Triaqua Tritherma AH-6, AH-8, AH-11, AH-15DC Installation And Operation Manual

AIR TO WATER HEAT PUMP
Installation and Operation Manual
DC INVERTERDC INVERTER
H series Only Heating series AC series Heating Cooling series HC series Mutifunctional Heating Cooling Hot water
:
Content
Safety Precautions
Transport and storage
General
2
2
2
3
4
11
12
17
19
2
Components
Wired LCD Controller
Error Code
Installation
Electric connection
Test run
Safety Precautions
Note!
It is required to read the Safety precautions in detail before operation. The precautions listed below are all-important for safety, please obey without fail.
Make sure that the fixed ground wire in the building is securely connected to earth.
Wiring tasks should be carried out by qualified electricians only, in addition, they should check the safety conditions of power utilization, for example, check if the line capacity is adequate, and check if the power cable is damaged.
Users must not install, repair or relocate the unit. Improper treatment might lead to the accidents e.g. personal injury caused by fire, electrical shock or unit's falling-
off, and water leakage in the machine. Please contact professional repair and service department of local dealer.
In case the leaked gas is congregated around the machine, there might be the risk of explosion.
The unit shall not be installed at a spot with potential hazard of leakage of inflammable gas.
If the foundation is unstable, the outdoor unit may drop and cause a casualty accident. so this must be validated carefully.
Make sure that the foundation of installation is stable.
If no electric leakage protection switch is fitted at the beginning of the electric supply, it maybe cause electric shocks or fires.
Make sure that the electric leakage protection switch is fixed.
Before cleaning, shut off the electric supply of the unit firstly to avoid injuries caused by fan in operation. Do not rinse the unit by water because the rinsed unit may cause electric shock.
Please observe the follow items when cleaning the unit.
Make sure to shut off the electric supply before maintaining the unit.
Please do not insert fingers or sticks into air outlet or air inlet.
The machine must be transported and stored vertically.
General
If any abnormity occurs in the unit (such as burned taste inside the unit), cut off the power supply immediately, and contact professional repair and service department of local dealer.
The machine must be transported and stored vertically.
Transport and storage
3
Components
4
Plate heat exchanger Fan and fan motor
20
Evaporator
Transformer
Terminal blocks Water system control board 4 way valve 3 way valve
1
2
3 4
5
6 7 8
9
10
12
13
14 15
16 17
18 19
Position
Position
Component
Component
Compressor
Gas liquid isolator
Water inlet
Drain
Needle valve
AH-6,AH-8,AH-11,AH-15DC
2
3
4
1
5
6
7
19
20
8
15
14
9
10
12
13
17
18
16
IPM Module Main control board AC Outlet
Thermal Expansion Valve
DHW Outlet Water circulation pump(Optional)
CONTROL PANEL
. 1 Wire controller
Wire controller contains a LCD and 6 operational keys (as show below). It can keep memory when power off
and be a timer.
2. Key functions
(1)Double-colored indicator light: when standby, blue light on; when compressor worked, red light on; when
breakdown happened, red light on. For more details, please check fault code sheet.
(2).H\³Rn/off´ : power on /power off.
(3).H\³WLPHDGMXVWLQJ´: adjust clock or set time.
(4).H\³Gown´LW¶s a combined key to decrease numerical value, continuous press, then continuous decrease;
short press, then decrease by 1.
(5).H\³Xp´: LW¶s a combined key also, but opposite to down key. Continuous press, then continuous increase; short press, then increase by 1.
(6).H\³Fonfirm´: confirm previous operations
(7).H\³Pode´: operational PRGH¶Vswitch. ,W¶VDFRPELQHGNH\DOVR.
3. Icon Meaning
NO. Icon meaning NO. Icon meaning NO. Icon meaning
8 Clock display 9 Returned AC Temp. 10 Maintain icon
11 Lock icon 12 Temperature icon (Reserved) 13 Parameter number icon
14 AC Cooling icon 15 Sterilization icon 16 AC heating icon
17 Sanitary hot water icon 18 Water/ground source display 19 Parameter icon
20 Domestic Hot Water
temp
21 Timer on icon 22 Timer off icon
20 Sterilization days dis-
play
21 Sterilization on display 22 Sterilization off display
23 Clock icon
5
UNIT OPERATION
. 1 Switch the unit On and off
To start the unit, press and hold the On/Off key for one second
To stop the unit, press and hold the On/Off key for one second
. 2 Mode switch5 modes in total
A. Under mode standby or On, press the M key repeatly, the following icons will flash by recycling.
AC cooling -> AC heating -> DHW(Domestic hot water)-> AC cooling + DHW ->AC heating +
DHW
When selected a mode, press button to confirm, then the icon will be solid, heat pump will perform as
selected.
B. When in mode AC cooling +DHW or AC heating & DHW, DHW heating will be the priority.
C. When select DHW mode, only hot water system working, no air conditioner working.
D. When select air conditioner mode, only air conditioner system working, no sanitary hot water system working.
E. Sterilization is independent and auto-operated. You can change parameter according to need.
.3 Procedures of setting parameter change
A. When in settled mode, the unit will operate in accordance with the factory default temperature or last modified
temperature.
6
B. Modification method for settled temperature
In the on / standby mode, press key M and for 3 seconds, the current operating mode light will flash;
by press the M key, you can switch modes in the following order: Cooling / heating / hot water / sterilization;
press to confirm the mode and press key or to setting value, then press key to confirm, then exit
and save current changes;
if didn’t press key to confirm, it will exit the parameter modification automatically 15 seconds later. Pre-
vious Changes will not be saved.
Detailed settings as follows:
NO. Meaning Settled temperature
range
Default temperature operation for modify settled para-
meters
1 AC cooling returned
water temp
10℃~25 12
M+
M→ →▲or▼→
2 AC Heating returned
water temp
10℃~55 45
M+ →M→ →▲or▼→
3 sanitary hot water
heating
AU10℃~60 50
M+
M→ →▲or▼→
4 Legionella
Anti-bacteria
60℃~70 65
M+
M→ →▲or▼→
UNIT OPERATION
C. Time setting procedure for health sterilization
Only in sanitary hot water mode, health sterilization will work. If sanitary hot water mode off, health sterilization
will fail to work.
In on or standby mode, first, press key M and for 3 seconds, second, press key M ,15 icon appears, then
SUHVVWKHŸRUźWRset sterilization temperature, press key to confirm, the number of days will flash and
show the original or default value 7 (that means 7 days), press key ŸRU źWRLQFUHDVHRUGHFUHDVHWKHQXPEHU
of days at predetermined intervals, the minimum of 7 days, maximum of no more than 99 days, after that ,press
key to confirm. At this time, "ON" character appears, "hour" appears and flashes, show the original setting
or the default value (default value 01 means it will start at 1:00 am), followed by press key ŸRUźWRPRGLI\
(0-23) ,after that, press key to confirm, then the new time start running. "ON" character disappears, "OFF"
character appears, "minute" value flashes and shows the original or default value (default value is 10), followed
by press key ŸRUźWRFKDQJHPLQLPXPis 10, maximum no more than 99), after that press key
to confirm
and exit change mode. If GLGQ¶WSUHss key to confirm, machine will exit change mode automatically after 15
seconds. But settings did right now will become invalid.
4 Time adjustment
Press key WLPH³KRXU´YDOXHZLOOIODVKWKHQSUHVVNH\ŸRUźWKHYDOXHZLOOLQFUHDVHRUGecrease. Press
key and keep, the valve will increase or decrease constantly as you want. After Settle down, please press key
to confirm, then exit from time adjusting mode.
5 Time setting
You can set one time to start and one time to off. And select one time working or cyclic working.
A settled time on method: (1) Press
for 3 seconds and come to time setting, will flash as show below.
(2) Press key ŸRUźWRPRGLI\WLPHYDOXHDQGSUHVV to confirm. This setting only valid for one time. If you
want time setting to work cyclic, please press key
after time setting, then press key to confirm.
B Timing off method are the same as timing on method. C Please press key
for 3 seconds and come to timing mode, press to cancel time setting.
7
. UNIT OPERATION
6 Parameter Checking and setting
Please press key M+Ÿ for 3 seconds and enter to parameter setting mode as show below.
³´LV SDUDPHWHU FRGH³´LV SDUDPHWHU YDOXH
s.
2WKHU LWHPV¶ SDUDPHWHUV PHDQLQJ DUH WKH VDPH ZLWK above
picture showed.
Parameter list as below:
Note
˖
Usage of Parameter 14: G3 function parameter (ref to Solar Application 1)
when this parameter is 1, when air conditioning heating run, it will compare solar water tank temp with air conditioning returned water temp, when solar water tank temp is 5 or more degree higher than air conditioning returned temp, the 3-way valve G3 electricity supply will be on; when solar water tank temp - air conditioning returned temp is less than 2 centigrade, G3 electricity supply will be off. This function is to use solar to preheat for room heating and DHW tank water. When this parameter is 0, G3 is seasonal switch valve, when the heat pump is working for heating, G3 is on, when heat pump is working for cooling, G3 is off. Normally use one 3-way valve with 3 wires. 2 wires are always connected with electricity supply and 1 signal wire is connected with heat pump G3 terminal port to enable function.
8
2. Usage of Parameter 14: G3 function parameter (ref to Solar Application 1)
Usage of Parameter 26: AC water pump working mode (ref to Page 16)3.Usage of Parameter 26: AC water pump working mode (ref to Page 16)
If no AC buffer tank, The Parameter 26 better to be set to 0, then AC water pump will work continously to keep the AC loop water
temp always the same.
If with AC buffer tank, the parameter 26 can be set to 1, but the AC inlet water temp must be changed to insert to AC
buffer tank as reference to page 16.
1.Press key for 5 seconds, after heard 1 beep, The Factory default parameter will be reset.
NO. Name range/meaning default status 00 power down auto restart 0not recovery1restart 1 check/set 01 DHW water temp. return differential 2~15℃,minus differential 2 check/set 02 air conditioning return differential 2~15℃,minus differential 2 check/set 03 Copper pipe temp to start defrost -20~5 0 check/set 06 defrost stop temp. 10~35 30 check/set 07 Max defrost duration time 15~99 mins 15 check/set 08 defrost interval time between 2 defrosts 15~99 mins 35 check/set 09 air temp to start DHW electrical heater -20~20 0 check/set 10 air temp. to start AC electrical heater -20~20 0 check/set 11 DHW working frequency limit. 2~10, (refer to DHW frequency 20hz~100hz) 10 check/set 12 Compressor discharge air protection temp A0~C7 = (100~127℃) B0 check/set 13 Defrost interval time multiply rate 0: No defrost 1~4: Parameter08*1~4 1 check/set 14 function parameter 0G3 is seasonal switch valve
1G3 is solar pre-heat valve
0 check/set
26 AC water pump running mode
0, 1, 2 (0:not stop, 1:stop when reach target temp, 2: run 1 minute every 15 minutes stopping)
0
check/set
27 2nd heat source control validation
0, 1 (0: 2nd heat source control disable; 1: control enable)
0
check/set
28 Air temp to start 2nd heat source control
-15~10
-15℃ check/set
UNIT OPERATION
.7 Machine operational status Checking
Press ERWKNH\0DQGźIRUVHFRQGVWKHQHQWHUHGPDFKLQHVWDWXVIRUP. Show as below.
³C0´LVSDUWRUSDUDPHWHU12. ³28´ stands for parameter. Parameter 0 means system on, 1 means system off.
For more detail, please check form below.
Press M+ źIRUVHFRQGVWRVHDUFK and check parameters .
9
NO. Name range/meaning status 00 Outdoor pipe temp. -30~97 check 01 Compressor Exhaust gas temp. inverter: -30~97(0:disconnected:1: connected) check 02 Ambient temp. -30~97 check 03 AC outlet water temp. -30~97 check 04 DHW pipe temp. -30~97 check 05 Solar pipe water temp. -30~97 check 06 Switch input status 0heating&cooling1heating only check 07 Switch input status 0air source); 1water source check 08 Switch input status 0DHW invalid); 1DHW valid check 09 Switch input status 0G1 valid); 1G1 invalid check 10 high pressure switch status 0off); 1on check 11 overcurrent protect switch status 0off); 1on check 12 low pressure switch status 0off); 1on check 13 inside water flow switch 0off); 1on check 14 outside water flow switch 0off); 1on check 15 The 2nd
high pressure switch status
0off); 1on check 16 Defrost temp check 17 air conditioning antifreeze temp check 18 System antifreeze temp check 19 Compress Inverter: actual running rate check 20 Outdoor fan motor 1run0stop check 21 crankcase heater 1run0stop check 22 4-way valve 1run0stop check 23 Bypass valve 1run0stop check 24 solenoid valve 1 1run0stop check 25 solenoid valve 2 1run0stop check 26 solenoid valve 3 1run0stop check 27 Electrical heater 1 1run0stop check 28 Electrical heater 2 1run0stop check 29 C4 water pump 1run0stop check
UNIT OPERATION
8 Displays for different kinds of modes
(1tritherma water/ground source heat pumps icons 2air source heat pumps icons:
3powered off display
(water source heat pump has water source Icon. If it has timer on/off setting, there is timer icon to indicate. )
4AC cooling display ᧤5heating display
(water source heat pump has water source Icon. If it has timer on/off setting, there is timer icon to indicate. )
10
29 C4 water pump 1run0stop check 30 C5 water pump 1run0stop check 31 C6 water pump 1run0stop check 32 functional parameter
0-99 (accumulated days from last sterilization till now
check 33 cooling target temp check 34 heating target temp check 35 DHW target temp check 36 Sterilization temp. check 37 outdoor unit module temp. -30~97 check 38 Outdoor unit returned gas temp. -30~97 check 39 Internal pipe temp. -30~97 check
UNIT OPERATION
6sanitary hot water display
(water source heat pump has water source Icon. If it has timer on/off setting, there is timer icon to indicate. )
7AC cooling and sanitary hot water display ᧤8AC heating and sanitary hot water display
(water source heat pump has water source Icon. If it has timer on/off setting, there is timer icon to indicate. )
9 way of communication
Non-polarity double wire, maximum running length is 100 meters and point to point connected.
Back view of wired controller showed below.
㒓᥻఼㚠䴶
(after change, need be repowered to enable the change)
SW1-8
OFF˖cooling valid˗ ON: cooling invalid
SW1-7
OFF˖heating valid˗ ON: heating invalid
SW1-6
OFF˖DHW valid; ON˖DHW invalid
SW1-5
SW1-4
OFF˖inverter outdoor model˗ ON˖on/off outdoor model
SW1-1
OFF˖geothermal˗ ON˖air source
11
10 Function Selection Switch: SW1
SW1-3 reserved
SW1-2 reserved
SW1
reserved
When machine has error, the control will show “P” or “E” at AC temp location and show error code at DHW temp location, press key
ź to search more error codes happened at the same time. Please see table below for error code meaning.
Code display like EX or Px, eg: E2ǃP5
12
ERROR CODE
code Breakdown meaning Outdoor Led2 Remark E1 compressor discharge gas high temp. protect Flash 10 times 1.Refrigerant low 2. throttling device problem E2 Outdoor air temp sensor fault Flash 3 times Sensor open circuit or short circuit E3 Pipe temp or returned air temp sensor fault Flash 6 times Sensor open circuit or short circuit E4 AC returned water temp. sensor fault No flash stop compressor in AC E5 AC output water temp. sensor fault No flash stop compressor in AC E6 Hot water temp. sensor fault No flash Hot water, stop compressor E7 Solar water temp. sensor fault No flash Compressor run E8 coil hot water protect Flash 15 times Decided by Outdoor unit E9 system antifreeze twice No flash Stop compressor EA DHW antifreeze twice No flash Stop compressor Eb Indoor refrigerant pipe temp sensor error No flash EC Water source inlet water temp sensor error Flash 16 times Ed Water source outlet water temp sensor error Flash 16 times EE Water source antifreeze protection Flash 15 times 1.Water source heat exchange not sufficient or water source
water temp too low. 2.water source water flow not enough EF Water source water flow volume not enough Flash 17 times Stop compressor
F1 Voltage protect Flash 1 times Voltage too high or too low (after voltage become normal
165~265VAC, unit auto recover)
F2 Rating module PFC error Flash F3 Compressor stopped abnormally Flash F4 outdoor module radiator sensor fault Flash 5 times IPM module temp sensor error F5 Outdoor unit current sensor fault Flash 8 times Current sensor fault or not cross the test wire F6 IPM or module control board fault Flash 14 times Communication not good or IPM broken F7 Compressor fail to start Flash Decided by Outdoor unit F8 Outdoor unit overcurrent Flash 11 times Compressor current too high F9 Exhausted gas temp. sensor fault Flash 7 times FA Outdoor module overheat,over-current Flash 5 times IPM temp too high, compressor current too high
FB/E8
Outdoor coil overheat Flash 15 times Outdoor heat exchange not sufficient
P1 high pressure protect Flash 2 times 1.Refrigerant high 2. throttling device problem 3. High
pressure switch fault P2 Low pressure protect Flash 9 times 1.Refrigerant low 2. throttling device problem 3. Low
pressure switch fault P5 indoor unit water flow fault Not flash 1.water flow too small. 2.Water flow switchfault P6 outdoor unit(water source side) water flow
fault
Flash 17 times 1.water source side water flow too small. 2.Water flow switch
fault P7 phase loss Flash Power connection fault P8 Wrong phase Flash Power connection fault P9 Communicate fault Flash Power connection fault or communication fault
.
Method 1
13
Method 2
DHW with Room Heating
Installation
1 Installationmethod
1. C4 water pump and multifunctional box can be built inside of heat pump according to order requirement.
2. C4 water pump can be used for both DHW and air conditioning water circulation.
3. installer should check the actual water resistance and make sure to keep enough minimum water flow volume, if necessary, more water pumps should be added for DHW (C5 water pump) and air conditioning(C6 water pump) water circulation. The water pump connection can be found in wiring diagram.
4. Safety valve(air discharge valve) should be installed at the top of the circulation system for easy air discharge.
Air conditoning circulation can utilize the fan coil or radiator air discharge valve.
Method 4
Method 3
14
Note:
16/17 Air discharge valve(Safety Valve)
1. Heat Pump
2. Wired Controller
3. DHW water pump
4. DHW temp sensor
5. DHW water tank
6. Safety valve
7. Filter
8. Water pump ->C4
9. Drain valve
10. Ball valve
14. Expansion tank
12. Water pump ->C5
13. Water pump ->C6
C4
C6
C5
15. Multifunctional 3 way valve (can be installed inner or outside of heat pump unit)
G1
.
Application 1
Application 2
15
Installation
2
Installation with solar assistant
.
Application 3 The most energy saving application
16
G1 DHW and AC switching valve G3 Solar automatic selection valve
: :
Installation
Application with AC water pump stop when reach target temp
Water Pump
Radiator
Ceiling Conceal Water Fan Coil
Floor Ceiling Fan Coil
Block here
AC Returned water temp sensor change to water tank
Water pump is controlled by room thermostat
Brine
Brine
1.Set parameter 26 to 1. Must change the AC inlet water temp sensor(6)IN2 into buffer tank.(ref to wiring diagram).
2.Must add AC buffer tank and 2 water pumps at both side of the buffer tank. The room side water pump is contrlled by room thermostat. Heat pump side water pump is controlled by heat pump C4 or C6.
3.Must use brine not pure water at both side of the buffer tank.
Installation position
Installation in exceptional circumstances(unit:mm)
6 The unit must be installed upon reliable machine base or framework. Weight capacity of framework should be 3
times of the body weight, and safeguard measures should be taken to avoid malfunction of fastenings.
4 Ensure the unit is well ventilated, direction of air exhaust is kept away from windows of neighboring buildings, and the exhaust air cannot flow back. moreover, adequate service clearance should be kept around the unit.
5 The unit should not be installed at places accompanied with oil, inflammable gases, corrosive components e.g. sulfur compound, or high-frequency equipment.
1 If the unit is to be installed on the floor, its undercarriage should be heightened, to avoid ingression of accumulated water in rainy season. In snowy areas, it is important to prevent accumulated snow from blocking up the air-out. The recommended height is 20cm to 30cm.
2 Drain ditch or other facilities should be arranged under the outdoor unit,
to avoid the environment influence
because of water discharge.
3 To install the unit at balcony or top of building, the installation site must meet the allowable bearing capacity of building structure, without affecting the structural safety.
7 The unit should not be installed at sites with typhoon/ earthquake hazards. Midair installation should be avoided as much as possible, for machine falling may result in severe accident.
Installation must be carried out by professional personnel.
No obstacle in front of the unit
200
200
350
Outdoor unit
500
350
Obstacle above the unit
Note!
1000
Obstacle in front of the unit
Several units in a row
Outdoor unit
400
200
350
Outdoor unit
Outdoor unit
Outdoor unit
17
5.Installation
General
The heat pump must not be connected without the permission of the electricity supplier and must be connected under the supervision of a qualified electrician.
The heat pump does not include an isolator switch on the incoming electrical supply. The power supply cable must be connected to a circuit-breaker with at least a 3 mm breaking gap. Incoming supply must comply with the technical requirements, with ground wire, via a distribution board with fuses.
Note!
Electrical installation and service must be carried out under the supervision of a qualified electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force.
Wires, spare parts and materials etc. must satisfy the relevant standards issued by the host country or region.
Isolator switch
If an insulation test is to be carried out in the building, please make sure to disconnect the heat pump.
To avoid the possibility of false action caused by electromagnetic coupling, the communication wire must
2
be STP(Shielded Twisted Pair). The size of communication wire should not less than 0.5mm .
Electric connection
18
W
B
D
H
A
AH-6,AH-8,AH-11,AH-15
:  
'  
+  
1091
400 780
$  
%  


0RGHO $+$+ $+
AH-15
Unit Dimension(mm)
Electric connection
19
2nd AC Switch Function(2nd On/Off Switch)
The 2nd switch function enable our heat pump to be controlled by any additional user's thermostat or remote switches for convenient control.
Function: When 2nd switch is off, the heat pump AC mode will run on standby mode no matter the AC water temp reach target or not. When 2nd switch is on, the heat pump will run according to set temp.
A Connected to
manual switch
.
B Connected to any user's thermostat.
C Connected to both manual switch
together with any user's thermostat
.
IN7(10)
Wiring Diagram (AHP-HC type,with built-inside water circulation pump)
Test run
Preparation
After finish the installation tasks, please check the items: 1 Check the dip switch setting and short wiring
2 Power cable
3 Communication wire
4 Water circuit
Check if the power cable is connected correctly, and check if the screws have been screwed down.
Check if the communication wire is connected correctly.
Check if the water pipes are correctly connected, and the pipe dimensions are correct.
Check if all the shut off valve and manual valve is opened, check if all the joint is fastened.
Heatproof measures must be taken for water outlet pipes and water inlet.
Please use specified cables.
Please adopt specified communication wire.
20
Water or Brine Filling
1 with water pipe connected to the unit s water system, and open all the air exhaust valves in water system
.
2. Discharge the air for both domestic hot water sytem and air conditioning water system, including all usage
and there is no air inside the water system.
Turn on the heat pump
select heating, domestic hot water mode , check whether the unit is running properly or not,the compressor will be started in 3~5 minute after powered on.
Running
MOST IMPORTANT !
3.Make sure it is not in cooling mode during first operation or test running unitl you make sure the air conditioning circulation pump is working properly and water is recycling smoothly.
2 Select a big enough water pump for the air conditioning water circuit
1.Alway keep electricity connection with heat pump to enable the antifreeze function.
. ,
.
. .
. .
and fill water into the system. Keep the air exhaust valve open untill there is continous water coming out
of the air exhaust valve. Then close the air exhaust valve.
terminals such as domestic hot water tank, fan coils,radiators and etc. To make sure all system are full of water
Note!
To avoid the heat pump to be frozen, if the air temp is possible to be under zero degree in winter,you need
.
to use brind(glycol) to replace pure water in case of electricity cut off
accident during winter