General Water Treatment ..................................................................................................... 3
Potable Water Systems ......................................................................................................... 3
Definitions of Potable Water Systems .................................................................................. 3
Safe Temperatures for Potable Water ................................................................................... 4
Near Water Heater Plumbing................................................................................................ 6
Water Heater System Plumbing ............................................................................................ 8
Stand Alone Water Heater Applications ............................................................................. 10
Multiple Water Heater Applications ................................................................................... 12
Line Voltage Connections .................................................................................................. 15
Low Voltage Connections .................................................................................................. 18
HAZARD SYMBOLS AND DEFINITIONS
Danger Sign: Indicates a hazardous situation which, if not avoided, will
result in serious injury or death.
Warning Sign: Indicates a hazardous situation which, if not avoided,
could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situation
which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous
situation which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if not avoided,
could result in property damage.
This Water Heater must be installed by a licensed and trained Heating
Technician or the Warranty is Void. Failure to properly install this
unit may result in property damage, serious injury to occupants, or possibly death.
NEW FEATURES
20% Larger Screen
Tank Sensor Option
Optional BACnet Gateway
TRIN & STOR
Lx 200-800
H
NTI # 86572
Page 2
2
Water Heater Applications – These instructions apply to plumbing and wiring of
Trinity Lx200-800 units operating as water heaters and covers instructions that are
specific to water heater applications. When these units are installed and operated as a boiler, and not used for
direct fired potable or process water heating, refer to "Appendix B - Boiler Applications: Plumbing & Wiring
Instructions". See Table 1-1 for a list of Application Manuals.
Terminology – The following terms in the instruction manuals are used to differentiate between which
instructions are common-to-both and which are appliance-specific. The term "APPLIANCE" applies to both
kinds of applications (boiler and water heater) and is used when conveying instructions which are common-toboth. The term "BOILER" or "WATER HEATER" is used when conveying instructions which are appliancespecific or specific to one or the other, but not both.
Table 1-1 Instruction Manuals
Appliance
Model No.
Common-to-Both
(Trinity Lx Series)
Appliance-Specific
(Application Based)
Boiler
Lx150-800
Installation
and Operation
Instructions
Appendix A -
Controller and
Touchscreen Display
Instructions
Appendix B Boiler Applications:
Plumbing and
Wiring Instructions
n/a
Water
Heater
Lx200-800
Installation
and Operation
Instructions
Appendix A Controller and
Touchscreen Display
Instructions
n/a
Appendix C - Water
Heating Applications:
Plumbing and Wiring
Instructions
Notes
1
The conversion kit is required to convert the Appliance so it will safely operate with Propane Gas (Lx150-400).
2
Do not convert the Lx600-800 to Propane (LP). Operate with Natural Gas only.
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
1.0 INTRODUCTION
General Installation Requirements
The installation of your NTI Trinity gas water heater must conform to the requirements of this manual, your
local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes.
Where required by the Authority, the installation must conform to the standard for “Controls and Safety Devices
for Automatically Fired Boilers ANSI/ASME CSD-1.
This document pertains to the correct installation and operation of NTI Trinity water heaters models Lx200,
Lx300, Lx400, Lx500, Lx600, Lx700 and Lx800. The instructions detailed in this document supersede any and
all previous instructions provided by NTI, written or otherwise. Each unit is provided with various manuals and
a Natural to LP Conversion Kit for applicable models. See notes and list of Instruction Manuals in Table 1-1.
Natural Gas Only - The Lx600-800 are not approved for operation with Propane (LP
Gas). Failure to comply with instructions will result in damage, serious injury or death.
Be Informed - Read and understand this entire document prior to proceeding with the
installation of the Trinity Lx water heater. Failure to follow the instructions outlined in
this document will result in property damage, serious injury or death.
Service - Failure to have the water heater properly service and inspect on a regular basis
by a qualified service technician may result in property damage, serious injury or death.
Water stored at temperatures between 68-113ºF is ideal for bacteria growth (see Table 1-
1); therefore consuming water from a Water Heater is not recommended. Consuming
water from a Water Heater may cause illness or death.
Page 3
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
3
Mandatory Wall Mounting Protection
follow these instructions may result in property damage, serious injury or death.
The Trinity Lx requires zero clearance to combustible walls; however, code requires all wall mounted
instantaneous water heaters be provided with suitable protection extending the full length and width of the water
heater. This is simply because the heat exchanger is surrounded by air, rather than water, which exposes the
burner flame to the surrounding air in the combustion chamber. Check with local authorities regarding
acceptable protection materials.
General Water Treatment
Prior to connecting plumbing to the water heater, flush the entire system to ensure it is free of sediment, flux,
solder, scale, debris or other impurities that may be harmful to the system and water heater. Toxic chemicals,
such as used for boiler treatment, shall not be introduced into the potable water system.
Potable Water Systems
This water heater is suitable for water (potable) heating and space heating. The water heater can be configured
for “water (potable) heating only” or “combination space heating” and is subject to the following requirements:
1) Piping and components connected to the water heater for use with water (potable) heating or combination
space heating applications shall be suitable for use with potable water.
2) Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water system.
3) This water heater which will be used to supply potable water shall not be connected to any heating system or
component(s) previously used with a non-potable water heating appliance.
4) When the system requires water for space heating at temperatures higher than required for other uses, a
means such as a mixing valve shall be installed to temper the water for those uses in order to reduce scald
hazard potential. These instructions shall include a piping diagram(s) for a typical installation.
Definitions of Potable Water Systems
Each potable water system described below is meant to be used with a storage tank (refer to Table 1-1):
Water (Potable) Heating Only - refers to an open potable water system dedicated to providing domestic
hot water and is not intended for space heating.
Combination Space Heating - refers to an open potable water system where the domestic hot water and
heating system water are drawn from the same storage tank. Heat exchange typically takes place in the water
heater and there is no separation or differentiation between water used for domestic hot water and water used
for space heating.
Storage Tank (Vessel) - refers to a tank used to store hot water that is heated indirectly by a water heater
external to the tank or a container provided for storage of hot water under pressure.
Users Responsibility - This appliance may only be installed and serviced by a qualified installer/service
technician. For normal residential applications this water heater must be serviced/inspected annually, by a
qualified heating technician. Other applications with more strenuous conditions, such as commercial, may require
more frequent service/inspection. As the User/Owner of this equipment, you are responsible for ensuring the
maintenance is performed at the required intervals.
Installers Responsibility - Although most provinces and states follow a national or international building code,
some municipalities impose additional or unique requirements that go beyond what the nationally accepted
standard requires. Combination space heating systems are no exception. Since it is impossible for a manufacturer
to know the particulars of all provincial, state and local codes, it is the installer’s responsibility to consult with
the local regulatory authorities and verify that combination space heating systems are allowed in your particular
jurisdiction. A suggested piping diagram has been included in this manual for information purposes only. In the
interest of public health and safety, it is imperative that any combination space heating system be approved by
local regulatory authorities and installed in accordance with applicable codes and current regulations.
The following is to be read in conjunction with the wall mounting installation instructions
in Section 3.0 of "Installation and Operation Instructions For Trinity Lx Series". Failure to
Failure to have your potable water system regularly inspected and maintained may result
in possible illness or death.
Page 4
4
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
responsibility with respect to installation, maintenance, and operation of this water heater in a combination space
heating application. Failure to follow instructions may result in possible illness or death.
Safe Temperatures for Potable Water
Two factors used to determine safe hot water temperatures are Legionella and scalding. Potable water needs to
be stored at temperatures hot enough to limit the growth of Legionella, yet be cool enough to prevent scalding.
Since both hazards present a potential risk to the user, they must be monitored and controlled. Table 1-1
indicates how water temperature affects Legionella bacteria and contributes to scald injury. Use of a thermostatic
mixing valve in the water heater plumbing system can help protect against both of these hazards. By storing
potable water at higher temperatures, bacteria growth is controlled, while still providing high temperature water
for dishwasher applications and low temperature water for bathing. Before proceeding, read the following
carefully and take all necessary pre-cautions to avoid potential illness and/or injury that can result from
Legionella or scalding hazards.
tanks, water distribution systems, fountains, hot tubs, humidification systems, refrigeration systems and grocery
produce misters. Health authorities agree that Legionella bacteria most often enter the lungs due to aspiration
when contaminated water spray is breathed in as opposed to ingesting drinking water contaminated with the
bacteria. Typical illnesses attributed to Legionella include flue like symptoms (Pontiac Fever) and a potentially
fatal type of pneumonia (Legionnaires’ disease). Failure to follow instructions may result in illness or death.
especially during non-heating seasons or low temperature water applications. Using higher temperature tank
water, routinely maintaining your water system, and having your water tested annually are considered "good
practice" when it comes to controlling conditions that contribute to Legionella. See Table 1-1. Failure to monitor
and maintain your combination space heating system may result in illness or death.
Contributing Factors to Legionella - Experts acknowledge that Legionella is an identified risk in most water
systems. Although eradicating Legionella is improbable, pre-cautions can be taken to control and monitor
conditions that promote bacteria growth. According to the World Health Organization (WHO); American
Society of Heating, Refrigeration, and Air-conditioning Engineers (ASHRAE); Canada Safety Council (CSC);
and Centers for Disease Control (CDC), contributing factors to the growth of Legionella in potable water
systems include:
Minerals and nutrients present in the source water and systems materials
Stagnation or low flow characteristic of dead ends in distribution piping systems and storage tanks
Scale, corrosion, and bio film
Tepid water in cold water lines
Water storage temperatures optimal for bacteria growth
Chlorine concentration
setting on the tank thermostat, refer to the thermostat manufacturers recommended settings. Failure to follow
these instructions may result in serious injury or death.
Combination Space Heating - A boiler with indirect fired water heater is the preferred
method for combination space heating; therefore, the building owner assumes all risk and
Legionella Hazard - This bacteria is naturally occurring in surface water and ponds. It
can also be found in man-made water systems around the world such as water storage
High Risk Application - Combination space heating systems can present a significantly
higher risk of developing Legionella than dedicated domestic hot water systems,
Scald Hazard - Hotter water increases the risk of scald injury. There is a hot water scald
potential if the storage tank thermostat is set too high. Before changing the temperature
A scald injury can occur when hot steam or liquid makes contact with one or more layers
of skin. Scald severity (degree of burn) is directly impacted by exposure time and
temperature. Refer to Table 1-1. The following basic precautions are common sense:
Young children and elderly adults burn more quickly and should use cooler water.
Never leave a child alone while drawing water in a bathtub.
Test the water temperature before bathing or showering.
Turn cold water on first, then add hot water until the temperature is comfortable.
Page 5
5
Water Temperature1
Legionella Bacteria 1
Water Temperature
2,5
Exposure Time vs Burn 5
158-176oF
70-80oC
Disinfection range
158oF
70oC
1 second - 2nd or 3rd degree burn
140-149oF
60-65oC
Bacteria die within minutes
140oF
60oC
5 seconds - 2nd or 3rd degree burn
122-131oF
50-55oC
Bacteria die within hours
131oF
55oC
5 seconds - 1st degree burn
68-113oF
20-45oC
Bacteria thrive and multiply
122oF
50oC
1 minute - 1st degree burn
below 68oF
below 20oC
Bacteria is dormant
111oF
44oC
5 hours - 1st degree burn
3,4
Notes:
1
Published by Chartered Institute of Plumbing and Heating Engineering, Databyte series, "Safe Hot Water Temperatures".
2
The elderly and small children are susceptible to bad burns at shorter exposure times than listed in this table.
3
A thermostatic mixing valve should be installed on DHW storage tanks when outlet temperatures exceed 115oF [46oC].
4
Typical water temperature for bathing or showering range between 98-113oF [37-45oC].
5
Temperature-Time-Burn Chart published by John Hopkins University, excluding notes.
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
Thermostatic Mixing Valve - When the system requires water at temperatures higher
than required for other uses, such as high temperature applications typically greater than
46oC (115oF), a means such as a thermostatic mixing valve shall be installed to temper the water for those uses
in order to reduce scald hazard potential. Anit-scald devices such as a thermostatic mixing valve allows potable
water to be stored at a higher temperature to limit bacteria growth, and allows water at the tap to be delivered at
a lower temperature to prevent scalds. Failure to follow these instructions may result in serious injury or death.
Water stored at temperatures between 68-113ºF is ideal for bacteria growth (see Table 1-
1); therefore consuming water from a Water Heater is not recommended. Consuming
water from a Water Heater may cause illness or death.
Legislation and Guidelines - At the time this document was written, standards and
guidelines regulating the prevention of Legionella in the United States and Canada were
mostly voluntary. The American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
(ASHRAE) is currently in the process of converting its guideline entitled "Minimizing the Risk of Legionellosis
Associated with Building Water Systems" (ASHRAE Guideline 12-2000) into an official standard. Consult with
your local authorities as to recommended guidelines for controlling Legionella in potable water systems.
General Guidelines - In the absence of a National standard or local codes, the following are general guidelines
for “good practice” on maintaining, monitoring and operating your potable water system:
Store hot water at temperatures > 60oC (140oF) for “water (potable) heating only” applications.
Store hot water at temperatures > 80oC (176oF) for “combined space heating” applications.
Store and distribute cold water at temperatures below 20oC (68oF).
System supply for uses other than high temperature applications typically greater than 46oC (115oF) shall be
equipped with a thermostatic mixing valve on the hot water outlet to reduce potential scald hazards.
Clean aerators and nozzles on water fixtures on a regular basis to reduce scale build-up.
Clean storage tanks and remove sediment. Flush storage tanks and piping systems regularly for 10-30
minutes at high water temperatures (depending on guidelines used) to rid the system of sediment and scale
that develops, typically in the bottom of storage tanks where water temperature is coolest and piping runs
where water can stagnate.
Abandoned water lines should be capped off at the distribution main, not at the most convenient place.
Avoid dead-ends in piping system. If unavoidable, provide a drainage port in these areas at the lowest point
to flush out stagnant water regularity.
Insulate DHW recirculation lines and keep pipe runs as short as possible.
Recommend annual water testing of water in your tank and piping system(s) to monitor water conditions.
Keep a maintenance record of when your water heater and storage tank were cleaned, piping systems
flushed and who did the service work.
Table 1-1 How Water Temperature relates to Legionella and Scald Hazard
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
2.0 WATER HEATER SYSTEM PIPING
The heat exchanger of the Trinity Lx water heater is designed to attain the highest level of heat transfer in a
compact design. To accomplish this, the heating water flows through a series of fin shaped tubes, designed to
maximize the heat transfer area. To maintain the efficient and reliable operation of the heat exchanger, and to
avoid heat exchanger failure, it is critical to ensure the rules and guidelines in this section are followed.
Water Chemistry - The installer of the Trinity Lx water heater must consider the condition of the water in the
water heating system. Ensure the water hardness condition falls within the following recommended parameters
to avoid scale build-up and aggressive PH levels that can result in corrosive reactions and damage to the heat
exchanger and system components:
Water hardness – between 5 and 25 Grains/gal.
chemicals, such as used for boiler treatment must not be introduced into the potable water system.
System Preparation -During the assembly of the water heating system, it is important to keep the inside of the
piping free of any debris including construction and copper dust, sand and dirt. For retrofits, this water heater
which will be used to supply potable water shall not be connected to any heating system or component(s)
previously used with a non-potable water heating appliance. All systems, old and new, must be cleansed to
remove flux, grease and carbon residue.
Near Water Heater Plumbing
Pressure Relief Valve - All Trinity Lx models dual certified as either a boiler or a water heater (Lx200-800)
have an additional factory supplied pressure relief valve. For water heater installations, use the higher pressure
relief value along with the corresponding higher pressure gauge. See Table 2-1 for pressure relief valve sizes.
The pressure relief valve must be installed at the water heater outlet and in the vertical position with the drain
pipe outlet exiting the side of the pressure relief valve horizontally and elbowing down. See Figures 2-1(a),(b).
installation or plugged. Failure to follow these instructions may result in serious injury or death.
Pressure Gauge - All Trinity Lx models dual certified as either a boiler or a water heater (Lx200-800) have an
additional factory supplied pressure gauge which must be installed at the water heater outlet prior to any
circulators, and in the vicinity of the pressure relief valve. Figures 2-1(a),(b). When using a higher pressure relief
valve, such as 125PSI, ensure the pressure gauge is sized to display the higher pressure value (e.g. 160PSI
pressure gauge). See Table 2-1 for pressure gauge sizes.
Failure to follow the instructions provided in this section will void the NTI warranty and
may result in property damage, fire, serious injury or death.
Water heater water that falls outside of the parameters listed above must only be
conditioned or treated with products approved for potable hot water systems. . Toxic
If installed with the incorrect orientation (horizontally with drain pipe out the bottom) the
relief valve may not function properly resulting in property damage or personal injury.
The Trinity Lx water heater is provided with a pressure relief valve. For safe operation of
the water heater, the relief valve(s) must not be removed from its designated point of
Ensure the discharge of the pressure relief is piped to a location where the steam or water
will not cause property damage or serious injury.
Page 7
7
Figure 2-1(a) Lx200-400 Models
Near Water Heater Piping
Figure 2-1(b) Lx500-800 Models
Near Water Heater Piping
Pressure Relief
Valve discharge
to floor drain
Outlet
To Water Heater and
system plumbing. Refer
to piping diagrams.
Mandatory Safety
Flow Switch
Pressure Gauge
Pressure Relief Valve
Inlet
Pressure Relief
Valve discharge
to floor drain
Near Water
Heater tees
and fittings
Safety Flow Switch
Pressure Relief Valve
Pressure Gauge
Trimmable paddle
Outlet
Inlet
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
Page 8
8
Model
Trigger Point
(no lower than)
Line Size for
Flow Switch
IMPORTANT: After the flow
switch, increase pipe diameter to the
size specified in Tables 2-4 or 2-5.
Refer to Section 3.0 for instructions
on wiring the safety flow switch.
Lx200
6 gpm
1
Lx300
9 gpm
1-1/4”
Lx400
12 gpm
1-1/4”
Factory Supplied Components
Field Supplied Components
Pressure Relief Valve (125PSI)
Bronze/Stainless SteelWater Heater Circulator (Pump B in Figure 2-2)
Pressure Gauge (160PSI)
System Backflow Preventor (check if required by local codes)
Flow Switch (Lx500-800 only)
DHW/Potable Water Expansion Tank (check if required by local codes) *
DHW Storage Tank
Tank Temperature and Pressure Relief Valve
Tank Thermostat (aquastat)
Thermostatic (Anti-Scald) Mixing Valve
Safety Flow Switch
General Notes
1
Expansion Tank is mandatory if using a System Backflow Preventor.
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Safety Flow Switch - A safety flow switch is required by code to ensure a sufficient rate of water supply is
available for proper operation of the water heater. The Lx500-800 are the only NTI models factory equipped with
flow switch. Locate the flow switch in series with the water heater and in accordance with the instructions
provided with the safety flow switch. NTI recommends a safety flow switch with a trigger point no lower than
the gpm specified in Table 2-2. Install the flow switch in a 1”diameter line for model Lx200 and a 1-1/4”
diameter line for model Lx300-400 at the appliance outlet.
Table 2-2Flow Switch Installation Requirements
When external safety devices are used, such as a LWCO, Flow Switch, or a Temperature
Limiting Switch, they must be wired as per the instructions provided in this manual. Refer
to Section 3.0 for more information.
requirements of these devices prior to installing the water heater as a LWCO is not required on Instantaneous
Water Heaters. Refer to Section 3.0 Field Wiring for more information.
Water Heater System Plumbing
The Trinity water heater uses a low mass heat exchanger that requires a minimum rate of forced water circulation
any time the burner is operating (See Table 2-3 for minimum flow rates). To ensure the minimum flow rate is
attained, the water heater must be installed with a safety flow switch (see Figure 2-2 for suggested plumbing
diagram). A properly installed system will as a minimum include the major components in Table 2-3.
Table 2-3System Major Component Checklist
When external safety devices are used, such as Safety Flow Switch, they must be wired as
per the instructions provided in this manual. Check with your local authorities as to the
Water Heater Circulator - The Lx water heater is equipped with three 120VAC pump outputs (Pump A, B and
C). Use only Pump Output B for the Water Heater Circulator. Note that bronze or stainless steel circulators are
required for potable water systems. Ensure that circulators (pumps) are oriented as per the pump manufacturers’
instructions. See Section 3.0 for wiring details.
Circulators responsible for forcing the water flow rate through the water heater must be
sized according to Table 2-4.
The installer must ensure a sufficient rate of water supply is available for proper operation
of the water heater prior to installation. A safety flow switch must be installed on the hot
water outlet side to ensure the minimum water flow rate through the water heater. Failure to follow instructions
will not only void the warranty but may also result in fire, property damage, serious injury or death.
Page 9
9
Model
Restriction
Head Loss
Min.
Pipe
Size
Min.
Flow
(GPM)
Max.
Temp.
Rise
Maximum
Current Load
Minimum Pump Size1
B&G
Grundfos
Armstrong
Taco
Lx200
17’ at 16 GPM
1-1/4”
16
23F
5 A or 2/5 hp
PL-36B
-
E8B
0013-SF
Lx300
17’ at 24 GPM
1-1/2”
24
23F
5 A or 2/5 hp
PL-36B
-
E14B/E9B3
2400-30S3
Lx400
22’ at 32 GPM
2”
32
23F
5 A or 2/5 hp
PL-55B
-
E24B
2400-45S
Lx500
17’ at 40 GPM
2”
40
23F
See Note
2
PDB-35
UPS 32-160
E14B
4
2400-50S
4
Lx600
23’ at 48 GPM
2-1/2”
48
23F
See Note
2
PDB-37
UPS 32-160
E-22B5 -
Lx700
19’ at 56 GPM
2-1/2”
56
23F
See Note
2
PDB-37
UPS 32-160
E-33B
6
2400-70S
Lx800
28’ at 64 GPM
2-1/2”
64
23F
See Note2
PDB-38
UPS40-160
-
-
Notes:
1
Pump models listed are for bronze or stainless steel circulators only; cast iron pumps are not permitted.
2
Maximum Current Load 1-1/2hp @ 120VAC or 3hp @ 240VAC.
3
Armstrong pumps E10B-E13B, and Taco pump 2400-40S are not recommended.
4
Armstrong pumps E15B-17B, and Taco pump 2400-60S are not recommended.
5
Armstrong pump E23B-E33B not recommended.
6
Armstrong pumps E22B and E24B also recommended.
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
This water heater must have water flowing through it whenever the burner is on or it will
damage the unit and void the warranty. Failure to follow these instructions may result in
fire, property damage, serious injury or death.
Table 2-4 Minimum Water Heater Circulator and Pipe Sizes
System Backflow Preventor - Check if a backflow preventor is required by local codes. This manufacturer and
most plumbing codes require a thermal expansion control device be installed if a backflow preventor, pressure
reducing valve or check valve is installed on a domestic supply line. Installing an expansion tank approved for
use with potable water is mandatory in applications using a System Backflow Preventor device. DHW/Potable Water Expansion Tank - Check if an expansion tank is required by local codes. If required, the
expansion tank must be suitable for use with potable water and be sized in accordance with the water volume of
the system as well as the firing rate of the appliance. The expansion tank must be installed downstream of any
backflow prevention device used to control system thermal expansion. See examples in Figure 2-3.
Ensure the expansion tank cannot become isolated from the water heater anytime the
system is operating. Failure to follow these instructions may result in discharge of the
Pressure Relief Valve may result in property damage or personal injury.
DHW Storage Tank - Storage vessels shall be equipped with a drain valve to facilitate emptying the tank for
cleaning or flushing debris or foreign deposits. Drain valves on counter type water heaters shall be accessible
from the front of the heater.In Canada, glass-lined storage tanks for household hot water service must comply
with the current performance requirements in CAN/CSA C309.
The DHW storage tank should be located in an area where leakage or connections will
not result in damage to the area adjacent to the appliance or to lower floors of the
structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately
drained, be installed under the appliance. This manufacturer is not responsible for any water damage that may
occur in connection with the storage tank or any of its components.
Tank Temperature and Pressure Relief Valve - The storage tank will require a temperature and pressure relief
valve sized to ASME specifications and that complies with the Standard for Relief Valves for Hot Water Supply
Systems, ANSI Z21.22•CSA 4.4. The relief valve is to be installed on the storage tank in accordance with Figure
2-3 and must be accessible for servicing or replacement. No valve is to be place between the T&P Relief Valve
and the storage tank. Check if local codes require storage tanks to have any additional valves.
Ensure the discharge of the temperature and pressure relief valve is piped to a drain or a
location where steam or water will not cause property damage, serious injury or death.
Page 10
10
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Tank Thermostat (Aquastat) - The aquastat is intended to allow the water heater to monitor and control tank
temperature, improve response time, and prevent short cycles of operation. Check that the aquastat will mate
with the tapping on the storage tank prior to commencing installation. Install the aquastat in the storage tank as
per the manufactures’ instructions. Refer to Section 3.0 Field Wiring for details.
Tank Sensor – In lieu of a Tank Thermostat, the Lx water heater control can monitor a tank sensor installed in
the storage tank. When a tank sensor is used, the tank temperature is set via the Lx control; burner demands are
generated directly by the Lx controller based on controller settings.
Tank sensor MUST be used in conjunction with a DHW temperature safety shutoff
switch. NTI recommends using P/N 84632 (Tank Sensor w/integrated safety switch).
Failure to provide such a switch may result in property damage, serious injury to
Thermostatic (Anti-Scald) Mixing Valve - An anti-scald mixing valve is recommended when storing domestic
hot water above 46°C (115°F) and should be used on branches supplying low temperature water to endpoint
plumbing fixtures. A mixing valve is optional on high temperature water applications, including but not limited
to process water, clothes washers, dishwashers or sanitizers, depending on the temperature desired at the
appliance and water storage temperature.
order to reduce scald hazard potential. Failure to follow these instructions may result in serious injury or death.
Stand Alone Water Heater Applications
In a stand alone (single) water heater application, the thermostat (aquastat) in the storage tank is connected to the
water heaters low voltage terminal strip and is used to trigger a DHW demand by completing the "DHW" to
"Sensor COM" circuit. See Table 3-2 for more details. Figures 2-2 is an example of a plumbing configuration for
stand alone water heaters using a single system circulator. This schematic also illustrates an optional low
temperature and/or high temperature return loop.
Figure 2-2: Stand Alone Water Heater Applications - This piping diagram demonstrates an application with
both low temperature requirements, such as bathing, and high temperature requirements, such as commercial
process water heating or laundry. When the system requires water at temperatures higher than required for other
uses, a thermostatic (anti-scald) mixing valve shall be installed to temper the water for those uses in order to
reduce scald hazard potential, see Table 1-1. An optional DHW Recirculation Return may be used on long
plumbing runs to prevent wait times for hot water on both low and high temperature water applications. Refer
to Section 3.0 for field wiring instructions.
installation. Concepts not shown include: prevention of thermal-siphoning (i.e. heat traps), isolation valves,
drain and purge valves, etc. It is the responsibility of the installing contractor and system designer to consider all
aspects of a proper system design including compliance with local codes. Contractor modifications to these
instructions may be required, based upon existing piping and system design.
Energy Efficiency - Although the Trinity Lx Water Heater is an energy efficient appliance, insulating long pipe
runs can improve the overall system efficiency by conserving energy and reducing standby losses.
occupants, or possibly death.
When the system requires water at temperatures higher than required for other uses, a
means such as a mixing valve shall be installed to temper the water for those uses in
The Water Heater Circulator (Pump B) must be sized according to Table 2-4 to provide
adequate circulation through the water heater.
Figure 2-2 illustrates a typical piping system. The Water Heater Plumbing Schematic
does not illustrate all of the required concepts and components required to have a proper
Page 11
11
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
Figure 2-2 All Models
Stand Alone Water Heater Plumbing Configuration
Page 12
12
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Multiple Water Heater Applications
The Lx controller has the internal capacity to stage or Lead-Lag up to 8 water heaters configured in a cascade.
This Lead-Lag capability allows a designated “Master” water heater to communicate with and effectively control
each water heater in a multiple water heater system. This function is accomplished by “Daisy Chaining” a 3wire cable between each of the water heaters and enabling the Master parameter in the water heater of your
choice. The water heater with the Master parameter enabled becomes the single point of contact for settings and
control wiring. Use the instructions detailed in this section to set-up and install the cascade water heater system;
reference Appendix A – Controller and Touchscreen Display Instructions for details on more advanced settings
and for assistance with navigating the touchscreen display.
Lead Lag Instructions
Plumbing – install as many as 8 Lx water heaters in a parallel plumbing configuration as illustrated in Figure 2-3.
Size common piping as per Table 2-5.
Water Heater Pump – each water heater must have its own circulator (see Figure 2-3) which is controlled by its PUMP B output; see Field Wiring Figures and Tables 3-1(a) and 3-1(b). The water heater pump must be sized
according to Table 2-4.
Communication Wiring – using 3-wire cable, daisy-chain terminals LL DATA +, LL DATA – and SENSOR
COM of each water heater in parallel; see Field Wiring Tables 3-2(a) and 3-2(b) and Figure 3-2.
System Sensor – a system sensor is NOT used in a water heater application, at the Master boiler set the
applicable sensor input to Unconfigured as follows:
Modbus Address – assign a unique MB2 Modbus Address to each water heater in the cascade. Access the MB2
Modbus Address setting via the System Identification & Access menu as follows:
Configure – System Identification & Access – MB2 Modbus Address
Master Enable – choose one (and only one) water heater in the cascade to be the Master, this water heater will
receive all control wiring and will be used for setting control parameters (see steps below). On this one water
heater, set Master enable equal to Enabled via the Lead Lag Master Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Master enable
Tank Thermostat – connect to SENSOR COM and DHW of the Master water heater; see Field Wiring Tables 3-
2(a) and 3-2(b) and Figure 3-2. Switch must be an isolated end switch (dry contact).
DHW Setpoint – at the Master water heater only, set the DHW setpoint via the Lead Lag Master Configuration
menu, accessed as follows:
Configure – Lead Lag Master Configuration – DHW setpoint
DHW switch (Lead Lag) – at the Master water heater only, set DHW switch equal to DHW (S6) sensor shorted
via the Lead Lag Master Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Advanced Settings – Domestic Hot Water – DHW switch
DHW enable (Local) – at the Master water heater only, set DHW enable equal to Disabled via the Domestic Hot
Water Configuration menu, accessed as follows:
Configure – Domestic Hot Water Configuration – DHW enable
Tank Sensor – when operating in a cascade system, the water heater controls do not
support the use of a tank sensor; a tank thermostat (switch) must be used.
Page 13
13
# of
Units
Lx200
Lx300
Lx400
Lx500
Lx600
Lx700
Lx800
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
Pipe Size
2
2"
2-1/2"
3"
3"
4"
4"
4"
3
2-1/2"
3"
4"
4"
4"
4"
4" 4 3"
4"
4"
4"
4"
5"
5"
5
3"
4"
4"
4"
5"
5"
5" 6 4"
4"
4"
5"
5"
5"
5" 7 4"
4"
5"
5"
5"
6"
6"
8
4"
4"
5"
5"
5"
6"
6"
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
Table 2-5 Minimum Pipe Sizes for Multiple Water Heater Applications
All Water Heater piping in Multiple Water Heater Applications must be sized based on
Table 2-5 in accordance with the number of units the piping supports.
All water heater circulators (Pump B) must be sized according to Table 2-4.
Page 14
14
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Figure 2-3 All Models
Multiple Water Heater Lead-Lag Plumbing Configuration
Page 15
15
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
3.0 FIELD WIRING
All wiring must be in accordance with the Canadian Electrical code, CSA C22.2 and any applicable local codes.
Ensure that the wiring complies with this manual. The water heater must be electrically grounded in accordance
with the National Electrical Code ANSI/NFPA 70, local codes, and/or the Canadian Electrical Code CSA C22.1.
any wiring connections are being made. Failure to follow these instructions may result in component failure,
serious injury or death.
Line Voltage Connections
Electrical rating for the Trinity Lx is 120V/1 Phase/60 Hz /12A. The Trinity Lx line voltage junction box is
located in the lower right corner of the water heater cabinet on model Lx200 and can be accessed by removing
the front door of the water heater, followed by the removal of the line voltage junction box cover. On Lx300 and
Lx400 models, the line voltage junction box is located at the top of the cabinet on the right hand side and can be
accessed by removing the top front cover of the water heater. On Lx500-800 models, the line voltage junction
box is located at the back of the cabinet on the power switch side. Remove the top back cover of the water heater
to access the three holes / knockouts needed for routing field wiring into the line voltage junction box. Line
voltage field connections are to be installed in accordance with Figures 3-1 and Tables 3-1 respectively.
Fuses (120VAC) – The Trinity Lx is equipped with either one or two 7 Amp fuses to protect 120VAC system
components. The fast-acting fuses are located on the front of the control panel box and can be easily accessed
from the outside of the control panel.
Lx200-400 Control Panel:
Fuse A: Protects the blower, spark generator and PUMP B output circuits.
Fuse B: Protects PUMP A and C output circuits.
Lx500-800 Control Panel:
Fuse A: Protects the 120VAC circuits within the appliance.
Pump Relays (Lx500-800) – In lieu of the 120VAC pump outputs, the Lx500-800 incorporates three non-
powered isolation relay contacts for switching high capacity pumps. Contact Secondary Maximum rating is
1.5HP @ 120V, 3.0HP @ 240V, or 30A. Refer to Figure 3-3(b) for Field Wiring requirements.
Failure to follow these instructions may result in component failure, serious injury or death.
Amps. Failure to follow instructions may result in component failure, serious injury or death.
result in property damage or personal injury.
or damage electrical components. Also check the polarity of the line and neutral wires. Line must measure
120VAC to ground; neutral must measure zero. Failure to follow instructions may damage the unit.
motor. See Table 3-1. Circulator outputs PUMP A and C are not to be used for water heater applications.
Avoid Shocks - To Avoid Electrical Shock, turn off electrical power to the water heater
prior to opening any electrical box within the unit. Ensure the power remains off while
Field Wiring - Wire grommets must be used to secure wiring and prevent chafing when
passing wiring through the cabinet wall. Failure to follow instructions may damage unit.
Wire Protection - When passing any wiring through the cabinet of the water heater, the
installer must use wire grommets suitable for securing the wiring and preventing chafing.
Power Supply - The Trinity Lx is designed to be powered by a single phase 120VAC
power supply that is fused (or protected via a circuit breaker) to allow a maximum of 15
Labeling - Label all wires prior to disconnecting them when servicing controls. Wiring
errors can cause improper and dangerous operation. Failure to follow instructions may
Continuity - Before connecting line voltage wiring, perform a continuity check between
all wires and ground to make sure that there are no electrical leaks that could blow a fuse
Max Load - Pump output B is used to control the Water Heater Circulator and is limited
to operating a circulator with a maximum current load of 5 Amps or a maximum 2/5 hp
Page 16
16
Line Voltage Field Wiring
Table 3-1 Line Voltage Field Connections
Connection
Location
Description
L1
(120VAC)
1
120VAC Hot - Location for connecting line voltage of the power supply. Note most
installation codes require the installation of a service switch to break line voltage to the
appliance.
PUMP A
2
Not used.
PUMP B
3
DHW Demand - Output to the Water Heater Circulator, powered during tank demand.
PUMP C
4
Not used.
L2
(Neutral)
5
120VAC Common - Location for connecting neutral of the power supply and circulator.
6
Ground
7
120VAC Ground - Location for connecting ground of the power supply and circulator.
8
No Conn.
9
Factory Wiring - This terminal is used only for factory wiring. Do not add or remove wires
from this location.
PUMP B
Green
White
Black
SERVICE SWITCH
(field supplied)
120VAC SUPPLY_
_Line Neutral Gnd__
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Figure 3-1(a) Lx200-400 Models
Page 17
17
Table 3-1(b) Line Voltage Field Connections (Lx500-800)
Connection
Location
Description
L1 (120VAC)
1
120VAC Hot - Location for connecting line voltage of the power supply. Note most
installation codes require the installation of a service switch to break line voltage to the
appliance.
L2
(Neutral)
2
120VAC Common - Location for connecting neutral of the power supply and circulator.
Ground
3
120VAC Ground - Location for connecting ground of the power supply and circulator.
Non-Powered
Dry Contacts
PUMP
A
4
Not used.
5
PUMP B
6
DHW Demand - Dry Contact for Water Heater circulator; Coil B powered during tank
demands.
7
PUMP C
8
Not used.
9
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
Figure 3-1(b) Lx500-800 Model
Line Voltage Field Wiring
Page 18
18
Connection
Location
Description
COM
(24VAC)
1
24VAC Common – Neutral for the 24VAC power supply within the water heater.
R
(24VAC)
2
24VAC Hot - Power supply for inputs LIM, CH1, and CH2 (LL).
3
LIM
4
External Limit – Input requiring 24VAC from terminal R to permit the burner to
operate. Comes factory equipped with a jumper to the R terminal. Remove the factory
installed jumper and install the normally open isolated contacts of the field supplied
Safety Flow Switch.
CH1 *
5
Local Central Heat Demand– Not applicable for Water Heater Applications.
CH2 (LL) *
6
Lead-Lag Central Heat Demand– Not applicable for Water Heater Applications.
Sensor
DHW
7
DHW Tank Demand – Input requiring closure of terminals 7 and 10 to initiate a demand
for DHW. Switch made via isolated end switch (dry contact) from the storage tank
thermostat (Aquastat). Or optional Tank Sensor (P/N 84632), see Appendix A.
NOTICE: Tank Sensor – when operating in a cascade system, the water heater controls
do not support the use of a tank sensor: a tank thermostat (switch) must be used.
OD
SENSOR *
8
Outdoor Temperature Sensor– Not applicable for Water Heater Applications.
SYSTEM *
9
System Water Temperature– Not applicable for Water Heater Applications.
SENSOR
COM
10
System Common – Common port for field inputs DHW, OD Sensor and System Sensor.
4-20mA
11
External Modulation Control – Using a 4-20mA signal, an external control can be used
to directly modulate the burner firing rate or adjust the active set point. This can be
useful for applications using external staging controls or Building Automation Systems.
12
Communications
LL DATA+
13
Lead-Lag – Connects internally to the controller’s MB2 Modbus communication port.
Terminals 13, 14 and 10 (common) can be "daisy-chained" to multiple water heaters (up
to 8 in total) for the purpose of staging.
LL DATA-
14
BMS D+
15
Building Management System (BMS) – Connects internally to the display’s COM2,
Modbus communication port. Terminals 15, 16 and 10 (common) can be connected to a
Gateway for communication to a BMS or other device.
BMS D-
16
ALARM
17
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm
condition. May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
18
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Low Voltage Connections
The Trinity Lx low voltage junction box is located in the lower left corner of the water heater cabinet on Lx200
models and can be accessed by removing the front door of the water heater, followed by the removal of the low
voltage junction box cover. On Lx300 and Lx400 models, the low voltage junction box is located at the top of
the water heater cabinet on the left hand side and can be accessed by removing the top front cover of the water
heater. The water heater is provided with one hole and two knockouts for routing field wiring into the low
voltage junction box. Low voltage field connections identified in Table 3-2 are to be read in conjunction with
Figure 3-2.
Table 3-2(a) Low Voltage Field Connections
* Asterisk indicates connection not used or applicable for Water Heater Applications. See descriptions in Table 3-2.
Page 19
19
Connection
Location
Description
COM (24VAC)
1
24VAC Common – Neutral for the 24VAC power supply within the water heater.
R1/R2 (24VAC)
2
24VAC Hot - Power supply for inputs EXT. LIM, CH1, and CH2 (LL).
3
EXT. LIM
4
External Limit – Input requiring 24VAC from terminals R1/R2 to permit the burner to
operate. Comes factory equipped with a jumper to the R2 terminal. For installations
requiring the use of an additional safety switch, such as a LWCO or auxiliary temperature
limit, remove the factory installed jumper and install the normally open isolated contacts
of the field supplied additional limit in place of jumper. Flow Switch factory installed and
prewired in series with EXT LIMIT jumper.
GAS LO PR.
1
5
Gas Low Pressure Switch (Optional) – Comes factory equipped with a jumper. For
applications requiring a Low Gas Pressure Switch, remove jumper and connect normally
open isolated contacts of the Gas Low Pressure Switch. Switch must be installed external
to unit (24VAC circuit). For preapproved High Gas Pressure Switch, see Note 1 below.
6
AUX. PROOF
7
Auxiliary Proof – Comes factory equipped with a jumper. For applications using Indoor
Combustion Air (Lx500-800 only), remove jumper and replace with field supplied end
switch incorporated with motorized damper/louver control.
8
CH1 *
9
Local Central Heat Demand– Not applicable for Water Heater Applications.
CH2 (LL) *
10
Lead-Lag Central Heat Demand– Not applicable for Water Heater Applications.
Sensor
DHW2 11
DHW Tank Demand – Input requiring closure of terminals 11 and 14 to initiate a demand
for DHW. Switch made via isolated end switch (dry contact) from the storage tank
thermostat (Aquastat). Or optional Tank Sensor (P/N 84632); see Appendix A.
OD / SYS
SENSOR *
12
Outdoor Temperature Sensor – Not applicable for Water Heater Applications.
System Water Temperature – Not applicable for Water Heater Applications.
TOD
13
Time of Day (Night Time Setback) – Input requiring closure of terminals 13 and 14 to
initiate TOD setback setting. Switch is made using an isolated end switch (dry contact)
using a timer, BAS or other device.
SENSOR
COM
14
System Common – Common port for field inputs DHW, OD Sensor and System Sensor.
4-20mA
(– / +)
15
External Modulation Control – Using a 4-20mA signal, an external control can be used
to directly modulate the burner firing rate or adjust the active set point. This can be useful
for applications using external staging controls or Building Automation Systems.
16
Communications
LL DATA+
17
Lead-Lag – Connects internally to the controller’s MB2, Modbus communication port.
Terminals 17, 18 and 14 (common) can be "daisy-chained" to multiple water heaters (up to
8 in total) for the purpose of staging.
LL DATA-
18
BMS D+
19
Building Management System (BMS) – Connects internally to the display’s COM2,
Modbus communication port. Terminals 19, 20 and 14 (common) can be connected to a
Gateway for communication to a BMS or other device.
BMS D-
20
ALARM
(A & B)
21
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm
condition. May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
22
Notes
1 For applications requiring a High Gas Pressure Switch, see supplemental instructions included with NTI High Gas
Pressure Switch Kit, P/N 84094. Note: this is the only High Gas Pressure Switch that has been tested with the unit
and preapproved for field installation within the appliance cabinet.
2 Tank Sensor – when operating in a cascade system, the water heater controls do not support the use of a tank sensor; a
tank thermostat (switch) must be used.
* Asterisk indicates connection not used or applicable for Water Heater Applications.
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
Table 3-2(b) Low Voltage Field Connections (Lx500-800)
Page 20
20
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
Low Voltage Terminals -Terminals 2 and 3 (R) have 24VAC potential from the internal
transformer. Do not connect power from these terminals to any other terminal other than
terminals 4, 5 and/or 6 [LIM, CH1, and CH2 (LL)] via an isolated end switch (dry
contact). Failure to follow these instructions may damage the unit.
Fuse (24VAC) - Trinity Lx150-400 models are equipped with a “blade style” 2 Amp fuse
to protect the internal transformer located within the slide-out control panel box.
Figure 3-2 All Models (Lx150-400 shown)
Low Voltage Field Wiring
Page 21
21
Water Heater Applications Plumbing and Wiring Instructions │Trinity Lx
NOTES
Page 22
22
Trinity Lx│Plumbing and Wiring Instructions Water Heater Applications
NOTES
Page 23
NOTES
Page 24
NY Thermal Inc. 65 Drury Cove Road Saint John, NB E2H 2Z8 Canada
Technical Assistance: 1-800-688-2575
Website: www.nythermal.com
Fax: 1-506-432-1135
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.