TriangleTube Smart Line, Smart 40, Smart 50, Smart 60, Smart 80 Installation And Maintenance Manual

...
Page 1
Technical Specifications
Indirect Fired Water Heater
L
I
S
T
E
D
Installation and Maintenance Guide
WARNING
Before proceeding with installation and operation, read entire manual care­fully. Failure to do so can cause injury or property damage.
When receiving SMART Water Heaters, any claims for damage or short-
IMPORTANT
age in shipment must be filed immediately against the transportation company by the consignee.
Retain and affix this manual near the water heater for future reference
Installations and service should be performed by a license plumber or gas fitter in the Commonwealth of Massachusetts.
Date Revised 01/8/12
2010-49 SMART IWH Manual
Page 2
Table of Contents
Product & Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Pre-Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Installation - Piping
Temperature & Pressure (T&P) Relief Valve  . . . . . . . . . . . . . . . . . .4-5 Drain Valve  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Automatic Air Vent  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Thermal Expansion   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Water Hammer  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Vacuum Breaker  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 General Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Domestic Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7 Thermostatic Mixing Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Recirculation Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Multiple Water Heater Systems   . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Boiler Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installation - Piping Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-14 Installation - Wiring
Wiring Requirements  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Circulators  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Zone Valves  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Snap-Set Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Installation - Wiring Drawings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-21 Water Heater Start-Up
Filling the Inner (Domestic Water) Tank  . . . . . . . . . . . . . . . . . . . . .22 Filling the Outer (Boiler Water) Tank   . . . . . . . . . . . . . . . . . . . . . . .22 General Notes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Adjusting the Water Heater Thermostat  . . . . . . . . . . . . . . . . . . . . . .24
Water Heater Maintenance
Maintenance Schedule  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Filling Water Heater  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Draining Water Heater  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25-27 Draining Inner (Domestic Water) Tank . . . . . . . . . . . . . . . . . . . . . . .26-27 Draining Outer (Boiler Water) Tank  . . . . . . . . . . . . . . . . . . . . . . . . .27
Replacement Parts List
SMART Series  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-29
Water Heater Specifications
SMART Series  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Performance SMART Series  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Page 3
Product & Safety Information
Following terms are used to bring attention  to the presence  of  various  risk  levels,  or  to  important information concerning product life.
DANGER
Indicates presence of a hazard which will cause severe personal injury, death or sub­stantial property damage if ignored.
WARNING
Indicates the presence of a hazard which can cause severe personal injury, death or substantial property damage if ignored.
CAUTION
Indicates the presence of a hazard which will or can cause minor personal injury or damage if ignored.
NOTICE
DANGER
Hot Water Can Scald!
Water  temperatures  over  125ºF  can  cause severe burns instantly or death from scalding.
Children,  disabled  and  elderly  are  at  highest risk of being scalded.
Never leave them unattended in or near shower, bathtub or sink.
Never allow  small  children  to use a hot water faucet or draw their own bath.
If anyone  using  hot  water  in  the  building  fits the above description or if local codes or state laws require specific water temperatures at hot water faucet, it is recommended:
- to install a thermostatic mixing valve at this appliance or at each water faucet. or
- to set the thermostat knob for the lowest tem­perature  which  satisfies  your  hot  water needs.
Indicates special instructions on installa­tion, operation, or maintenance which are important but not related to personal injury hazards.
BEST PRACTICE
Indicates recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equipment
Water  drained  from  the  system  drain  valves may be extremely hot.  To avoid injury:
– Make sure all connections are tight. – Direct water flow away from any person.
CAUTION
Protection must be taken against excessive temperature and pressure!
Installation  of  a  Temperature  &  Pressure
(T&P) relief valve is required.
CAUTION
To prevent damage to the inner tank, the Installer must:
Always  fill  inner  tank  prior  to  outer  tank
and always  drain  outer  tank prior  to  inner tank.
Relieve primary system pressure below 15
psig prior to draining inner tank.
1
Page 4
Pre-Installation
Codes Compliance
Water  heater  installation  must  conform  with  the instructions in this manual and where applicable:
local, state, provincial, and national codes, laws, regulations and ordinances.
in Canada - CAN / CGA B149.1 or B149.2 Installation Code.
SMART water  heaters  are  exempt  from  ASME Section  VIII,  Division  1  Code  construction  per Interpretation VIII-86-136.  Check with local codes for applicability.
NOTICE
SMART Series water heaters will absorb less than 200,000 BTU/hr when domestic water outlet temperature is 210ºF and boiler water supply temperature is 240ºF. Listed outputs are based on ASME Section VIII Interpretation VIII-1-86-136.
Where  recommendations  in  this  manual  differ from local, or national codes, the local or national codes take precedence.
2. The  pressure of  the heat transfer  medium  is maintained  less  than  the  normal  minimum operating pressure of the potable water system
Exception: Steam  complying  with  sec-
tion #1 above.
3. The  equipment  is  permanently  labeled  to indicate  that  only  additives  recognized  as safe by  the  FDA  shall  be  used in  the  heat transfer medium.
Other  heat  exchanger  designs  may  be  permitted where approved by the Administrative Authority.
Operating Restrictions
Maximum domestic hot water temperature is  194ºF  for  commercial  applications  and 140ºF for residential applications.
Maximum  boiler  water  temperature  is 210ºF.
Maximum  working  pressure  for  inner (domestic water) tank is 150 psig.
Maximum  working  pressure  for  outer (boiler water) tank is 45 psig.
pH  and  chloride  limits  for  water  heaters are:
Codes Restrictions
Single  wall  heat  exchanger  in  the  SMART water heater complies with  National Standard Plumbing Code, provided that:
– boiler water (including additives) is practically
non-toxic, having toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products, and
– boiler  water  pressure  is  limited  to  maximum
30 psig by approved relief valve.
Single wall heat exchangers are permitted under the Uniform Plumbing code - Paragraph L3.2. and L3.3 if they satisfy all  of the following requirements.
1. The heat transfer medium is potable water or contains  only  substances  which are  recog­nized  as  safe  by  the  U.S.  Food  and  Drug Administration.
- chloride, less than 150 mg/l (ppm)
- pH value min. 6 - max. 8
NOTICE
Any water conditioning system must be installed and maintained in accordance with manufacturer’s specifications.
NOTICE
Do not install the water heater on any appli­cation if the boiler piping contains non-oxy­gen barrier tubing or if the boiler piping is considered an “open system”. Exposing the outer tank of the water heater to oxygen contamination will lead to premature tank failure and denial of the warranty.
2
Page 5
Pre-Installation
Locating Water Heater
This water  heater  is  not  intended  for  out­door installations.
Keep  distance  between  boiler  and  water heater to a minimum to:
– reduce piping heat loss
– provide minimal friction loss
Locate water  heater  so  that  any  leakage  from the  tank  or  water  connections  will  not  cause damage to the area adjoining the water heater or to lower floors in the structure.
– When such a location is unavoidable, a
suitable drain pan with adequate drainage, should be placed under the water heater.  
The SMART Series Water Heaters are designed for vertical installation only.
Recommended Clearances
Water  heater  should  be  installed  to  allow adequate clearance for servicing.
Zero clearance is permissible to any side of the SMART Series water heater, but infor­mation labels may be hidden.
Recommended top or vertical clearance is 12” minimum.
Refer to boiler manual for boiler clearances.
3
Page 6
Installation - Piping
Temperature & Pressure (T&P) Relief Valve
CAUTION
To reduce risk of excessive pressures and tem­peratures in the water heater, install tempera­ture and pressure protective equipment required by local codes, but no less than a com­bination temperature and pressure relief valve certified by a nationally recognized testing lab­oratory that maintains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. This valve must be marked with a maximum working pressure of the water heater.
Every SMART water heater must be protected with a T&P relief valve.
Determine T&P relief valve size by the follow­ing  specifications,  unless  they  conflict  with local codes:
Standard Installation
Install T&P relief valve  in the Auxiliary con-
nection located behind the air vent on the top of the water heater (Figure 1 page 8).
or
Install the T&P relief valve in the run (straight through leg) of a tee located at the domestic hot water outlet when using the Auxiliary connec­tion for a recirculation return (Figure 2 page 8).
Commonwealth of Massachusetts Installation
Follow this procedure for jurisdictions requiring a vacuum  breaker  to  be  installed  on  the  domestic cold water inlet.
Install the T&P in the run (straight through leg) of a tee located at the domestic hot water out­let. Use a  long element T&P relief valve (Fig. 3B page 9).
T&P Relief Valve Discharge Piping
T&P relief valve discharge piping must be:
- SMART 30/40/50: 3/4”NPT with an AGA Rating of 100,000 BTU/hr and a maximum pressure rating of 150 psig. (Watts 100XL­8 or equivalent).
- SMART 60/80/100/120: 3/4”NPT with an AGA Rating of 200,000 BTU/hr and a maxi­mum pressure rating of 150 psig.  (Watts 40XL-8 or equivalent).
NOTICE
For proper operation of the T&P and to pre­vent the T&P from activating due to boiler water temperature, use a T&P relief valve with extended element. We recommended an 8” minimum length to ensure element senses domestic water.
- made of material serviceable for tempera­tures of 250ºF or greater.
- directed so that hot water flows away from all persons.
- directed to a suitable place for disposal.
- installed so as to allow complete draining of the T&P relief valve and discharge line.
T&P relief valve discharge piping must not
- excessively long.  Using more than 2 elbows or 15 feet of piping can reduce dis­charge capacity.
- directly connected to a drain.  Terminate discharge piping within 6” from drain. Refer to local codes.
- plugged, reduced or restricted.
- subject to freezing.
be:
4
Page 7
Installation - Piping
WARNING
Do not install any valve between T&P relief valve and tank connection or on T&P relief valve discharge piping. Do not plug T&P relief valve or discharge piping. Improper placement and piping of T&P relief valve can cause severe personal injury, death or substantial property damage.
Drain Valve
Drain valve and fittings are supplied by others.
Standard Installation
Install a tee connection at the domestic cold water inlet (Fig. 1 and 2 page 8 and Fig. 2A on page 9).
Pipe the drain piping with drain valve from the tee connection to:
- a suitable place for disposal or
- terminate within 12” of the floor
3. Once the tank is full and air has stop escaping and air vent is seated and closed, screw the vent cap completely close.
NOTICE
For proper operation of the air vent ensure vent cap is tighten at all times. The air vent is provided both a hygroscopic cap that prevents leakage of water due to an internal membrane.
Thermal Expansion
If  a  backflow  preventer,  check  valve  or  pressure reducing valve is piped on cold water supply piping of  water  heater,  install  an  expansion tank  on  cold water supply line to prevent normal thermal expan­sion from repeatedly forcing open T&P relief valve.
CAUTION
Commonwealth of Massachusetts Installation
Thread  a  3/4”  close  nipple  onto  the Auxiliary  connection  and  insert  an  open­end dip tube  into the Auxiliary connection on top of water heater. As shown in Fig. 3A page 9.
Install a 3/4”  NPT  elbow to  the Auxiliary connection, see Fig. 3B page 10.
Pipe the drain piping with drain valve from the elbow connection to:
- a suitable place for disposal or
- terminate within 12” of the floor 
Automatic Air Vent
1. Remove plastic shipping cap from 1/2” NPT pipe fitting on top center of water heater.
2. Install automatic air vent provided with water heater, using suitable pipe dope or tape.
T&P relief valve is not intended for constant duty, such as relief of pressure due to repeated normal system expansion. Correct this condition by installing a properly sized expansion tank in domestic water system. Refer to expansion tank manufacturer’s installation instructions for proper sizing.
Water Hammer
Dishwashers, clothes washers and fast-closing pos­itive shut-off valves incorporated in the system all contribute to creating water shock.  Install a water hammer  arrester  to  prevent  damage  to  pipes  and appliances.  See device manufacturer’s instructions for application and installation.
5
Page 8
Installation - Piping
NOTICE
Water hammering within the domestic pip­ing system can cause premature failure of the inner tank of the water heater. This type of failure is NOT covered under warranty.
Vacuum Breaker
Installing a vacuum breaker Watts N36-M1 or equiv­alent on the domestic  cold water inlet will prevent damage  to  the inner  tank  if  a  negative pressure is developed in the domestic supply line.  See manu­facturer’s instructions for application and installation of the vacuum breaker.
General Piping
For domestic water piping diagrams, see pages 8 through 10.
See pages 11 through 14  for:
- Boiler water piping.
Use  pipe  dope  or  tape  suitable  for  potable water systems.
Use isolation valves to isolate system components.
Domestic Piping
Union on  domestic  hot  water outlet should be piped at a higher elevation than domestic water drain valve.  This will make draining the water heater easier.
Install unions for easy removal of water heater. It  is  recommended  to  use  dielectric  unions  or couplings to protect hot and cold water fittings from  corrosion  when  connecting  dissimilar materials  such  as  copper  and  galvanized  iron pipe.
If copper pipe is used for domestic water con­nections, first solder pipe to a threaded adapter and then screw adapter into cold water inlet on top of water heater.  Inlet contains an internal plastic dip tube which can be damaged by heat from soldering.
NOTICE
- Multiple water heater domestic and boiler piping.
See  Chart  1  for  domestic  and  boiler  piping connection sizes .
All  plumbing  must  meet  or  exceed  all  local, state and national plumbing codes.
Do not apply heat to the cold water inlet when making sweat connections to water heater. Sweat tubing to adapter before fit­ting adapter to cold water inlet of heater. It is imperative that no heat be applied to the cold water inlet, as it contains a non metal­lic dip tube.
Chart 1
Connections (Inches) Recirculation Dip Tube Draining Dip Tube
Water
Heater
Model
SMART 30 3/4 NPT 1 NPSC 3/4 NPSC 34 3/4 34 3/4 1
SMART 40 3/4 NPT 1 NPSC 3/4 NPSC 43 3/4 43 3/4 1
SMART 50 3/4 NPT 1 1/4 NPSC 3/4 NPSC 25 3/4 52 3/4 1
SMART 60 3/4 NPT 1 1/4 NPSC 3/4 NPSC 34 3/4 62 3/4 1 1/4
SMART 80 1 1/2 NPT 1 1/2 NPSC 1 1/2 NPSC 25 1 1/2 48 1 1/2 1 1/4
SMART 100 1 1/2 NPT 1 1/2 NPSC 1 1/2 NPSC 32 1 1/2 61 1 1/2 1 1/2
SMART 120 1 1/2 NPT 2 NPSC 1 1/2 NPSC 32 1 1/2 61 1 1/2 1 1/2
Domestic
Water
Inlet/Outlet
Boiler Water
Supply/
Return
Auxiliary
Connection
Length
(Inches)
Diameter
(Inches)
Length
(Inches)
Diameter
(Inches)
Recommended
Minimum
Boiler Piping
Diameter
(Inches)
6
Page 9
Installation - Piping
When the water supply pressure is higher than 70 psig, it is recommended to install a pressure reducing  valve  on  cold  water  supply  line  to prevent water loss through T&P relief valve.
If  water  heater  will  replace  tankless  coil  in boiler, disconnect piping to coil.  Allow  water to drain from coil.  Do not plug tankless coil.
DANGER
Plugging tankless coil inlet and outlet will result in severe personal injury, death, or substantial property damage.
Thermostatic Mixing Valve
It is recommended to install an optional mixing valve on the domestic hot water outlet.
Mixing valve should comply with ASSE 1017
Recirculation Piping
T&P  relief  valve  must  be  installed  in  run (straight through leg) of tee located at domestic hot water outlet of water heater.
It is recommended that the recirculation dip tube be installed in auxiliary connection using a close nipple assembly as shown Fig. 3A, page 9.  See Chart 1 page 6 for diameter  and  length of dip tube.
DANGER
Failure to install automatic mixing valve where recommended will result in severe personal injury or death.
Boiler Piping
If plastic pipe is used for boiler water piping, it must have a maximum oxygen diffusion rate of
0.1  mg/liter-day  for  boiler  and  water  heater protection.
NOTICE
The Smart IDWH must be installed on a closed type hydronic system. Failure to pro­vide such a system will result in premature failure of the outer tank and annulment of warranty.
Boiler  water  (including  additives)  must  be practically non-toxic, having toxicity rating or class  of  1,  as  listed  in  Clinical Toxicology of Commercial Products.
If  antifreeze  is  used  in  boiler  system,  local codes  may  require  a  backflow  preventer  on cold water supply line.  Use antifreeze specifi­cally  intended  for  hydronic  heating  systems. Inhibited propylene glycol is recommended  at a maximum 50/50 mixture.
A stainless steel or bronze circulator is required on potable water systems.
Install automatic mixing valve either at the hot water outlet of water heater or  each  hot  water faucet.
Multiple Water Heater Systems
Parallel Pipe Recirculation Systems - Manifold recirculation return to all water heaters.
Series Piped Systems - Piped return to the lead­ing (cold water inlet) water heater.
Install automatic mixing valve either at the hot water outlet of water heater or  each  hot  water faucet.
DANGER
Do not use automotive, ethylene glycol or petroleum-based antifreeze. Do not use any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage.
7
Page 10
Cold Water
Inlet
6
1
12" min.
Heat Trap
Loop
(Optional)
12" min.
Heat Trap
Loop
(Optional)
1
5
5
1
8
7
4
10
M
H
C
Installation - Piping
7
Cold Water
Inlet
6
1
Recirculating
Loop
2
3
4
1
5
5
1
8
12" min.
Heat Trap
Loop
(Optional)
12" min.
Heat Trap
Loop
(Optional)
9
Fig. 1:
Standard Installation Domestic Piping SMART Series
Fig. 2:
Standard Installation Domestic Piping with Recirculation SMART Series
1. Shut-off valve
2. Recirculation Circulator
3. Flow Check Valve
4. T&P relief valve
5. Unions
6. Backflow preventer or pressure reducing valve(*)
7. Drain valve
8. Thermal expansion tank (potable)
9. Recirculation dip tube
10. Thermostatic mixing valve (*)
(*) Optional devices may be required by local codes.
8
Page 11
7
Cold Water
Inlet
6
1
Recirculating
Loop
2
3
4
1
5
5
1
8
12" min.
Heat Trap
Loop
(Optional)
12" min.
Heat Trap
Loop
(Optional)
Fig. 2A:
Optional Installation Domestic Piping with Recirculation SMART Series
1. Shut-off valve
2. Recirculation Circulator
3. Flow Check Valve
4. T&P relief valve
5. Unions
6. Backflow preventer or pressure reducing valve(*)
7. Drain valve
8. Thermal expansion tank (potable)
(*) Optional devices may be required by local codes.
9
Page 12
Installation - Piping
Cold Water
Inlet
6
1
12" min.
Heat Trap
Loop
(Optional)
12" min.
Heat Trap
Loop
(Optional)
4
1
5
5
8
9
11
10
M
H
C
7
Fig. 3A:
Fig. 3B:
Drain Tube Assembly­Commonwealth of Massachusetts
Commonwealth of Massachusetts Domestic Piping SMART Series
1. Shut-off valves
4. T&P relief valve
5. Unions
6. Backflow preventer or pressure reducing valve (*)
7. Drain valve
8. Thermal expansion tank (potable)
9. Vacuum breaker
10. Mixing valve (*)
11. Dip tube - Draining per Chart 1
(*) Optional devices may be required by local codes.
10
Page 13
Installation -Piping
4
1
3
2
2-Port
Priority Valve
(normally open)
2-Port
Priority Valve
(normally close)
1
6
5
Cold water
inlet
1
2
4
1
3- Port
Priority
Valve
3
1
6
Cold water
inlet
5
Fig. 4:
Fig. 5:
SMART System Piping with 3-Port Zone Valve (Domestic Priority)
SMART System Piping with 2-Port Zone Valves (Domestic Priority)
1. Shut-off valves
2. Circulator
3. Expansion tank 
4. Drain valve
5. Feed valve
6. Air separator  
11
Page 14
9
1
1
2
Zone
valve
Zone Valve
1
4
7
6
Cold water
inlet
9
1
1
3
2
2
2
Zone
Circulator
Zone Circulator
3
3
4
1
7
6
Cold water
inlet
Installation - Piping
Fig. 6:
SMART System Piping with Zone Valves (Non Domestic Priority)
Fig. 7:
SMART System Piping with Zone Circulators
1. Shut-off valves
2. Circulator
3. Flow check valve
4. Expansion tank 
5. Drain valve 
6. Feed valve
7. Air separator  
12
Page 15
Installation - Piping
Circulator
Recirculated
Water
Automatic
Mixing Valve
Hot Water
Outlet
Cold Water
Inlet
T&P Relief Valve
Cold Water
Inlet
Isolation
Valve
Circulator
Automatic
Mixing Valve
Hot Water
Outlet
Cold Water
Inlet
T&P Relief Valve
Cold Water
Inlet
Isolation
Valve
Recirculated
Water
Fig. 8:
Multiple SMART Series Water Heater System Domestic Piping - Parallel
Recommended for most applications.
Any one water heater tank thermostat may be utilized to control system temperature.
Install automatic mixing valve at either the hot water  outlet  of  the  water  heater  system  or at each hot water fixture.
Each  tank  should  be  piped  with  a  drain  as shown in Fig. 1.
Fig. 9:
Multiple SMART Series Water Heater System Domestic Piping - Series
Recommended  for  applications  in  which  there  is  a large water consumption in short period of time.
A maximum of 3 water heaters may be piped in series.
Utilize the lead (hot water outlet) SMART tank ther­mostat to control system temperature.
Install automatic mixing valve at either the hot water outlet of the water heater system or at each hot water fixture.
Each  tank should be piped with  a  drain  as shown in Fig. 1.
13
Page 16
2
3
5
4
1
7
Cold water
inlet
6
1
1
2
3
5
4
1
7
Cold water
inlet
6
Installation - Piping
Fig. 10:
Fig. 11:
Multiple SMART Series Water Heater System Boiler Piping Reverse Return Balanced Flow
Multiple SMART Series Water Heater System Boiler Piping - Manifold
1. Shut-off valves
2. Circulator
3. Flow check valve
4. Expansion tank 
5. Drain valve
6. Feed valve
7. Air separator  
14
Page 17
Installation - Wiring
Connect to
outer 2 terminals
Wiring Requirements
WARNING
Electrical shock hazard can cause severe personal injury, death or substantial prop­erty damage. Disconnect power before installing and/or servicing.
1. All  wiring  must  be  a  minimum  of  18  gauge and installed in accordance with:
U.S.A. -  National Electrical Code and any other national,  state  or  local code require­ments having jurisdiction.
Canada - C.S.A. C22.1 Canadian Electrical Code Part 1 and any other national, provin­cial  and  local  code  requirements  having jurisdiction.
2. If original wire  supplied with appliance must be replaced, Type 90ºC or its equivalent must be used.
Circulators
Priority relay must be sized for total amp draw of all circulators.
Zone Valves
Transformer must be sized for  maximum load of all zone valves.
Snap Set Connection
For easy wiring between water heater thermo­stat and boiler controls see Installation Wiring section pages 15 through 18.
Make sure snap set is  firmly snapped together after wiring.
Snap Set Wiring
3. Refer  to  control  component  instructions packed with boiler for application information.
4. An optional service switch may be installed in water  heater  electrical  circuit.    This  switch would  only  shut  off  the  water  heater,  not  the home  heating  system.    Do  not  shut  off  water heater if there is a chance of freezing.
5. All  electrical  contacts  shown  do  not  have power  applied  -  off  the  shelf  condition.  See pages 15 thru 18.
15
Page 18
Fig. 12:
Optima Zone Panel SZC5 with Zone Pumps Wiring
16
Page 19
Fig. 13:
Optima Zone Panel SCZ5 with Zone Valves Wiring
17
Page 20
H
N
High Vo l t a g e
120
V
.A.C.
24
V.A.C.
Room
Thermostat
Zone 1
Additional zones
Additional zones may
be added as shown above
Transformer
(Power)
Zone Valve
Zone Valve
1
2
C
W
ater Heater
Thermostat
Snap-Set
Water
Heater
Z
one
*Isolation Relay
Boiler
Thermostat
Terminals
* Use isolation relay on 3-wire zone valves with non-isolated end switches. Transformer and boiler control can burn out if isolation relay is not used
Priority
Relay
H
N
High Voltage
120
V.A.C.
24
V
.A.C.
Room
Thermostat
Zone 1
Additional zones
Additional zones may
be added as shown above
Transformer
(
Power)
Zone Valve
Zone Valve
1 2C
W
ater Heater
Thermostat
Snap-Set
W
ater
Heater
Z
one
Boiler
Thermostat
Terminals
High Voltage Low Voltage Boiler Low Voltage
Priority
Relay
Installation - Wiring
Fig. 14:
Typical 4-wire Zone Valve Zoning, with Domestic Priority
Fig. 15:
Typical 3-wire Zone Valve Zoning, with Domestic Priority
18
Page 21
Installation - Wiring
H
N
High Voltage
120
V
.A.C.
24
V.A.C.
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
Transformer
(Power)
Z
one Valve
Zone Valve
Zone Valve
1 2
C
Water Heater
Thermostat
S
nap-Set
W
ater
H
eater
Z
one
*Isolation Relay
Boiler
Thermostat
Terminals
* Use isolation relay on 3-wire zone valves with non-isolated end switches. Transformer and boiler control can burn out if isolation relay is not used
H
N
High Voltage
120
V.A.C.
2
4
V.A.C.
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
T
ransformer
(Power)
Zone Valve
Zone Valve
Zone Valve
1 2C
W
ater Heater
T
hermostat
Snap-Set
W
ater
Heater
Zone
Boiler
Thermostat
Terminals
High Voltage Low Voltage Boiler Low Voltage
Fig. 16:
Typical 4-wire Zone Valve Zoning, without Domestic Priority
Fig. 17:
Typical 3-wire Zone Valve Zoning, without Domestic Priority
19
Page 22
2
T
T
1
4
3
5
6
Circulator
Z
one 1
Thermostat
zone 1
Honeywell
R845A
R
elay
120
H
V
A C
N
2
T
T
1
4
3
6
Circulator
Zone 2
Thermostat
z
one 2
5
2
T
T
1
4
3
6
Water Heater
Circulator
Water Heater
Thermostat
Snap-Set
5
1 2
C
Boiler
Thermostat
Terminals
Priority Relay
2
T
T
1
4
3
5
6
Circulator
Zone 1
Thermostat
zone 1
Honeywell
R845A
R
elay
120
H
V
A C
N
2
T
T
1
4
3
6
Circulator
Zone 2
T
hermostat
zone 2
5
2
T
T
1
4
3
6
Water
Heater
Circulator
Water Heater
Thermostat
Snap-Set
5
1
2
C
High Vo l t a g e
Low Vo l t a g e
Boiler
Thermostat
Terminals
Installation - Wiring
Fig. 18: Fig. 19:
Typical Circulator Zoning with Domestic Priority
Typical Circulator Zoning without Domestic Priority
20
Page 23
Installation - Wiring
T
T
1
4
3
5
6
Circulator
Z
one 1
T
hermostat
zone 1
Honeywell
R
845A
C
irculator
Relay
120
H
VAC
N
2
T
T
1
4
3
6
Circulator
Zone 2
Circulator
Zone 3
T
hermostat
zone 2
Thermostat
zone 3
5
2
T
T
1
4
3
6
5
High Voltage
Low Voltage
To Boiler 24 VAC
Thermostat Leads
2
ON
PRIORITY
ZONING CIRCULATOR
CIRC
ON
PR1
LIVE
NEUT
TT
2
1
C
Water Heater
Thermostat Snap Set
Priority Zone
Circulator
Fig. 20:
Priority Zone Circulator Wiring
Note: Maximum  of  4  total  circulator
zone when wiring 1 zone for priority.
21
Page 24
A
B
Water Heater Start-Up
Filling the Inner (Domestic Water) Tank
CAUTION
Never use water heater unless inner and outer tanks are completely filled with water.
Inner tank must be completely filled and pressurized before pressurizing outer tank.
1. Close domestic water drain valve.
2. Open  domestic  water  isolation  valves  for water heater.
3. Vent air from inner (domestic water) tank by opening  nearest  hot  water  faucet.    Fill domestic water tank completely by allowing water to run until there is a constant flow of water.
4. Close hot water faucet.
5. When  tank  is  full,  air  will  stop  escaping, and the automatic air vent will close.  If air vent  does  not  seat  properly  (water  leaks out), remove cap A.  Briefly push in valve B and release it to clean valve seat.  Screw cap A on completely,  See Fig. 19.
NOTICE
For proper operation of the air vent ensure vent cap is tightened at all times. The air vent is provided with a hydroscopic cap that prevents leakage of water due to internal membrane.
6. If  antifreeze  is  used  in  boiler  water,  check concentration.  Boiler  water  (including  addi­tives)  must  be  practically  non-toxic,  having toxicity  rating  or  class  of  1,  as  listed  in Clinical Toxicology of Commercial Products
.
Filling the Outer (Boiler Water) Tank
CAUTION
Never use water heater unless inner and outer tanks are completely filled with water.
Inner tank must be completely filled and pressurized before pressurizing outer tank.
1. Close boiler water drain valve at boiler water outlet of water heater.
2. Open  water  heater’s  boiler  water  isolation valves.
3. Allow air to escape from outer (boiler water) tank by opening vent cap A on automatic air vent, located on top of water heater.  See Fig.
19.
4. Follow  instructions furnished  with  boiler  to fill with water.
WARNING
Do not use automotive, ethylene glycol or petroleum-based antifreeze. Do not use any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage.
22
Fig. 21:
Automatic Air Vent
Page 25
Water Heater Start-Up
DANGER
HOT WATER CAN SCALD!
Water temperatures over 125ºF can cause severe burns instantly, or death from scalds.
Feel water before bathing or showering.
Consumer Product Safety Commission and some states recommend temperatures set­tings of 130ºF or less. Setting thermostat higher than 130ºF will increase risk of scald injury and cause severe personal injury or death.
Water heated to a temperature suitable for clothes washing, dish washing and other san­itizing needs will scald and cause permanent injury.
Children and elderly, infirm, or physically handicapped persons are more likely to be injured by hot water. Never leave them unattended in or near a bathtub. If anyone using hot water in the building fits this description, or if state laws or local codes require certain water temperatures at hot water faucets, take special precautions.
General Notes
Household  water  usage  patterns  will  affect water  temperature  at  any  faucet  or  shower. Occasionally  check  temperature  at  each  point of  use,  then  adjust  thermostat  accordingly. Always  recheck  temperature  after  adjusting thermostat.
When hot water is used in repeated small quan­tities,  a  “stacking”  effect  can  develop  in  the water heater.  The upper layer of water in tank can be hotter than lower layer.
Lowering  the  thermostat  setting  or  installing automatic  mixing  valves  as  indicated  in  these instructions will reduce water temperature levels. Consult your installer or service technician.
WARNING
At no time should boiler limit control be set above 210ºF. This can cause severe person­al injury, death or substantial property damage if ignored.
- Install an automatic mixing valve at water heater or at each hot water faucet, bath and shower outlet. Selection and installation must comply with valve manufacturer’s recommendation and instructions.
- Use the lowest practical temperature set­ting.
- Check water temperature after any adjustment. You must follow “Adjusting the Water Heater Thermostat” procedures.
23
Page 26
Temperature
Up
Temperature
Down
Water Heater Start-up
Adjusting the Water Heater Thermostat
Water  heater  thermostat  is  factory  set  to  its lowest  temperature.    This may  or  may  not  be suitable for your needs.
Turn thermostat knob clockwise to increase water temperature. Turn thermostat knob counter-clockwise to decrease water temperature.
WARNING
Studies have indicated that dangerous bac­teria, including legionella, pneumophila, can form in the potable water distribution sys­tem if certain minimum water temperatures are not maintained. Contact your local health department for more information.
Check water temperature at  a hot water faucet immediately after  first  heating  cycle.  Further temperature  adjustment  may  be  necessary  as water heating system  is  used.   Recheck water temperature at faucet after adjustment.
When adjusting thermostat, be sure boiler limit control is set a minimum of 20ºF higher.
SMART Series Knob
24
Page 27
Water Heater Maintenance
Maintenance Schedule
Annual service by qualified service technician should include the following:
Any procedure required by local codes.
Check air vent operation.
Verify  system  pressure.   Air venting  proce­dure may require adding water to bring sys­tem up to pressure, typically 12 psig.
Manually  operate  T&P  relief  valve  at  least once a year.  This will release some hot water.
WARNING
Before operating T&P relief valve, make sure no one is in front of or around T&P relief valve discharge piping. Hot discharge water can cause severe personal injury or substantial property damage.
Move  operating  lever  to  open  position  for  a few seconds and then move it back, allowing it to snap closed.  After T&P relief valve is oper­ated, if it continues to release water, close cold water  inlet  to  water  heater  immediately. Follow  draining  instructions,  to  relieve  pres­sure from the inner tank and replace T&P relief valve.  If T&P relief valve weeps periodically, it  may  be  due  to  thermal  expansion  see Thermal Expansion, page 5.  Do not plug T&P relief valve or discharge piping.
DANGER
Plugging T&P relief valve or discharge pip­ing can cause excessive pressure in water heater, resulting in severe personal injury, death, or substantial property damage.
Follow instructions on circulator to oil it, if required.
Check  mixing  valve,  valves,  pipes  and  fit­tings for leaks.
Check  function  of  field-installed  controls and valves.    See  component manufacturer’s instructions.
Review  homeowner’s  maintenance  responsi­bilities  and  their  frequencies, including  any not listed in the following section.
Homeowner monthly maintenance to include:
Check air vent operation.
Automatic  air  vent  -  remove  hygroscopic
cap.  Briefly push in valve and release it to clean valve seat.  Screw cap on completely. If  air  vent does  not  operate,  call  qualified service technician.
Visually check valves, pipes  and fittings for leaks.    Call  qualified  service  technician  to repair leaks.
Filling Water Heater
See “Filling the Inner (Domestic Water) Tank  and “Filling the Outer (Boiler Water) Tank” on page 22.
Draining Water Heater
Drain water heater if it will be shut off and exposed to  freezing  temperatures.    Freezing  water  will expand and damage water heater.
If  boiler  water  contains  sufficient
antifreeze,  then  only  the  domestic  water needs to be drained.
WARNING
Close boiler water isolation valves and relieve system pressure to below 15 psig in outer tank before draining inner tank to prevent damage to inner tank.
If boiler  water  does  not  contain  sufficient
antifreeze,  then  the  boiler  water  and domestic water must be drained.
If antifreeze is used in boiler water, check concen­tration. Boiler water (including additives) must be practically  non-toxic,  having  toxicity  rating  or class  of  1,  as  listed  in  Clinical  Toxicology  of Commercial Products.  A maximum 50/50 mixture of  inhibited  propylene  glycol  is  recommended. Follow antifreeze manufacturer’s instruction.
25
Page 28
Water Heater Maintenance
WARNING
Do not use automotive, ethylene glycol or petroleum-based antifreeze. Do not use any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage.
WARNING
Water from opened drain valves, unions and other connections may be extremely hot. To avoid severe personal injury, death or substantial property damage:
- Tighten all drain hose connections.
- Direct hot water away from all persons.
Draining Inner (Domestic Water) Tank
BEST PRACTICE
There are 3 methods typically used in the draining of the inner tank. The first method outlined as Option 1 is to siphon the water out. This method is typically the easiest to perform, but may be lengthly in time to com­plete. The second method, shown as Option 2, uses compressed air. This method is more complicated however it is generally quicker in draining the tank. The final method, Option 3, use a pump to drain the tank. As with Option 2, Option 3 is generally more complicated, but is quicker in draining the tank.
NOTICE
Prior to draining the inner tank, ensure the following is completed:
1. The snap-set wiring connection at the
water heater is disconnected.
2. The DHW system supply isolation valve
is closed.
3. The outer (boiler water) tank pressure is
less than 15 psig.
Reference domestic piping diagrams Figs. 1, 2 and 3B on page 8 and 9.
Draining Inner Tank - Option 1
1. Connect  a  hose  to  the  domestic  water  drain valve at the cold water inlet. The hose should extend to a drain at floor level to allow siphon­ing of the domestic inner tank.
2. Open a hot water faucet at the highest point above the water heater.
3. Open the domestic water drain valve to start the siphoning of the domestic inner tank.
4. When  draining  is  complete,  close  the  hot water faucet and the domestic drain valve.
Draining Inner Tank - Option 2
1. Connect  a  hose  to  the  domestic  water  drain valve at the cold water inlet. Direct the hose to a proper drain/suitable place for drainage.
2. Close the isolation valve on the DHW system hot outlet of the water heater.
3. On  the  hot  water  outlet  piping  between  the water  heater and the isolation  valve install a shrader (air tank) valve or some other fitting or means  that  allows connection  of  an  air  hose from a compressor.
4. Open  the  domestic  water  drain  valve  on  the cold water inlet.
26
Page 29
5. Apply compressed air at a maximum regulated pressure of 40 psig.
6. When  draining  is  complete,  remove  the  air hose  and  fittings  needed  to  connect  the  air hose.
Draining Outer (Boiler Water) Tank
1. Disconnect  snap  set  wiring  connection  at water.
2. Close  boiler water  isolation  valves  between boiler and water heater.
7. Close the domestic water  drain valve on the cold water inlet and open the isolation valve on the hot water outlet.
Draining Inner Tank - Option 3
1. Connect  the  suction side  of  the pump  to  the domestic water drain valve using a hose and/or piping fittings.
2. Connect  a  hose  to  the  discharge  side  of  the pump. Direct the hose to a proper drain or a suitable place for drainage.
3. Open a  hot  water faucet  at  the  highest  point above the water heater.
4. Open the domestic water drain valve and start the pump to begin draining the inner tank.
5. When  draining  is  complete  stop  the  pump, close the hot water faucet and close the domes­tic  drain  valve.  Remove  the  pump  and  all hoses and fittings.
3. Connect  hose to  boiler  water  drain valve  at water heater.  Open and drain water to a safe place.
4. To speed draining procedure, loosen air vent on top of tank.
5. When draining is complete, close drain valve and retighten air vent.
27
Page 30
Replacement Parts
SMART Series
Item Part # Models Description
1 P3KITAV01 All Air vent, automatic
2
3
4
5
6
7
(Not shown)
8 P3KITWRS01 All Snap-set wire harness 9 P3KNB02 All Knob
10 P3CVR04 All Cover plate
P3KITTH01 All Aquastat - 160ºF residential P3KITTH03 All Aquastat - 194ºF commercial
P3KITBTM02 SMART 30, 40, 50 60
Bottom capP3KITBTM03 SMART 80, 100
P3KITBTM04 SMART 120
P3KITTOP02 SMART 30, 40, 50 60
Top capP3KITTOP03 SMART 80, 100
P3KITTOP04 SMART 120
P3DW05 SMART 30 P3DW01 SMART 40 P3DW02 SMART 50
P3DW03
P3DW04
P3WKITDT01 SMART 30 P3WKITDT02 SMART 40 P3WKITDT03 SMART 50 P3WKITDT04 SMART 60
P3WKITDT08
P3WKITDT09 SMART 120 P3WKITDT01 SMART 30 P3WKITDT02 SMART 40 P3WKITDT02 SMART 50 P3WKITDT01 SMART 60
P3WKITDT08
(cut to length)
SMART 60 SMART 80 SMART 100 SMART 120
SMART 80 SMART 100
SMART 80 SMART 100 SMART 120
Drywell
Dip tube
Dip Tube - recirculation (optional)
28
Page 31
Replacement Parts
10
2
8
9
Thermostat
Cover Plate
Assembly
Located Below Thermostat
Cover Plate Assembly
6
3
4
5
SMART
Thermostat Cover Plate Assembly
29
Page 32
Water Heater Specifications
E
F
Hot Water
Outlet
Cold Water
Inlet
Auxiliary
Connection
Thermostat
& Cover Plate
Air Vent
B
A
C
D
C
old Water
I
nlet
Hot Water
Outlet
Auxiliary
Boiler
Return
Boiler
Supply
Top View
Rear View
30
Page 33
Performances
MODEL
oiler Heating
B Capacity MBH
eak Flow
P
gal./ 10 min.
st Hour Flow
1
Gal./Hour
ontinuous Flow
C
Gal./ Hour
irculator
C
Min. GPM
SMART 30 87 40 140 115 5
SMART 40 112 50 180 150 7
SMART 50 140 65 220 185 8
SMART 60 270 100 410 360 16
SMART 80 300 125 460 400 18
SMART 100 337 150 525 450 25
SMART 120 420 190 650 560 28
Conditions:
- 50ºF Domestic cold water inlet temperature
- 140ºF Domestic hot water outlet temperature
- 200ºF Boiler water supply temperature
MODEL
Boiler Heating Capacity MBH
SMART 30 115 60 235 210 8
Peak Flow
gal./ 10 min.
1st Hour Flow
Gal./Hour
Continuous Flow
Gal./ Hour
Circulator
Min. GPM
SMART 40 130 70 270 240 9
SMART 50 180 95 370 330 12
SMART 60 320 145 635 590 21
SMART 80 340 165 690 630 24
SMART 100 380 185 775 700 26
SMART 120 445 235 915 820 30
Conditions:
- 50ºF Domestic cold water inlet temperature
- 115ºF Domestic hot water outlet temperature
- 200ºF Boiler water supply temperature
31
Page 34
Additional quality water heating equipment available from: Triangle Tube
An
Company
Prestige Condensing Wall Mounted Boiler
-  96% AFUE - Energy Star 
- Fully modulating
- Natural gas or propane
- Stainless Steel Contruction
- Direct vent PVC, CPVC, PP and SS
- Outdoor Reset
- Low NOx
Challenger Solo
- Up to 95% AFUE
- Fully modulating
- Natural gas propane
- Combination  copper  water  tube/aluminum  block heat exchanger
- Direct vent, PVC, CPVC, PP and SS
- Outdoor reset
- Low NOx
Optima Controls
- SCC4 Multiple modulatin boiler control
- SCCX6 Multiple boiler control extension
- SZC5 Zone control panel
- S3S Three stage boiler control
-  SMV Mixing valve control
- SIM Injection mixing control
- SSM Snow melt control
Freeway Center  - 1 Triangle Lane  - Blackwood, NJ 08012 (856) 228 8881  Fax (856) 228 3584
www.triangletube.com  / sales@triangletube.com.
Loading...