Triangle Tube PT60, PT399, PT175, PT250 User Guide

Page 1
prestige
Solo 60 Solo 175 Solo 250 Solo 399
Water Boiler
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
L
I
S
T
E
D
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
M A N U A L
M A N U A L
NOTICE
WARNING
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa­tion in order to gain warranty coverage.
Leave all documentation received with appliance with owner for future reference.
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
FOR YOUR SAFETY
2011-50 Manual Prestige 60/175/250/399_TriMax_Revised 5/29/12
Page 2
Table of Contents
PRODUCT AND SAFETY INFORMATION
Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Product and Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SECTION I - PRE-INSTALLATION ITEMS
Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Determining Product Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Boiler Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Recommended Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Residential Garage Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Boiler Freeze Protection Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SECTION II - COMBUSTION AIR AND VENTING
Combustion Air Contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ventilation and Combustion Air Requirements - Direct Vent . . . . . . . . . . . 6
Ventilation and Combustion Air Requirements - Category IV . . . . . . . . . . 6
Methods of Accessing Combustion Air into a Space - Category IV . . . . . . 7
- Indoor Combustion Air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
- Outdoor Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
- Combination of Indoor and Outdoor Combustion Air. . . . . . . . . . 9
Combustion Air and Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Removal of an Existing Boiler from a Common Vent System . . . . . . . . . . 10
Commonwealth of Massachusetts Installation . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION III - UNIT PREPARATIONS
Handling Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wall Mounting Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wall Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wall Bracket Installation - Stud Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wall Bracket Installation - Solid Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Boiler Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SECTION IV - BOILER PIPING
General Piping Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Low Water Cut Off Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Additional Limit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Backflow Preventer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
i
Page 3
Table of Contents
Boiler System Piping Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Expansion Tank and Makeup Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-17
Diaphragm Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Closed-Type Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Circulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Sizing Primary Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Domestic Hot Water System Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
System Piping - Zone Circulators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
System Piping - Zone Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Piping Component Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Near Boiler Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Piping - Through Boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
System Piping - Radiant Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
System Piping - Special Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
System Piping - Multiple Units Installation . . . . . . . . . . . . . . . . . . . . . . . . . 20
System Piping Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-23
SECTION V - INSTALLING VENT / COMBUSTION AIR & CONDENSATE DRAIN
Installing Vent and Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installing Condensate Drain Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-25
SECTION VI - GAS PIPING
Gas Supply Piping Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Natural Gas
Pipe Sizing -Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Natural Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . . . 27
Propane Gas
Pipe Sizing - Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Propane Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . . 28
Gas Valve/Venturi Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
SECTION VII - INTERNAL WIRING
General Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fuse Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Internal Factory Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SECTION VIII - EXTERNAL WIRING
Installation Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Line Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Circulator Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-33
ii
Page 4
Table of Contents
Alarm Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-34
Outdoor Sensor Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Domestic Hot Water Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Additional Boiler Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
External Modulation Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
System Sensor Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-35
Cascade Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Modbus Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Zone Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Zone Circulator Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
System Piping Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-39
SECTION IX - TRIMAX OPERATION
TriMax User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
TriMax Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Trimax Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Home Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Status Line Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
EZ Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Heating EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-47
Domestic Hot Water EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-49
EZ Setup Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Display EZ Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
CH/DHW Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Boiler Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Information Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Lockout History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Lockout Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Manual Reset Hard Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Automatic Reset Soft Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
SECTION X - START-UP PREPARATION
Check Boiler System Water Chemistry
Water pH Level 6.0 to 8.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Water Hardness Less Than 7 Grains. . . . . . . . . . . . . . . . . . . . . . . . . 56
Chlorinated Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Flush Boiler System to Remove Sediment. . . . . . . . . . . . . . . . . . . . . . . . . . 56
Cleaning of Old Boiler/System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
iii
Page 5
Table of Contents
Cleaning of New Boiler/System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Check and Test Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Use of Antifreeze in the Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Filling the Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Check Low Water Cut-Off Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Check for Gas Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Check Thermostat Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Inspection of Condensate Drain Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 58
SECTION XI- START-UP PROCEDURES
Final Checks Before Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
PRESTIGE Solo Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
If PRESTIGE Solo does Not Start Correctly . . . . . . . . . . . . . . . . . . . . . . . . 59
Check the PRESTIGE Solo and System . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-61
Operating Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
SECTION XII - OUTDOOR RESET CONTROL
Mounting the Outdoor Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Wiring the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
SECTION XIII - EXTERNAL MODULATING CONTROL
Wiring the Modulating Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
TriMax Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Programming of External Modulating Control . . . . . . . . . . . . . . . . . . . . . . 64
Factory TriMax Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
SECTION XIV - CHECK-OUT PROCEDURES
Check-Out Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
SECTION XV - INSTALLATION RECORD
Installation Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
SECTIONS XVI - MAINTENANCE SCHEDULE
Service Technician - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Owner Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
iv
Page 6
Table of Contents
SECTION XVII - MAINTENANCE PROCEDURES
Maintenance Procedures
Reported Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Check Surrounding Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Inspect Burner Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Check System Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Clean Condensate Drain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 70
Check Ventilation Air Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Inspect Vent and Combustion Air Piping . . . . . . . . . . . . . . . . . . . . . 70
Check Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Check Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Check Boiler Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Inspection of Ignition Electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Check Ignition Wiring and Ground Wiring . . . . . . . . . . . . . . . . . . . 71
Check Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Check Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Perform Start-Up and Checkout Procedure . . . . . . . . . . . . . . . . . . . 72
Check Burner Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Check Flame Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Check Combustion Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Check Flue Gas Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Clean Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Review with Owner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Handling Previously Fired Combustion Chamber Insulation . . . . . 74
REPLACEMENT PARTS
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75-83
PRODUCT SPECIFICATIONS
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84-93
v
Page 7
Product & Safety Information
Definitions
The following terms are used throughout this manual to bring attention to the presence of potential hazards or important information concerning the product.
DANGER
Indicates the presence of a hazardous situation which, if ignored, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situa­tion which, if ignored, can result in death, serious injury or substantial property damage.
CAUTION
Indicates a potentially hazardous situa­tion which, if ignored, may result in minor injury or property damage.
NOTICE
Indicates special instructions on installa­tion, operation or maintenance, which are important to equipment but not related to personal injury hazards.
BEST PRACTICE
Indicates recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equipment
NOTICE
Triangle Tube reserves the right to modify the technical specifications and components of its products without prior notice.
1
Page 8
Product & Safety Information
DANGER
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water.
WARNING
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas suppli­er, call the fire department.
Installation and service must be per­formed by a qualified installer, service agency or the gas supplier.
WARNING
Should overheating occur or the gas supply fails to shut off, turn OFF the manual gas control valve external to the appliance.
WARNING
DO NOT add cold make up water when the boiler is hot. Thermal shock can cause potential cracks in the heat exchanger.
CAUTION
When servicing the boiler:
- Avoid electrical shock by discon­necting the electrical supply prior to performing maintenance.
WARNING
Qualified Installer:
Prior to installing this product read all instructions included in this manual and all accompanying manuals/documents with this appliance. Perform all installation steps required in these manuals in the proper order given. Failure to adhere to the guide­lines within these manuals can result in severe personal injury, death or substantial property damage.
Homeowner:
- This product should be maintained / serviced and inspected annually by a qualified service technician.
- This manual is intended for use by a qualified Installer/Service Technician.
NOTICE
Please reference the unit’s model num­ber and the serial number from the rat­ing label, on the backside of the control panel when inquiring about service or troubleshooting.
NOTICE
Triangle Tube accepts no liability for any damage resulting from incorrect instal­lation or from the use of components or fittings not specified by Triangle Tube.
2
Page 9
Pre-Installation Items
SECTION I - Pre-Installation Items
Code Compliance
This product must be installed in accordance to the following:
- All applicable local, state, national and provincial codes, ordinances, regula­tions and laws.
- For installations in Massachusetts, code requires the boiler to be installed by a licensed plumber or gas fitter, and if antifreeze is utilized, the installation of a reduced pressure backflow preventer device is required in the boiler’s cold water fill or make up water supply line.
- For installation in Massachusetts all direct vented appliances must comply with the guidelines as outlined on page 11.
- The National Fuel Gas Code NFPA54/ ANSI Z 223.1 - Latest edition.
- National Electric Code ANSI/NFPA 70.
- For installations in Canada -“Installation Code for Gas Burning Equipment” CGA/B149.1 or B149.2 Canadian Electrical Code Part 1 CSA C22.1.
- Standards for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required.
Ensure the boiler location allows the combus­tion air/vent piping to be routed directly through the building and terminate properly outside with a minimum amount of length and bends.
Ensure the area chosen for the installation of the PRESTIGE Solo is free of any combustible materials, gasoline and other flammable liquids.
WARNING
Failure to remove or maintain the area free of combustible materials, gasoline and other flammable liquids or vapors can result in severe personal injury, death or substantial property damage.
Ensure the PRESTIGE Solo and its controls are protected from dripping or spraying water during normal operation or service.
The PRESTIGE Solo should be installed in a location so that any water leaking from the boiler or piping connections or relief valve will not cause damage to the area surrounding the unit or any lower floors in the structure.
Boiler Replacement
If the PRESTIGE Solo is replacing an existing boiler, the following items should be checked and corrected prior to installation:
NOTICE
The PRESTIGE Solo boiler gas manifold and gas controls meet the safe lighting and other performance requirements as speci­fied in ANSI Z21.13 latest edition.
Determining Product Location
Before locating the PRESTIGE SOLO check for convenient locations to:
- Heating system piping
- Venting
- Gas supply piping
- Electrical service
- Boiler piping leaks and corrosion.
- Improper location and sizing of the expansion tank on the boiler heating loop.
- If applicable, level and quality of freeze protection within the boiler system.
Recommended Clearances
The PRESTIGE Solo is approved for zero clearance to combustibles, excluding vent and boiler piping.
- Boiler Piping - 1/4 inch from com­bustible materials.
3
Page 10
Pre-Installation Items
- Reference the appropriate vent supple­ment for clearance requirements.
BEST PRACTICE
To provide serviceability to the unit it is recommended that the following clear­ances be maintained:
Top boiler jacket - 24 inches [610 mm].
Front - 24 inches [610 mm].
Bottom boiler piping - 24 inches [610 mm].
Rear - 0 inches
Sides - 6 inches [153 mm]
WARNING
If the clearances listed above cannot be maintained or the enclosure in which the boiler is installed is less than 85 cubic feet, the space must be ventilated. See page 6 for ventilation requirements.
NOTICE
Residential Garage Installations
When installing the PRESTIGE Solo in a resi­dential garage, the following special precautions per NFPA 54/ANSI Z223.1 must be taken:
- Mount the unit a minimum 18 inches [458 mm] above the floor level of the garage. Ensure the burner and ignition devices / controls are no less than 18 inches [458 mm] above the floor level.
- Locate or protect the unit in a manner so it cannot be damaged by a moving vehicle.
Boiler Freeze Protection Feature
The TriMax boiler management system has a freeze protection feature built in. This feature monitors the boiler temperature and responds as follows when no call for heat is present:
- 46ºF [8ºC] CH (1) & Auxiliary Boiler Pumps ON
- 42ºF [6ºC] CH (1), Auxiliary Boiler & System Pumps ON, Burner operates at low fire
- 60ºF [15ºC] Freeze protection ends. Burner & all pumps OFF after complet­ing CH Post Pump Time.
When maintaining zero clearance or less than recommended clearances, some product labeling may become hidden and unreadable.
WARNING
When installing the PRESTIGE Solo in a confined space, sufficient air must be provided for proper combustion and venting and to allow, under normal oper­ating conditions, proper air flow around the product to maintain ambient tem­peratures within safe limits to comply with the National Fuel Gas Code NFPA 54 - latest edition.
CAUTION
The boiler freeze protection feature is disabled during a hard lockout, however the circulators will operate.
CAUTION
The boiler freeze protection feature is designed to protect the boiler. The boiler should be installed in a primary/sec­ondary piping arrangement if it is installed in an unheated space or exposed to water temperatures of 46ºF or less. See Section IV for primary/sec­ondary piping examples. See Section X for antifreeze guides.
4
Page 11
Combustion Air Venting
SECTION II - Combustion Air and Venting
Combustion Air Contamination
WARNING
If the PRESTIGE Solo combustion air inlet is located in any area likely to cause or contain contamination, or if products, which would contaminate the air cannot be removed, the combustion air must be repiped and terminated to another loca­tion. Contaminated combustion air will damage the unit and its burner system, resulting in possible severe personal injury, death or substantial property damage.
WARNING
Do not operate a PRESTIGE Solo if its combustion air inlet is located near a laundry room or pool facility. These areas will always contain hazardous con­taminants.
Potential contaminating products
- Spray cans containing chloro/fluorocar­bons
- Permanent Wave Solutions
- Chlorinated wax
- Chlorine - based swimming pool chem­icals / cleaners
- Calcium Chloride used for thawing ice
- Sodium Chloride used for water soft­ening
- Refrigerant leaks
- Paint or varnish removers
- Hydrochloric acid / muriatic acid
- Cements and glues
- Antistatic fabric softeners used in clothes dryers
- Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
- Adhesives used to fasten building prod­ucts and other similar products
Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the burner and vent system, they can form strong acids. These acids can create cor­rosion of the heat exchanger, burner components and vent system, causing serious damage and presenting a possi­ble threat of flue gas spillage or water leakage into the surrounding area.
Please read the information listed below. If contaminating chemicals are located near the area of the combustion air inlet, the installer should pipe the combustion air inlet to an outside area free of these chemicals per SECTION V of this installation manual.
Areas likely to contain these products
- Dry cleaning / laundry areas and estab­lishments
- Beauty salons
- Metal fabrication shops
- Swimming pools and health spas
- Refrigeration Repair shops
- Photo processing plants
- Auto body shops
- Plastic manufacturing plants
- Furniture refinishing areas and estab­lishments
- New building construction
- Remodeling areas
- Garages with workshops
5
Page 12
Combustion Air Venting
Ventilation and Combustion Air Requirements - Direct Vent
A Direct Vent appliance utilizes uncontamined outdoor air (piped directly to the appliance) for combustion.
For Direct Vent installations, involving only the PRESTIGE Solo, in which the minimum service clearances are maintained as listed on page 4, no ventilation openings are required.
For Direct Vent, zero clearance installations involving only the PRESTIGE Solo, the space / enclosure must provide two openings for ven­tilation. The openings must be sized to provide 1 square inch of free area per 1,000 BTUH of boiler input. The openings shall be placed 12 inches from the top of the space and 12 inches from the floor of the space.
For installations in which the PRESTIGE Solo shares the space with air movers (exhaust fan, clothes dryers, fireplaces, etc.) and other com­bustion equipment (gas or oil) the space must be provided with adequate air openings to pro­vide ventilation and combustion air to the equipment. To properly size the ventilation / combustion air openings, the installer must comply with the National Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S or CSA B149.1 and B149.2 for installa­tions in Canada.
WARNING
The space must be provided with venti­lation / combustion air openings proper­ly sized for all make-up air requirements (exhaust fans, clothes dryers, fireplaces, etc.) and the total input of all appliances located in the same space as the PRES­TIGE Solo, excluding the input of a Direct Vent PRESTIGE Solo which uses combustion air directly from the outside, thus additional free area for the open­ings is not required. Failure to provide or properly size the openings could result in severe personal injury, death or substantial property damage.
Ventilation and Combustion Air Requirements - Category IV
A Category IV appliance utilizes uncontami­nated indoor or outdoor air (surrounding the appliance) for combustion.
BEST PRACTICE
In order to reduce the potential risks associated with indoor contaminates (listed on page 5), flammable vapors and tight housing construction (little or no infiltration air), it is recommended to pipe uncontaminated combustion air directly from the outdoors to the appli­ance. This practice also promotes higher system efficiency by reducing heated indoor air from being exhausted from the house and replaced by cold infiltra­tion air into the house.
For installations in which the PRESTIGE Solo shares the space with air movers (exhaust fan, clothes dryers, fireplaces, etc.) and other com­bustion equipment (gas or oil) the space must be provided with adequate air openings to pro­vide ventilation and combustion air to the equip­ment. To properly size the ventilation / com­bustion air openings, the installer must comply with the National Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S or CSA B149.1 and B149.2 for installations in Canada, as referenced in this section of the manual and titled Methods of Accessing Combustion Air into a Space.
WARNING
The space must be provided with venti­lation / combustion air openings proper­ly sized for all make-up air requirements (exhaust fans, clothes dryers, fireplaces, etc.) and the total input of all appliances, including the PRESTIGE Solo when located in the same space. Failure to pro­vide or properly size the openings could result in severe personal injury, death or substantial property damage.
6
Page 13
Combustion Air Venting
Methods of Accessing Combustion Air Into A Space - Category IV
Indoor Combustion Air
NOTICE
The methods listed in this section for accessing Indoor Combustion Air assume that the infiltration rate is ade­quate and not less than .40 ACH. For infiltration rates less than .40 ACH, ref­erence the NFPA 54 National Fuel Gas Code for additional guidance.
Opening Size and Location
Openings used to connect indoor spaces shall be sized and located in accordance with the following see Fig. 1:
The minimum dimension of air open­ings shall be not less than 3 inches.
- Combining spaces in different stories. The volumes of spaces in different sto­ries shall be considered as communicat­ing spaces where such spaces are con­nected by one or more openings in doors or floors having a total minimum free area of 2 sq. in./1000 Btu/hr of total input rating of all gas utilization equipment.
Outdoor Combustion Air
BEST PRACTICE
Isolating the combustion appliance room from the rest of the building and bring­ing in uncontaminated outside air for combustion and ventilation is always preferred.
Fig. 1:
All Combustion Air from Adjacent Indoor Spaces Through Indoor Combustion Openings
- Combining spaces on the same story. Each opening shall have a minimum free area of 1 sq. in./1000 Btu/hr of the total input rating of all gas utilization equipment in the space, but not less than 100 sq. inches. One opening shall com­mence within 12 inches of the top, and one opening shall commence within 12 inches of the bottom of the enclosure.
Opening Size and Location
The minimum dimension of air openings shall be not less than 3 inches
Openings used to supply combustion and ven­tilation air shall be sized and located in accor­dance with the following:
One Permanent Opening Method. See Fig. 2
One permanent opening, commencing within 12 in. of the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 inch from the sides and 6 in. from the front of the appliance. The opening shall directly communi­cate with the outdoors or shall communicate through a vertical or horizontal duct to the out­doors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
- 1sq. in./3000 Btu/hr of the total input rating of all equipment located in the enclosures, and
7
Page 14
Combustion Air Venting
Fig. 2:
All Combustion Air from Outdoors Through One Permanent Air Opening
- Not less than the sum of the areas of all vent connectors in the space.
Two Permanent Openings Method.
Two permanent openings, one commencing within 12 in. of the top and one commencing within 12 in. of the bottom of the enclosure, shall be provided. The openings shall commu­nicate directly, or by ducts, with the outdoors or spaces that freely communicate with the out­doors, as follows:
- Where directly communicating with the outdoors or where communication to the outdoors is through vertical ducts, each opening shall have a minimum free area of 1 sq. in./4000 Btu/hr of total input rat­ing of all equipment in the enclosure. See Fig.3.
Fig. 3:
Fig. 4:
All Combustion Air from Outdoors Through Ventilated Attic
All Combustion Air from Outdoors Through Horizontal Ducts
- Where communicating with the out­doors is through horizontal ducts, each opening shall have a minimum free area of not less than 1 sq.in./2000 Btu/hr of total input rating of all equip­ment in the enclosure. See Fig. 4.
8
Page 15
Combustion Air Venting
Combination of Indoor and Outdoor Combustion Air
Indoor Openings: Where used, openings con­necting the interior spaces shall comply with the Indoor Combustion Air section on page 7.
Outdoor Opening(s) Location. Outdoor open­ing(s) shall be located in accordance with the Outdoor Combustion Air section.
Outdoor Opening(s) Size. Outdoor opening(s) shall be calculated in accordance with the following:
- The ratio of the interior spaces shall be the available volume of all communi­cating spaces divided by the required volume.
- The outdoor size reduction factor shall be 1 minus the ratio of interior spaces.
- The minimum size of outdoor open­ing(s) calculated in accordance with the above outdoor air section multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in.
DANGER
Do not install the PRESTIGE Solo into a common vent with other gas or oil appli­ances. This may cause flue gas spillage or appliance malfunction, resulting in possi­ble severe personal injury, death or sub­stantial property damage.
Combustion Air and Vent Piping
The PRESTIGE Solo requires a Category IV venting system, which is designed for pressur­ized venting and condensate.
The PRESTIGE Solo is certified per ANSI Z21.13 as a Category IV or Direct Vent (sealed combustion) appliance. A Category IV appli­ance utilizes uncontamined indoor or outdoor air (surrounding the appliance) for combustion. A Direct Vent appliance utilizes uncontaminat­ed outdoor air (piped directly to the appliance) for combustion.
BEST PRACTICE
In order to reduce the potential risks associated with indoor contaminates (listed on page 5), flammable vapors and tight housing construction (little or no infiltration air), it is recommended to pipe uncontaminated combustion air directly from the outdoors to the appli­ance. This practice also promotes higher system efficiency by reducing heated indoor air from being exhausted from the house and replaced by cold infiltra­tion air into the house.
NOTICE
Install combustion air and vent pipe as detailed in the PRESTIGE Solo Vent Supplement included in the boiler installation envelope. Refer to optional vent kit instructions for addition vent installation instructions.
DANGER
Verify installed combustion air and vent piping are sealed gas tight and meet all provided instructions and applicable codes, failure to comply will result in severe personal injury of death.
9
Page 16
Combustion Air Venting
Removal of an Existing Boiler from a Common Vent System
BEST PRACTICE
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the fol­lowing steps shall be followed with each appliance remaining connected to the com­mon venting system placed in operation, while the other appliances remaining con­nected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and deter­mine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or can­dle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the com­mon venting system properly vents when tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation codes. When resizing any portion of the common venting system, the common venting sys­tem should be resized to approach the min­imum size as determined using the appro­priate tables in Part II of the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation codes.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remain­ing connected to the common venting sys­tem are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
DANGER
Do not install the PRESTIGE Solo into a common vent with other gas or oil appli­ances. This may cause flue gas spillage or appliance malfunction, resulting in possi­ble severe personal injury, death or sub­stantial property damage.
10
Page 17
Combustion Air Venting
Commonwealth of Massachusetts Installations Only
For direct-vent appliances, mechanical­vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are bed­room(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The car­bon monoxide detector shall comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall also
be located in the room that houses the appliance or equipment and shall:
a. Be powered by the same electrical cir-
cuit as the appliance or equipment such that only one service switch services both the appliance and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005 Edition); and
d. Have been approved and listed by the
Nationally Recognized Testing Laboratory as recognized under 527 CMR.
3. A Product-approved vent terminal must
be used, and if applicable, a Product­approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
4. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
NOTICE
Installer must provide tag identification plate and ensure the lettering meets code requirements.
For direct-vent appliances, mechanical­vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake are installed above four feet above grade the following requirements must be satisfied:
1. If there is not one already present, on each floor level where there are bed­room(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The car­bon monoxide detector shall comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses the
appliances or equipment;
b. Be either hard wired or battery powered
or both; and
c. Shall comply with NFPA 720 (2005
Edition)
3. A Product-approved vent terminal must be used, and if applicable, a Product­approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
11
Page 18
Unit Preparations
SECTION III - Unit Preparations
Handling Instructions
The PRESTIGE Solo is generally easier to handle and maneuver once removed from the shipping carton.
To remove the shipping carton:
CAUTION
Use care not to drop, bump or rotate the boiler upside down, as damage to the boiler will result.
1. Remove any shipping straps and open the side of the shipping carton.
2. Slide the unit with the foam inserts out of the carton.
3. Discard all packing materials.
Wall Mounting Installation
Wall Mounting Guidelines
1. The wall-mounting bracket is designed for stud spacing of 12 inch or 16 inch on cen­ters. For unconventional stud spacing, a solid / secure mounting surface must be provided for installation of the bracket.
2. For applications using wood studs, install the bracket using the lag screws provided with the boiler. Ensure both lag screws are installed securely in the studs.
3. For applications using metal studs, install the bracket to the studs using 3/16” toggle bolts and washers.
4. DO NOT mount or attempt to mount the wall bracket to hollow sheet rock or lath walls using anchors. Only install boiler to studs or equivalent wood structure.
5. For applications using solid walls (rock, concrete, brick, cinder block, etc.), install the wall bracket using anchors (double expansion shields) and bolts with washers provided with the boiler.
The PRESTIGE Solo should be wall mounted using the bracket provided with the boiler. The PRESTIGE Solo is not designed for floor installation. If floor installation is required an optional floor stand is available through Triangle Tube.
NOTICE
The wall used for mounting the PRES­TIGE Solo must be vertically plumbed and capable of supporting a minimum 130 pounds [59 kg] for the PRESTIGE Solo 60, 175 pounds [80 kg] for PRES­TIGE Solo 175/250 and 250 pounds [115 Kg] for PRESTIGE Solo 399. Failure to comply with these requirements could result in personal injury, death or sub­stantial property damage.
6. The boiler is too heavy and bulky for a sin­gle person to lift and attempt to mount; a minimum of 2 people is required for mounting the boiler.
NOTICE
Use extreme care not to drop the boiler or cause bodily injury while lifting or mounting the boiler onto the bracket. Once mounted verify that the boiler is securely attached to the bracket and wall. Failure to comply with the above guidelines could result in property dam­age, personal injury or death.
12
Page 19
Unit Preparations
PRESTIGE Solo 60/175/250 Stud Walls ­Installation
1. Locate the studs in the general area of the boiler placement.
2. Place the wall-mounting bracket on the wall centering the mounting slots with the stud centers and ensuring the upper edge of the bracket is away from the wall.
3. Level the bracket, while maintaining it’s centering with the studs and use a pencil to mark the location of the mounting slots.
4. Remove the bracket from the wall and drill 1/4” diameter hole by 3” deep positioned in the center of each mark. For applications using metal studs and 3/16” toggle bolts, drill the required clearance hole.
5. Reposition the bracket onto the wall and align mounting slots/holes. Insert the two lag screws provided (or toggle bolts for metal studs) through the mounting slots/holes and loosely tighten.
Wall Bracket Installation - Solid Walls
1. Locate the general area of the boiler place­ment.
2. Place the wall-mounting bracket on the wall ensuring the upper edge of the bracket is away from the wall.
3. Level the bracket and use a pencil to mark the location of the mounting slots on the wall.
4. Remove the bracket from the wall and drill a 5/8” diameter hole by 1-3/8” deep posi­tioned in the center of each mark.
5. Install the anchors (provided) flush or slightly recessed in the drilled holes with threaded side facing down.
6. Reposition the bracket on the wall and align mounting slots/holes. Insert the two bolts (provided) through the mounting slots/holes and loosely tighten.
7. Level bracket and tighten bolts securely.
6. Level bracket and tighten screws (bolts for metal studs) securely making sure not to over-tighten to avoid damaging drywall or plaster.
PRESTIGE Solo 399 Stud Walls ­Installation
1. To distribute the weight of the boiler even­ly when mounting onto a stud wall it is rec­ommended to use the PRESTIGE Solo Wall Frame kit.
2. When using the wall frame to mount the boiler reference the kit installation instruc­tions and ensure the frame is securely fas­tened to the wall.
3. If the structure of wall is questionable, in supporting a minimum weight of 250 pounds [115 kg.], it is recommended to use the optional floor stand.
Boiler Mounting
1. Obtain assistance in lifting the boiler onto the wall bracket.
2. Install the boiler making sure the boiler mounting lip located along the upper edge of the rear jacket panel engages the wall­mounting bracket. Ensure the boiler is seated properly and is secure.
13
Page 20
Boiler Piping
SECTION IV - Boiler Piping
General Piping Requirements
- All plumbing must meet or exceed all local, state and national plumbing codes.
- Support all piping using hangers. DO NOT support piping by the unit or its components.
- Use isolation valves to isolate system com­ponents.
- Install unions for easy removal of the PRESTIGE Solo from the system piping.
WARNING
Use a two wrench method when tighten­ing piping onto the boiler connections. Use one wrench to prevent the boiler piping from turning / twisting. Failure to support the boiler piping and connec­tions in this manner could cause damage to the boiler and its components.
Pressure Relief Valve
1. The PRESTIGE Solo is supplied with a 30 psi pressure relief valve and must be piped using the PRV connection as shown in Fig. 5 page 15.
2. To avoid potential water damage to the sur­rounding area or potential scalding hazard due to the operation of the relief valve, the discharge piping:
- Must be connected to the discharge out-
let of the relief valve and directed to a safe place of disposal.
- Length should be as short and direct as
possible. The size of the discharge line should not be reduced, maintain the same size as the outlet of the relief valve.
- Should be directed downward towards
the floor at all times. The piping should terminate at least 6 inches [153 mm] above any drain connection to allow clear visibility of the discharge.
- Should terminate with a plain end, not with a threaded end. The material of the piping should have a serviceable temperature rating of 250ºF or greater.
- Should not be subject to conditions where freezing could occur.
- Should not contain any shut-off valves or obstructions. No shut-off valve should be piped between the boiler and relief valve.
WARNING
Failure to comply with the guidelines on installing the pressure relief valve and discharge piping can result in personal injury, death or substantial property damage.
Low Water Cutoff Device
- The PRESTIGE Solo is equipped with a fac­tory installed pressure switch type Low Water Cut Off device.
- The minimum operating system pressure allowable with this device is 10 psig.
- Check local codes if a Low Water Cutoff Device is required. If so, determine if this device meets the requirements of the local codes.
NOTICE
The PRESTIGE Solo control system also senses the system water temperatures entering and exiting the heat exchanger to provide protection against low water conditions Where local codes and juris­diction do not accept a pressure device for low water protection, the jurisdic­tions may accept these PRESTIGE Solo integral control functions as a means of providing low water protection.
14
Page 21
Boiler Piping
Boiler Return Connection
with Tee Fitting and
Boiler Drain Valve
Boiler Supply
Connection
Pressure Relief Valve
(Supplied with Boiler)
3/4" Street Elbow
Air Vent
Drain Piping Directed
to a Suitable
Place of Drainage
Fig. 5: Pressure Relief Valve and Boiler Drain Valve Installation
15
Page 22
Boiler Piping
Additional Limit Control
If a separate LWCO device is required by cer­tain local jurisdictions or when the boiler is installed above the system piping, the follow­ing guidelines must be followed:
- The LWCO device must be designed for water installations, electrode probe­type is recommended.
- The LWCO device must be installed in a tee connection on the boiler supply piping above the boiler.
- Wiring of the LWCO device to the PRES­TIGE Solo is done directly onto the low voltage terminal strip, reference Fig. 19 page 31 for available terminals for an external limit (manual or auto reset).
If the installation is to comply with ASME or Canadian requirements, an additional high temperature limit may be needed. Consult local code requirements to determine compli­ance. The limit should be installed as follows:
Boiler System Piping Applications
BEST PRACTICE
It is recommended on all piping applica­tions to utilize a primary/secondary piping arrangement as a means to provide freeze protection of the boiler, which is an integral function of the boiler control. Maintain the minimum boiler flow rate, see Graphs 2 through 7 on pages 91 through 93. For other piping arrangements, consult the Engineering Department at Triangle Tube or consult other approved/recognized design arrangements.
BEST PRACTICE
On piping applications utilizing a single zone or other recognized piping design arrangements, it is recommended that the installer uses flow/check valves with weighted seats at or near the appliance to prevent gravity circulation.
- Install the limit in the boiler supply pip­ing between the boiler and any isolation valve.
- Maximum set point for the limit is 194ºF.
- For wiring of the limit reference Fig. 19, page 31, using the external limit/manual reset terminals on the low voltage termi­nal strip. This will provide a "hard" lockout requiring a manual reset of the control.
Backflow Preventer
- Use a backflow preventer valve in the make-up water supply to the unit as required by local codes.
Expansion Tank and Makeup Water
Ensure the expansion tank is properly sized for the boiler volume (3 gallons [12 L] for the PRESTIGE Solo 60, 5 gallons [19 L] for the PRESTIGE Solo 175/250, 7 gallons [26 L] for PRESTIGE Solo 399) and the system volume and temperature.
CAUTION
Undersized expansion tanks will cause system water to be lost through the pres­sure relief valve and cause additional makeup water to be added to the system. Eventual boiler heat exchanger failure can result due to this excessive makeup water addition.
The expansion tank must be located as shown in Fig. 7 and Fig. 8 on page 19 when using a primary/secondary piping arrangement or as per recognized design methods. Refer to the expansion tank manufacturer instructions for additional installation details.
16
Page 23
Boiler Piping
Connect the expansion tank to an air separator only if the air separator is located on the suc­tion side (inlet) of the system circulator. Always locate and install the system fill con­nection at the same location as the expansion tank connection to the system.
Diaphragm Expansion Tank
Always install an automatic air vent on the top of the air separator to remove residual air from the system.
Closed-Type Expansion Tank
It is recommended to pitch any horizontal piping upwards toward the expansion tank 1 inch per 5 feet of piping. Use 3/4” piping for the expansion tank to allow air within the system to rise.
CAUTION
DO NOT install automatic air vents on a closed-type expansion tank system. Air must remain in the system and be returned to the expansion tank to pro­vide an air cushion. An automatic air vent would cause air to be vented from the system resulting in a water-logged expansion tank.
Circulator
Domestic Hot Water System Piping
See Fig. 9 through 12, page 21-22 for recom­mended piping to a DHW system. This recom­mended piping configuration ensures priority is given to the production and recovery of the DHW.
The piping for the DHW is separate from the boiler system piping and does not require a pri­mary / secondary piping configuration.
To wire the DHW circulator to the boiler control module, reference Section VIII - External Wiring.
System Piping - Zone Circulators
Connect the PRESTIGE Solo to the system piping as shown in Fig. 9 page 21 when zoning with zone circulators.
The installer must provide a separate circulator for each zone of space heating as well as the boiler circulator.
NOTICE
To ensure an adequate flow rate through the PRESTIGE Solo, the boiler supply and return piping size must be a minimum of 1 inch for the PRESTIGE Solo 60, 1-1/4 inch for the PRESTIGE Solo 175/250 and 1-1/2 inch for the PRESTIGE Solo 399.
The PRESTIGE Solo requires an external circula­tor to provide circulation through the boiler. The circulator when wired directly to the PRESTIGE Solo will allow for domestic hot water priority and to provide circulation for the freeze protection fea­ture of the boiler control. See Graphs 2 through 7 on pages 91 & 93 for pressure drop and minimum flow rate through the boiler.
Sizing Primary Piping
See Fig. 9 through 13, pages 21 - 23, for rec­ommended piping arrangements based on vari­ous applications. Size the piping and system components required in the space heating sys­tem, using recognized design methods.
System Piping - Zone Valves
Connect the PRESTIGE Solo to the system pip­ing as shown in Fig. 10 page 21 when zoning with zone valves. The primary / secondary piping ensures that the boiler loop has sufficient flow.
NOTICE
To ensure an adequate flow rate through the PRESTIGE Solo, the boiler supply and return piping size must be a mini­mum of 1 inch for the PRESTIGE Solo 60, 1-1/4 inch for the PRESTIGE Solo 175/250 and 1-1/2 inch for the PRESTIGE Solo 399.
17
Page 24
Boiler Piping
Fig. 6: Piping Component Legend
18
Page 25
Boiler Piping
Fig. 7: Near Boiler Piping - Diaphragm Expansion Tank
Note: Pitch horizontal pip-
ing upwards (1” of pitch per 5 ft of piping) towards expansion tank.
Fig. 8 : Near Boiler Piping - Closed Type Expansion Tank
19
Page 26
Boiler Piping
System Piping - Through Boiler
In new or retrofit applications in which primary/secondary arrangement is not utilized, the PRESTIGE Solo allows this flexibility due to a lower boiler pressure drop, see Graphs 2 through 7 on pages 91 through 93.
Figure 11, page 22 illustrates a multiple zone valve system with a single system/boiler circu­lator. A by-pass loop with a pressure differential valve must be installed on the system piping.
Figure 12, page 22 illustrates a single zone utiliz­ing the boiler circulator as the system circulator.
System Piping - Radiant Heating
The heat exchanger design of the PRESTIGE allows operation in a condensing mode. This feature requires no regulation of the return temperature back to the boiler in radiant heat­ing applications.
The design and construction of the PRESTIGE heat exchanger allows the installation of the boil­er on systems with non - oxygen barrier tubing.
NOTICE
To ensure an adequate flow rate through the PRESTIGE Solo, the boiler supply and return piping size must be a mini­mum of 1 inch for the PRESTIGE Solo 60, 1-1/4 inch for the PRESTIGE Solo 175/250 and 1-1/2 inch for the PRESTIGE Solo 399.
NOTICE
The addition of the high temperature limit is important if the PRESTIGE is connect­ed to a domestic hot water system, which requires a high primary supply water temperature.
System Piping - Special Application
If the boiler is used in conjunction with a chilled water/medium system, the boiler and chiller must be piped in parallel. Install flow/check valves to prevent the chilled medi­um from entering into the boiler.
CAUTION
DO NOT install a SMART tank along with the PRESTIGE in systems with non-oxygen barrier tubing. Failure to comply could result in premature failure of the SMART tank.
The boiler water supply temperature can be maintained by the PRESTIGE, eliminating the need for a mix system to achieve the desired temperature.
It is recommended for the installer to install a high temperature limit to ensure that the pri­mary supply temperature does not exceed the maximum allowable temperature for the radi­ant tubing.
Size the system piping and circulator to pro­vide the flow needed for the radiant system.
If the boiler is used to supply hot water to the heating coils of an air handler where they may be exposed to chilled air circulation, install flow/check valves or other automatic means to prevent gravity circulation of the boiler water during cooling cycles.
System Piping - Multiple Units Installation
Use a balanced manifold system as the prima­ry / secondary connection to the space heating piping as shown in Fig. 13 page 23.
Maintain a minimum of 6 inches [153 mm] of clearance between units to allow for servicing.
For the space heating piping refer to the appli­cations mentioned in this manual or use recog­nized design methods.
20
Page 27
Boiler Piping
Note: Reference Fig. 23, page 38 for Prestige Wiring.
Fig. 9: System Piping - Zoning with Zone Circulators
Note: Reference Fig. 24, page 38 for Prestige Wiring.
Fig. 10: System Piping - Zoning with Zone Valves
NOTICE
The boiler system piping shown must be a “closed” system to avoid any oxygen contamination and potential failure of the outer tank of the Smart.
21
Page 28
Boiler Piping
Note: Reference Fig. 25, page 39 for Prestige Wiring.
Note: Verify CH circulator is properly sized to overcome the system pressure drop and pro­vide adequate flow through the boiler system.
Fig. 11: System Piping - Multiple Zone Valve with Single System/Boiler Circulator
Note: Reference Fig. 26, page 39 for Prestige Wiring.
Note: Verify CH circula­tor is properly sized to overcome the system pres­sure drop and provide ade­quate flow through the boiler system.
Fig. 12: System Piping - Single Zone System with Single System/Boiler Circulator
NOTICE
The boiler system piping shown must be a “closed” system to avoid any oxygen contamination and potential failure of the outer tank of the Smart.
22
Page 29
Boiler Piping
Note: Consult the PRESTIGE
TriMax Control Supplement for
information on wiring and con-
figuring the boilers using the
built-in Cascade function
23
Fig. 13: Multiple PRESTIGE Solo Boiler Piping - Primary / Secondary
Page 30
Installing Vent/Combustion Air & Condensate Drain
SECTION V - Installing Vent / Combustion Air & Condensate Drain
Installing Vent and Combustion Air
DANGER
The PRESTIGE Solo must be vented and supplied with combustion air as shown in the PRESTIGE Solo Vent Supplement, included in the boiler installation envelope. Refer to optional vent kit instructions for additional vent installation instructions. Once installa­tion is completed, inspect the vent and combustion air system thoroughly to ensure systems are airtight and comply with the instructions given in the venting supplement and are within all require­ments of applicable codes. Failure to comply with the installation require­ments on the venting and combustion air piping will cause severe personal injury or death.
WARNING
Ensure the condensate drain assembly contains the plastic seated ball. Do not install the condensate drain assembly if the ball is lost or missing, replace the entire assembly.
3. Remove the compression nut and rubber seal from the drain outlet.
4. Using 3/4” x 2’ flexible PVC tube provid­ed, slide the compression nut and rubber seal over the pipe
NOTICE
The use of 3/4” PVC or CPVC pipe is also acceptable. If 3/4” pipe is used deburr and chamfer pipe to allow mat­ing onto the drain assembly.
5. Thread the rubber seal into the compres­sion nut to ease installation of the pipe to the drain assembly.
Installing Condensate Drain Assembly
1. Locate the condensate drain assembly and install as shown in Fig. 14 page 25.
NOTICE
The installer may want to fill the con­densate trap with water prior to assem­bling on the unit.
2. Remove the retaining nut, metal washer and rubber seals from the condensate drain assembly and slide over the heat exchanger condensate drain nipple. Make sure to place the metal washer on top of the rubber seals. Connect the condensate drain assem­bly to the retaining nut and tighten. Hand
tight only!
6. Seat the pipe onto the drain assembly and
tighten the compression nut. Hand tight
only!
NOTICE
The installer may opt to using 13/16" ID tubing in lieu of rigid piping.
NOTICE
The drain line materials must be an approved material by the authority hav­ing jurisdiction. In absence of such authority, PVC and CPVC piping must comply with ASTM D1785 or D2845. The cement and primer used on the pip­ing must comply with ASME D2564 or F493. For installations in Canada, use CSA or ULC certified PVC or CPVC pipe, fittings and cement/primer.
7. Continue the pipe from the drain assembly to a floor drain or condensate pump.
24
Page 31
Installing Vent/Combustion Air & Condensate Drain
Flexible Tubing
(or 3/4 PVC/ CPVC Piping
to Drain)
Compression
Nut with Rubber Seal
Fill Plug
with Vaccum
Break Port
Condensate
Drain Assembly
Retaining Nut
(Hand Tight Only)
Place the Metal Washer
and (2) Rubber Gaskets
in this Order for Proper
Seal.
NOTICE
When selecting and installing a conden­sate pump, ensure the pump is approved for use with condensing boilers and fur­naces. The pump should be equipped with an overflow switch to prevent prop­erty damage from potential condensate spillage.
8. The PRESTIGE Solo will typically produce a condensate that is considered slightly acidic with a pH content below 3.0. Install a neutralizing filter if required by authority having jurisdiction.
CAUTION
The condensate drain must remain filled and unobstructed and allow unrestricted flow of condensate. The condensate should not be subject to conditions where freezing could occur. If the con­densate is subjected to freezing or becomes obstructed , it can leak, result­ing in potential water damage to the boil­er and surrounding area.
Fig. 14: Condensate Drain Assembly
25
Page 32
Gas Piping
Sediment Trap Min. Length of 3"
Union Fitting
Cap
Tee Fitting
External Manual Gas Shut Off Valve (Must Be Within 6' of the Boiler)
Gas Flow
SECTION VI - Gas Piping
Gas Supply Piping Connection
NOTICE
The gas supply piping must be installed in accordance to all applicable local, state and national codes and utility requirements.
1. Install a 1/2” NPT for PRESTIGE Solo 60, 3/4” NPT for PRESTIGE Solo 175/250 or 1” NPT for PRESTIGE Solo 399 pipe union at the factory supplied gas nipple, for ease of service.
2. Install a manual shutoff valve in the gas supply piping as shown in Fig. 15. For installations in Canada the installer must tag and identify the main shutoff valve.
3. Install a sediment trap (drip leg) on the gas supply line prior to connecting to the PRES­TIGE Solo gas train as shown in Fig. 15.
7. Use pipe dope compatible with natural and propane gases. Apply sparingly only to the male threads of pipe joints so that pipe dope does not block gas flow.
WARNING
Failure to apply pipe dope as detailed above can result in severe personal injury, death or substantial property damage.
WARNING
Use a two-wrench method of tightening gas piping near the unit and its gas pip­ing connection. Use one wrench to pre­vent the boiler gas line connection from turning and the second to tighten adja­cent piping. Failure to support the boil­er gas piping connection could damage the gas line components.
4. Support the gas piping using hangers. Do not support the piping by the unit or its components.
5. Purge all air from the gas supply piping.
6. Before placing the PRESTIGE Solo into operation, check and test all connections for leaks.
- Close the manual shutoff valve during
any pressure test with less than 13”w.c..
- Disconnect the PRESTIGE Solo and its
gas valve from the gas supply piping during any pressure test greater than 13”w.c..
WARNING
Do not check for gas leaks with an open flame. Use a gas detection device or bub­ble test. Failure to check for gas leaks can cause severe personal injury, death or substantial property damage.
Fig. 15: Recommended Gas Supply Piping
26
Page 33
Gas Piping
NATURAL GAS
Pipe Sizing - Natural Gas
Refer to Table 1 for schedule 40 metallic pipe length and diameter requirements for natural gas, based on rated PRESTIGE Solo input (divide by 1,000 to obtain cubic feet per hour).
- Table 1 is based on Natural Gas with a spe­cific gravity of 0.60 and a pressure drop through the gas piping of 0.30”w.c..
- For additional gas piping sizing informa­tion, refer to ANSI Z223.1. For Canadian installations refer to B149.1 or B149.2.
Natural Gas Supply Pressure Requirements
1. Pressure required at the gas valve inlet supply pressure port:
- Maximum 13”w.c. at flow or no flow
conditions to the burner.
- Minimum 5”w.c. during flow conditions
to the burner. Must be verified during start up and with all other gas appliances operating within the building.
2. Install 100% lockup gas pressure regulator in the gas supply line if inlet pressure can exceed 13”w.c at any time. Adjust the lock­up pressure regulator for 13”w.c maximum.
WARNING
DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is factory-set for the correct outlet pres­sure. This setting is suitable for natural gas and propane and requires no field adjustment. Attempts by the installer to adjust or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death or substantial property damage.
NOTICE
The natural gas orifice requirements are:
PRESTIGE Solo 60: 0.204” (5.2 mm)
PRESTIGE Solo 175: None Required
PRESTIGE Solo 250: None Required
PRESTIGE Solo 399: 0.339” (8.6 mm)
Table 1: Gas Piping Sizing - Natural Gas
Length of Pipe in
Feet
SCH 40 1/2" 3/4" 1" 1-1/4" 1-1/2"
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 890
40 63 130 245 500 760
50 56 115 215 440 670
75 45 93 175 360 545
100 38 79 150 305 460
150 31 64 120 250 380
Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas Per
Hour (based on 0.60 specific gravity, 0.30" w.c. pressure drop)
27
Page 34
Gas Piping
PROPANE GAS
Pipe Sizing - Propane Gas
Contact the local propane gas supplier for rec­ommended sizing of piping, tanks and 100% lockup gas regulator.
Propane Gas Supply Pressure Requirements
1. Adjust the propane supply regulator pro­vided by the gas supplier for 13”w.c. max­imum pressure
2. Pressure required at the gas valve inlet sup­ply pressure port:
- Maximum 13”w.c. at flow or no flow
conditions to the burner
- Minimum 5”w.c. during flow conditions
to the burner. Must be verified during start up and with all other gas appliances operating within the building.
WARNING
Prior to start up, ensure the unit is set to fire propane. Check the rating label for the type of fuel. Check the gas valve for propane conversion label. If there is a conflict or doubt on the burner set up, remove the gas valve and check for the propane orifice, see Fig. 16 or 17, page
29. Failure to ensure proper burner setup could result in severe personal injury, death or substantial property damage.
NOTICE
The propane orifice requirements are:
PRESTIGE Solo 60: 0.120” (3.1 mm)
PRESTIGE Solo 175: 0.221” (5.6 mm)
PRESTIGE Solo 250: 0.250” (6.3 mm)
PRESTIGE Solo 399: 0.264” (6.7 mm)
WARNING
DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is factory-set for the correct outlet pres­sure. This setting is suitable for natural gas and propane and requires no field adjustment. Attempts by the installer to adjust or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death or substantial property damage.
28
Page 35
Gas Piping
Gas Valve
Orifice
Gaskets
Venturi
Venturi
Orifice
Gas Valve
Gasket
Gas Valve
Fig. 16: Gas Valve / Venturi Assembly - PRESTIGE Solo 60/175/250
Fig. 17: Gas Valve / Venturi Assembly - PRESTIGE Solo 399
29
Page 36
Internal Wiring
Location of Fuses
TriMax Line Voltage Fuse Location
SECTION VII - Internal Wiring
WARNING
ELECTRICAL SHOCK HAZARD. For your safety, disconnect electrical power supply to the unit before servicing or making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe person­al injury or death.
CAUTION
Prior to servicing, label all wires before disconnecting. Wiring errors can cause improper and dangerous operation. Verify proper wiring and operation after servicing.
General Requirements
- Wiring must be N.E.C Class 1.
Fig. 18: TriMax Control Module Fuse Location
Additional fuses are also located on the line voltage terminals as shown in Fig. 18A and Fig. 19.
TriMax Line Voltage Fuses
- If original wiring as supplied with the unit must be replaced, use only Type T 194ºF [90ºC] wire or equivalent as a minimum.
- The PRESTIGE must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 - latest edi­tion and / or the Canadian Electrical Code Part 1, CSA C22.1, Electrical Code.
Fuse Locations
The TriMax control module contains 2 internal replaceable 5A fuses as shown in Figure 18.
Fuse Size Terminals Purpose
2.5A 23,24,25 CH2 /System Pump
2.5A 26,27,28 Auxiliary Boiler Pump
2.5A 29,30,31 DHW Pump / Diverter Valve
2.5A 32,33,34 CH1 Pump/Diverter Valve
8.0A 35,36,37 Power Supply
2.5A 38,39,40 Alarm
Fig. 18A: Fuse Location on the line volt­age Terminals
30
Page 37
Internal Wiring
1 2
CH1
Thermostat
3 4
CH2
Thermostat
5 6
Outdoor
Sensor
7 8
DHW
Aquastat
or Sensor
9 10
Manual
Reset
Limit
11 12
Auto
Reset
Limit
13 14
+ -
Modulation
Signal
15 16
System
Sensor
17 18 19
Cascade
Master
20 21 22
A B G
Modbus
25
L G N
CH2 Pump /
System Pump
23 24
37
L G N
Power Supply
35 36 40
Alarm
38 39
Cascade
Slave
31*
L G N
DHW Pump /
*Diverter Valve
29* 30
Circulator Terminals
28
L G N
Auxiliary
Boiler Pump
26 27
Circulator factory
wired on Prestige
Solo 110 only.
14711
428125136
5
1
65432
1
G
N
L
X00
X01
X11
X13
X14
X02
X15
TriMax
Control
Module
On / Off
Switch
65432
1
3291054168
7
6
3
1
4
18732
9
X03
X04
X07
X05
X01
TriMax
Display
Module
543
X06
2
94837
2105
71268
3
2
1
3
2
563
4
Flue Temperature Sensor
Supply Temperature Sensor
Return Temperature Sensor
LWCO
BKBKBK
BK
BK BK BK BK W W V V BR BR O O BL BL R R W W W BR Y GY BK BK BK BK BK RW W W W W R
WWWWW
W
W
W
V
V
BR
BR
O
O
BL
BL
R
R
WWW
BR
Y
GY
YYYYY
Y
R
R
BK
BK
BK
R
BL
WBKWBKWBKWBKWBKW
O
BL
BL
R
R
Y
Y
WBKW
BK
YYYYY
Y
O
124
5
321
Blower
Power Terminals
Blower
Blower
Signal Terminals
GND
5
Gas Valve
(All except Solo 399)
V1
V1GV2
V2
GND
Gas Valve
(Solo 399 only)
1
3
GND
F00
GND
GND
Ignitor
Notes:
1. If any of the original wire supplied with the appliance must be replaced, it must be replaced with the same
type or its equivalent.
2. All 120 VAC field wiring to the boiler shall have a minimum size of 14 AWG with a temperature rating of at
least 194°F [90°C].
Wire Legend
- Low Voltage
- Line Voltage
- Ignition Cable
Wire Color Legend
BK – Black
W – White
GR – Green
BL – Blue
R – Red
O – Orange
V – Violet
Y – Yellow
BR – Brown
GY - Gray
Prestige Solo Internal Wiring
34
L G N
CH (1) Pump /
*Diverter Valve
32* 33
Fig. 19: Prestige Solo Boiler Factory Wiring
31
Page 38
External Wiring
SECTION VIII- External Wiring
Installation Compliance
All field wiring made during installation must comply with:
- National Electrical Code NFPA 70 and any other national, state, provincial or local codes or requirements.
- In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any other local codes.
WARNING
ELECTRICAL SHOCK HAZARD. Before making any electrical connec­tions to the PRESTIGE, disconnect elec­trical power supply at the service panel. Failure to comply can cause severe per­sonal injury or death.
Circulator Wiring
1. Reference Table 2 to determine the appro­priate circulator connections required. The circulator connections used will depend on the systems piping layout.
Table2: Circulator Operation Default Setting
Auxillary
Boiler
Pump
ON ON
System
Pump
OFF
(Note 2)
CH 1 or
CH 2 Call
DHW Call
CH (1)
Pump
ON
OFF
(Note 1)
DHW
Pump
OFF
(Note 1)
ON ON
Note 1: Domestic Hot Water Priority can be
disabled in the Installer Menu which allows the CH (1) and DHW circulators to operate at the same time. Consult the PRESTIGE TriMax Control Supplement for more information.
NOTICE
The line voltage terminals are located on the right set of terminals 23 through 40. The low voltage terminals are located on the left set of terminals 1 through 22.
Line Voltage Connections
1. Connect a dedicated 120 VAC/15A service to the line voltage terminal strip on the wiring panel below the PRESTIGE control module, as shown in Fig. 19, page 31.
2. Route the incoming 120 VAC power wire through the provided openings in the bot­tom jacket panel.
3. The unit is provided with a service switch located on the front panel, check local code requirements for compliance.
NOTICE
If local electrical codes or conditions require an additional service switch, the installer must provide and install a fused disconnect or 15 amp (minimum) service switch.
Note 2: The system circulator can also be
enabled during a DHW Call in the Installer Menu. Consult the PRES­TIGE TriMax Control Supplement for more information.
NOTICE
Each circulator is individually fused with a
2.5A fuse located in the terminal strip. The total combined amp draw of the CH (1), DHW, and Auxiliary Boiler Circulators must not exceed 4 amps at any time for the Solo 60, 175, or 250. The total combined amp draw of the CH (1), DHW, and Auxiliary Boiler Circulators must not exceed 3 amps at any time for the Solo 399. Use an isolation relay to lower the total com­bined amp draw if exceeding these limits.
2. Connect the CH circulator to the line volt­age terminal strip on the wiring panel below the PRESTIGE control module, as shown in Fig. 19 on page 31. The CH cir­culator is enabled during a CH 1 or CH 2 call. This circulator is used to supply heat to the central/space heating loop.
32
Page 39
External Wiring
3. Connect the DHW circulator to the line voltage terminal strip on the wiring panel below the PRESTIGE control module, as shown in Fig. 19 on page 31. The DHW circulator is enabled during a DHW call. This circulator is used to supply heat to an indirect hot water heater.
4. Connect the Auxiliary Boiler circulator to the line voltage terminal strip on the wiring panel below the PRESTIGE control mod­ule, as shown in Fig. 19 on page 31. The auxiliary boiler circulator is enabled during a CH or a DHW call. This circulator is typ­ically used in retrofit applications where the CH and DHW systems are connected to a common boiler supply.
5. Connect the System circulator to the line voltage terminal strip on the wiring panel below the PRESTIGE control module, as shown in Fig. 19 on page 31. The system circulator is enabled during a CH1 or CH2 call with the factory default TriMax set­tings. This circulator is typically used to circulate water in the secondary CH loop when zoning with zone valves.
Low Voltage Connections
NOTICE
Line and Low Voltage wiring should be separated to prevent possible electrical noise on the low voltage circuits. Line and Low Voltage wiring should use sepa­rate electrical knockouts on the PRES­TIGE cabinet and should remain sepa­rated inside the PRESTIGE.
NOTICE
CH and DHW call connections to the PRESTIGE require a dry contact with no external voltage present. Ensure no exter­nal voltage is present on each set of wires before connecting to the PRESTIGE. If external voltage is present, the use of an isolation relay is required to prevent dam­age to the TriMax controller.
Thermostat Wiring
Alarm Wiring
The alarm contact closes whenever the Prestige is in a soft or hard lockout. This dry contact can be connected to an external monitoring system or other indicator to alert the operator that the Prestige is locked out.
1. Connect the external monitoring device to the line voltage terminal strip on the wiring panel below the PRESTIGE control mod­ule, as shown in Fig. 19 on page 31.
NOTICE
The alarm contact is fused with a 2.5A fuse located in the terminal strip. An iso­lation relay is required if the external monitoring device draws more than 2.5A.
The TriMax control has two thermostat call inputs for multiple zone / temperature systems. This allows each call to have its own outdoor reset curve and maximizes the efficiency of the system.
WARNING
Simultaneous CH1 and CH2 calls will result in the PRESTIGE operating at the highest target temperature. The use of a mixing device on the lower temperature zones such as the Triangle Tube Optima Series SMV Control may be required to protect the lower temperature zones from damage.
1. Connect the room thermostat or dry contact end switch to the low voltage terminal strip on the wiring panel below the PRESTIGE control module, as shown in Fig. 19 on page 31.
33
Page 40
External Wiring
2. Follow thermostat manufacturer’s instruc­tions for proper installation. Thermostat should be located on an inside wall away from any heat or cold influences such as drafts, lights, fireplaces, etc.
3. Set the thermostat anticipator (If applica­ble) as follows:
- Set for 0.2 amps when wired directly to
the PRESTIGE.
- Set to match the electrical power
requirements of the connected device when wired to zone relays or other devices. Refer to the relay manufactur­er’s specifications and the thermostat instructions for additional information on anticipator setting.
NOTICE
The use of power stealing thermostats which draw their power from the PRES­TIGE can lead to erratic or unpre­dictable operation. Honeywell T87 series thermostats are excluded from this notice since they are designed to operate with the TriMax control.
Additional Boiler Limits
Additional boiler limits (High Limit, LWCO, etc.) can be wired into either the Manual Reset Limit or Auto Reset Limit terminals of the PRESTIGE. These limit connections will pro­vide a “hard” lockout requiring a manual reset of the PRESTIGE or a “soft” lockout in which the PRESTIGE will automatically reset when the limit resets.
NOTICE
Manual Reset Limit and Auto Reset Limit connections to the PRESTIGE require a dry contact with no external voltage present. Ensure no external volt­age is present on each set of wires before connecting to the PRESTIGE. If exter­nal voltage is present, the use of an isola­tion relay is required to prevent damage to the TriMax controller.
1. Remove the factory installed jumper wire on the Manual Reset or Auto Reset termi­nals that will accept the additional boiler limit.
Outdoor Sensor Wiring
The Outdoor Reset function and Warm Weather Shutdown (WWSD) features require the connection of the included outdoor temper­ature sensor. See page 63 for outdoor sensor installation and setup.
Domestic Hot Water Wiring
The Domestic Hot Water terminals can accept either a call from an aquastat (switch) or tem­perature sensor. Use of the included indirect water heater sensor is recommended.
1. Connect the DHW aquastat or temperature sensor to the low voltage terminal strip on the wiring panel below the PRESTIGE con­trol module, as shown in Fig. 19 on page 31.
2. Connect the additional boiler limit to the low voltage terminal strip on the wiring panel below the PRESTIGE control mod­ule, as shown in Fig. 19 on page 31.
External Modulation Control
The PRESTIGE firing rate can be controlled by an external modulating boiler controller. See page 64 for external modulation signal wiring and setup.
System Sensor Wiring
An optional system temperature sensor can be placed on the central heating loop to control the temperature in the central heating loop instead of the boiler loop. When connected, the PRES­TIGE will automatically modulate to maintain the target temperature in the central heating loop. The boiler supply temperature sensor will continue to be used as a high temperature limit.
34
Page 41
External Wiring
CAUTION
Locate the system temperature sensor where it can accurately measure the sup­ply temperature to the heating system. Inaccurate system temperature readings could lead to overheating or under heat­ing resulting in property damage.
Cascade Wiring
The TriMax control includes the ability to operate up to six boilers together as one with­out the need for external controllers. Consult the PRESTIGE TriMax Control Supplement for more information.
Modbus Wiring
1. Connect the system temperature sensor to the low voltage terminal strip on the wiring panel below the PRESTIGE control mod­ule, as shown in Fig. 19 on page 31.
The TriMax control includes the ability to communicate with building management sys­tems (BMS) through a Modbus interface. Consult the PRESTIGE TriMax Control Supplement for more information.
35
Page 42
External Wiring
Fig. 20: Multiple Zone Field Wiring Using Zone Valves
36
Page 43
External Wiring
Fig. 21: Multiple Zone Field Wiring using Zone Circulators
37
Page 44
External Wiring
Note: Reference Fig. 9, page 21 for System Piping.
Fig. 23: Prestige Wiring - Zoning with Zone Circulators
Note: Reference Fig. 10, page 21 for System Piping.
Fig. 24: Prestige Wiring - Zoning with Zone Valves
38
Page 45
External Wiring
DHW Aquastat
Outdoor Sensor
Zone #2 Zone Valve
End Switch
Zone #1 Zone Valve
End Switch
DC1
HC1
120V/15A
Service
C21
Smart Tank
Snap Set
CH1
T-stat
5
Low voltage terminal strip
Cascade
Slave
CH2
T-stat
Outdoor Sensor
DHW
Stat/Sens
Manual
Reset/lmt
Auto
Reset/lmt
Modulation
Signal
+ -
System Sensor
Cascade
Master
Modbus
A B G
CH2 / Sys
Pump
L G N
Aux Boiler
Pump
L G N
DHW Pump /
Divert Valve
L G N
CH1 Pump
Diverter Valve
L G N
Power
Supply
L G N
Alarm
Contact
Line voltage terminal strip
1 2 34 6 7 8 910111213141516171819202122 232425262728293031323334353637383940
DHW Aquastat
Outdoor Sensor
Room Thermostat
DC1
HC1
120V/15A
Service
C21
Smart Tank
Snap Set
CH1
T-stat
5
Low voltage terminal strip
Cascade
Slave
CH2
T-stat
Outdoor Sensor
DHW
Stat/Sens
Manual
Reset/lmt
Auto
Reset/lmt
Modulation
Signal
+ -
System Sensor
Cascade
Master
Modbus
A B G
CH2 / Sys
Pump
L G N
Aux Boiler
Pump
L G N
DHW Pump /
Divert Valve
L G N
CH1 Pump
Diverter Valve
L G N
Power
Supply
L G N
Alarm
Contact
Line voltage terminal strip
1 2 34 6 7 8 910111213141516171819202122 232425262728293031323334353637383940
68
Note: Reference Fig. 11, page 22 for System Piping.
Fig. 25: Prestige Wiring - Multiple Zone Valve with Single System/Boiler Circulator
Note: Reference Fig. 12, page 22 for System Piping.
Fig. 26: Prestige Wiring - Single Zone System with Single System/Boiler Circulator
39
Page 46
TriMax Operation
SECTION IX- TriMax Operation
The TriMax Boiler Management System is designed to be flexible yet easy to use. TriMax mon­itors and controls the Prestige to provide heat as efficiently as possible. TriMax includes many advanced features which previously were not available in the Prestige.
• Two central/space heating (CH) call inputs with separate outdoor reset curves.
• Domestic Hot Water (DHW) call input with optional priority.
• EZ Setup feature allows the installer to quickly customize TriMax for each installation.
• Cascade function allows up to six Prestige boilers to operate together in a single heating system.
• Modbus interface for integrating with building management systems.
All TriMax features are easy to use through a graphical display where information is presented either graphically or in plain English, so code charts are not required. Figure 30 shows a TriMax display example of the Prestige fired for a domestic hot water demand.
Fig. 30: TriMax User Interface
40
Page 47
TriMax Operation
TriMax Navigation
Navigation is performed through four arrow buttons UP, DOWN, LEFT, RIGHT with a center OK button for making selections and entering information. The INSTALLER button (the small
round button) provides the installing contractor with full access to all available features after entering a password. Reference the TriMax Control Supplement for Installer level functions.
Figure 31 – TriMax Navigation Buttons
The Main Menu can be entered from the Home Screen by pressing the OK button. The menu system utilizes icons to represent each selection. The current selected menu is displayed as a reversed image with a text description shown at the top of the display. Menus can be entered by highlighting the desired icon and pressing the OK button. The Home Screen icon at the bot­tom of each screen returns to the Home Screen when selected. The Previous Screen icon at the bottom of each screen returns to the previous screen when selected.
41
Page 48
TriMax Operation
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
f
b
g
a
b
c
d
Boiler Information
Boiler Information MenuCH/DHW Operation Menu
EZ Setup Menu
Main Menu
Home Screen
Heating Enabled
TriMax Menu Structure
42
Page 49
TriMax Operation
The status line displays the current operating state of the Prestige. See page 44 for a list of all Status Line Messages.
The radiator icon indicates that a central heating call has been received. A small number 1 or 2 indicates which CH calls are active.
Circulator icons indicate which circulators are currently powered.
The faucet icon indicates that a domestic hot water call has been received.
The percentage icon indicates that an external modulation call has been received.
This line provides basic information. The user can press the LEFT or RIGHT arrow buttons to view Target, Supply, Return, Domestic and Outdoor Temperatures.
The Prestige is represented in the center of the Home Screen. Basic operating information such as supply and return temperatures are displayed as well as current burner status. A flame symbol is displayed when the unit is fired. The flame size changes to indicate the current firing rate.
1
2
Home Screen
The Home Screen presents status information in a very user friendly way so that the current state of the boiler can be quickly accessed.
The screen backlight will illuminate when any button is pressed and remain illuminated for five minutes. Press the UP or DOWN buttons to turn on the backlight while at the Home Screen without making any changes.
The screen contrast can be adjusted at the Home Screen by pressing and holding the OK but­ton then pressing and holding the LEFT arrow along with the OK button. The contrast can then be increased by pressing the UP button or decreased by pressing the DOWN button while holding in the OK button and LEFT arrow. All buttons must be released and the procedure performed again to switch between increasing and decreasing contrast.
43
Page 50
TriMax Operation
Status Line Message Description
Standby Indicates that the Prestige is ready to respond when a demand is received.
CH Demand A central heating call has been received.
DHW Demand A domestic hot water call has been received.
CH / DHW Demand
DHW Priority
Priority Timeout
External Demand An external modulation call has been received.
Slave Operation
Status Line Messages
Central heating and domestic hot water calls are being received simultane­ously. Both calls are being satisfied simultaneously because domestic hot water priority has been disabled.
Central heating and domestic hot water calls are being received simultane­ously. Domestic hot water call is being satisfied first because it has priority over central heating calls.
Central heating and domestic hot water calls are being received simultane­ously. The domestic hot water priority time limit has been exceeded. Priority will now switch back and forth between central heating and domes­tic hot water calls until one call is satisfied.
The Prestige is responding to a call from the master Prestige boiler in a cas­cade system.
Manual Operation The burner or circulators have manually been enabled in the Installer Menu.
CH Burner Delay The burner will not fire until the call blocking time has elapsed.
DHW Burner Delay The burner will not fire until the call blocking time has elapsed.
The burner is not fired because the supply/system water temperature
CH Setpoint Reached
DHW Setpoint Reached
CH Post Pump
DHW Post Pump
Freeze Protection
Boiler Protection
exceeds the setpoint. The central heating circulator continues to operate and the burner will fire again once the supply/system water temperature drops below the setpoint.
The burner is not fired because the supply/system water temperature exceeds the setpoint. The domestic circulator continues to operate and the burner will fire again once the supply/system water temperature drops below the setpoint.
The central heating circulator is running to remove heat from the Prestige at the completion of a call.
The domestic hot water circulator is running to remove heat from the Prestige at the completion of a call.
The burner is fired because the freeze protection feature has been activated. Freeze protection will end once the supply/system water temperature is raised to 60ºF [16ºC].
The burner firing rate is being reduced because of an excessive difference between the boiler supply and return temperatures. The firing rate will begin increasing once the temperature difference is less than 45ºF [25ºC].
Lockout Description The lockout which currently has the Prestige shut down is displayed.
44
Page 51
TriMax Operation
Press OK Button
The EZ Setup menu can be accessed by selecting this icon.
The CH / DHW Operation Menu can be accessed by selecting this icon.
Currently selected menu
The Boiler Information Menu can be accessed by selecting this icon.
The Home Screen icon at the bottom of each screen returns to the Home Screen when selected.
The Previous Screen icon at the bottom of each screen returns to the previous screen when selected.
Main Menu
The Main Menu can be entered from the Home Screen by pressing the OK button. The menu system utilizes icons to represent each selection. The currently selected menu is displayed as a reversed image with a text description shown at the top of the display. Menus can be entered by highlighting the desired icon and pressing the OK button.
45
Page 52
TriMax Operation
Select CH Demand
Switch & Outdoor Reset
Constant & Outdoor Reset
Constant & Setpoint
0-10V Modulation Signal
Switch & Outdoor Reset
Select CH Demand
Switch & Setpoint
Constant & Setpoint
0-10V Modulation Signal
OR
Switch & Setpoint
68ºF
194ºF
180ºF
CH1 Setpoint
EZ Setup
Navigation: Home Screen>Main Menu>EZ Setup
The EZ Setup menus provide a simple way to quickly customize the TriMax for each installation. EZ Setup prompts the user to make selections which allows the Prestige to be setup very quickly without searching through long lists of settings and manually making adjustments.
Heating EZ Setup
Navigation: Home Screen>Main Menu>EZ Setup>Heating EZ Setup
Heating EZ Setup allows the installer to quickly customize the central heat­ing settings for the application.
Select CH Demand Default: Switch & Outdoor Reset
Select CH Demand prompts the installer to select how a CH Demand is gen­erated. Press the UP or DOWN buttons to select the CH Demand type then press the OK button to store the setting. The Select CH Demand options are:
• Switch & Outdoor Reset – This option is only displayed when the
outdoor temperature sensor is connected. A central heating call from a thermostat or zone panel will enable the Prestige and the setpoint will vary with the outdoor temperature for central heating calls.
• Switch & Setpoint - This option is only displayed when the outdoor
temperature sensor is not connected. A central heating call from a ther­mostat or zone panel will enable the Prestige and the setpoint will be fixed for central heating calls
• Constant & Outdoor Reset - This option is only displayed when the
outdoor temperature sensor is connected. The Prestige will maintain set­point without an external call from a thermostat or zone panel. The set­point will vary with the outdoor temperature for central heating calls.
• Constant & Setpoint - The Prestige will maintain setpoint without an
external call from a thermostat or zone panel. The setpoint will be fixed for central heating calls.
• 0-10V Modulation Signal – This option allows the Prestige firing rate
to be controlled by an external control system.
CH1 Setpoint Default: 180°F [82°C]
CH1 Setpoint prompts the installer to enter the fixed setpoint for a CH1 heating call when a Setpoint option is chosen in Select CH Demand. Press the LEFT or RIGHT buttons to adjust the CH1 Setpoint then press the
OK button to store the setting.
CH2 Setpoint Default: 140°F [60°C]
CH2 Setpoint prompts the installer to enter the fixed setpoint for a CH2 heating call when a Setpoint option is chosen in Select CH Demand. Press the LEFT or RIGHT buttons to adjust the CH2 Setpoint then press the OK button to store the setting.
46
Page 53
TriMax Operation
180ºF
120ºF
64ºF
0ºF
Current Settings
Off 78ºF
Off
Set Warm Weather
Shutdown Temperature
Select CH1 Reset Curve Default: Finned Tube Baseboard
Select CH1 Reset Curve prompts the installer to select an outdoor reset curve for a CH1 heating call when an Outdoor Reset option is chosen in Select CH Demand. Outdoor reset curve presets are available to cover most applica­tions. The outdoor reset curve can also be adjusted to any desired settings in the Installer Menu. Press the UP or DOWN buttons to select the outdoor reset curve appropriate for the type of heating system then press the OK but- ton to store the setting.
Select CH2 Reset Curve Default: Low Mass Radiant
Select CH2 Reset Curve prompts the installer to select an outdoor reset curve for a CH2 heating call when an Outdoor Reset option is chosen in Select CH Demand. Outdoor reset curve presets are available to cover most applica­tions. The outdoor reset curve can also be adjusted to any desired settings in the Installer Menu. Press the UP or DOWN buttons to select the outdoor reset curve appropriate for the type of heating system then press the OK but- ton to store the setting.
Table 3: Outdoor Reset Preset Selections
Preset Minimum Setpoint Maximum Setpoint
Low Mass Radiant 80ºF [27ºC] 140ºF [60ºC]
High Mass Radiant 80ºF [27ºC] 120ºF [49ºC]
Cast Iron Baseboard 100ºF [38ºC] 170ºF [77ºC]
Finned Tube Baseboard 120ºF [49ºC] 180ºF [82ºC]
Radiators 120ºF [49ºC] 170ºF [77ºC]
Fan Coil 140ºF [60ºC] 180ºF [82ºC]
Set Warm Weather Shutdown Temperature Default: OFF
Warm Weather Shutdown prompts the installer to enter an optional outdoor temperature at which to disable the central heating function. The Prestige will continue to respond to a domestic hot water call or a 0-10V Modulation Signal when the outdoor temperature exceeds the Warm Weather Shutdown Temperature setting. Press the LEFT or RIGHT but­tons to adjust the Warm Weather Shutdown Temperature then press the OK button to store the setting. The Warm Weather Shutdown icon is dis­played on the home screen when the outdoor temperature reaches the Warm Weather Shutdown Temperature.
47
Page 54
TriMax Operation
Select DHW Demand
Switch Sensor
Switch
96ºF
194ºF
186ºF
Boiler
DHW Setpoint
68ºF
150ºF
140ºF
DHW
Storage Setpoint
Domestic Hot Water EZ Setup
Navigation: Home Screen>Main Menu>EZ Setup>DHW EZ Setup
Domestic Hot Water EZ Setup allows the installer to quickly customize the domestic hot water settings for the application.
Select DHW Demand Default: Switch
Select DHW Demand prompts the installer to select the type of device which will generate a DHW call. Press the UP or DOWN buttons to select the DHW Demand type then press the OK button to store the setting. The Select DHW Demand options are:
• Switch – A domestic hot water call from an aquastat or dry contact
switch will enable the Prestige with a fixed setpoint for a domestic hot water call.
• Sensor – This option requires the use of Indirect Water Heater Sensor
PSRKIT22. The Prestige will monitor the DHW storage temperature and generate a domestic hot water call when the temperature drops below the DHW Storage Setpoint by 6ºF [3ºC].
Boiler DHW Setpoint Default: 186°F [86°C]
Boiler DHW Setpoint prompts the installer to enter the fixed boiler setpoint temperature during a Domestic hot water call when the Switch option is cho­sen in Select DHW Demand. Press the LEFT or RIGHT buttons to adjust the Boiler DHW Setpoint then press the OK button to store the setting.
DHW Storage Setpoint Default: 140°F [60°C]
DHW Storage Setpoint prompts the installer to enter the domestic hot water storage setpoint temperature when the Sensor option is chosen in Select DHW Demand. Press the LEFT or RIGHT buttons to adjust the DHW Storage Setpoint then press the OK button to store the setting.
NOTICE
The Boiler DHW Setpoint will automatically be set 46°F [25°C] higher than the DHW Storage Setpoint setting.
48
Page 55
TriMax Operation
Off
60 min.
Off
DHW Priority Timeout
EZ Setup Reset
Press OK button
to restore factory settings.
Any other button
to keep current settings.
Select Units
Fahrenheit
Celsius
Fahrenheit
DHW Priority Timeout Default: Off
DHW Priority Timeout prompts the installer to enter an optional time limit that a domestic hot water call has priority over a central heating call. Press the LEFT or RIGHT buttons to adjust the DHW Priority Timeout then press the OK button to store the setting.
EZ Setup Reset
Navigation: Home Screen>Main Menu>EZ Setup>EZ Setup Reset
EZ Setup Reset allows the installer to reset all EZ Setup settings back to the original factory defaults. Follow the onscreen instructions to reset all EZ Setup settings back to the original factory defaults.
Display EZ Setup
Navigation: Home Screen>Main Menu>EZ Setup>Display EZ Setup
Display EZ Setup allows the installer to select the type of temperature units displayed as well as the language used for all text. Press the UP or DOWN buttons to select then press the OK button to store the setting.
49
Page 56
TriMax Operation
Heating Enabled
Boiler Information
Boiler Status Heating Call DHW Call Boiler Firing Rate Flame Ionization Current Boiler Setpoint
Standby
No No
0%
OuA
__
Boiler Status
Standby
194
68
-24.00
-16.00 -8.00
0.00
Boiler Setpoint
CH/DHW Operation
Navigation: Home Screen>Main Menu>CH / DHW Operation
CH / DHW Operation provides a simple way to disable either the central heating or domestic hot water functions of the Prestige. Operation can be enabled and disabled by selecting the central heating or domestic hot water icon then pressing the OK button to toggle between enabled and disabled. An icon with an X through it indicates that function has been disabled. The disabled icon is also displayed on the home screen when a function has been disabled.
Boiler Information
Navigation: Home Screen>Main Menu>Boiler Information>Boiler Information
Boiler Information provides real time operating information of the Prestige. Each line contains an information item followed by its current value. Six information items are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional information items. See page 51 for a list of all information items.
Boiler Information Logging
Some information items include a logging function which records one sam­ple every 12 minutes to produce a graph of the last 24 hours. Select the infor­mation item in Boiler Information then press the OK button to view its graph. The following items have a logging function:
• Boiler Firing Rate
• Flame Ionization Current
• Boiler Setpoint
• Boiler Supply Temperature
• Boiler Return Temperature
• Boiler Flue Temperature
• Outdoor Temperature
• DHW Storage Temperature
• External Modulation Signal
50
Page 57
TriMax Operation
Information Item Description
Information Items
Boiler Status
Heating Call Displays if a central heating call is present.
DHW Call Displays if a domestic hot water call is present
Boiler Firing Rate Displays the current firing rate of the Prestige.
Flame Ionization Current Displays the current flame ionization current from the ignitor.
Boiler Setpoint Displays the current setpoint of the Prestige.
Boiler Supply Temperature Displays the current supply temperature of the Prestige.
Boiler Return Temperature Displays the current return temperature of the Prestige.
Boiler Flue Temperature Displays the current flue temperature of the Prestige.
Outdoor Temperature Displays the current outdoor temperature.
DHW Storage Temperature
Displays the current operating state of the Prestige. This is the same as the status line on the home screen.
Displays the current DHW storage temperature when Indirect Water Heater Sensor PSRKIT22 is installed.
External Modulation Signal
CH Ignitions
CH Runtime
DHW Ignitions
DHW Runtime
Displays the current external modulation signal being received from an external controller.
Displays the number of central heating ignitions since the unit was installed. This counter increases in increments of twenty.
Displays the number of hours the Prestige has run for a central heating call since the unit was installed.
Displays the number of domestic hot water ignitions since the unit was installed. This counter increases in increments of twenty.
Displays the number of hours the Prestige has run for a domestic hot water call since the unit was installed.
51
Page 58
TriMax Operation
Lockout History
1: Low water 2: No error 3: No error 4: No error 5: No error 6: No error
5h ago 25h ago 25h ago 25h ago 25h ago 25h ago
Lockout Details
Low Water
Boiler Status Heating Call DHW Call Boiler Firing Rate Flame ionization Current
Standby
No No 0%
OuA
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
f
b
g
a
b
c
d
Lockout History
Navigation: Home Screen>Main Menu>Boiler Information>Lockout History
Lockout History records the last eight lockouts. Each line contains a lock­out description followed by how long ago the lockout occurred. Six lock­outs are displayed on the screen at one time. Press the UP or DOWN but­tons to scroll through additional lockouts. See pages 54 & 55 for a list of lockouts and descriptions.
Lockout Details
Some information items are recorded at the time of a lockout to aid in diag­nosing the cause of the lockout. Select the lockout description in Lockout History then press the OK button to view the recorded information. Press the UP or DOWN buttons to scroll through the recorded information. The fol­lowing information items are recorded at the time of a lockout:
• Boiler Status
• Heating Call
• Domestic Call
• Boiler Firing Rate
• Flame Ionization Current
• Boiler Setpoint
• Boiler Supply Temperature
• Boiler Return Temperature
• Boiler Flue Temperature
• Outdoor Temperature
• System Temperature
52
Page 59
TriMax Operation
Press any ARROW Button
The status line now displays the lockout
The lockout message is displayed at the top of the screen
The lower right corner displays the lockout reference code.
The second sentence gives a possible cure for the lockout.
The first sentence gives a description of the lockout.
The third sentence tells how to reset the lockout.
Press any ARROW button to return to the Home Screen while locked out.The main menu can then be entered from the Home Screen to help diagnose the problem. Select the Home Screen icon at the bottom of any menu screen to return to the Lockout Screen.
Water level has fallen below
an acceptable operating
level. Increase pressure to
normal range. Boiler will automatically reset once
water level returns to normal
Low Water
If problem persists,
call for service
E37
--
Lockout Screen
The Lockout Screen replaces the Home Screen if a lockout occurs. The screen backlight will also illuminate constantly while the Prestige is locked out. Pressing any arrow button will return to the Home Screen so that additional troubleshooting can be performed. See pages 54 and 55 for a list of lockouts and descriptions.
53
Page 60
TriMax Operation
Manual Reset Hard Lockouts
Code Lockout Message Description
E1 Failed Ignition The burner failed to light after 5 ignition attempts.
E2 False Flame A flame is being detected prior to ignition.
E3 High Boiler Temperature Boiler temperature exceeds 212°F [100ºF]
E5 Blower Speed
E8 Flame Circuit Error Flame circuit test failed.
E9 Gas Valve Circuit Error Gas valve circuit test failed.
E13 Reset Limit Reached Resets are limited to 5 every 15 minutes.
E15 Sensor Drift Supply or return sensor reading has drifted.
E16 Supply Sensor Stuck Supply sensor reading is not changing.
E17 Return Sensor Stuck Return sensor reading is not changing.
E18 Sensor Failure Supply or return sensor reading changed very rapidly.
E21 Internal Control Fault A / D conversion error.
E30 Supply Sensor Shorted
Blower is not at correct speed or speed signal is not being received by control module.
A short circuit has been detected in the boiler supply temperature sensor circuit.
E31 Supply Sensor Open
E43 Return Sensor Shorted
E44 Return Sensor Open
E80 Return > Supply Return temperature is higher than supply temperature.
E87 External Limit Open An external manual reset limit has opened
An open circuit has been detected in the boiler supply temperature sensor circuit.
A short circuit has been detected in the boiler return temperature sensor circuit.
An open circuit has been detected in the boiler return temperature sensor circuit.
54
Page 61
TriMax Operation
Automatic Reset Soft Lockouts
Code Lockout Message Description
E7 High Flue Temperature Flue temperature exceeds high limit.
E12 Internal Control Fault EEPROM misconfiguration
E25 Internal Control Fault CRC check error.
E32 DHW Sensor Shorted A short circuit has been detected in the DHW temperature sensor circuit.
E33 DHW Sensor Open An open circuit has been detected in the DHW temperature sensor circuit.
E34 Low Voltage Line voltage has fallen below an acceptable operating level.
E37 Low Water Water level has fallen below an acceptable operating level.
E45 Flue Sensor Shorted
E46 Flue Sensor Open
E76 External Limit Open An external automatic reset boiler limit has opened.
E81 Sensor Drift Supply and return temperatures are not equal.
E89 Incorrect Setting A parameter setting is outside the settings range.
E90 Firmware Mismatch Control module and display firmware versions are incompatible.
E91 System Sensor Shorted A short circuit has been detected in the system temperature sensor circuit.
E92 System Sensor Open An open circuit has been detected in the system temperature sensor circuit.
E93 Outdoor Sensor Shorted A short circuit has been detected in the outdoor temperature sensor circuit.
E94 Internal Display Fault Display memory error.
E95 Supply Sensor Error Supply sensor reading is invalid.
E96 Outdoor Sensor Open
A short circuit has been detected in the boiler flue temperature sensor circuit.
An open circuit has been detected in the boiler flue temperature sensor circuit.
An open circuit has been detected in the outdoor temperature sensor circuit.
E97 Cascade Mismatch Cascade configuration has changed.
E98 Cascade Bus Error Communication with other boilers has been lost.
E99 Controller Bus Error
Communication between boiler display and control module has been lost.
55
Page 62
Start-Up Preparation
SECTION X - Start-Up Preparation
NOTICE
Requirements below must be met for warranty coverage of Prestige heat exchangers. A thorough cleaning of any existing system, using approved heating system cleaning agents is required prior to installation of the Prestige boiler. System should be treated with an approved inhibitor after filling for long term protection.
Check Boiler System Water Chemistry
WARNING
Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to seals and gaskets in the sys­tem components could occur, resulting in substantial property damage.
Chlorinated Water
Do not use the PRESTIGE Solo to heat a swimming pool or spa directly.
Maintain the chlorine level of the water at lev­els considered safe for drinking.
Flush Boiler to Remove Sediment
The installer must flush the boiler system to remove any sediment to allow proper operation of the PRESTIGE Solo .
Flush the systems until the water runs clean and is free of sediment.
For zoned systems, each zone should be flushed through a purge valve. Purge valves and isolation valves should be installed on each zone to allow proper flushing of the system.
Cleaning of Old Boiler/System:
• Drain the existing system.
NOTICE
System water including additives must be practically non-toxic, having a toxicity rating or Class of 1, as listed in Clinical Toxicology of Commercial Products.
Water pH Level 6.0 to 8.0
Maintain the boiler water pH between 6.0 and
8.0. Check using litmus paper or contact a water treatment company for a chemical analysis.
If the pH does not meet this requirement, do not operate the PRESTIGE Solo or leave the unit filled until the condition is corrected.
Water Hardness Less Than 7 Grains
For areas with unusually hard water (hardness above 7 grains) consult a water treatment company.
• Fill system with fresh water and cleaner, place existing boiler in operation and run all zones.
• Follow manufacturer’s instructions for proper cleaner concentration and proper cleaning time.
• Thoroughly drain and flush system with fresh water after cleaning.
• Install new boiler, fill system with fresh water and proper amount of inhibitor.
• Verify pH and inhibitor level per inhibitor manufacturer’s specs; add inhibitor if necessary.
Cleaning of New Boiler/System:
• Install new boiler and flush system with cleaner water to remove any debris.
• Fill system with fresh water and proper amount of inhibitor.
• Verify pH and inhibitor level per inhibitor manufacturer’s specs; add inhibitor if necessary.
56
Page 63
Start-Up Preparation
Check and Test Antifreeze
For boiler systems containing antifreeze solu­tions, follow the antifreeze manufacturer’s instructions in verifying the inhibitor level and to ensure the fluid characteristics are within specification requirements.
Due to the degradation of inhibitors over time, antifreeze fluids must be periodically replaced. Refer to the manufacturer of the antifreeze for additional instructions.
Use of Antifreeze in the Boiler System
WARNING
NEVER use automotive or ethylene glycol antifreeze or undiluted antifreeze in the primary system as freeze protection. This can cause severe personal injury, death or substantial property damage if ignored.
Determine the antifreeze fluid quantity using the system water content volume and following the antifreeze manufacturer instructions.
The water volume of the PRESTIGE Solo is approximately 3 gallons [12 L] for PRESTIGE Solo 60 or 5 gallons [19 L] for PRESTIGE Solo 175/250 or 7 gallons [26 L] for PRESTIGE Solo 399 . Remember to include the volume of the expansion tank.
NOTICE
System water, including additives, must be practically non-toxic, having a toxicity rating or Class of 1, as listed in Clinical Toxicology of Commercial Products.
Filling the Boiler System
1. Close the boiler drain valve located on the bottom of the unit and any manual or auto­matic air vent in the system.
2. Open all system isolation valves.
3. Fill the boiler system to correct system pressure. Correct pressure will vary with each application.
NOTICE
Typical residential system fill pressure is 12 psi. System pressure will increase when system temperature increases. Operating pressure of the system should never exceed 25 psi.
4. Purge air and sediment in each zone of the boiler system through the purge valve. Open air vents to allow air to be purged in the zones.
5. Once the system is completely filled and purged of all air and sediment, check the system pressure and check/repair any leaks.
Check with local codes requirements for the installation of backflow preventers or actual disconnection from the boiler’s cold water fill or make up water supply line.
NOTICE
Massachusetts Code requires the instal­lation of a backflow preventer if antifreeze is used.
Ensure the concentration of antifreeze to water does not exceed a 50/50 ratio.
WARNING
Unrepaired system leaks will cause con­tinual makeup water to be added to the boiler. Continual makeup water will cause mineral buildup within the heat exchanger, reducing the heat transfer, causing possible heat buildup and even­tual heat exchanger failure.
Check Low Water Cut-Off Device
- The PRESTIGE Solo is provided with a factory installed LWCO device that mea­sures system pressure of more than 10 psi.
57
Page 64
Start-Up Preparation
- Remove the front jacket panel and check for continuity across the low water cut-off device wire terminals. The contacts should be closed when system pressure is greater than 10 psi. See item 6, on Fig. 36 page 78(PRESTIGE Solo 60) or on Fig. 37 page 79 (PRESTIGE Solo 175/250) or Fig. 38 page 80 (PRESTIGE Solo 399) for location of the LWCO.
Check For Gas Leaks
WARNING
Prior to start-up and during initial opera­tion, smell near the floor and around the unit for gas odorant or any unusual odor. Do not proceed with the start-up if there is any indication of a gas leak. Any leaks found must be repaired immediately.
WARNING
Propane installations only - The propane supplier mixes an odorant with the propane to make its presence detectable. In some cases the odorant can fade and the gas may no longer have an odor.
Prior to start-up of the unit and periodi­cally after start-up have the propane sup­plier check and verify the odorant level.
Check Thermostat Circuit
- Disconnect the external thermostat wires from the low voltage terminal strip.
NOTICE
In systems using 3-wire zone valves, back­feed of voltage to the unit is a common problem. Use an isolation relay to prevent voltage from the external circuit entering the PRESTIGE Solo control panel.
- Reconnect the external thermostat wires to the low voltage terminal strip.
Inspection of Condensate Drain Assembly
1. Inspect and ensure the Condensate Drain Assembly is properly installed as described on page 24 and shown in Fig. 14 on page 25.
2. Remove the plug from the Condensate Drain Assembly and fill with fresh water.
NOTICE
The condensate drain assembly must be filled with water when the PRESTIGE Solo is in operation. The condensate drain assembly prevents flue gas emis­sions from entering the condensate line. Failure to ensure trap is filled with water could result in severe personal injury or death.
3. Re-Install plug in condensate drain assem­bly.
- Connect a voltmeter across the wire ends of the external thermostat wiring.
- Close each thermostat, zone valve and relay in the external circuit one zone at a time and check the voltage reading across the wire ends.
- There should NEVER be voltage measured at the wire ends.
- If voltage is measured at the panel under any condition, check and correct the external wiring.
58
Page 65
Start-Up Procedures
SECTION XI - Start-Up Procedures
Final Checks Before Start-Up
c Read page 40 through 55 regarding the
operation of the TriMax Boiler Managemnt System.
c Verify the PRESTIGE Solo and the boiler
system are full of water and all system components are correctly set for operation, including the minimum flow rate through the boiler, see pages 91 through 93.
c Verify Start-up Preparation items outlined on
pages 56 thru 58 have been completed.
c Verify all electrical connections are correct
and securely fastened.
c Inspect vent and combustion air piping for
signs of deterioration from corrosion, physical damage or sagging. Verify combustion air and vent piping are intact and correctly installed and supported. Reference the PRES­TIGE Solo vent supplement.
c Verify burner configuration - Propane only.
- Check for proper labeling on the gas valve and the rating label for propane configuration.
- If there is doubt on the burner configura­tion, remove the gas valve and check for proper propane gas orifice size: 0.120” (3.1 mm) for PRESTIGE Solo 60, 0.221” (5.6 mm) for PRESTIGE Solo 175, 0.250” (6.3 mm) for PRESTIGE Solo 250, 0.264” (6.7 mm) for PRESTIGE Solo 399. Refer to Figs. 16 & 17, page 29 for location of the propane gas orifice.
PRESTIGE Solo Start-Up
1. Press the ON-OFF button located on the front control panel to the OFF position. Turn ON the electrical supply/service to the unit.
2. Read and follow the Operating Instructions outlined on page 62.
If PRESTIGE Solo Does Not Start Correctly
1. Check for loose electrical connections, blown fuses, (on control module and in ter­minals) or an open service switch.
2. Verify CH and DHW operation is enabled. A radiator or faucet icon with an X through it indicates that function is disabled.
3. Check continuity across the LWCO device for a closed circuit. See item 6 on Fig. 36, page 78 and item 6 Fig. 37, page 79 and Fig. 38, page 80.
4. Is an external limit control (if applicable) open? Ensure the external limit is reset to the closed position.
5. Are the gas supply valves open at the unit and meter?
6. Is incoming gas supply pressure at the unit more than 5”w.c. and less than 13” w.c. for natural or propane with all gas appliances ON or OFF.
7. Are the heating thermostats set above room temperature?
If none of these conditions correct the problem, refer to the PRESTIGE Solo Trouble-Shooting Guide or contact Triangle Tube Tech Service.
NOTICE
For natural gas applications the Prestige 60 requires an orifice: 0.204” (52mm), and the Prestige 399 requires an orifice: 0.330” (8.6 mm)
c Ensure the vent Condensate Drain
Assembly is filled with water.
Check the PRESTIGE Solo and System
c Check Boiler Piping.
Check Boiler system piping and com­ponents for leaks. If found, shut down the unit and repair immediately.
Purge any remaining air from the system piping. Air in the system piping will interfere with circulation creating heat distribution problems and system noise.
59
Page 66
Start-Up Procedures
Manual Operation
Released
O
O
O
CH
CH1
FAN
DHW
SYS CH2
c Check Vent Piping and Combustion Air
Piping.
Check for gas-tight seal at every con­nection and seam of the venting and combustion air piping.
WARNING
Venting system must be sealed gas-tight to prevent flue gas spillage and potential carbon monoxide emissions, which will result in severe personal injury or death.
c Check Gas Piping
Check around the unit for gas odor fol­lowing the procedure outlined in this manual on Page 58.
WARNING
If any gas leaks are found or suspected, shut the unit down immediately. Use a gas detection device or bubble test to locate the source of the gas leak and repair at once. Do not operate the unit until the leak is corrected. Failure to comply with this procedure could result in severe personal injury, death or sub­stantial property damage.
2. Test for CO2 or O2 and for CO during
high firing rate. The combustion read­ings should be within the range listed in Table 4. The CO level should not
exceed 100 ppm when combustion is correct. Perform the following proce-
dure to manually place the burner into high fire.
a. Press the round INSTALLER button.
Reference Fig. 31, page 41.
b. Enter the installer access code “054” by
using the LEFT and RIGHT buttons to select a digit and the UP and DOWN buttons to change the digit. Press the OK button to enter the access code.
c. Press the RIGHT button to highlight
the Manual Operation icon then press the OK button.
d. Press the OK button while the FAN
icon is highlighted to manually fire the burner and power the CH circulator.
c Verify Flame Pattern and Combustion
1. Check the flame pattern through the inspection port of the heat exchanger. The flame should be blue and stable. The flame should be the length of the burner head openings.
WARNING
The combustion testing and adjustments must be performed by a qualified installer, service agency or the gas suppli­er. All combustion measurements must be performed with calibrated equipment to ensure proper reading and accuracy.
NOTICE
An adequate CH load must be present to dissipate the heat generated during the combustion test. If an adequate CH load is not available, an indirect water heater can be used to dissipate the heat by cre­ating a DHW call which will enable the DHW circulator.
60
Page 67
Start-Up Procedures
e. Press the LEFT and RIGHT buttons to
adjust the firing rate from 0% to 100%. Hold down the LEFT or RIGHT but­ton to rapidly increase or decrease the firing rate.
Table 4: Recommended Combustion Levels
Natural Gas
All Models
O2 Min. 2.30% 2.70% 3.70%
O2 Max. 5.30% 4.70% 5.20%
CO2 Min. 8.80% 10.70% 10.00%
CO2 Max. 10.50% 12.00% 11.00%
CO Max. 100 ppm 100 ppm 100 ppm
Propane
Solo 60/175/250
Propane
Solo 399
f. Press the OK button while the FAN
icon is highlighted to shutdown the burner.
c Measure Input - Natural Gas Only
1. Ensure the boiler is firing at maximum firing rate. To manually place the boiler into high fire mode, reference page 60.
2. Operate the unit for approximately 10 minutes.
3. Turn off all gas appliances within the build­ing, except the PRESTIGE Solo.
4. At the gas meter, record the time required to use one cubic foot of gas.
5. Calculate Natural gas input using the fol­lowing equation:
3600 x 1000 / number of second recorded for one cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate the input rating listed on the unit.
g. Cycle power to the Prestige once com-
bustion testing is complete to return to normal operation.
WARNING
The combustion levels should be mea­sured at high firing rate. If the combus­tion levels are not within the range given in Table 4 for the firing rate, shut the boiler down and contact Triangle Tube Engineering Department. Failure to comply with this requirement could result in severe personal injury, death or substantial property damage.
61
Page 68
Start-Up Procedures
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which automat­ically lights the burner. DO NOT try to light the burner by hand.
B. BEFORE OPERATING, smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building
•Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above. This
appliance is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
2. Set room thermostat(s) to lowest setting. Turn the external manual gas valve handle clockwise
“CLOSE” (valve handle shall be per-
pendicular to gas piping).
3. Turn the service switch on the PRESTIGE con­trol panel OFF.
4. Remove the front jacket panel on the unit.
5. Turn the external manual gas valve handle counter clockwise to “OPEN” gas sup­ply (valve handle shall be parallel to gas piping).
6. Wait five (5) minutes to clear out any gas. If you then smell gas in the jacket enclosure or around the unit, STOP! Follow “B” in the safety infor­mation above. If you don’t smell gas, go to the next step.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to turn the external manual gas
valve. Never use tools. If the valve will not turn by hand, don’t try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
7. Turn the service switch on the PRESTIGE con­trol panel “ON”.
8. Set room thermostat(s) to desired setting(s).
9. The PRESTIGE control panel display will show the current operating status on the Status Line at the bottom of the screen. “Standby” means there is no call for heat (all thermostats are satisfied). “CH Demand” indicates a space heating call has been received. “DHW Demand” indicates a domestic hot water call has been received. A flame icon will be displayed when the unit is fired.
10. If the unit will not operate with a call for heat and the system piping is not hot, follow the instructions “To Turn Off Gas to Appliance”, below and call your service technician or gas supplier.
11. Replace the front jacket panel. Make sure the panel is seated firmly in place and all mounting screws are tightened.
TO TURN OFF GAS TO APPLIANCE
1. Set the room thermostat to lowest setting.
2. Turn the service switch on the PRESTIGE con­trol panel to “OFF”
3. Turn the external manual gas valve handle clock­wise to “CLOSE”.
62
Page 69
Outdoor Reset Control
Sensor Enclosure
(2) Plastic Anchors
Seal Gasket
Front Cover
(2) Mounting
Screws
SECTION XII - Outdoor Reset Control
The boiler setpoint for a space heating call can be fixed or vary with the outdoor temperature. The use of the outdoor reset function is recom­mended to optimize boiler efficiency. The default setting of the boiler is for outdoor reset operation. The outdoor reset function must be disabled in Heating EZ Setup after the outdoor sensor is disconnected from the boiler. (See NOTICE on page 64).
4. Mount the sensor enclosure at an elevation on the exterior wall to prevent accidental damage or tampering.
5. Avoid mounting the enclosure in areas sub­jected to excessive moisture.
6. Once an area on the exterior wall has been determined, to affix the enclosure use the enclosure as a template to mark the location of the mounting screws.
7. Using a 3/16” drill bit, drill 2 pilot holes on the marked locations.
8. Tap the enclosed plastic anchors into the pilot holes. Use care not to damage the anchors.
9. Mount the sensor enclosure using the screws provided.
Wiring the Sensor
1. Cut a small slit in the seal gasket and route 18 AWG 2-wire cable or similar wire cable through the seal gasket into the enclosure.
Fig. 32: Sensor Enclosure and Components
Mounting the Outdoor Sensor
1. Remove the front cover and mounting screws / anchors from the sensor enclosure.
2. When mounting the enclosure, the exterior wall selected should represent the heat load of the building. Typically a northern or northeastern wall will suit most buildings. A southern facing wall for those buildings, which may have large glass walls or win­dows on the southern face.
3. Ensure the sensor enclosure is shielded from direct sunlight or the effects of heat or cold from other sources (exhaust fans, appliance vents...) to prevent false temper­ature sensing.
2. Route the sensor wire back to the PRES­TIGE Solo boiler, ensuring the wires are not run parallel to telephone or power cables.
NOTICE
If the sensor wires are located in an area with sources of potential electromagnetic interference (EMI) the sensor wires should be shielded or the wires should be routed in a grounded metal conduit. If using shielded cable, the shielding should be connected to the common ground of the unit.
5. Connect the sensor wires to the outdoor sen­sor terminals on the low voltage terminal strip located inside the boiler enclosure (see boiler wiring diagram, Fig. 19 page 31).
63
Page 70
External Modulating Control
SECTION XIII - External Modulating
The boiler can directly accept an analog 0-10 VDC signal to control the firing rate from an external modulating boiler controller such as the Optima SCC4.
Wiring the Modulating Controller
Run two 18 gauge wires from the external modulating boiler controller’s 0-10 VDC boil­er output to the modulation signal terminals on the low voltage terminal strip inside the boiler. (see boiler wiring diagram, Fig. 19 page 31). This signal will both enable and modulate the boiler. No wiring is required at the thermostat terminals.
NOTICE
Ensure that the polarity of the connec­tions from the external modulating boil­er controller to the boiler are correct. Reversed polarity will lead to no response from the boiler.
TriMax Adjustment
The TriMax control must be programmed to accept the 0-10 VDC signal from the external modulating boiler control.
1. Use the Heating EZ Setup function to set the CH Demand to 0-10V Modulation Signal. Reference page 46 for the Heating EZ Setup function.
Programming of External Modulating Control
The external modulating control must be pro­grammed to send 2 VDC to enable the boiler and run it at low fire, and 10 VDC to run the boiler at high fire. Once the control enables the boiler, it must wait 30 seconds to allow the burn­er to stabilize before modulating the boiler.
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boil­er is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primari­ly to permit the use of an external energy management system that serves the same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOL­LOWING CONDITIONS IS TRUE.
• An external energy management system is installed that reduces the boiler water tem­perature as the heating load decreases.
• This boiler is not used for any space heating
• This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
64
Page 71
External Modulating Control
Factory TriMax Setting
HEATING SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
Heating Operation Enabled
Demand Switch & Outdoor Reset
Absolute Max CH Setpoint 194°F [90°C]
CH1 Maximum Setpoint 180°F [82°C]
CH1 Minimum Setpoint 120°F [49°C]
Reset Curve Coldest Day 0°F [-18°C]
Reset Curve Warmest Day 64°F [18°C]
CH2 Circuit Enabled
CH2 Maximum Setpoint 140°F 60°C]
CH2 Minimum Setpoint 80°F [27°C]
Warm Weather Shutdown OFF
Pump Constant Circulation Disabled
CH Post Pump Time 1 minute
Freeze Protection Enabled
Frost Protection Setpoint -22°F [-30°C]
Parallel Shift Value 0°F [0°C]
CH Call Blocking 1 minute
DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
DHW Operation Enabled
Prestige Model Solo
Demand Switch
Boiler DHW Setpoint 186°F [86°C]
DHW Storage Setpoint 140°F [60°C]
DHW On Differential 6°F [3°C]
DHW Storage Adder 46°F [25°C]
System Pump During DHW Disabled
DHW Post Pump Time 1 minute
DHW Priority Timeout OFF
DHW Priority Enabled
DHW Call Blocking 0 minute
DHW to CH Call Blocking 1 minute
Antilegionella Function Disabled
65
Page 72
Check-Out Procedures
SECTION XIV- Check-Out Procedures
NOTICE
Perform the following check-out proce­dures as outlined and check off items as completed. When procedures are com­pleted, the installer should complete the installation record on page 67.
Check-Out Procedures
c Boiler system water chemistry checked and
verified as outlined on page 56.
c Boiler system was completely flushed to
remove any debris/sediment.
c The boiler air vent and any automatic air
vents placed within the system are open one full turn.
c Air is purged from the heating zones and
boiler system piping.
c In multiple zone applications, adjusted for
correct flow of boiler water to each zone.
c Checked and verified room thermostat(s)
function properly and the thermostat(s) heat anticipator (if used) was properly set.
c Observed several operating cycles for
proper operation of the PRESTIGE Solo and the system.
c Set the room thermostat(s) to the desired
room temperature.
c Reviewed all instructions shipped with the
PRESTIGE Solo with the homeowner or maintenance personnel.
c Completed the Installation Record on page
67.
c Ensure all manuals and other documents
are returned to the Installation envelope and given to the owner for safekeeping.
c If applicable, confirm that the burner has
been properly configured for Propane as outlined on page 28.
c Thermostat circuit wiring checked and ver-
ified that no voltage is present to the low voltage terminals as outlined on page 58.
c Operating Instructions on page 62 were fol-
lowed during start-up.
c Combustion levels and flame pattern veri-
fied as outlined on page 60.
c Measured the rate of input on Natural Gas
as outlined on page 61.
c Checked the incoming gas pressure to the
PRESTIGE Solo to ensure a minimum pressure of 5”w.c during flow conditions to all gas appliances and a maximum pressure of 13”w.c during non-flow conditions for Natural and Propane.
c Adjusted balancing valves and system limit
controls to provide design temperatures to the primary space heating system.
66
Page 73
Installation Record
PRESTIGE Model Number:
Serial Number:
Date of Installation:
Fuel: Natural Gas Propane
Measured Rate of Input:
Combustion Readings:
CO
2
O2
CO
The following items were completed during installation:
 Installation instructions have been followed and completed
 Check-out procedures have been followed and completed
 Information regarding the unit and installation received and left with owner /  maintenance personnel.
Installer Information
(Company)
(Address)
(Address)
(Phone Number)
Btu/hr
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
_________________________________________________________________
%
%
ppm
SECTION XV - Installation Record
67
Page 74
Maintenance Schedules
SECTION XVI - Maintenance Schedule
Service Technician
At least on an annual basis the following main­tenance should be performed by a qualified ser­vice technician:
General
- Attend to any reported problems.
- Inspect the interior of the boiler jacket area; clean and vacuum if necessary.
- Clean the condensate drain assembly and fill with fresh water.
- Check boiler water pH on systems with inhibitors and/or antifreeze.
- Check for leaks: water, gas, flue and con­densate.
- Verify flue vent piping and air inlet piping are in good condition, sealed tight and properly supported.
- Check boiler water pressure, piping and expansion tank.
Owner Maintenance
Periodically:
- Check the area around the unit.
- Check and remove any blockage from the combustion air inlet and ventilation open­ings.
- Check the temperature and pressure gauges.
Monthly:
- Check vent piping.
- Check combustion air inlet piping.
- Check the pressure relief valve.
- Check the condensate drain system.
Every 6 months:
- Check boiler piping and gas supply piping for corrosion or potential signs of leakage.
- Operate the pressure relief valve.
- Check control settings.
- Check ignition electrode (sand off any white oxide; clean and reposition).
- Check ignition wiring and ground wiring.
- Check all control wiring and connections.
- Check burner flame pattern (stable and uni­form).
Additional items if combustion or performance is poor:
- Clean heat exchanger and flue ways.
- Remove burner assembly and clean burner head using compressed air only.
Once the maintenance items are completed, review the service with the owner.
WARNING
Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the PRES­TIGE Solo or in system components, resulting in severe personal injury, death or substantial property damage.
68
Page 75
Maintenance Procedures
SECTION XVII- Maintenance Procedures
Maintenance Procedures
WARNING
The PRESTIGE Solo should be inspect­ed and serviced annually, preferably at the start of the heating season, by a qual­ified service technician. In addition, the maintenance and care of the unit as out­lined on page 68 and further explained on pages 69 through 74 should be per­formed to assure maximum efficiency and reliability of the unit. Failure to ser­vice and maintain the PRESTIGE Solo and the system components could result in equipment failure, causing possible severe personal injury, death or substan­tial property damage.
NOTICE
The following information provides detailed instruction for completing the maintenance items outline in the mainte­nance schedule on page 68. In addition to this maintenance, the PRESTIGE Solo should be serviced at the beginning of the heating season by a qualified ser­vice technician.
Reported Problems
Verify that combustion air inlet area is free of any contaminates. Refer to the materials listed on page 5 of this manual. If any of these prod­ucts are in the area from which the unit takes its combustion air, they must be removed immediately or the combustion air intake must be relocated to another area.
Inspect Burner Area
Remove the boiler front jacket panel and ven­turi inlet elbow.
Vacuum any dirt or debris from the burner/blower components.
Re-install venturi inlet elbow and front jacket panel when completed.
WARNING
Do not use solvents to clean any of the burner components. The components could be damaged, resulting in unreli­able or unsafe operation.
Check System Piping
Inspect all piping (water and gas) on the boiler system for leaks and verify that the piping is leak free and properly supported.
Inspect the fittings and components on the unit and verify they are leak free.
Any problems reported by the owner should be checked, verified and corrected before pro­ceeding with any maintenance procedures.
Check Surrounding Area
Verify that the area surrounding the PRES­TIGE Solo is free of combustible / flammable materials or flammable vapors or liquids. Remove immediately if found.
WARNING
Eliminate all boiler water system leaks. Continual fresh make-up water will reduce the heat exchanger life causing boiler failure. Leaking water may also cause severe property damage to the sur­rounding area. Inspect the gas supply piping using the procedure outlined on Page 60.
69
Page 76
Maintenance Procedures
Clean Condensate Drain Assembly
1. Loosen the retaining nut from the conden­sate drain assembly and disconnect the assembly from the boiler.
2. Empty any water from the trap and drain assembly. Flush with fresh water as neces­sary to clean.
3. Check the drain piping from the condensate drain assembly to the drain. Flush to clean as necessary.
4. Reassemble the condensate drain assembly onto the boiler by tightening the retaining nut with rubber seal onto the boiler. Hand tight only.
5. Remove the fill plug on the condensate drain assembly and fill with water. See Fig. 14 on page 25.
6. Replace the fill plug on drain assembly.
Check Ventilation Air Openings
Verify that all ventilation openings to the mechanical room or building are open and unobstructed. Check the operation and wiring of any automatic ventilation dampers.
WARNING
Failure to inspect the vent system and combustion air inlet piping and to have any conditions repaired, can result in severe personal injury or death.
Check Boiler System
Verify all system components are correctly installed and operating properly.
Check the cold fill pressure for the system, typ­ical cold water fill pressure is 12 psig.
Verify the system pressure, as the unit operates at high temperature, to ensure the pressure does not exceed 25 psig. Excessive pressure reading indi­cates expansion tank sizing is incorrect or system performance problems.
Inspect air vent and air separators in the sys­tem. Remove the caps on automatic air vents and briefly depress the valve stem to flush vent. Replace the cap when completed. Ensure vents do not leak, replace any leaking vents.
Verify boiler water pH level is between 6.0 and
8.0.
Check and verify the vent discharge and the combustion air intake are free of debris and obstructions.
Inspect Vent and Combustion Air Piping
Visually inspect the venting system and com­bustion air piping for blockage, deterioration or leakage. Repair any deficiencies.
Verify that the combustion air inlet piping is connected, sealed and properly supported.
Check and verify inhibitor /antifreeze concen­tration within the boiler water meets inhibitor/antifreeze manuafacturer’s specifica­tions.
If necessary contact a boiler water treatment company for a chemical analysis.
70
Page 77
Maintenance Procedures
Check Expansion Tank
Refer to Section IV - Boiler Piping for rec­ommended location of the expansion tank and air eliminators.
Closed -Type Tank:
- Ensure tank is partially filled with
water leaving an air gap as a cushion. Refer to the manufacturer’s instruction for proper fill level.
- Ensure the tank is fitted with a device
that reduces gravity circulation of air­saturated tank water back into the sys­tem. This device prevents air from bubbling up through the water as it returns from the system.
- Ensure no automatic air vents are used
in the system. This will allow air to escape from the system instead of returning to the tank.
Diaphragm Tank:
- Ensure the system contains a minimum of
one automatic air vent. Recommended location of the air vent should be atop an air eliminator.
- Remove the tank from the system and
check the charge pressure. For residen­tial applications the charge pressure is typically 12 psig. If tank does not hold a charge pressure, then the membrane is damaged and the tank should be replaced.
WARNING
Before manually operating the pressure relief valve, ensure the discharge piping is directed to a suitable place of disposal to avoid a potential scald hazard. The dis­charge piping must be full size without restriction and installed to permit com­plete drainage of both the valve and line.
If after closing the valve, the valve fails to seat properly or continually weeps, replace the relief valve. Ensure the cause of the relief valve to weep is the valve itself, not due to sys­tem over-pressurization caused by an expan­sion tank that is waterlogged or undersized.
Inspection of Ignition Electrode
Remove the ignition electrode from the burner mounting plate.
Remove any white oxides accumulated on the electrode using fine grit sandpaper or steel wool. If the electrode does not clean to a satisfactory condition, replace the ignitor .
When replacing the ignition electrode, ensure the gasket is in good condition and correctly positioned, replace gasket if necessary.
Check Ignition Wiring and Ground Wiring
Inspect the ignition cable from the ignitor to the TriMax control module.
Check Boiler Relief Valve
Inspect the relief valve and lift the lever to ver­ify flow at least annually or as recommended on the warning tag of the valve.
Inspect the ground wire from the ignitor to the boiler jacket ground terminals.
Ensure wiring is in good condition and secure­ly connected.
Check ground continuity of the wiring to the boiler jacket or piping using a continuity meter.
Replace and correct ground wire if ground con­tinuity is not completed and satisfactory.
71
Page 78
Maintenance Procedures
Check Control Wiring
Inspect all control wiring. Ensure wiring is in good condition and properly connected.
Check Control Settings
1. Review all boiler settings in the Heating & DHW EZ Setup menus. Adjust settings as necessary, see page 46-49
2. Check any external limit control settings (if used). Adjust settings as necessary.
Perform Start-up and Checkout Procedures
Start the unit and perform the start-up proce­dure as listed in this manual.
Verify the cold water fill pressure is correct and the operating pressure of the boiler is within normal operating range.
Complete the checkout procedures as refer­enced in this manual.
Check Burner Flame
Carefully remove the burner mounting plate assembly from the heat exchanger. Ensure combustion chamber insulation is not damaged during removal of burner mounting plate assembly. See WARNING on page 74.
Remove the burner head mounting screws and remove the burner head. Inspect the burner head for deterioration. Use compressed air or a vacuum to clean the burner head.
Remove the venturi and gas valve assembly from the blower.
Use a vacuum cleaner or compressed air to clean the interior of the blower assembly. Inspect the blower blades to ensure they are clean and not damaged.
Re-assemble the venturi and gas valve onto the blower. Ensure the venturi gasket is in good condition, positioned correctly and replace gas­ket if necessary.
Re-assemble the burner head onto the burner mounting plate. Ensure the burner head gasket is in good condition, positioned correctly and replace gasket if necessary.
Inspect the burner flame through the observa­tion port on the heat exchanger.
If flame pattern is not fully blue and covers the entire burner surface during high fire, shut the unit down and allow it to cool thoroughly before disassembly.
Close the external manual gas valve on the gas supply line and disconnect the gas piping and gas valve wire harness connector.
Disconnect the wiring harness connectors from the blower and remove the blower retaining screws or nuts. Remove the blower from the unit.
Remove the mounting nuts securing the burner mounting plate to the heat exchanger and set aside.
Re-assemble the burner mounting plate assem­bly onto the heat exchanger. Ensure the burner plate gasket and combustion chamber insula­tion is in place and not damaged, replace gas­ket and insulation if necessary. See WARNING on page 74.
Re-assemble the blower onto the burner mounting plate and reconnect the wiring har­ness connectors.
Re-assemble the gas supply connection and wire harness to gas valve. Open the external manual gas valve. Check gas piping for any leaks as outlined on page 58 and repair if nec­essary. Place the unit back into service.
72
Page 79
Maintenance Procedures
Check Flame Signal
The flame signal can be read from the Boiler Information screen. It should be a min. 1μ Α
−DC.
Check the ignitor for fouling or damaged insulation if a low flame signal is read.
Check ground wiring and continuity as a cause for low flame signal. Replace ignitor if condi­tions are satisfactory.
Check Combustion Levels
Refer to page 60 of this manual for measuring combustion levels and burner adjustments.
Check Flue Gas Temperature
1. Manually place the boiler into high fire. See page 60 for procedure.
2. Navigate to the Boiler Information Menu to observe the flue gas temperature. See page 50 for procedure.
3. If the flue gas temperature is more than 54°F [30°C] above the supply water temperature, shut the boiler down and follow the heat exchanger cleaning procedure below.
Clean Heat Exchanger
1. Shut down the boiler:
- Follow the instructions on Page 62 "To Turn Off Gas to Appliance"
- Do not drain the boiler unless the boil­er will be subject to freezing condi­tions.
- Do not drain the boiler if freeze protec­tion fluid is used in the system.
2. Allow the boiler to cool down to room tem­perature before servicing.
3. Disconnect the gas piping and gas valve wire harness connector.
4. Disconnect the wiring harness connectors from the blower and remove the blower retaining screws or nuts. Remove the blow­er from the unit.
5. Remove the mounting nuts securing the burner mounting plate to the heat exchang­er and set aside.
6. Carefully remove the burner mounting plate assembly from the heat exchanger. Ensure combustion chamber insulation is not damaged during removal of burner mounting plate assembly. See WARNING on page 74.
7. Carefully remove the combustion chamber insulation from the heat exchanger and set aside. See WARNING on page 74.
8. Use a vacuum cleaner, compressed air or water to remove any accumulation from the heat exchanger flue ways. Do not use any solvent.
9. Re-install the combustion chamber insula­tion onto the heat exchanger.
10. Re-assemble the burner mounting plate assembly onto the heat exchanger. Ensure the burner plate gasket and combustion chamber insulation is in place and not dam­aged, replace gasket and insulation if nec­essary. See WARNING on page 74.
11. Re-assemble the blower onto the burner mounting plate and reconnect the wiring harness connectors.
12. Reconnect the gas piping and wire harness to gas valve. Check for leaks, repair if nec­essary.
13. Close isolation valves on the boiler water piping to isolate the boiler from the heating system.
14. Attach a hose to the boiler drain valve and flush the boiler thoroughly with fresh water by using the purge valves to allow water to enter through the make-up water line to the boiler.
73
Page 80
Maintenance Procedures
15. Once the boiler has been completely flushed, return the boiler and system piping back to operation.
16. Perform the required startup and checkout procedures as outlined on pages 56 to 66.
Handling Previously Fired Combustion Chamber Insulation
WARNING
The combustion chamber insulation contains ceramic fibers, which are clas­sified as a possible human carcinogen. When exposed to extremely high tem­peratures, the ceramic fibers, which contain crystalline silica, can be con­verted into cristobalite.
Avoid Breathing and Contact with Skin and Eyes
Review With Owner
Ensure the owner understands the impor­tance to perform the maintenance schedule specified in this manual.
Remind the owner of the importance to call a licensed contractor should the unit or sys­tem exhibit any unusual behavior.
2. Wear long sleeved, loose fitting clothing, gloves and eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes separately from other laundry and rinse washing machine thoroughly.
6. Discard used insulation in an air tight plastic bag.
When removing or repairing the combustion chamber insulation follow these precaution measures:
1. Use a NIOSH approved respirator which meets OSHA requirements for cristobalite dust, similar to N95. Contact NIOSH at 1-800-356-4676 or on the web at www.cdc.gov/niosh for latest recommen­dations.
NIOSH Stated First Aid:
Eye/Skin: Immediately irrigate Breathing: Clean fresh air
74
Page 81
Replacement Parts
4
7
9
10
3
4
2
5
1
6
8
Fig. 33: PRESTIGE Solo 60 Jacket Components
Item Part # Description
1 PTJKT10R Rear Panel
2 PTJKT08F Front Jacket Panel
3 PTRKIT129 Control Enclosure Bezel
4 PTJKT22S Side Jacket Panel (Left or Right)
5 PTJKT14T Top Jacket Panel
6 PTJKT18T Top Jacket Access Panel
7 PSRKIT21 Wall Mounting Bracket with Hardware
8 PTJKTSUP02 Support - Boiler Supply Piping
9 PTJKTSUP03 Support - Boiler Return Piping
10 PTJKTSUP01 Support - Jacket
75
Page 82
Replacement Parts
4
9
3
4
2
5
1
6
8
Fig. 34: PRESTIGE Solo 175/250 Jacket Components
Item Part # Description
1 PTJKT12R Rear Panel
2 PTJKT08F Front Jacket Panel
3 PTRKIT129 Control Enclosure Bezel
4 PTJKT22S Side Jacket Panel (Left or Right)
5 PTJKT17T Top Jacket Panel
6 PTJKT20T Top Jacket Access Panel
7 PSRKIT21 Wall Mounting Bracket with Hardware (Not Shown)
8 PTJKT21D Combustion Air Deflector
9 PTJKTSUP01 Support - Jacket
76
Page 83
Replacement Parts
4
3
4
2
5
1
6
8
7
Fig.35: PRESTIGE Solo 399 Jacket Components
Item Part # Description
1 PTJKT13R Rear Panel
2 PTJKT09F Front Jacket Panel
3 PTRKIT129 Control Enclosure Bezel
4 PTJKT23S Side Jacket Panel (Left or Right)
5 PTJKT16T Top Jacket Panel
6 PTJKT21T Top Jacket Access Panel
7 PSRKIT21 Wall Mounting Bracket with Hardware
8 PTJKT21D Combustion Air Deflector
77
Page 84
Replacement Parts
9
8
4
6
2
4
7
1
10
3
5
Fig. 36: PRESTIGE Solo 60 Internal Components
Item Part # Description
1 PTRKIT124 Heat Exchanger Body
2 PTADPT07 Vent Outlet/ Combustion Air Inlet Adapter
3 PTRKIT115 Polypropylene Vent Pipe
4 PTRKIT122 Supply / Return Temperature Sensor
5 PTRKIT123 Flue Temperature Sensor
6 PGRKIT20 LWCO Pressure Device
7 PSRKIT05 Condensate Drain Assembly
8 PSRKIT06 Boiler Piping - Return Assembly
9 PSRKIT52 Boiler Piping - Supply Assembly
10 PTRKIT119 Polyproplylene Condensate Pan
78
Page 85
Replacement Parts
9
8
4
6
2
4
7
1
3
5
10
Fig. 37: PRESTIGE Solo 175/250 Internal Components
Item Part # Description
1
PTRKIT127 Heat Exchanger Body Solo 250
2 PTADAPT07 Vent Outlet/ Combustion Air Inlet Adapter
PTRKIT126 Heat Exchanger Body Solo 175
3 PTRKIT116 Polypropylene Vent Pipe
4 PTRKIT122 Supply / Return Temperature Sensor
5 PTRKIT123 Flue Temperature Sensor
6 PGRKIT20 LWCO Pressure Device
7 PSRKIT05 Condensate Drain Assembly
8 PSRKIT28 Boiler Piping - Return Assembly
9 PSRKIT29 Boiler Piping - Supply Assembly
10 PTRKIT120 Polyproplylene Condensate Pan
79
Page 86
Replacement Parts
4
8
3
6
2
7
9
5
1
4
10
Fig. 38: PRESTIGE Solo 399 Internal Components
Item Part # Description
1 PTRKIT128 Heat Exchanger Body
2 PTADPT08 Vent Outlet/ Combustion Air Inlet Adapter
3 PTRKIT117 Polypropylene Vent Pipe
4 PSRKIT47 Supply / Return Temperature Sensor
5 PTRKIT123 Flue Temperature Sensor
6 PGRKIT20 LWCO Pressure Device
7 PSRKIT05 Condensate Drain Assembly
8 PSRKIT48 Boiler Piping - Return Assembly
9 PSRKIT49 Boiler Piping - Supply Assembly
10 PTRKIT121 Polypropylene Pan
80
Page 87
7
2
5
4
1
3
9
6
8
Replacement Parts
Fig. 39: PRESTIGE Solo 60/175/250 Burner Components
Item
PRESTIGE
Solo 60
1 PSRKIT09 PSRKIT30 Combustion Chamber Insulation
2 PSRKIT11 PSRKIT31 Burner Head with Gasket
Part #
3 PTRKIT114 PSRKIT13 Blower with Gasket
4 PSRKIT12 PSRKIT32 Burner Plate
5 PSGSK15 PSGSK16 Burner Plate Gasket
6 PTRKIT111 Gas Valve
PSRKIT80 Venturi - 055 Solo 60
7
PSRKIT82 Venturi - 052 Solo 175
PSRKIT83 Venturi - 051 Solo 250
8 PTRKIT113 Igniter and Cable with Gasket
9 PSRKIT16 Sight Glass Assembly (Glass, Gasket and Bracket)
Part #
PRESTIGE
Solo 175-250
Description
81
Page 88
Replacement Parts
7
2
10
4
1
3
9
7
6
8
Fig. 40: PRESTIGE Solo 399 Burner Components
Item Part # Description
1 PSRKIT37 Combustion Chamber Insulation
2 PSRKIT38 Burner Head with Gasket
3 PSRKIT40 Blower with Gasket
4 PSRKIT39 Burner Plate
5 PSGSK17 Burner Plate Gasket (Not Shown)
6 PTRKIT112 Gas Valve
7 PSRKIT84 Venturi
8 PTRKIT113 Igniter and Cable with Gasket
9 PSRKIT16 Sight Glass Assembly (Glass, Gasket and Bracket)
10 PSRKIT42 Gas Valve Piping
82
Page 89
8
3
4
1
6
5
2
7
Replacement Parts
Fig. 41: PRESTIGE Solo Control Enclosure
Item Part # Description
PTRKIT109 Pressure Gauge and Fitting (All except Solo 399)
1
PTRKIT110 Pressure gauge and Fitting (Solo 399)
2 PTSWI01 Power Switch
3 PTSWI02 Power Switch Cover
4 PTRKIT108 Control Enclosure
PTRKIT105 TriMax Control Module (Solo 60, 110 &175)
5
PTRKIT106 TriMax Control Module (Solo 250 & 399)
6 PTRKIT107 TriMax Display Module
7 PTCON19 Control Enclosure Cover
8 PTGRO01 Igniter Cable Grommet
9 PTFUSE02 TriMax Control Module 5A Fuse (Not Shown)
10 PTFUSE01 Circulator 2.5A Fuses (Not Shown)
11 PTFUSE03 In-Line Voltage 8A Fuse (Not Shown)
83
Page 90
Product Specifications
35 1/2” [902 mm]
15 3/8” [392 mm]
8 1/2” [216 mm]
9 7/8” [251 mm]
2 1/4” [56 mm]
3”
[76 mm]
1 ” NPT Boiler Supply
1/2” NPT Gas Connection
3/4” NPSC Pressure Relief Valve
3” Combustion AIr Inlet
3” Vent Outlet
19 3/4” [502 mm]
7 3/8” [186 mm]
1” NPT Boiler Return
Front View PRESTIGE Solo 60
84
Page 91
Product Specifications
35 1/2” [902 mm]
17 1/4” [437 mm]
12” [305 mm]
4 1/4”
[108 mm]
14 1/2” [368 mm]
2 3/4” [70 mm]
19 3/4” [502 mm]
7 3/8” [186 mm]
3/4” NPT Gas Connection
1-1/4” NPT Boiler Return 1-1/4” NPT Boiler Supply
3” Vent Outlet 3” Combustion AIr Inlet
3/4” NPSC Pressure Relief Valve
Front View PRESTIGE Solo 175/250
85
Page 92
Product Specifications
37 1/2” [953 mm]
24 3/4” [628mm]
20 1/4” [516 mm]
18 5/8” [473 mm]
13 1/4” [340 mm]
9 1/4” [235 mm]
3 1/4” [83 mm]
1 1/2” NPT Boiler Supply
1” Gas Connection
1 1/2” NPT Boiler Return
4” Combustion Air Inlet
3/4” NPSC Pressure Relief Valve
4” Vent Outlet
17 3/4” [454 mm]
Front View PRESTIGE Solo 399
86
Page 93
Product Specifications
11 3/8” [289 mm]
1 7/8” [48mm]
15 5/8” [396 mm]
2 1/4” [58mm]
12” [306 mm]
1” NPT Boiler Return
1” NPT Boiler Supply 1/2” NPT Gas Connection
3” Vent Outlet 3” Combustion AIr Inlet
3/4” NPSC Pressure Relief Valve
Side View PRESTIGE Solo 60
87
Page 94
Product Specifications
11 3/8” [288 mm]
6 7/8” [176 mm]
11 3/8” [288 mm]
1 7/8”
[51 mm]
15 5/8” [396 mm]
3/4” NPT Gas Connection
1-1/4” NPT Boiler Supply 1-1/4” NPT Boiler Return
3” Vent Outlet 3” Combustion AIr Inlet
3/4” NPSC Pressure Relief Valve
Side View PRESTIGE Solo 175/250
88
Page 95
Product Specifications
21 1/4” [540 mm]
15 3/8” [390 mm]
14 3/4” [374 mm]
16 3/8” [416 mm]
5 7/8” [150 mm]
1 1/2” NPT Boiler Supply
1 1/2” NPT Boiler Return
1” Gas Connection
4” Combustion Air Inlet
4” Vent Outlet
3/4” NPSC Pressure Relief Valve
Side View PRESTIGE Solo 399
89
Page 96
Product Specifications
94.1%
95.1%
Fuel
Combustion
Efficiency
Input
Note 4
Output Note 4 Note 5
Thermal
Efficiency
Net IBR
Rating Note 2
Shipping
Weight
Lbs / Kg
Boiler
Model
379,000
399,000
330,000
225 / 102
Natural
SOLO 399
102,500
110,000
102,500
Propane
87,000
Fuel
DOE
Heating Capacity
Note 1 & 4
Input
Note 4
DOE Seasonal
Efficiency AFUE
Note 3
Net IBR
Rating
Note 2
60,000
96%
Shipping
Weight
Lbs / Kg
95 / 43
Natural
Boiler Model
SOLO 60
47,000
110,000
102,500
96%
95 / 43
Propane
87,000
154,000
54,000
170,000
96%
131 / 60
Natural
SOLO 175
134,000
102,500
102,500
96%
131 / 60
Propane
Propane
87,000
223,000
245,000
96%
142 / 65
Natural
SOLO 250
194,000
102,500
110,000
102,500
96%
142 / 65
87,000
Note 1: The heating capacity of the PRESTIGE Solo
60/175/250 is based on the test requirements of the U.S. Department of Energy.
Note 2: The IBR rating is based on a piping and pick
up allowance of 1.15. This allowance should be sufficient for the standard radiation requirements for a building load.
Note 3: Based on the given AFUE the PRESTIGE
Solo 60/175/250 meets the energy efficiency guidelines established by Energy Star.
DOE
Note 4: Input and output ratings are shown for sea
level applications. The PRESTIGE Solo automatically derates the input at approxi­mately 2% for every 1,000 Ft. of altitude. No alterations to the boiler or burner system is required.
Note 5: PRESTIGE Solo 399 output rating is based
off of the thermal efficiency.
90
Page 97
Product Specifications
Pressure Drop Comparison -Grundfos
Graph 2: Pressure Loss Through Boiler-Grundfos Circulator
Pressure Drop Comparison -Taco
Graph 3: Pressure Loss Through Boiler-Taco Circulators
Note: Minimum allowable flow rate at full input:
- 3 gpm SOLO 60
91
Page 98
Product Specifications
Graph 4: Pressure Loss Through Boiler - Grundfos Circulators
Graph 5: Pressure Loss Through Boiler - Taco Circulators
Note: Minimum allowable flow rate at full input:
- 8 gpm SOLO 175
- 12 gpm SOLO 250
92
Page 99
Product Specifications
Graph 6: Pressure Loss Through Boiler - Grundfos Circulators
Graph 7: Pressure Loss Through Boiler - Taco Circulators
Note: Minimum allowable flow rate at full input:
- 19 gpm SOLO 399
93
Page 100
Additional quality water heating equipment available
An
Company
from Triangle Tube
Maxi-Flo and Spa Heat Exchangers
SMART Indirect Fired Water Heaters
- Construction of high quality corrosion resistant stainless steel (AISI 316) or titanium
- Specially designed built-in flow restrictor to assure maximum heat exchange
- Compact and light weight
- Available in 5 sizes that can accommodate any size pool or spa
TTP Brazed Plate Heat Exchangers
- Exclusive Tank-in-Tank design
- Stainless steel construction
- Available in 8 sizes and 2 models
- Limited LIFETIME residential warranty
- 15 year limited commercial warranty
- Self cleaning/self descaling design
- For domestic water, snow melting, radiant floor, refrigeration
- Plates made of stainless steel, with a 99.9 % copper and brazed, ensuring a high resistance to corrosion
- Self cleaning and self descaling
- Computerized sizing available from Triangle Tube/Phase III
- Available in capacities from 25,000 BTU/hr to 5,000,000 BTU/hr