Trident PD765-6R3-10, PD765-6R2-00, PD765-7R0-00, PD765-6R5-10, PD765-7R2-00 Instruction Manual

...
TRIDENT & TRIDENT X2
MODEL PD765
Instruction Manual
Accepts Current, Voltage, TC, & RTD Inputs
4 Digit Display, 0.56" (14 mm) or 1.20" (31 mm)
Linear or Square Root with Low-Flow Cutoff
Maximum/Minimum Display
Type 4X, NEMA 4X, IP65 Front
Universal Power Supply 85-265 VAC
12-36 VDC/12-24 VAC Power Option
Two Relays and 4-20 mA Output Option
24 VDC Transmitter Power Supply Options
USB, RS-232, & RS-485
Serial Communication Adapters Options
Free Modbus
®
RTU Protocol
Copy Meter Settings to Other Meters
Free MeterView
®
Software - Configuration & Data Acquisition
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
2
Disclaimer
The information contained in this document is subject to change without notice. Precision Digital makes no representations or warranties with respect to the contents hereof, and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
Registered Trademarks
MeterView® is a registered trademark of Precision Digital Corporation, Modbus
®
is a registered trademark of Schneider Automation Inc. All other trademarks mentioned in this document are the property of their respective owners.
© 2011-2016 Precision Digital Corporation. All rights reserved.
INTRODUCTION
The Trident is a multipurpose, easy to use digital panel meter. It accepts current, voltage, thermocouple, and RTD signals. The four front panel buttons make the setup and programming an easy task.
The isolated 24 VDC transmitter power (optional) can be used to power the input transmitter, the 4-20 mA output, or other devices.
The two relays (optional) can be used for alarm indication or process control applications, such as pump alternation control.
Two relays and a 4-20 mA output are available together in the same meter. The 4-20 mA isolated output and Modbus
®
RTU serial communication
options make the Trident an excellent addition to any system.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
3
ORDERING INFORMATION
Trident
85-265 VAC Model
12-36 VDC Model
Options Installed
PD765-6R0-00 PD765-7R0-00 No options
PD765-6R0-10 24 V transmitter supply
PD765-6R2-00 PD765-7R2-00 2 relays
PD765-6R2-10 2 relays & 24 V transmitter supply
PD765-6R3-00 PD765-7R3-00 4-20 mA output
PD765-6R3-10 4-20 mA output & 24 V supply
PD765-6R3-20 4-20 mA output & dual 24 V supplies
PD765-7R5-00 2 relays & 4-20 mA output
PD765-6R5-10 2 relays, 4-20 mA output, & 24 V supply
Trident X2
85-265 VAC Model
12-36 VDC Model
Options Installed
PD765-6X0-00 PD765-7X0-00 No options
PD765-6X0-10 24 V transmitter supply
PD765-6X2-00 PD765-7X2-00 2 relays
PD765-6X2-10 2 relays & 24 V transmitter supply
PD765-6X3-00 PD765-7X3-00 4-20 mA output
PD765-6X3-10 4-20 mA output & 24 V supply
PD765-6X3-20 4-20 mA output & dual 24 V supplies
PD765-7X5-00 2 relays & 4-20 mA output
PD765-6X5-10 2 relays, 4-20 mA output, & 24 V supply
Accessories
Model Description
PDA7232 RS-232 serial adapter with PDA7420 included
PDA7420 Trident meter copy cable, 7' (2.1 m)
PDA7422 RS-485 serial adapter with PDA7420 included
PDA7485-I RS-232 to RS-485 isolated converter
PDA7485-N RS-232 to RS-485 non-isolated converter
PDA8485-I USB to RS-422/485 isolated converter
PDA8485-N USB to RS-422/485 non-isolated converter
PDA8006 USB Serial Adapter
MeterView® Free MeterView® software download at www.predig.com
Enclosures NEMA 4 & explosion-proof enclosures – See Web site.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
4
Table of Contents
INTRODUCTION ------------------------------------------------------------ 2 ORDERING INFORMATION --------------------------------------------- 3 SPECIFICATIONS ---------------------------------------------------------- 7
General ------------------------------------------------------------------------------- 7 Process Input ---------------------------------------------------------------------- 8 Temperature Inputs -------------------------------------------------------------- 9 Relays Option -------------------------------------------------------------------- 10 Isolated 4-20 mA Transmitter Output ------------------------------------ 11 Serial Communications ------------------------------------------------------- 11
COMPLIANCE INFORMATION ---------------------------------------- 12
Safety ------------------------------------------------------------------------------- 12 Electromagnetic Compatibility --------------------------------------------- 12
SAFETY INFORMATION ------------------------------------------------ 13 INSTALLATION ------------------------------------------------------------ 14
Unpacking ------------------------------------------------------------------------- 14 Panel Mounting ------------------------------------------------------------------ 14 Connections ---------------------------------------------------------------------- 15
Connector Labeling ---------------------------------------------------------- 15 Power Connections ---------------------------------------------------------- 16 Signal Connections ---------------------------------------------------------- 16 Serial Communication ------------------------------------------------------- 20 Relays and 24 V Output Connections ----------------------------------- 20 Switching Inductive Loads -------------------------------------------------- 20 4-20 mA Output & Input Signal Connections -------------------------- 22
SETUP AND PROGRAMMING ---------------------------------------- 23
Front Panel Buttons and Status LED Indicators --------------------- 24 Display Functions and Messages ----------------------------------------- 25 Main Menu ------------------------------------------------------------------------ 28 Setting Numeric Values ------------------------------------------------------ 28 Setting Up the Meter (setu) ------------------------------------------------- 29
Setting the Input Signal (inpt) -------------------------------------------- 30 Setting the Decimal Point (dc.pt) ----------------------------------------- 31 Setting the Temperature Scale (F C) ---------------------------------- 31 Programming the Meter (prog) ------------------------------------------- 32 Scaling the Meter (scal) ---------------------------------------------------- 33 Calibrating the Meter (Cal) ------------------------------------------------- 35 Recalibrating Temperature Inputs (Cal) -------------------------------- 35
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
5
Recalibrating Process Inputs (ICal) ------------------------------------- 36 Setting the Relay Operation (rely) -------------------------------------- 37 Relay and Alarm Operation ------------------------------------------------ 41 Pump Alternation Control Operation ------------------------------------- 46 Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 47 Program the Sensor Break Output Value (SEbr) --------------------- 48 Analog Output when Display is Out of Range ------------------------- 48
Setting Up the Password (pass) ------------------------------------------- 49
Locking the Meter ------------------------------------------------------------ 49 Unlocking the Meter ---------------------------------------------------------- 49
Advanced Features Menu ---------------------------------------------------- 50
Advanced Features Menu & Display Messages ---------------------- 51 Offset Adjustment (Adj) ----------------------------------------------------- 53 Noise Filter (fltr) ------------------------------------------------------------ 53 Noise Filter Bypass (byps) ------------------------------------------------- 54 Serial Communications (serl) -------------------------------------------- 54 Protocol Selection Menu (Prot) ------------------------------------------ 54 Select Menu (SElc) ---------------------------------------------------------- 55 Linear or Square Root Function (linr or Sqrt) ---------------------- 55 Low-Flow Cutoff (cutF) ----------------------------------------------------- 56 Display Intensity (inty) ----------------------------------------------------- 56 Meter Copy Function (Copy) ----------------------------------------------- 57 Internal Calibration (ICal) -------------------------------------------------- 59
OPERATION ---------------------------------------------------------------- 62
Front Panel Buttons Operation -------------------------------------------- 62 Maximum/Minimum Readings ---------------------------------------------- 63
MOUNTING DIMENSIONS ---------------------------------------------- 64 TROUBLESHOOTING ---------------------------------------------------- 65
Diagnostics Menu (diag) ----------------------------------------------------- 65
Determining Software Version -------------------------------------------- 65
Reset Meter to Factory Defaults ------------------------------------------- 66
Factory Defaults & User Settings ----------------------------------------- 67
Troubleshooting Tips --------------------------------------------------------- 69
QUICK INTERFACE REFERENCE GUIDE ------------------------- 70 EU DECLARATION OF CONFORMITY ----------------------------- 73
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
6
Table of Figures
Figure 1. Panel Cutout and Mounting ............................................... 14
Figure 2. Labeling for 2 Relay, Analog Out, & 24 V Supply Model . 15
Figure 3. Labeling for Analog Out & Two 24 V Supply Model ........ 15
Figure 4. Power Connections ............................................................ 16
Figure 5. Transmitter Powered by Ext. Supply or Self-Powered .... 16
Figure 6. Transmitters Powered by Internal Supply (Optional) ...... 17
Figure 7. Voltage Input Connections ................................................ 17
Figure 8. Thermocouple Input Connections .................................... 18
Figure 9. Three-Wire RTD Input Connections .................................. 18
Figure 10. Two-Wire RTD Input Connections ................................... 19
Figure 11. Four-Wire RTD Input Connections .................................. 19
Figure 12. Relay & 24 V Output Connections ................................... 20
Figure 13. AC and DC Loads Protection ........................................... 20
Figure 14. Low Voltage DC Loads Protection .................................. 21
Figure 15. 4-20 mA Output & Input Signal Powered by Meter ........ 22
Figure 16. 4-20 mA Output Powered Externally ............................... 22
Figure 17. Meter Copy Connection ................................................... 57
Figure 18. Meter Dimensions – Side View ........................................ 64
Figure 19. Case Dimensions – Top View .......................................... 64
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
7
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Trident: 0.56" (14 mm), Trident X2: 1.20" (31 mm),
Four digits (-1999 to 9999), automatic lead zero blanking.
DISPLAY INTENSITY Eight intensity levels
DISPLAY UPDATE RATE
Process/RTD: 3.7-5/second Thermocouple: 1.8-2.5/second
OVERRANGE
Display flashes
9999
UNDERRANGE
Display flashes
-1999
PROGRAMMING METHODS
Four front panel buttons, PC and MeterView® software, or cloning using Copy function
NOISE FILTER Programmable from 2 to 199 (0 will disable filter)
RECALIBRATION All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN DISPLAY
Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PASSWORD Programmable password restricts modification of settings.
NON-VOLATILE MEMORY
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
POWER OPTIONS
85-265 VAC, 50/60 Hz 90-265 VDC, 20 W max or 12-36 VDC, 12-24 VAC, 6 W max See table for power consumption (*X: number depends on option)
Model Watts
PD765-6RX-0* 8
PD765-6RX-1, 2* 20
PD765-7RX-0* 6
FUSE Required fuse: UL Recognized, 5 A max, slow blow
Up to 6 meters may share one 5 A fuse
ISOLATED TRANSMITTER POWER SUPPLY
One or two transmitter power supplies (Optional) P or P1: 24 VDC ± 10% @ 200 mA max. (-1 option) P1 & P2: 24 VDC ± 10% @ 200 mA & 40 mA max. (-2 option)
NORMAL MODE REJECTION
64 dB at 50/60 Hz
ISOLATION 4 kV input/output-to-power line
500 V input-to-output or output-to-P1/P2 supplies
-6R5 & -6X5 models only: 100 V output-to-24 VDC supply
OVERVOLTAGE CATEGORY
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Instal­lation Overvoltage Category III.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
8
ENVIRONMENTAL Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ11 for serial communication adapters
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: gray
MOUNTING 1/8 DIN panel cutout required. Two panel mounting bracket
assemblies provided
TIGHTENING TORQUE
Screw terminal connectors: 5 lb-in (0.56 Nm)
OVERALL DIMENSIONS
2.45" x 4.68" x 4.19" (62 mm x 119 mm x 106 mm) (H x W x D)
WEIGHT 9.5 oz. (269 g) (including options)
WARRANTY 3 years parts & labor
Process Input
INPUTS Field selectable:
±20 mADC (0-20, 4-20 mA) and ±10 VDC (0-5, 1-5, 0-10 V)
ACCURACY ±0.05% of span ±1 count, square root: 10-100% FS
FUNCTION Linear or square root
LOW-FLOW CUTOFF
0-9999 (0 disables cutoff function)
TEMPERATURE DRIFT
0 to 65°C ambient -40 to 0°C ambient
Current: ±0.20% FS (50 PPM/°C) Voltage: ±0.02% FS (1.7 PPM/°C)
Current: ±0.80% FS Voltage: ±0.06% FS
DECIMAL POINT Up to three decimal places for process inputs:
d.ddd, dd.dd, ddd.d, or dddd
CALIBRATION RANGE
An Error message will appear if input 1 and input 2 signals are too close together.
Input Range Minimum Span
Input 1 & Input 2
4-20 mA 0.40 mA
±10 V
0.20 V
INPUT IMPEDANCE
Voltage ranges: greater than 1 MΩ Current ranges: 50 - 100 Ω
(depending on resettable fuse impedance)
INPUT OVERLOAD
Current input protected by resettable fuse. Fuse resets automatically after fault is removed.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
9
Temperature Inputs
INPUTS Field selectable: type J, K, T, or E thermocouples;
100 Ω platinum RTD (0.00385 or 0.00392 curve)
RESOLUTION
1° or 0.1° for all RTD inputs. 1° for all thermocouples. 1° or 0.1° for Type T thermocouple
ACCURACY
Input Type Range Accuracy
(0 - 65 C)
Accuracy (-40 - 0 C)
Type J
-58° to 1382° F
-50° to 750°C
±2°F ±1°C
±5°F ±3°C
Type K
-58° to 2300° F
-50° to 1260°C
±2°F ±1°C
±4°F ±2°C
Type T
-292° to 700° F
-180° to 371°C
±2°F ±1°C
±13°F ±7°C
Type T
0.1° Res
-199.9° to 700.0° F
-180.0° to 371.0°C
±1.8°F ±1.0°C
±13°F ±7.2°C
Type E
-58° to 1578° F
-50° to 870°C
±2°F ±1°C
±11°F ±6°C
100 Ω RTD
-328° to 1382°F
-200° to 750°C
±1°F ±1°C
±5°F ±3°C
COLD JUNCTION REFERENCE
Automatic, fixed, no user calibration needed
OFFSET ADJUSTMENT
Programmable to ±19.9°. This parameter allows the user to apply an offset value to the temperature being displayed.
INPUT IMPEDANCE
Greater than 100 kΩ
SENSOR BREAK DETECTION
Open TC or RTD sensor indicated by display flashing oPEn. All relays and alarm status LEDs go to alarm or non-alarm state, programmable for each relay individually. Analog output goes to the programmed sensor break value.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
10
Relays Option
RATING 2 SPDT (Form C); rated 3 A @ 30 VDC or 3 A @ 250 VAC
resistive load; 1/14 HP @ 125/250 VAC (50 watts) for induc­tive loads
ELECTRICAL NOISE SUPPRESSION
A suppressor (snubber) should be connected to each relay contact switching inductive loads to prevent disruption to the microprocessor’s operation. Recommended suppressor value: 0.01 µF/470 Ω, 250 VAC (PDX6901).
DEADBAND 0-100% of full scale, user selectable
HIGH OR LOW ALARM
User may program any alarm for high or low trip point.
RELAY OPERATION
Automatic (non-latching) Latching Pump alternation control
RELAY RESET User selectable via front panel buttons or PC
Automatic reset only (non-latching)
Automatic + manual reset at any time (non-latching) Manual reset only, at any time (latching) Manual reset only after alarm condition has cleared (latching) Automatic reset: Relays will automatically reset when the in-
put passes the reset point. Manual reset: Front panel ACK button. Pressing ACK re-
sets all manually resettable relays.
TIME DELAY 0 to 199 seconds, on and off delays
Programmable and independent for each relay
FAIL-SAFE OPERATION
Programmable Independent for each relay
AUTO INITIALIZATION
When power is applied to the meter, relays will reflect the state of the input to the meter.
Fail-safe operation: relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
11
Isolated 4-20 mA Transmitter Output
OUTPUT RANGE 1.00 to 23.00 mA typical
CALIBRATION Factory calibrated for 4-20 mA
SCALING RANGE 0.00 to 23.99 mA for any display range,
see output range above
ACCURACY ± 0.1% FS ± 0.004 mA
TEMPERATURE DRIFT
0.4 uA/°C from -40 to 65°C ambient
Note: Analog output drift is separate from input drift.
ISOLATED TRANSMITTER POWER SUPPLY
One or two transmitter power supplies (Optional) P1: 24 VDC ± 10% @ 200 mA max. (-1 option) P1 & P2: 24 VDC ± 10% @ 200 mA & 40 mA max. (-2 option)
EXTERNAL LOOP POWER SUPPLY
35 VDC maximum
OUTPUT LOOP RESISTANCE
Power supply Minimum Maximum
24 VDC
10 Ω 700 Ω
35 VDC (external)
100 Ω 1200 Ω
Serial Communications
METER ADDRESS
PDC protocol: 0 - 99 Modbus protocol: 1 - 247
BAUD RATE 300 – 19,200 bps
TRANSMIT TIME DELAY
Programmable between 0 and 199 ms
DATA 8 bit (1 start bit, 1 stop bit)
PARITY None (1 or 2 stop bits), even, or odd
(Modbus only; PDC protocol does not use parity)
BYTE-TO-BYTE TIMEOUT
0.01 – 2.54 sec (Modbus only)
TURN AROUND DELAY
Less than 2 ms (fixed)
Refer to PDC and Modbus Serial Communication Protocol manuals for details. These can be downloaded from: www.predig.com.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
12
COMPLIANCE INFORMATION
Safety
UL LISTED USA and Canada
UL 508 Industrial Control Equipment
UL FILE NUMBER E160849
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE DIRECTIVE
EN 61010-1:2010 Safety requirements for measurement, control, and la­boratory use
Electromagnetic Compatibility
EMISSIONS
EN 55011:2009 + A1:2010 Group 1 Class A ISM emissions requirements
Radiated Emissions
Class A
AC Mains Conducted Emissions
Class A
IMMUNITY
EN 61326-1:2013 Measurement, control, and laboratory equipment
EN 61000-6-2:2005 EMC heavy industrial generic immunity standard
RFI - Amplitude Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast Transients
±2kV AC mains, ±1kV other
Electrostatic Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency Magnetic Field
30 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods 70%V for 25 periods
Voltage Interruptions
<5%V for 250 periods
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
13
Note:
Testing was conducted on Trident Meters installed through the co­vers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.predig.com
SAFETY INFORMATION
CAUTION: Read complete
instructions prior to instal­lation and operation of the meter.
WARNING: Risk of electric shock.
WARNING Hazardous voltages exist within enclosure. Installa­tion and service should be performed only by trained service personnel.
!
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
14
INSTALLATION
There is no need to remove the meter from its case to com­plete the installation, wiring, and setup of the meter.
Unpacking
Remove the meter from box. Inspect the packaging and con­tents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to MOUNTING DIMENSIONS, page 64 for more details.
Clearance: allow at least 4" (102 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel.
To achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. Panel Cutout and Mounting
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
15
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
Connector Labeling
The connectors label, affixed to the meter, shows the location of all con­nectors available with requested configuration. It also identifies the loca­tion of the RTD/TC selector switch. The below two images are common connector configurations for the PD765. Note that the connector in the upper left of the diagram has two different configurations based on the model.
Figure 2. Labeling for 2 Relay, Analog Out, & 24 V Supply Model
Figure 3. Labeling for Analog Out & Two 24 V Supply Model
DW2206
POWER
SIGNAL
EXC T+ V+ mA+ COM
RTD
SWITCH
TC
SERIAL
TC
RTD
1 2 3 4 5 6
COM NONO NC NC COM
RELAY2 RELAY1
4
3
6 5
2 1
3 41 2 5
2 1
+
I
-
I
+
mA OUT
6 5
24V OUT
2 1
P+ P-
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
16
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 2. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
Figure 4. Power Connections
Signal Connections
Signal connections are made to a five-terminal connector labeled SIGNAL on Figure 2. The COM (common) terminal is the return for all types of input signals.
Current and Voltage Connections
The following figures show examples for current and voltage connections. There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
Figure 5. Transmitter Powered by Ext. Supply or Self-Powered
12
AC or DC
POWER
Required External Fuse:
5 A max, Slow Blow
POWER CONNECTOR
+-
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
17
Figure 6. Transmitters Powered by Internal Supply (Optional)
The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condi­tion, and automatically resets itself when the fault condition is removed.
Figure 7. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
18
Thermocouple and RTD Connections
The following figures show examples for thermocouple and RTD con­nections.
The RTD/TC selector switch must be set to the proper position for the meter to accept the selected temperature input.
The input type is selected using the Setup menu. Selected thermocouple input must correspond to thermocouple sensor
and wire type used.
Figure 8. Thermocouple Input Connections
Figure 9. Three-Wire RTD Input Connections
The meter accepts two, three, or four-wire RTDs. The three-wire RTD connection has built-in lead wire compensation.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
19
Figure 10. Two-Wire RTD Input Connections
Lead wire compensation for two-wire RTDs can be applied using the Adjust menu. See Offset Adjustment (Adj), page 53.
Figure 11. Four-Wire RTD Input Connections
The four-wire RTD connection is similar to the three-wire. One of the leads of a four-wire RTD is not connected, and may be clipped off.
The three-wire connection provides sufficient lead wire compensation to provide accurate readings even with long leads.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
20
Serial Communication
Serial communication connection is made to an RJ11 connector labeled SERIAL on Figure 2. Use PDA7232 for RS-232 interfacing.
Use PDA7422 for RS-485 interfacing. Use PDA7420 for meter-to-meter interfacing for cloning purposes (i.e.
copying programmed settings from one meter to other meters).
Relays and 24 V Output Connections
Relay connections are made to a six-terminal connector labeled RELAY1, RELAY2 on Figure 2. The COM (common) terminals of the re­lays should not be confused with the COM (common) terminal of the SIGNAL connector. The 24 VDC output is available at the connector la­beled 24V OUT, next to the relays connector.
Figure 12. Relay & 24 V Output Connections
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching in­ductive loads to prevent disrupting the microprocessor’s operation. The suppres­sors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as com­plete assemblies. Refer to the following circuits for RC network assembly and in­stallation:
Figure 13. AC and DC Loads Protection
C
R
C
R
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
21
Choose R and C as follows: R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Inductive relay rating is 1/14 HP (50 W) at 115/230 VAC
2. Use capacitors rated for 250 VAC.
3. RC networks may affect load release time of solenoid loads. Check to con­firm proper operation.
4. Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load. Experiment for best results.
Figure 14. Low Voltage DC Loads Protection
RC Networks Available from Precision Digital
RC networks are available from Precision Digital and should be applied to each relay contact switching an inductive load. Part number: PDX6901.
Note:
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Use a diode with a reverse breakdown voltage two to three times the circuit volt­age and forward current at least as large as the load current.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
22
4-20 mA Output & Input Signal Connections
Connections for the 4-20 mA transmitter output are made to the con­nector terminals labeled “mA OUT, I-, I+”. The 4-20 mA output may be powered from an internal power supply (optional) or from an external power supply.
Figure 15. 4-20 mA Output & Input Signal Powered by Meter
Figure 16. 4-20 mA Output Powered Externally
COM
SIGNAL CONNECTOR
mA+
21 354
V+ T+
EXC
2-Wire
4-20 mA
Transmitter
-
+
I-
mA OUT
P2-P1+
45 312
P2+
P1-
24V OUT
6
I+
Remote Display,
Chart Recorder,
etc.
+
-
External
Power
Supply
-
+
I-
mA OUT
56
I+
Remote Display,
Chart Recorder,
etc.
+
-
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
23
SETUP AND PROGRAMMING
Programming From a PC with MeterView®
Precision Digital’s free MeterView® software allows all PD765 Trident setup parameters to be programmed from a PC (requires PDC protocol selection) and to save the configuration settings to a file for reporting or programming other meters. And since the serial adapter is an external device, one serial adapter can program an infinite number of meters!
The MeterView screen shot above shows how the input is selected. No­tice there are tabs for Scaling, Relays/Alarms, Advanced, and Factory Values.
There is no need to recalibrate the meter when first received from the fac-
tory.
The meter is factory calibrated prior to shipment, for all input types, in milliamps, volts, and degrees respectively. The calibration equipment is certified to NIST standards.
Overview
There are no jumpers involved in the setup process of the meter. The RTD/TC selector switch, located between the SIGNAL and SERIAL con­nectors, must be set accordingly for the meter to accept RTD or thermo­couple inputs, Figure 2.
Setup and programming is done through the front panel buttons. After power and signal connections have been completed and verified,
apply power to the meter.
For
QUICK INTERFACE REFERENCE
GUIDE
go to page 70
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
24
Front Panel Buttons and Status LED Indicators
Button Symbol
Description LED Status
Menu
1 Alarm 1
Right arrow/Reset
2 Alarm 2
Up arrow/Max
S Set point indicator
Enter/Ack
R Reset point indicator
Press the
Menu
button to enter or exit the Programming Mode at
any time.
Press the
Right
arrow button to move to the next digit during digit
programming.
Press the Up arrow button to scroll through the menus, decimal
point, or to increment the value of a digit.
Press the
Enter/Ack
button to access a menu or to accept a setting.
Press the
Right
arrow and
Menu
button simultaneously or hold the
Menu
button for approximately 3 seconds to access the
Advanced
Features Menu
of the meter.
For Interactive Virtual
Meter Demo visit tvm.predig.com
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
25
Display Functions and Messages
The meter displays various functions and messages during setup/pro­gramming and operation. The following table shows the displayed func­tions and messages with their action/setting description.
Display Parameter Action/Setting
setu
Setup
Enter Setup menu
inpt
Input
Enter Input menu
4-20
4-20 mA
Set meter for 4-20 mA input
0-10
0-10 VDC
Set meter for ±10 VDC input
rtd
RTD
Set meter for RTD input
a385
Alpha 385
Set α = 0.00385 European curve 100Ω RTD
A392
Alpha 392
Set α = 0.00392 American curve 100Ω RTD
tC
TC
Set meter for TC input
0 J
0 J
Type J
1 k
1 K
Type K
2 T
2 T
Type T
3 t.0
3 T.0
Type T, 0.1° resolution
4 E
4 E
Type E
f C
°
F or °C
Set temperature scale
°F
°
F
Set meter to Fahrenheit
°C
°
C
Set meter to Celsius
dec.p
Decimal point
Set decimal point
prog
Program
Enter the Program menu
scal
Scale
Enter the Scale menu
Cal
Calibrate
Enter the Calibrate menu
inp1
Input 1
Calibrate input 1 signal or program input 1 value
dis1
Display 1
Program display 1 value
inp2
Input 2
Calibrate input 2 signal or program input 2 value
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
26
Display Parameter Action/Setting
dis2
Display 2
Program display 2 value
err
Error
Error, calibration not successful, check signal
RELY
Relay
Enter the Relay menu
RLY1
Relay 1
Relay 1 setup
Act1
Action 1
Set relay 1 action (automatic, latching, etc.)
Auto
Automatic
Set relay for automatic reset
A-m
Auto-manual
Set relay for automatic + manual reset any time
LtCH
Latching
Set relay for latching operation
L-CL
Latching­cleared
Set relay for latching operation with manual reset only after alarm condition has cleared
Altr
Alternate
Set relays for pump alternation control
oFF
Off
Disable relay and front panel status LEDs Disable relay’s fail-safe operation
Set1
Set 1
Program set point 1
rSt1
Reset 1
Program reset point 1
RLY2
Relay 2
Setup relay 2
Act2
Action 2
Set relay 2 action (automatic, latching, etc.)
Set2
Set 2
Program set point 2
RSt2
Reset 2
Program reset point 2
FLSF
Fail-safe
Enter Fail-safe menu
FLS1
Fail-safe1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS2
Fail-safe2
Set relay 2 fail-safe operation
DLAY
Delay
Enter Time Delay menu
DLY1
Delay 1
Enter relay 1 time delay setup
On1
On 1
Set relay 1 On time delay
OFF1
Off 1
Set relay 1 Off time delay
DLY2
Delay 2
Enter relay 2 time delay setup
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
27
Display Parameter Action/Setting
On2
On 2
Set relay 2 On time delay
OFF2
Off 2
Set relay 2 Off time delay
brek
Break
Set RTD/TC input break relay behavior
Brk1
Relay 1 Break
Set relay 1 input break relay behavior
Off
Off
Set relay to non-alarm condition at break
On
On
Set relay to alarm condition at break
Brk2
Relay 2 Break
Set relay 2 input break relay behavior
Aout
Analog output
Enter the Analog output menu
Scal
Scale
Enter the Scale menu
Dis1
Display 1
Program display 1 value
out1
Output 1
Program output 1 value (e.g. 4 mA)
Dis2
Display 2
Program display 2 value
out2
Output 2
Program output 2 value (e.g. 20 mA)
SEbr
Sensor break
Program TC or RTD sensor break value for analog out
pass
Password
Enter the Password menu
unlC
Unlocked
Program password to lock meter
loCd
Locked
Enter password to unlock meter
9999
-1999 open
Flashing dis­play
Overrange condition Underrange condition Open TC or RTD sensor
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
28
Main Menu
The main menu consists of the most commonly used functions:
Setup
and
Password
.
Press
Menu
button to enter Programming Mode then press Up ar-
row button to scroll main menu.
Press
Menu
, at any time, to exit and return to Run Mode. Changes
made to settings prior to pressing
Enter/Ack
are not saved.
Changes to the settings are saved to memory only after pressing
Enter/Ack
.
The display moves to the next menu every time a setting is ac-
cepted by pressing
Enter/Ack
.
Setting Numeric Values
The numeric values are set using the
Right
and Up arrow buttons.
Press
Right
arrow to select next digit and
Up
arrow to increment digit
value. The digit being changed is displayed brighter than the rest. Press the
Enter/Ack
button, at any time, to accept a setting or
Menu
button to exit without saving changes.
The decimal point is set using the
Up
arrow button in the
Setup-decimal
point
menu.
9765 setu pass
Run
Mode
0 4.00 04.00 0 5. 00
Increment Digit
Value
Next
Setting
Select Next Digit
A
ccept Setting
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
29
Setting Up the Meter (setu)
The
Setup
menu is used to select:
1. Input signal the meter will accept
2. Decimal point position for process inputs
3. Units (
°
F or °C) for temperature inputs
4. Relay operation
5. 4-20 mA analog output set up
Press the
Enter/Ack
button to access any menu or press Up arrow but-
ton to scroll through choices. Press the
Menu
button to exit at any time.
R TD
TC
Note:
Selecting R TD o
r
TC mode from
the Input menu will include the Fahrenheit/Celsius menu in the setup menu structure. RTD will allow the selection of a decimal point location after this menu and TC has a fixed decimal point loca
­tion and will not allow the selec­tion of a decimal point location.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
30
Setting the Input Signal (inpt)
Enter the Input menu to set up the meter to display current (4-20), volt­age (0-10), thermocouple (tC), or RTD (rtd) inputs.
The voltage input is capable of accepting any signal from -10 to +10 VDC. Select voltage input to accept 0-5, 1-5, 0-10, or ±10 VDC signals.
The current input is capable of accepting any signal from -20 to 20 mA. Select current input to accept 0-20 or 4-20 mA signals.
If RTD is selected, the display shows A385 or A392. Select the coeffi­cient to match the RTD sensor, either 0.00385 (A385, European curve) or 0.00392 (A392, American curve). The display then shows the decimal point menu, DEc.P. Select the decimal point resolution as shown on page
31. If TC is selected, scroll through the thermocouple types and select the
type matching the TC sensor. The input signal must be connected to the appropriate input terminals
and the RTD/TC selector switch must be set, see Figure 8 on page 18.
For thermocouple inputs, allow at least 30 minutes warm-up
time for meter to reach specified accuracy.
inpt
4-20 0-10 rtd tC
a385
a392
0 j
1 k
2 t
3 t.0
4 e
Press Enter/Ack to
Make Selections
Press Up Arrow
to Scroll Through
Choices
Press Menu to
Exit at any Time
J
K
T
T.0
E
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
31
Setting the Decimal Point (dc.pt)
Decimal point for process inputs may be set with up to three decimal places or with no decimal point at all.
Decimal point for RTD inputs may be set with 1 decimal place or none. Decimal point for thermocouple inputs is fixed. Pressing the Up arrow moves the decimal point one place to the right
until no decimal point is displayed, it then moves to the leftmost position.
Setting the Temperature Scale (F C)
The meter can be set to display temperature in degrees Fahrenheit or Celsius.
Press Up arrow to change selection. Press Enter/Ack to accept.
dec.p
dddd
Next
Select Decimal
Point
Previous
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
32
Programming the Meter (prog)
It is very important to read the following information, before proceeding to program the meter:
There is no need to recalibrate the meter when first received from
the factory.
The meter is factory calibrated prior to shipment, for all input types, in milliamps, volts, and degrees respectively. The calibration equipment is certified to NIST standards.
Use the Scale menu to scale process inputs (e.g. 4-20 mA). A cali- brated signal source is not needed to scale the meter.
For thermocouple and RTDs, just connect the sensor to the proper terminals and turn the power on. No calibration needed! (when the meter is first received from the factory).
The Program menu contains the Calibrate and the Scale menus. Process inputs may be calibrated or scaled to any display within the
range of the meter.
Additional parameters, not needed for most applications, are pro­grammed with the Advanced Features menu, see Advanced Features Menu, page 50.
prog ScAl
CAL
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
33
Scaling the Meter (scal)
The process inputs (4-20 mA and ±10 VDC) can be scaled to display the process in engineering units.
A signal source is not needed to scale the meter; simply program the in­puts and corresponding display values.
For instructions on how to program
numeric values see Setting Numeric
Values, page 28.
Note:
The Scale menu is not available for temperature inputs.
dis1 00.0
Press Enter to Accept Setting
inp2
Scale
Input 2
inp1
Set Input 1
Value
scal
04.00
Set Display 1
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
34
Error Message (Err)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 1, allow­ing the appropriate input signals to be applied.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is con­nected backwards.
2. Wrong signal selection in Setup menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and in­put 2 signals required to complete the calibration or scaling of the meter.
Input range Input 1 & input 2 span 4-20 mA 0.40 mA
±10 VDC
0.20 VDC
TC
100°F (56°C)
RTD
50°F (28°C)
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
35
Calibrating the Meter (Cal)
To scale the meter without a signal
source, refer to Scaling the Meter
(scal), page 33.
The meter can be calibrated to display the process in engineering units by applying the appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to cali­brate the meter.
Recalibrating Temperature Inputs (Cal)
Remember, the meter is calibrated at the factory prior to shipment. Re­calibration is recommended at least every twelve months.
The Calibration (CAL) menu is used to recalibrate the thermocouple and RTD inputs.
Allow at least 30 minutes warm-up time
before performing recalibration proce-
dure to ensure specified accuracy.
inp1 dis1 04.00
Set Display 1
Value
inp2
Calibrate
Input 2
Cal
Display
Flashes
Accepting
Input
See Scaling the Meter for Button
Functions Description
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
36
Recommended Calibration Points
To recalibrate the meter, it is recommended to use the Fahrenheit scale; this will give a greater degree of accuracy to the calibration. The scale can be changed to the Celsius scale after calibration is completed. The meter will display temperature accurately in any scale. The following ta­ble shows the recommended low and high calibration points for all types.
Type of in­put
Input 1 (Low)
Input 2 (High)
Check (Middle)
Type J T/C
32
°F 1182°F 600°F
Type K T/C
32
°F 1893°F 960°F
Type T T/C
32
°F 693°F 360°F
Type T T/C
32.0
°F 693.0°F 360.0°F
Type E T/C
32
°F 1652°F 840°F
100 Ω RTD (0.00385)
32°F
100
Ω
1148°F
320.12
Ω
590
°F
215.61
Ω
100 Ω RTD (0.00392)
32°F
100
Ω
1127°F
320.89
Ω
580
°F
215.87
Ω
Recalibration Procedure for Temperature Inputs
1. Connect signal to the meter using the appropriate wire (e.g. type J
thermocouple wire to recalibrate type J input), see page 18.
2. Set up the meter to accept the selected input (e.g. type J T/C), see
page 30.
3. Set up the meter to display temperature in degrees Fahrenheit, see
page 31.
4. Apply signal corresponding to input 1 (32°F) and program display 1 to
32, see page 35.
5. Apply signal corresponding to input 2 (1182°F for type J) and program
display 2 accordingly, see page 35.
6. After the meter accepts input 2, the display flashes the message
CJr
that indicates the meter is sensing the cold junction reference. This completes the recalibration procedure for the selected input.
Recalibrating Process Inputs (ICal)
The Internal Calibration (ICAL) menu, located in the Advanced features menu, is used to recalibrate the current and voltage inputs. Recalibra­tion is recommended at least every twelve months.
Refer to Internal Calibration (ICal), page 59 for instructions.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
37
Setting the Relay Operation (rely)
This menu allows you to set up the operation of the relays:
1. Relay action
a. Automatic reset only (non-latching) b. Automatic + manual reset at any time (non-latching) c. Latching (manual reset only) d. Latching with Clear (manual reset only after alarm condi-
tion has cleared) e. Pump alternation control (automatic reset only) f. Off (relay and status LED disabled)
2. Set point
3. Reset point
4. Fail-safe operation a. On (enabled) b. Off (disabled)
5. Time delay a. On delay (0-199 seconds) b. Off delay (0-199 seconds)
6. Break Condition Behavior a. Off (non-alarm condition) b. On (alarm condition)
Refer to page 25 for a description of Display
Functions and Messages
rLY1 rLY2
FLSF
rELY
dLAY
Act1
SEt1
rSt1
FLS1
FLS2
dLy1
dLY2
Same
Functions as
Relay 1
From Setup
Menu
Press Enter/Ack button to access any menu Press Menu button to exit at any time
brek
brk1
brk2
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
38
Setting the Relay Action
The relays’ Action menu allows the user to set up the operation of the relays. The relays may be set up for any of the following modes of oper­ation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Pump alternation control (automatic reset only)
6. Off (relay and status LED disabled)
The following graphic shows relay 1 action setup; relay 2 is set up in a similar fashion.
Programming Set and Reset Points
High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point. The deadband is determined by the difference between set and reset
points. Minimum deadband is one display count. If set and reset points are programmed the same, relay will reset one count below set point.
Auto A-m
LtCH
Act1
L-CL
From Relay 1
Menu
Press
Enter/Ack
button to accept setting
Press
Menu
button to exit at any time
ALtroFF
SEt1
rSt1
Program Set
Point
Program Reset
Point
Quick Set Points
Press Up arrow and Menu at the same time to access set/reset points quickly.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
39
Setting Fail-Safe Operation
The fail-safe operation is set independently for each relay. Select on to enable or select off to disable fail-safe operation.
Programming Time Delay
The On and Off time delays may be programmed for each relay be­tween 0 and 199 seconds. The relays will transfer only after the condi­tion has been maintained for the corresponding time delay.
The On time delay is associated with the set point. The Off time delay is associated with the reset point.
FLSF
FLS1
FLS2
on oFF
Press
Enter/Ack
button to accept setting
Press
Menu
button to exit at any time
on oFF
Program On
Time Delay
Program Off
Time Delay
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
40
Setting Sensor Break Condition
The sensor break relay condition may be programmed for each relay as
On (alarm) or Off (non-alarm). The relays will enter these states when a
sensor break is detected for RTD or thermocouple inputs. These set­tings have no effect when current or voltage inputs are selected.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
41
Relay and Alarm Operation
The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back "on", signal must go below set point, and then go above it.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
42
Low Alarm Operation (Set < Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back "on", signal must go above set point, and then go below it.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
43
Time Delay Operation
The following graphs show the operation of the time delay function.
If the signal crosses the set point, the
On
time delay timer starts and the relay trips when the time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the
On
time delay timer resets and the relay does not change state. The same principle applies to the
Off
time delay.
* Note:
The LED is not affected by Time Delay when
“Automatic or
Manual”
reset mode is selected. Rather the LED follows the set
and reset points.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
44
High Alarm with Fail-Safe Operation (Set > Reset)
Fail-safe operation:
relay coil is energized in non-alarm condition. In
case of power failure, relay will go to alarm state.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
45
Low Alarm with Fail-Safe Operation (Set < Reset)
Fail-safe operation:
relay coil is energized in non-alarm condition. In
case of power failure, relay will go to alarm state.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
46
Pump Alternation Control Operation
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
47
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal for any display range selected.
No equipment is needed to scale the analog output; simply program the display values to the corresponding mA output signal.
Depending on the version of meter purchased, the
Analog Output menu
may not appear in the
Setup menu. This menu is enabled or disabled at
the factory via the
Advanced Features menu. For more information on
the Advanced Features Menu see page 50.
The
Analog Output menu is used to program:
1. 4-20 mA output based on display values
2. Sensor break value in mA
For instructions on how to program
numeric values see
Setting Numeric
Values
, page 28.
out1 04.00
Press Enter to Accept Setting
dis2
Scale
Output 2
dis1
Set Display 1
Value
scal
00.00
Set Output 1
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
Aout
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
48
Program the Sensor Break Output Value (SEbr)
The sensor break value corresponds to the output signal generated when the meter detects a sensor break for thermocouple and RTD in­puts.
For example if there is an open thermocouple, the meter displays the message “
open” and the analog output goes to the programmed sensor
break value (e.g. 3.00 mA). The sensor break value can be programmed from 0.00 to 23.99.
The typical output signal range is 1.00 to 23.00 mA (e.g. If sensor break value is programmed to 0.00, the actual output will not be greater than
1.00 mA).
Analog Output when Display is Out of Range
The analog output reflects the display out of range conditions as follows:
Input Condition Display Analog Output
Underrange Flashing -1999 3.00 mA Overrange Flashing 9999 21.00 mA Open TC or RTD Flashing open Sensor break value
sEbr
Set Sensor
Break Value
scal
03.00
Aout
Program
Menu
Press Enter to Accept Setting
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
49
Setting Up the Password (pass)
The Password menu is used to program a four-digit password to pre­vent unauthorized changes to the programmed parameter settings.
Locking the Meter
Enter the Password menu and program a four-digit password.
For instructions on how to program numeric values see Setting Numeric Values, page 28.
Record the password for future reference. If appropriate, it may be rec­orded in the space provided.
Model: Serial Number: Password: __ __ __ __
Unlocking the Meter
If the meter is password protected, the correct password must be en­tered in order to make changes to the parameter settings.
pass unlC 0000
Program
Password
loCd
Run Mode
pass loCd 0000
Enter
Password
unlC
Run Mode
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
50
Entering the correct four-digit number sets the password to 0000, disa­bling the protection.
Changes to the programmed parameter settings are allowed only with the password set to 0000.
If the password entered is incorrect, the meter displays
LoCd (Locked)
for about two seconds, then it returns to Run Mode. To try again, press
Enter/Ack while the Locked message is displayed.
Forgot the Password?
The password may be disabled by the following procedure:
1. Note display reading prior to pressing the Menu button. Ignore decimal point and sign.
2. Access the
Password menu, add 2 to the noted
reading and enter that number as the password (e.g. display reading = -1.23, password = 0125).
Advanced Features Menu
To simplify the setup process, functions not needed for most applica­tions are located in the
Advanced Features menu.
Press the
Right arrow and Menu button simultaneously or hold the
Menu button for approximately 3 seconds to access the
Advanced Fea-
tures Menu
of the meter.
Copy
I Cal
Press Enter/Ack to Access Menu or to Accept Setting
diag
byps
fltr
serl
Press Up to Scroll Menu and to Increment Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
adj
Press Simultaneously
*
* Available for temperature inputs only
**
* * Available for process inputs only
SELc
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
51
Advanced Features Menu & Display Messages
Display Parameter Action/Setting
adj
Adjust
Set offset adjustment for temperature, not available for process inputs
fltr
Filter
Set noise filter value
byps
Bypass
Set filter bypass value
serl
Serial
Set serial communication parameters
prot
Protocol
Enter the Protocol menu
PDC
PDC
Select PDC protocol
mbs
Modbus
Select Modbus protocol
addr
Address
Set meter address
baud
Baud rate
Select baud rate
trdE
Transmit delay
Set transmit delay for serial communication
prty
Parity
Select none, even, or odd (Modbus only)
tbyt
Byte-to-byte
Program byte-to-byte timeout (silent time – Modbus only)
Copy
Copy
Enter copy function
send
Send
Send meter settings to another meter
done
Done
Copy function completed
Selc
Select
Enter the Select menu (function, cutoff, out)
Func
Function
Select linear or square root function
Linr
Linear
Set meter for linear function
Sqrt
Square root
Set meter for square root extraction
cutF
Cutoff
Set low-flow cutoff
out
Output
Set meter for either relay or analog output
(factory set only – only included in certain model
s
Aout
Analog output
Set meter for analog output option
rEly
Relay
Set meter for relay option
Aout
Analog output
Enable or disable analog output
(factory set only – only included in certain model
s
Yes
Yes
Enable analog output
no
No
Disable analog output
Inty
Intensity
Select display intensity
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
52
Display Parameter Action/Setting
ICal
Initial calibration
Enter initial calibration for process inputs
Curr
Current
Calibrating current input
I lo
I low
Calibrate low current input
I Hi
I high
Calibrate high current input
volt
Volt
Calibrating voltage input
Vlo
V low
Calibrate low voltage input
VHi
V high
Calibrate high voltage input
diag
Diagnostics
Display parameter settings
led
LED
Test display
CJC
CJC
Display cold junction compensation voltage
Cfg
CFG
Display meter configuration
pts
Points
Display calibration points for process inputs
RELY
Relays
Display relay settings
Aout
Analog output
Display analog output settings
GoFF
Gain/offset
Display gain and offset for process inputs
SErL
Serial
Display serial communication settings
Info
Information
Display software version and S/N information
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
53
Offset Adjustment (Adj)
This parameter allows the user to select an offset adjustment to the temperature being displayed. Offset adjustment values can be either positive or negative and can be any number within
±19.9°. The offset
adjustment value is programmed through the
Adjust menu.
The offset adjustment feature can be useful to compensate for errors due to thermocouple junctions or excessive lead wire resistance in RTDs.
The offset adjustment value is automatically reset to zero whenever the type of temperature sensor is changed (
i.e. Thermocouple type or RTD
curve). Celsius/Fahrenheit conversion of the offset adjustment value is auto-
matic, see note 2 below for important limitations.
Notes:
1. Offset adjustment is available only when TC or RTD input is se­lected.
2. If adjustment value is greater than 11
°C and the temperature
scale is changed to Fahrenheit, the maximum applied adjust­ment will be 19.9
°F.
Noise Filter (fltr)
Most applications do not require changing this parameter. It is intended to help attain a steady display with an unsteady (noisy) input signal.
The field selectable noise filter averages any minor or quick changes in the input signal and displays the reading with greater stability.
Increasing the filter value will help stabilize the display, however this will reduce the display response to changes on the input signal.
The filter level may be set anywhere from 2 to 199. Setting filter value to zero disables filter function, and bypass setting be-
comes irrelevant.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
54
Noise Filter Bypass (byps)
The meter can be programmed to filter small input changes, but allow larger input changes to be displayed immediately, by setting the bypass value accordingly.
If the input signal goes beyond the bypass value, it will be displayed im­mediately with no averaging done on it.
The noise filter bypass value may be set anywhere from 0.2 to 99.9. It corresponds to percentage of full scale for process inputs and to de­grees Fahrenheit for temperature inputs.
Increasing the bypass value may slow down the display response to changes on the input signal.
Serial Communications (serl)
The meter is equipped with serial communications capability as a stand­ard feature using PDC Serial Communication Protocol. The Modbus RTU protocol is included on all models after 5/1/2010. To communicate with a computer or other data terminal equipment, an RS-232 or RS-485 adapter option is required; see
Ordering Information on page 3 for de-
tails.
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique address. The address may be pro­grammed from 00 to 99 for PDC protocol and from 1 to 247 for Modbus protocol. The transmit delay may be set between 0 and 199 ms (see Se­rial Communication Adapter manual for more details).
The Trident can also be connected directly to another Trident meter through a cable assembly (PDA7420). This allows the user to copy all the settings from one meter to another, using the
Copy function.
Protocol Selection Menu (Prot)
The Protocol selection menu is used to select either the PDC or the Modbus protocol.
Serl Prot
Addr
bAud trde
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
55
Select Menu (SElc)
The Select menu is used to select linear or square root function, display intensity, and low-flow cutoff. Selection for relay or analog output is a factory setting depending on the option installed.
Output options are installed
and set up at the factory.
Changing the output selec-
tion will cause erroneous op­eration.
Linear or Square Root Function (linr or Sqrt)
Meters are set up at the factory for linear function. The linear function provides a display that is linear with respect to the input signal.
The square root function is used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units.
Note:
Depending on meter model, the Select menu will display either out or Aout. In either case, the output selection menu is for factory use only. Do not attempt to change output selection.
Linr
Func
Sqrt
SELc
Advanced
Features
Press Enter to Accept Setting
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
56
Low-Flow Cutoff (cutF)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 9999. Below the cutoff value, the meter will display zero. Programming the cutoff value to zero disables the cutoff.
Display Intensity (inty)
The Display Intensity function allows the selection of eight levels of in­tensity for various lighting conditions.
Next Menu Item
inty
Select Display Intensity Level
Func
int3
SELc
Press Enter to Accept Setting
Press Up to Select Value
Press Menu to Exit at any Time
Advanced
Features
Next
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
57
MeterView® Software
Precision Digital’s MeterView® software allows the Trident to be pro­grammed from a PC and to act as a data logger.
MeterView
®
software allows all setup parameters to be saved to a file
for reporting, restoring, or programming other meters. See
Ordering Information, page 3 to order MeterView
®
software.
Note: PDC protocol must be selected to communicate with MeterView®.
Meter Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one meter to other meters requiring exactly the same setup and program­ming (
i.e. type of input, scaling, decimal point, filter, bypass, etc.).
Figure 17. Meter Copy Connection
Copy Function Requirements
To successfully copy settings from one me­ter to another, both meters must have:
1. Same software version
2. Same baud rate setting
3. PDC protocol selected
See Determining Software Version,
page 65 for instructions.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
58
Meter Cloning Instructions
NOTICE!
Do not connect the two meters to the same 4-20 mA loop while cloning. Internal calibration may be affected.
1. Connect the two meters using cable assembly PDA7420 or equiva­lent (
e.g. Digi-Key P/N H1663-07-ND). Cable should not exceed
7' (2.1 m).
2. Power up both meters. Leave Clone meter in Run Mode.
3. Enter the
Advanced Features Menu of the Master meter, see Ad-
vanced Features Menu
, page 50.
4. Scroll to
Copy function using Up arrow button then press
Enter/Ack.
5. The meter displays the message
Send. Press Enter/Ack, the dis-
play flashes while sending data. The message
done is displayed
when copying is completed.
6. The Clone meter displays the memory address being programmed then the message
done when copying is completed. The meter ini-
tializes and returns to Run Mode using the same settings as the Master.
7. If meter to be cloned does not respond to the data being sent, refer to
Copy Function Requirements above.
Copy send
Advanced
Features
done
Display
Flashes While
Sending
Press
Menu
to Exit and
Return to Run Mode
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
59
Internal Calibration (ICal)
There is no need to recalibrate the meter
when first received from the factory.
The meter is factory calibrated prior to
shipment, for all input types, in milliamps, volts, and degrees respectively. The cali­bration equipment is certified to NIST standards.
The internal calibration allows the user to scale the meter without apply­ing a signal. This menu is not available if the meter is set up for TC or RTD inputs.
The use of calibrated signal sources is necessary to perform the internal calibration of the meter.
Check calibration of the meter at least every 12 months. Each input type must be recalibrated separately, if meter will be used with all input types.
Notes:
If meter is in operation and it is intended to
accept only one input type (e.g. 4-20 mA), recalibration of other inputs is not necessary.
Allow the meter to warm up for at least
15 minutes before performing the internal cali­bration procedure.
The
Internal calibration menu is part of the Advanced Features Menu.
1. Press the Right arrow
and Menu button simultaneously or hold the
Menu button for approximately 3 seconds to access the
Advanced
Features Menu of the meter.
2. Press the
Up arrow button to scroll to the Internal calibration menu
and press
Enter/Ack.
3. The meter displays either current (
Curr) or voltage (volt), accord-
ing to the meter input setup. Press
Enter/Ack to start the calibra-
tion process.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
60
Example for current input internal calibration:
4. The meter displays Low input current (I lo). Apply the low input signal and press
Enter/Ack. The display flashes for a moment
while meter is accepting the low input.
5. After the display stops flashing, a number is displayed with the left­most digit brighter than the rest. The bright digit is the active digit that can be changed by pressing the
Up arrow button. Press the
Right arrow button to move to the next digit.
6. Set the display value to correspond to the input signal being cali­brated.
7. The display moves to the high input calibration (
I Hi). Apply the
high input signal and press
Enter/Ack.
8. Set the display for the high input calibration in the same way as it was set for the low input calibration.
For instructions on how to pro-
gram numeric values see Set-
ting Numeric Values
, page 28.
The graphic above shows the calibration of the current input. The volt­age input is calibrated in a similar way.
I lo 04.00
Set Display Value
for Low Input
I Hi
Calibrate
High Input
Curr
Display
Flashes
While
Accepting
Input
I Cal
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
61
Tips:
Low and high input signals can be any valid values within the
range of the meter.
Observe minimum input span requirements between input 1
and input 2.
Low input must be less than high input signal.
Error Message (Err)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 1, allow­ing the appropriate input signals to be applied.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is con­nected backwards.
2. Wrong signal selection in
Setup menu.
3. Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and in­put 2 signals required to complete the calibration or scaling of the meter.
Input range Input 1 & input 2 span 4-20 mA 0.40 mA
±10 VDC
0.20 VDC
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
62
OPERATION
For process inputs, the meter is capable of accepting positive and nega­tive signals and displaying these signals in engineering units from -1999 to 9999 (
e.g.
a signal from -10 to +10 VDC could be displayed as -10.00
to 10.00). The temperature inputs are displayed according to the input type and
temperature units (
°
F or °C) selected. RTD and Type T thermocouple in-
puts can be displayed with either 1
°
or 0.1° resolution.
Front Panel Buttons Operation
Button Symbol
Description
Press to enter or exit Programming Mode, view settings, or exit Max/Min readings
Hold to enter Advanced features menu.
Press to reset Max/Min readings
Press to display Max/Min readings alternately
Press to display Max/Min reading indefinitely while displaying Max/Min
Press ACK to acknowledge relays
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
63
Maximum/Minimum Readings
The main function of the front panel buttons during operation is to dis­play the maximum and minimum readings reached by the process or temperature inputs.
1. Press
Up arrow/Max button to display maximum reading since the
last reset/power-up.
2. Press
Up arrow/Max again to display the minimum reading since
the last reset/power-up.
3. Press
Enter/Ack to hold Max/Min display reading, the meter will
continue to track new Max/Min readings.
4. If
Enter/Ack is not pressed, the Max/Min display reading will time
out after ten seconds and the meter will return to display the actual reading.
5. Press
Right arrow/Reset button to reset Max/Min while reading is
being displayed. Max/Min display readings are reset to actual reading.
2468 Hi lo
Actual
Reading
9846 200
Press
Enter
to Hold Max/Min
Press
Up
to Display and to
Toggle Between Max & Min
Press
Right
to Reset Max/Min
Press
Menu
to Exit Max/Min
10 Sec Time Out
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
64
MOUNTING DIMENSIONS
Figure 18. Meter Dimensions – Side View
Figure 19. Case Dimensions – Top View
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.6"
(91mm)
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
65
TROUBLESHOOTING
For an Interactive Virtual
Meter Demo visit
tvm.predig.com
Due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see. If the meter is not working as expected, refer to the
Diagnostics
menu and consult the recommendations described below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the Advanced Features Menu, to ac­cess
Diagnostics menu see Advanced Features Menu, page 50.
It provides an easy way to view the programmed parameter settings for troubleshooting purposes. Press the
Enter/Ack button to view the set-
tings and the
Menu button to exit at any time.
For a description of the diagnostics messages
see Advanced Features
Menu & Display Messages, page 51.
Determining Software Version
To determine the software version of a meter:
1. Go to the
Diagnostics menu (diAG) and press Enter/Ack but-
ton.
2. Press
Up arrow/Max button and scroll to Information menu
(
Info).
3. Press
Enter/Ack to access the software number (SFT), version
(
UER). Write down the information as it is displayed. Continue
pressing
Enter/Ack until all the information is displayed.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
66
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to de­termine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features Menu. See Advanced Features
Menu
, page 50.
2. Press
Up arrow to go to Diagnostics menu
3. Press and hold
Right arrow/Reset for five seconds, press
Enter/Ack when display flashes reset.
Note: If
Enter/Ack is not pressed within three seconds, display re-
turns to
Diagnostics menu.
4. The meter goes through an initialization sequence (same as on power-up), and loads the factory default settings.
rset
diag
Press Simultaneously
Meter Re-
Initializes
Press and Hold for 5 Sec
Flashing Display
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
67
Factory Defaults & User Settings
The following table shows the factory setting for most of the program­mable parameters on the meter. Next to the factory setting, the user may record the new setting for the particular application. MeterView
®
software allows the saving of all meter parameters to a file for restoring meter settings, reporting, and copying settings to other meters.
Model: ______________ S/N: _______________ Date: _________
Parameter Display Default Setting User
Setting
Input type
inpt
4-20 mA
Decimal point
dd.dd
2 places
Programming
prog
Input 1
InP1
4.00 mA
Display 1
Dis1
4.00
Input 2
InP2
20.00 mA
Display 2
Dis2
20.00
Relay 1
Rly1
Action 1
Act1
Automatic
Set 1
Set1
7.00
Reset 1
RSt1
6.00
Relay 2
Rly2
Action 2
Act2
Automatic
Set 2
Set2
10.00
Reset 2
RSt2
9.00
Fail-safe
flsf
Fail-safe 1
Fls1
Off
Fail-safe 2
Fls2
Off
Time delay
dlay
On delay 1
On1
0 sec
Off delay 1
Off1
0 sec
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
68
Parameter Display Default Setting User
Setting
On delay 2
On2
0 sec
Off delay 2
Off2
0 sec
Break 1
Brk1
Off
Break 2
Brk2
Off
Password
pass
0000 (unlocked)
Advanced Features
N/A
Adjust
Adj
0.0° (temp only)
Filter
fltr
10
Bypass
byps
0.2
Serial settings
serl
Protocol
pdC
PDC protocol
Address
addr
00
Baud rate
baud
2400
Trans delay
trde
10 ms
Function
Func
Linear
Cutoff value
CutF
0.00 (disabled)
Output option
out/Aout
Factory set only
Display intensity
inty
Level 8
Modbus defaults N/A
Address
addr
247
Parity
prty
Even
Byte-to-byte timeout*
tbyt
0.01 sec
*Note: The byte-to-byte timeout setting might be updated automatically de­pending on the baud rate selected and the previous timeout setting. The minimum timeout allowed is saved to memory if a lower value is entered (e.g. If user enters 0.00 with a baud rate of 300, 0.06 is saved).
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
69
Troubleshooting Tips
Symptom Check/Action
No display at all
Check power at power connector
Not able to change setup or pro­gramming,
LoCd is displayed
Meter is locked, enter correct four-digit password to unlock
Meter displays error message dur­ing calibration (
err)
Check:
1. Signal connections
2. Input selected in
Setup menu
3. Minimum input span requirements
Meter displays
open
9999
-1999
Displays negative number,
not responding to RTD.
Check:
1. Input selected in
Setup menu
2. TC/RTD Switch position
3. Corresponding signal at Signal connector
Display alternates between
1.
Hi and a number
2.
Lo and a number
Press
Menu to exit Max/Min
display readings.
Display response is too slow
Check filter and bypass values
Inaccurate temperature reading
Check:
1. Temperature units (
°F or °C)
2. TC type or RTD curve selected
3. Offset adjustment
4. TC wire used
5. Calibration
If the display locks up or the meter does not respond at all
Cycle the power to restart the microprocessor.
Relay operation is reversed
Check:
1. Fail-safe in
Setup menu
2. Wiring of relay contacts
Relay and status LED do not respond to signal
Check:
1. Relay action in
Setup menu
2. Set and reset points
Meter not communicating with Me­terView
®
or other programs
Check:
1. Serial adapter and cable
2. Serial protocol selected
3. Meter address and baud rate
4. MeterView address and baud rate
Other symptoms not described above
Call Technical Support for assistance.
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
70
QUICK INTERFACE REFERENCE GUIDE
Run Mode
Setup
Password
Display
Max/Min
Input
4-20 mA
0-10 V
RTD
TC
Decimal
Point
dddd
d . ddd
dd . dd
ddd . d
A385
A392
Type J
Type K
Type T
Type T.0
Type E
F
C
F or C
To Program
Locked Unlocked
TC or RTD? Yes No
Relays
Relay 1
Relay 2
Failsafe
Delays
Action
Set point
Reset point
Auto
Auto & Manual
Latch
Latch w/Clear
Pump Alt
Off
To
Set point
Failsafe 1
Failsafe 2
To Delays
Delay 1
Delay 2
On
Off
Analog
output
Scale
Sensor
break
To Password
RTD or Type T
No Yes
Calibrate
Scale
TC or RTD? Yes No
Program
To Relays
www.GlobalTestSupply.com
Trident Model PD765 Universal Input Meter Instruction Manual
71
Right Arrow & Menu
(or hold Menu for 3 sec)
Pushbutton Function Menu Go to Programming Mode or leave Programming, Advanced
Features, and Max/Min Modes.
Right Arrow Move to next digit. Up Arrow Move to next selection or increment digit. Enter/Ack Accept selection/value and move to next selection.
Right Arrow & Menu simultaneously enters Advanced Features
Max/Min Mode
While in Run Mode, pressing Up Arrow will initiate Max/Min Mode. Up Arrow toggles between Max & Min displays, and Right Arrow resets the Max/Min to the current value. Press Menu or wait 10 seconds to return to Run Mode. Pressing Enter/Ack will disable the 10 second timeout and continuously display Max or Min.
Press Right arrow and Menu to access Advanced Features Menu
When the meter is locked, Adjust, Filter and Bypass can only display their settings, and the Copy and ICAL functions are not available.
Adjust
Filter
Bypass
Serial
Copy Send
TC or RTD? Yes No
TC or RTD? Yes No
Initial
Calibrate
Diagnostics
Select
Function
Cutoff
Output
Linear
Sq. Root
Address
TX Delay
Baud
Protocol
Parity
Modbus
PDC
Byte-to-byte
timeout
Modbus? No Yes
Intensity
Program
Run
Max &
Min
Advanced
Features
Up Arrow
Menu
Menu
Menu
Menu
Operational Modes
www.GlobalTestSupply.com
Loading...