rods (not provided).
3. The inlet plenum is equipped with a ½” half coupler to connect drain piping. Plumbing should be routed to the collection point to facilitate drainage (P – trap not Required).
4. Affix duct(s) or elbow fitting(s) or flex hose(s) to the inlet plenum flange collar using hose clamps or other similar connection method (not provided).
MINI-HELIC GAUGE (Optional Mounting)
1. Gauge may be mounted directly on MP600M unit or may be remotely mounted for improved visibility.
2. Gauge may be connected to measure entire system static pressure or only pressure drop across filter section.
3. All hardware, components and detailed installation instructions are included in gauge kit option.
Figure 3 - MP 600M Wall Mounted with 8” Arm Assembly and Drain Pipe
5
Figure 4 - MP 600M Inlet Plenum and Stand Options
6
Figure 5 – Wiring Diagrams for Model MP 600M
7
Figure 6 – Wiring Diagram
8
Figure 6A – Motor Wiring Diagram
9
The MP600M is wired directly from the power source with 20 amps minimum, service utilizing 3 wire grounded cable, (115-208-230-460-575/60/3) for single 208­230/60/1, phase service and 4 wire grounded cable for 3 phase service, routed through appropriate conduit (See figure 5 wiring diagram). All wiring must be connected in accordance with local electrical codes.
The conduit is connected to the cabinet junction box, or motor starter enclosure on the top-right front corner of unit.
OPERATION
To start the air cleaner, close the access door and activate the ON-OFF control switch to ON. The blower motor should start.
the pressure reading when the pre-filter is replaced. At that point, the unit would be allowed to run until 3.1” w.c. and both filters replaced.
NOTE:
The unit can continue to run beyond the 3.1” w.c. pressure reading; however, airflow will be reduced further.
CAUTION:
To check internal components, disconnect power source to unit to prevent accidental shock.
MAINTENANCE
Blower Rotation (3 phase power only)
By looking down through the MP600M discharge grille confirm blower rotation agrees with rotation label on motor mount. If rotation is incorrect reverse two (2) input power leads connections in the junction box, switch box or motor starter enclosure. Again verify correct blower rotation.
FILTER CHANGE (MINI-HELIC GAUGE) INDICATOR (OPTIONAL) OPERATION
Change filter according to the pressure drop across the filter. A minihelic gauge with a range from 0-5” water column is optional for reading filter pressure.
Estimated Filter Change Pressure
Main Filter Both Filters Change Pre-filter Recommended Final
95% 1.8”w.c. 3.1”w.c.
HEPA 1.8”w.c. 3.1”w.c.
These readings will vary slightly due to altitude and temperature.
Upon installation of the unit, note the initial pressure reading and record in the table above. Check daily and replace pre-filter at the reading shown in the table. Pressure should return to near the initial pressure reading. When the pressure reading, with new pre-filter, shows little improvement (less than 0.1”) allow unit to run until recommended final pressure is reached. At that point, both pre-filter and main filter should be replaced. Impinger models will have greater pressure initially than standard models.
Estimated Estimated
NOTE:
Precision equipment will require a minimum amount of maintenance to keep it in operating condition. You can perform all normal preventative maintenance. If you are unfamiliar with the terminology used in the in the following sections, refer to the Parts List (Figure 7-A).
CLEANING AND INSPECTION
Cleaning of Impinger, and inspection and replacement of pre-filter and main filter.
CAUTION:
Always disconnect the power source before working on or near any electrical component. If the disconnect point is out of sight, lock it in the proper position and tag to prevent unexpected application of power.
1. Turn unit off.
2. Open access door by turning door latches counter clockwise.
3. Remove filter element, pre-filter and impinger assembly or pre-filter support.
4. Clean impinger by first rinsing with warm to hot water, then immerse in a commercial grade detergent. Trion recommends our specially formulated Tridex detergent to provide maximum cleaning efficiency on air cleaning equipment. For best results, the cleaning solution should be 140ºF to 160ºF. The impinger should be soaked in the solution for 1½ to 2 hours (longer if extremely dirty).
NOTE:
Using non-factory approved detergents can cause damage to the metal surface.
Once a pattern is established, the pre-filters can be replaced on a calendar basis with the main filter being replaced when the gauge reads “Recommended Final” in the Table. For example, if the unit takes 6 weeks to go from initial reading to 1.8” w.c., the pre-filter would then be replaced every 6 weeks until no change occurred in
5. While impinger is soaking, make the following inspections:
10
A.
Thoroughly inspect the main and pre­filter for holes, tears or any other condition that might allow air to leak through or around the filter. Replace the filters if any damage is found.
B. Inspect the cabinet. Remove all foreign
debris and dirt accumulation inside the cabinet.
C. Check for dirt accumulation on the
blower wheel blades and clean if there is a buildup.
D. Bearings of blower motor should be
checked for signs of unusual wear.
E. If liquids are being collected, check the
drain fittings for proper drainage.
6. When soaking of impinger is complete, rinse
7. Reinstall impinger and filters into the unit.
8. Switch unit on at the control switch. The blower
9. If the air flow is now adequate to draw the
F. Check rubber gasketing and adhesion of
gasketing to cabinet surfaces.
with clean water and allow to dry.
should start.
contaminant being collected off the process, it will not be necessary to replace the main filter. If, however, the air flow remains unsatisfactory, replace the main and pre-filter.
TROUBLESHOOTING CHART
SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION
Failure to start (motor does not start when unit is turned on
Motor / Blower operates with little or no air volume
Blow Through / Bypass
1. Proper power not reaching unit
2. Loose electrical connections
3. Defective control switch
4. Defective Motor
1. Dirty or dogged filters
2. Discharge grille obstructed
3. Blower wheel blades loaded with dirt
4. Blower wheel loose on motor shaft
5. Incorrect voltage
6. Dirty or dogged impinger
7. Motor rotation incorrect
1. Filter ruptured or torn
2. Gasket missing or damaged
3. Filter saturated or damaged
1. Check that unit is connected to live power line with good fuses, and that the voltage at the unit is correct
2. Check; tighten if necessary
3. Replace control switch
4. Replace motor/ blower assembly
1. Replace filters
2. Clean or remove obstruction
3. Clean blower wheel blades
4. Tighten blower wheel on shaft
5. Supply correct line voltage
6. Clean impinger
7. Reverse 2 of the 3 input power leads (3 Phase only)
1. Replace filter
2. Install or repair
3. Replace filter
11
Figure 7 – MP 600M Unit Assembly
12
Figure 7A – Unit Assembly Parts List
MP 600M MP 600M HS
Qty Qty Item Part No. Description Remarks
1 1 1 353613-001 Cabinet Assembly 1 1 2 354477-001 Access Door 1 1 3 253619-001 Blower Housing Cover 2 2 5 248956-002 Clamping Knob 2 2 6 321449-002 Nut Retainer 2 2 7 146442-002 Hinge
6’ 6’ 8 224779-015 Gasket ¼” x 1”
1 - 9 247350-101 Blower Motor Assembly 120/240/50-60/1 Feature & Option 1 - 10 253631-001 Adapter Plate Feature & Option
- 1 11A 150825-001 Motor 115/208/-230/60/1 Feature & Option
- 1 11B 150825-003 Motor 208-230/460/60/3 Feature & Option
- 1 11C 150825-004 Motor 575/60/3 Feature & Option
- 1 11D 150825-005 Motor 110/220/50/1 Feature & Option
- 1 11E 150825-006 Motor 220/380-440/50/3 Feature & Option
- 1 12 250819-007 Inlet Cone Feature & Option
- 1 13 250837-102 Blower Wheel Feature & Option
- 1 14 253617-001 Motor Mount Feature & Option
- 2 15 253621-001 Motor Adjusting Angle Feature & Option 1 1 16A 353622-001 Plenum 1 – 8” Hose Feature & Option 1 1 16B 353622-002 Plenum 2 – 6” Hose @ 90º Feature & Option 1 1 16C 353622-003 Plenum 2 – 6” Hose @ 180º Feature & Option 1 1 16D 353622-004 Plenum 2 – 6” Hose @ 0º Feature & Option 1 1 16E 353622-005 Plenum 1 – 8” Arm @ Bottom Feature & Option 1 1 16F 353622-006 Plenum 1 – 8” Hose @ Bottom Feature & Option 1 1 16G 354988-001 Plenum 1 – 8” Arm @ Side Feature & Option 1 1 17A 246901-011 Impinger Feature & Option 1 1 17B 248533-001 Pre-Filter Support Feature & Option 1 1 18A 148534-001 Synthetic Filter - 22¼ x 22¼ x 2 Feature & Option 1 1 18B 224451-022 Aluminum Mesh Feature & Option 1 1 19A 248535-008 Filter 55%, 30 SF – Special Order Feature & Option 1 1 19B 248535-007 Filter 65%, 30 SF – Special Order Feature & Option 1 1 19C 248535-006 Filter 85%, 30 SF – Special Order Feature & Option 1 1 19D 248535-005 Filter 95%, 30 SF – Special Order Feature & Option 1 1 19E 248535-004 Filter 65%, 54 SF – Special Order Feature & Option 1 1 19F 248535-003 Filter 85%, 54 SF – Special Order Feature & Option 1 1 19G 248535-002 Filter 95%, 70 SF – Stock Feature & Option 1 1 19H 248535-001 Filter 99.97% DOP, 90 SF – Stock Feature & Option 1 1 19J 248535-009 Filter 95% DOP – Stock Feature & Option
- 1 20A 253625-002 Switch Box Assembly 1Ø Feature & Option
- 1 20B 253625-003 Switch Box Assembly 1Ø w/ Cord Feature & Option
- 1 20C 253625-004 Switch Box Assembly 3Ø Feature & Option
- 1 20D 355032-006 Compact Starter 110-120/50-60/1 Feature & Option
- 1 20E 355032-007 Compact Starter 220-240/50-60/1 Feature & Option
- 1 20F 355032-008 Compact Starter 208/60/1 Feature & Option
- 1 20G 355032-009 Compact Starter 208/60/3 Feature & Option
- 1 20H 355032-010 Compact Starter 220-230/50-60/3 Feature & Option
- 1 20I 355032-011 Compact Starter 380/50/3 Feature & Option
- 1 20J 355032-012 Compact Starter 440-460/50-60/3 Feature & Option
- 1 20K 355032-013 Compact Starter 575/60/3 Feature & Option 1 - 21A 253625-002 Switch Box Assembly 1Ø Feature & Option 1 - 21B 253625-003 Switch Box Assembly 1Ø w/ Cord Feature & Option
REF REF 22 253625-001 Junction Box Assembly Feature & Option
1 1 23A 253763-001 Gauge Kit System Feature & Option 1 1 23B 253763-002 Gauge Kit Filter Feature & Option 1 1 23C 253763-003 Gauge Kit System – Remote Feature & Option 1 1 23D 253763-004 Gauge Kit Filter – Remote Feature & Option 1 1 24A 354970-001 Arm Assembly 8” x 10” Feature & Option 1 1 25 253761-001 Mounting Bar Feature & Option 1 1 26 60000-0003-01-00 Swivel Caster Feature & Option
REF REF 27A 238001-002 Toggle Switch 1Ø Feature & Option REF REF 27B 238001-003 Toggle Switch 3Ø Feature & Option
1 1 28 254643-001 Stand Not Shown
- 4 29 145541-003 Vibration Isolator
13
Figure 8 – Filter Locking Mechanism
- Access opening increased 3.5” height
- 16 GA tapered filter retainer welded in door and cabinet rear
- As door closes, filter gasket is compressed and seal is made
14
Figure 9 – System Performance Curves (without Filters)
Flow – CFM @ 60 Hz
Added Static @ Filter 600 CFM 1000 m3/hr
Filter Inches W.C. Pascals
99.97% DOP HEPA 1.00 250 95% DOP 0.35 87 90-95% ASHRAE 0.20 50 80-85% ASHRAE 0.15 37 60-65% ASHRAE 0.10 25 45-55% ASHRAE 0.05 13 Impinger 0.15 37 Aluminum Mesh Pre-Filter 0.05 13 Glass Pre-Filter 0.00 1
** To determine performance with various filter combinations, add total static of filters (from table)
15
WARRANTY
All Trion air cleaners are warranted for component failure and workmanship for a period of three years after purchase. Do not return defective parts without prior permission from the factory. Contact your local Trion Distributor or Trion Customer Service Department at 1-800-884-002 of Fax 1-800-458-2379 to obtain material return authorizations and service information.
Form No. 153632-001 June 2002
Corporate Office: 101 McNeill Road Sanford, NC 27330
Phone: 800-884-0002 Fax: 800-458-2379 Email: sales@trioninc.com
www.trioninc.com
Loading...