Triangle Tube SMART60, SMART80, Smart 30,Smart 40,Smart 50,Smart 60,Smart 80,Smart 100,Smart 120 Submittal

Page 1
SMART Series
Indirect Fired
Water Heater
Suggested Specifications
SMART Series
General Requirements
A. Furnish and install _____ (qty) Indirect Fired Water
Heater designed for the production of domestic hot water using boiler water as a heating source.
B. Installation of the Indirect Fired Water(s) shall be
according to manufacturer’s installation instructions and all work shall be completed in a neat and work­manship like manner.
C. The Indirect Fired Water Heater shall be a Triangle
Tube SMART _______ having a minimum continu­ous (recovery) of _____ GPH at a 90°F domestic temperature rise at boiler output listed in the perfor­mance table on page 3 and a minimum actual stor­age capacity of not less than _______ gallons per water heater.
D. The water heater shall have a minimum of _______
square feet of heat transfer surface area.
E. The water heater shall be designed for a maximum
boiler side pressure drop through the outer tank of 3ft of pressure loss or less at volume flow rate of 28 gpm.
1. Consist of two (2) concentric tanks. The inner tank shall contain the domestic water and the outer tank shall contain the heating system water. This “Tank in Tank” design concept shall allow the inner tank to be self-descaling.
2. The inner tank shall be 304L corrugated stain­less steel material that is passivated to provide additional resistance to corrosion.
4. The outer tank shall be of carbon steel material and have a maximum working pressure of 45 psi.
5. The water heater shall provide a cold water inlet connection, hot water outlet connection and an AUX connection that is to be utilized for the Temperature / Pressure relief valve or a recircu­lation return connection.
6. The outer tank shall be covered with a minimum 2 inches of CFC/HCFC-free rigid polyurethane foam insulation with an equivalent “R” value of 16.
F. The water heater shall have a standby loss less than
1°F per hour.
G. The water heater shall have a maximum allowable
system heating water temperature of 210°F.
H. The water heater shall comply to the construction
standards of UL 174 and be certified by ITS/ETL or other third party agency.
Product Specifications
A. Water Heater Construction
7. The water heater shall be covered by a single piece polypropylene exterior jacket that resists dents, cuts and abrasions.
B. Temperature Control
1. A drywell shall be inserted into and extend the full length of the inner tank.
1
Page 2
Suggested Specifications - SMART Series
3. The thermostat shall open a circuit contact when the temperature rises above the set point and shall close when the temperature falls to a tem­perature no more than 9°F below the set point.
4. The thermostat shall be adjustable from 90º F to a maximum temperature setting of 164°F for residential and 194°F for commercial.
5. The thermostat shall be mounted on a remov­able cover plate and wired to a removable snap­set connector to allow easy installation and ser­vicing. All field wiring to the thermostat / snap­set connector shall be 24V.
C. Field Installation
1. The water heater shall have a field installed Temperature / Pressure relief valve with a minimum element length of 8 inches (extended element).
2. The T&P relief valve shall bear the ASME rat­ing, have a relief pressure of 150 psi and a relief temperature of 210°F.
B. The Indirect Fired Water Heater(s) shall comply
with the National Standard Plumbing Code provid­ed that:
1. The boiler (system heating) water (including additives) is practically non-toxic, having toxic­ity rating or Class of 1 as listed in Clinical Toxicology of Commercial Products and
2. Boiler water pressure is limited to a maximum 30 psig by an approved relief valve.
C. The Indirect Fired Water Heater(s) shall comply
with the Uniform Plumbing Code Paragraph L3.2 and L3.3 provided that:
1. The heat transfer medium is potable water or contains only substances which are recognized as safe by the US Food and Drug Administration.
2. The pressure of the heat transfer medium is maintained less than the normal minimum oper­ating pressure of the potable water system.
D. Manuals
1. The water heater(s) shall be provided with com­plete instruction manuals, including:
a) Operational and Maintenance Manual
Warranty
A. The water heater shall carry a limited lifetime war-
ranty when installed in a residential application.
B. The water heater shall carry a six (6) year non-pro-
rated warranty when installed in a commercial application.
Code Requirement
A. The Indirect Fired Water Heater(s) shall be recog-
nized as an ASME Equal by the Commonwealth of Massachusetts Plumbing Board.
3. The equipment is permanently labeled to indicate that only additives recognized as safe by the FDA shall be used in the heat transfer medium.
Other heat exchangers designs may be permitted where approved by the Administrative Authority.
D. The installer shall be responsible to ensure that the
installation of the Indirect Fired Water Heater is in compliance with all applicable local, state and national codes.
2
Page 3
Suggested Specifications - SMART Series
Model
No.
Dimension
H
eight Boiler/Supply
Return
Domestic
Inlet/Outlet
D
omestic
Capacity
(gal.)
Heating
Water Capacity
(
gal.)
H
eat
Surface
(sq. ft.)
Empty
Weight
(lbs)
3rd Domestic
Connection*
2"
22" dia.
38"
1" 3/4" 3/4" 28
13
115
5
Smart 30
22" dia.
46" 1"
3/4"
3/4"
36
16
135
6
Smart 40
22" dia. 57"
1
1
4
/
"
3/4"
3/4" 46 8 20
165
Smart 50
22" dia.
66"
1
1
4
/
"
3/4" 3/4"
56
8
24
190
Smart 60
1
2
26" dia.
61"
1
/
"
1
2
1
/
"
1
2
1
/
"
70
14
28
271
Smart 80
1
2
26" dia.
78"
1
/
"
1
2
1
/
"
1
2
1
/
"
95
25
36
362
Smart 100
32" dia.
72"
1
2
1
/
"
1
2
1
/
"
119
43
42
479
Smart 120
Model
No.
Boiler Output
Btu/hr
1st Hour
Recovery
(gal.)
Peak/Flow
Gal/10 min.
Continuous
Flow
(gal.)
87,000 140 40
Smart 30
115
112,000
180
50
Smart 40
150
140,000
220
65
Smart 50
185
270,000
410
100
Smart 60
360
300,000
460
125
400
Smart 80
337,000
525
150
Smart 100
450
420,000
650
190
560
Smart 120
Product Specifications
(*) This fitting can be used as a return connection if circulated domestic water is required or can be used as a connection for the T&P Relief Valve.
Performance
Date 12/29/09
3
Conditions:
- 200º boiler water supply
- 90º temperature rise
2009-47 SMART Suggested Spec
Loading...