COMFORTSTEAM
COMFORTSTEAM
TM
W
W
W
.
T
R
I
O
N
I
N
C
.
C
O
M
W
W
W
.
H
E
R
R
M
I
D
I
F
I
E
R
-
H
V
A
C
.
C
O
M
HUMIDIFICATION
SYSTEMS
Water Level Sensors
Top View
Steam Outlet
Heating Element
Water Tank
Internal Drain
Outlet (Factory
installed
with hose)
Electric
Valve
Tank
Cover
Tank
Latch
Manual Thermal
Cut-Out
Humidification System
TECHNICAL ENGINEERING SPECIFICATION
Electronic Humidistat
With Outdoor Sensor
TM
Performance:
COMFORTSTEAMTM is an isothermal system that produces odorless,
sterile, and bacteria-free humidication. Steam is produced at atmospheric
pressure and dispersed into the HVAC ductwork via a steam nozzle or
perforated steam diffuser. Selection includes three capacities ranging
from 13 GPD to 34.5 GPD (4.5 – 12 lbs/hr steam). Units are available in
120 VAC and 240 VAC. An available electronic humidistat with outdoor
reset automatically reduces the humidity setpoint as the outdoor
temperature falls. Each unit is factory tested and CSA certied.
Features:
Clean Steam – Odorless & Sterile, Bacteria – Free Humidication•
Installation Flexibility – Duct Or Remote Mountable•
On-Board Diagnostics – User Friendly Display Shows Mode Of •
Operation And Status
Fault Annunciation – LED Blinks To Simplify Fault Diagnosis•
Ease Of Service– Quick Release, Stainless Steel Tank•
Versatile Microprocessor Controls – Adaptable To Various Water •
Qualities
Siphon Draining System – Eliminates The Chance Of Blocked •
Solenoid Valves And Drains At A Safe Temperature
Compact Chassis Design – Light Weight And Simple To Install •
Silent Operation•
Full Complement Of Accessories•
CSA Certied •
02-0405
Tank Detail
Applications:
Residential•
Commercial•
Hospitals•
Computer Rooms•
Laboratories•
Clean rooms•
Telecommunications•
Switch Gear Facilities•
Humidors•
Warranty:
2-Year Limited Warranty•
www.trioninc.com | www.herrmidifier-hvac.com
TECHNICAL ENGINEERING SPECIFICATION
13.00"
16.00"
14.00"
11.63"
9.00"
11.88"
10.88"
1.50"
4.50"
Humidistat
Wiring
Electrical
Knockout
Steam
Outlet
Supply Water
Connection
13.00"
16.00"
14.00"
11.63"
9.00"
COMFORTSTEAMTM Dimensional Data
TM
COMFORTSTEAM
Humidification System
COMFORTSTEAM
Top View
TM
Specifications
Front View
Side View
Specifications CFS-05B CFS-05D CFS-05R CFS-05 CFS-10 CFS-15
Capacity (GPD/PPH)
Kilowatts (KW) 1.5 1.5 1.5 1.5 3.0 4.0
Voltage 120 VAC 120 VAC 120 VAC 120 VAC 240 VAC 240 VAC
Full Load Amps (FLA) 12.5 12.5 12.5 12.5 12.5 16.6
Dimensions 16"H x 13"W x 9”D 16"H x 13"W x 9"D 16"H x 13"W x 9"D 16" H x 13"W x 9"D 16"H x 13"W x 9"D 16”H x 13”W x 9”D
Airow Switch No Yes Yes Yes Yes Yes
Water Hammer Absorber No Yes Yes Yes Yes Yes
Electronic Humidistat Not Included Duct Room Not Included Not Included Not Included
Shipping Weight 23 Lbs. 23 Lbs. 23 Lbs. 23 Lbs. 23 Lbs. 23 Lbs.
Tight Home
2
Average Home
Loose Home
1. Gallons Per Day/Pounds Per Hour (steam)
2. A “Tight Home” is assumed to be well insulated with vapor barriers, tight storm windows and doors, and a dampered replace. Air exchange rate of .5 changes per hour.
3. An “Average Home” is insulated and has a dampered re place, but there are no vapor barriers, storm doors, or storm windows. Air exchange rate of 1.0 change per hour.
4. A “Loose Home” is generally one constructed before 1930, has little or no insulation, no storm doors, storm windows, weather stripping or vapor barriers, and often no effective
dampering of replaces. Air exchange rate is as high as 1.5 changes per hour.
1
13/4.5 13/4.5 13/4.5 13/4.5 26/9 34.5/12
4000 Sq. Ft. 4000 Sq. Ft. 4000 Sq. Ft. 4000 Sq. Ft. 8000 Sq. Ft. 10600 Sq. Ft.
3
4
2000 Sq. Ft. 2000 Sq. Ft. 2000 Sq. Ft. 2000 Sq. Ft. 4000 Sq. Ft. 5300 Sq. Ft.
1300 Sq. Ft. 1300 Sq. Ft. 1300 Sq. Ft. 1300 Sq. Ft. 2600 Sq. Ft. 3500 Sq. Ft.
©2009 Trion®- Indoor Air Quality Solutions | Herrmidier® - Engineered Humidication Solutions Trion® and Herrmidier® are registered trademarks of
www.trioninc.com | www.herrmidifier-hvac.com
Air System Components, Inc. Trion® reserves the right to revise or modify products and/or specications without notice.
All product specications reect available information at the printing of this brochure.
Trion® | 101 McNeill Road | Sanford, NC 27330 | Phone: 800-884-0002 | Fax: 800-458-2379
Web: www.herrmidier-hvac.com | Email: customerservice@trioninc.com