TriangleTube Prestige Trimax Solo Series User Manual

Page 1
Prestige TriMax Boiler
Manual Addendum
This addendum replaces Section V in the Prestige Installation and Maintenance Manual
SECTION V - Installing Vent / Com­bustion Air & Condensate Drain
Installing Vent and Combustion Air
DANGER
The PRESTIGE must be vented and sup­plied with combustion air as shown in the PRESTIGE Vent Supplement, included in the boiler installation envelope. Refer to optional vent kit instructions for additional vent installation instructions. Once instal­lation is completed, inspect the vent and combustion air system thoroughly to en­sure systems are airtight and comply with the instructions given in the venting sup­plement and are within all requirements of applicable codes. Failure to comply with the installation requirements on the vent­ing and combustion air piping will cause severe personal injury or death.
Installing Condensate Drain Assembly
1. Locate the condensate drain assembly and install as shown in Fig. 14.
NOTICE
The installer may want to fill the conden­sate trap with water prior to assembling on the unit.
3. Slide the rubber seals from the condensate drain assembly over the heat exchanger con­densate drain nipple. Connect the condensate drain assembly to the retaining nut and tighten.
WARNING
Ensure the condensate drain assembly contains the plastic seated ball. Do not in­stall the condensate drain assembly if the ball is lost or missing, replace the entire assembly.
4. Remove the compression nut and rubber seal from the drain outlet.
5. Using 3/4” x 2’ flexible PVC tube provided, slide the compression nut and rubber seal over the pipe
2. A metal washer must be installed when in­stalling the condensate drain assembly. On all models except the Solo 399, the metal washer must first be cut using a pair of di­agonal cutting pliers to make it into a split washer. Insert the metal washer into the re­taining nut and screw onto the condensate drain assembly without rubber gaskets. Use the condensate drain assembly as a tool to press the retaining nut with metal washer onto the polypropylene condensate pan. Un­screw the condensate drain assembly and proceed to the next step.
WARNING
Ensure installation of the condensate drain assembly included the metal washer. Fail­ure to comply could result in the trap as­sembly dislocating from the boiler.
NOTICE
The use of 3/4” PVC or CPVC pipe is also acceptable. If 3/4” pipe is used deburr and chamfer pipe to allow mating onto the drain assembly.
6. Thread the rubber seal into the compression nut to ease installation of the pipe to the drain assembly.
7. Seat the pipe onto the drain assembly and tighten the compression nut. Hand tight
only!
NOTICE
The installer may opt to using 13/16" ID tubing in lieu of rigid piping.
1
Page 2
Prestige TriMax Boiler Manual Addendum
Flexible Tubing
(or 3/4 PVC/ CPVC Piping
to Drain)
Compression
Nut with Rubber Seal
Fill Plug
with Vaccum
Break Port
Condensate
Drain Assembly
Plastic Ball
(Not shown)
Retaining Nut
Place the Metal Washer
and (2) Rubber Gaskets
in this Order for Proper
Seal.
NOTICE
The drain line materials must be an ap­proved material by the authority having jurisdiction. In absence of such authority, PVC and CPVC piping must comply with ASTM D1785 or D2845. The cement and primer used on the piping must comply with ASME D2564 or F493. For installa­tions in Canada, use CSA or ULC certi­fied PVC or CPVC pipe, fittings and cement/primer.
8. Continue the pipe from the drain assembly to a floor drain or condensate pump.
NOTICE
When selecting and installing a condensate pump, ensure the pump is approved for use with condensing boilers and furnaces. The pump should be equipped with an overflow switch to prevent property damage from potential condensate spillage.
9. The PRESTIGE will typically produce a con­densate that is considered slightly acidic with a pH content below 3.0. Install a neu­tralizing filter if required by authority hav­ing jurisdiction.
CAUTION
The condensate drain must remain filled and unobstructed and allow unrestricted flow of condensate. The condensate should not be subject to conditions where freezing could occur. If the condensate is subjected to freezing or becomes ob­structed , it can leak, resulting in potential water damage to the boiler and surround­ing area.
Date: 7/25/2013
Fig. 14: Condensate Drain Assembly
2
2013-30 Prestige TriMax_Manual-Addendum
Loading...