TriangleTube prestige Service Technician's Trouble Shooting Manual

Page 1
prestige
Condensing
Water Boiler
SERVICE TECHNICIAN’S
TROUBLE SHOOTING GUIDE
2004-28 TSG-SOLO-9/04
Page 2
Table of Contents
SERVICING TIPS AND INSTRUCTIONS Page 3
CONTROL MODULE DISPLAY - GENERAL Page 5
PRESTIGE CONTROL MODULE DISPLAY Page 8
SOFT LOCKOUT ERROR CODE Page 9
HARD LOCKOUT ERROR CODE Page 14
COMBUSTION TEST/SETTINGS Page 20
INTERNAL WIRING Page 22
REPLACEMENT PARTS Page 24
Page 3
Introduction
Definitions
WARNING
Indicates a potentially hazardous situation which, if ignored, can result in death, serious injury or sub­stantial property damage.
NOTICE
Indicates special instructions on installation, operation or maintenance, which are important to the equip­ment/product, but not related to personal injury hazards.
WARNING
This guide is to be used in conjunction with the PRESTIGE Installation and Maintenance manual. Procedures and servicing listed in this manual must be performed by a qualified service technician, installer, service agency or gas supplier. Any procedures or service performed by an unqualified individ­ual or service agency can result in severe personal injury, death or substantial property damage.
1
Page 4
Introduction
Introduction
This guide is to be used in conjunction with the Triangle Tube PRESTIGE Boiler Installation and Maintenance Manual.
Good Troubleshooting Practices
Before leaving for the job site:
Check your parts and tools
Test equipment and tools you will need: Electrical meter that tests both voltage and continuity Temperature gauge or metering device Manometer Combustion Analyzer
Standard tools of the trade (wrenches, screwdrivers...)
Parts to solve most problems Control module PSRKIT18 Transformer with surge protection PSRKIT19 Blower with gasket PSRKIT13
Review all appropriate manuals before leaving for the job site
At the job site:
- Clarify problem
- Have the PRESTIGE manual and any other wiring, zone control or piping diagrams, or installation guides readily available.
REMEMBER
Follow the Troubleshooting Guide step by step, always double checking your results. Skipping steps or not complet­ing steps can lead to wrong conclusions, repeated visits to the job site, unhappy customers and unnecessary warran­ty claims.
2
Page 5
Servicing Tips and Instructions
WARNING
Label all wires and wire connections prior to disconnecting when servicing any boiler controls. Wiring errors can cause improper and dangerous operation. Always disconnect the power supply to the boiler before serv­icing. Failure to comply could result in severe personal injury, death or substantial property damage.
WARNING
Never bypass (jumper) any boiler control or device except for momentary testing when troubleshooting the boiler as outlined in this guide, severe personal injury, death or substantial property damage can result.
Initial Troubleshooting Checks
- Ensure all wire connectors to the control module and sensors are securely connected.
- Ensure the maximum gas supply pressure does not exceed 13”w.c during flow or no flow conditions.
- Ensure the gas supply pressure is a minimum 5” w.c during flow conditions (burner firing on all gas appliances).
Control Module Fuses
NOTICE
The control module contains 2 internal replaceable fuses. Ensure the fuses are in working condition prior to replacing the control module or any boiler component. If one of the fuses has blown, it will prevent the con­trol module and/or boiler components from operating properly.
To check or replace the control module fuses:
1. Disconnect the external power supply to the boiler.
2. Remove the front jacket panel of the boiler by removing the mounting screws along the top edge.
3. Remove the electical quick connects on the control and the black plastic housing cover off the control module. Use care not to damage the cover when removing it.
4. Inspect both fuses to determine if blown.
5. The control module is supplied from the factory with 2 spare fuses, a 5 amp fast acting fuse and a 4 amp slow acting fuse, attached to the control module cover.
6. When replacing the fuses ensure the amp rating and type of the fuse matches the replacement fuse. Reference Fig. 1, page 4 for amperage and location of the fuses.
WARNING
Do not bypass any fuse with a jumper. Do not replace any fuse with a fuse that is not specified. Failure to comply could result in severe personal injury, death or substantial property damage.
7. Re-install the control module cover, electrical quick connects and the front jacket panel when completed.
3
Page 6
Servicing Tips and Instructions
8. Reconnect the external power supply to the boiler and perform the verification of operation steps as outline in the Prestige Installation Manual.
WARNING
After completing any servicing of the boiler verify proper operation of the boiler. Steps to verify proper oper­ation are outlined in the Start-Up Preparation in the PRESTIGE Installation manual. Failure to comply could result in severe personal injury, death or substantial property damage.
F3 Fuse Rating
4 - AMP/250V
Slow Acting
for 24V-Low Voltage
Fig. 1 Control Module Fuse Locations (Housing Cover Removed)
F1 Fuse Rating
5 - AMP/250V
Fast Acting
for 120V-High Voltage
120V-High Voltage
Electrical Quick
Control Module
Connect
4
Page 7
Control Module Display - General
Standby Mode
After the boiler is turned on, the control panel will display STANDBY mode as shown in the figure above.
This is the standard mode for the PRESTIGE. The control automatically returns to this mode after 20 minutes if no keys have been pressed on the display. Any parameters that were modified are then enabled.
The first character shows (on the left side of the display) the current status of the boiler depending on the condition of both the boiler and the burner. The last 3 characters indicate the start temperature. See page 8 for additional information.
If the burner is blocked due to a “soft” lockout, the display alternates between a 9 followed by the boiler outlet tem­perature and “b” with a two digit error code. See page 9 ­13 for detailed information on the corrective and preven­tive actions for the soft lockouts.
Display
A
18 18
H L
18
TO TEMPORARY PLACE THE BURNER INTO HIGH FIRE MODE: press the MODE button with + button simul-
taneously and hold for 2 or 3 seconds.
TO TEMPORARY PLACE THE BURNER INTO LOW FIRE MODE: press the MODE button with - button simul-
taneously and hold for 2 or 3 seconds.
NOTICE
The control module will maintain the fixed firing rate for approximately 10 minutes before default­ing to normal operating conditions.
Internal check
0
Test function: Burner on, high fire mode
0
Test function: Burner on, low fire mode
0
S
tb
Boiler function
Y
Display
0
18
1
18 18
2 3
18 18
4
18
5
18
6 7
18 18
8 9
18
b
b
b
b
b
b
b
b
b
b
b
Boiler function
STANDBY, no demand for heat
0
Fan prepurge (10 seconds) or post purge cycle
0
(30 seconds)
Ignition sequence
0
Burner ON for space heating (CH)
0
Burner ON for domestic water heating (DHW)
0
Pre-check for air flow prior to prepurge cycle
0
Burner OFF due to reaching temperature
0
set point Post pump cycle for primary space heating
0
(1 minute) Post pump cycle for domestic hot water
0
(30 seconds)
Burner blocked:
0
Supply temperature too high (203 F) .Burner will remain OFF until outlet temperature drops
8
1
1
2
2
2
2
2 2
3
3
4 5
below 200 F
Return temperature too high (203 F). Burner will remain OFF until return temperature drops
9
below 200 F
Return temperature is measured higher than supply
4
5
6
8
9
0
5
0
2
temperature. Burner will remain OFF
until corrected.
Supply temperature increased too quickly. Burner will remain OFF for a 10 minute period. Burner will recycle, increasing waiting period 1 minute for a max. 15 minutes
Factory supplied LWCO pressure device or external limit (terminals 15 & 16) is OPEN. Burner off for 150 seconds, auto
No blower signal
Blower signal present, Burner will remain OFF until condition terminates
Temperature rise between the supply and return is more than 72 F. Burner will remain OFF for 150 seconds. Burner will recycle increasing wating period 1 minute for a max. 20 cycle.
Short circuit measured across flue temperature sensor terminals.
Open circuit measured across the flue temperature sensors.
Flue temperature greater than 241 F less than 250 F. Burner off for 150 seconds
Burner OFF until corrected.
reset.
Press the + and - button simultaneously to deactivate the high or low fire mode.
b
6
5
Wait for the blower to start
5
Page 8
NF
O
I
Control Module Display - General
o
Parameter Mode
To access PARAMETER mode when the system is in STANDBY mode, press the MODE button once.
To scroll through the list of parameters, simply press the “STEP” button. To modify a parameter value, use the + or
- keys. Then press “STORE” to save the value you just changed. The display flashes once to confirm the data has been saved.
To activate the parameters you changed, press MODE once more (which brings you into the INFORMATION mode). However, if you do not press a key, the system returns to STANDBY mode after 20 minutes and automat­ically enables the changes.
Key:
Display
A
AR
P
MODE
Key:
Screen
STEP
STEP
STEP
STEP
1. 2 3
4
15
.
.
.
1
.
0 0
8
0 1 1
0
P
Pressing MODE once
Description of parameters
Domestic Hot W ater Setting
Dom estic Hot Water Setup (See Note 1)
Space Heating Mode (See Note 2)
Maximum tem perature in space heating (CH) m ode. In applications using an outdoor sensor, this is the boiler target temperature at an outd temperature of 0 F or less.
AR
A
Information Mode
To switch from STANDBY mode to INFORMATION mode, press MODE twice.
Press STEP until the system displays the information you need. The point located behind the first position flashes to indicate that the boiler is in INFO mode.
Key:
Display
Pressing MODE once
A
AR
P
MODE
Pressing MODE twice
O
NF
I
MODE
Key:
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Display
1.
18
2
1
-
3
.
4
.
5.
15
6.
18
7
.
8
.
9
.
6 2 5
0
Description of parameters Measured outlet (supply) water
0
temperature
Measured inlet (return) water
0
temperature
This parameter is not used (Note 3)
2
Measured outdoor temperature
5
(Optional outdoor sensor required)
Measured flue temperature
0
Calculated (target) outlet water
0
temperature Rate of increase in the outlet water
1
temperature F/sec
Rate of increase in the return water
1
temperature F/sec
This parameter is not used (Note 3)
0
Note 1: The factory setting of this parameter is 01, which is the ON setting for domestic hot water. To turn the domestic ON or OFF press and hold the “-” button, while in the STBY (standby) mode until the display shows the desired setting “dOFF” or ‘d---” and than release. Where “---” is the temperature set point and the ON position.
Note 2: The factory setting of this parameter is 01, which is the ON setting for space heating. To turn the space heating ON or OFF press and hold the “+” button, while in the STBY (standby) mode until the display shows the desired setting “cOFF” or “c---” and than release. Where “-
--” is the temperature set point and the ON position.
NOTICE
If Parameter 2 and/or Parameter 3 is adjusted to a set­ting of “00” or “02” the burner will not respond when a call for heat is indicated.
If STEP is pressed after parameter 9, the display will show A-22.
Note 3: Parameter 3 will display the measured storage domestic temperature of an IDWH when an optional IDWH sensor is utilized. Parameter 9 will display the rate of increase in the domestic storage temperature ºF/sec.
6
Page 9
Control Module Display - General
Gas valve harness not properly connected
Failed ignition after 5 attempts
Power supply lost after lockout occured
Internal control failure
Internal control failure
E E
0
2 03 0
4
0
8 0
9
E E
E
Display
Hard Lockout
Internal control failure
0
5
E
Internal control failure
0
6
E
Internal control failure
0
7
E
Flame detected prior to burner startup
E
0
0
Internal control failure
External limit (terminal 13 & 14) control is OPEN
Blower signal does not reset to zero
No blower signal present
Supply temperature sensor is short circuited
1
1 1
2
1
5 1
6
2
9
2
8
E
E E
E E
E
Flue temperature exceeds 250 F
5
2
E
Internal Control error - failure to read parameters
6
1
E
Return temperature is short circuited
Supply temperature sensor is OPEN
Return temperature sensor is OPEN
Internal control failure
Internal control failure
Inadequate power supply to the fan
E E
3
1 32 3
6 3
7 4
4
60
6
5
E E E
E E
Return temperature exceeds 212 F
Supply temperature increased too rapidly
Internal control failure
Internal control failure
Internal control failure
Internal control failure
Internal control failure
1
7
1
9 2
5
1
3
E
E E
E
Supply Temperature exceeds 212 F
1
8
E
E
1
4
Error Hard Lockout Mode
If a fault occurs while the boiler is running, the system goes into lockout and the display starts to flash with the first digit as an E and the next two digits give the code for this fault. For detailed information on the corrective and preventive actions for the hard lockout, see pages 14-19.
7
Page 10
Prestige Control Module Display
Boiler control display is blank
- Check for 120 volts at terminals 1 and 2 of the 120V terminal strip
If no power is measured check the external power supply, external fuse or breaker.
- Check the internal fuse F1 by locating the control module and removing the black housing. The internal fuse F1 is located in the right corner of the control module near the 120V high voltage electrical quick connect on the control as shown in Fig. 1, page 4. 120 volts should be measured across the fuse. See Servicing Tips and Instructions, page 3, for accessing the internal fuses of the control module.
If fuse F1 has blown and 120 volts is not present, replace the fuse with a 5-amp/250V fast acting fuse. Check
the wiring for possible causes for the fuse to blow.
- Check external wiring at 120V terminal strip and boiler internal wiring, ensure all wiring is properly connected, in good condition and all control module and boiler connections are secure.
Correct/replace any mis-wiring or wiring components if needed. If problem continues replace the control module.
Boiler display shows UI.25
- Check transformer connections
- Check the internal fuse F3 by locating the control module and removing the black housing. The internal fuse F3 is located in the center of the control module as shown in Fig. 1 page 4.
See servicing tips and instructions, page 3, for accessing the internal fuses of the control module.
If fuse F3 has blown, replace the fuse with a 4-amp/250V slow acting fuse. Check external boiler wiring for
exteral source of 24V backfeed.
Boiler display shows a 0 for the first digit on the left followed by 2 or 3 digits (boiler tem­perature)
- Check to see if room and DHW thermostats are satisfied.
If the thermostats are satisfied the boiler is off due to no call for heat. Turn up a thermostat and the boiler should
begin ignition sequence.
- If the room thermostat or DHW thermostat is calling for heat and the boiler is not firing and the boiler is below the maximum operating temperature.
Check and verify Parameters 2 and 3 are correct as outlined on page 6. Both parameters should be set as
01”, which turns DHW and CH modes ON.
Temporarily jump low voltage terminals 7 and 8 on the 24V terminal strip. If boiler operates check the room
thermostat wiring and thermostat control. Replace as needed. Remove jumper when completed.
Temporarily jump low voltage terminals 11 and 12 on the 24V terminal strip. If boiler operates check the DHW
thermostat wiring and thermostat control. Replace as needed. Remove jumper when completed.
Disconnect power to the boiler. Check all wiring and wiring connections and compare to the wiring diagram.
Ensure all wiring and wiring connection are in good condition and secure. If necessary, replace complete wiring harness.
Check for 24 volts across the control module internal fuse F3, which is located toward the middle of the con-
trol and positioned vertically see Fig. 1 page 4. If necessary replace the fuse. See Serving Tips and Instructions, page 3, for accessing the internal fuses of the control module.
If all the above steps fail to resolve the problem, replace the control module.
Boiler display shows a number of 1 to 8 for the first digit on the left followed by 2 or 3 dig­its (boiler temperature)
- The boiler is in normal operating mode. Reference the boiler installation manual for detailed explanation of the boiler operation.
8
Page 11
Soft Lockout Error Code
The boiler will display Soft Lockouts with a flashing “9”, then “b” as the first digit on the left of the display followed by a steady two digit code. The boiler will automatically reset a Soft Lockout once the condition has been corrected and returned to standard operating condition.
Code
b- 18
Error Condition
High Temperature Limit, Boiler Supply
Correcting Error Condition
If the primary boiler supply water temperature exceeds 202ºF, the burner will shut down until the supply temperature drops below 200ºF. The boiler circula­tor will continue operating.
This problem should only occur if the heat load demand is less than the low input-firing rate of the boiler, typically found on small single heat zones and there is a potential flow issue.
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Prestige Installation Manual or per other approved/recognized designed configurations.
Use a temperature-metering device to measure the supply water tem­perature leaving the boiler. Compare this measured temperature with the display temperature (INFO Mode display, “1” is the first digit on the left followed by the temperature.)
- Replace the supply temperature sensor if the temperature com­parison is largely varied by more than 10ºF.
- Replace the control module if the sensor replacement does not resolve the problem.
b- 19
High Temperature Limit, Boiler Return
Ensure system and/or zone circulators are operating properly
If the primary boiler return water temperature exceeds 202ºF, the burner will
shut down until the return temperature drops below 200ºF. The boiler circula­tor will continue operating.
This problem rarely occurs unless the boiler experiences an Error Code 18 and the system is charged with a water temperature in excess of 202ºF
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Prestige Installation Manual or per other approved/recognized designed configurations.
- Ensure the boiler piping is correct and the water flow is not reversed or pipes are cross connected.
Use a temperature-metering device to measure the return water tem­perature entering the boiler. Compare this measured temperature with the display temperature (INFO Mode display, “2” is the first digit on the left followed by the temperature.)
- Replace the return temperature sensor if the temperature com­parison is largely varied by more than 10ºF.
- Replace the control module if the sensor replacement does not resolve the problem.
9
Page 12
Soft Lockout Error Code
Code
b- 24
Error Condition
High Temperature Limit, Boiler Supply and Return
Correcting Error Condition
If the primary boiler return water temperature exceeds the boiler supply temper­ature, the burner will shut down until the boiler return temperature drops below the boiler supply temperature. The boiler circulator will continue operating.
The following items should be checked:.
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Prestige Installation Manual or per other approved/recognized designed configurations.
- Ensure the boiler piping is correct and the water flow is not reversed or pipes are cross connected.
Use a temperature-metering device to measure the supply water tem­perature leaving the boiler. Compare this measured temperature with the display temperature (INFO Mode display, “1” is the first digit fol­lowed by the temperature.)
- Replace the supply temperature sensor if the temperature com­parison is largely varied by more than 10ºF.
Use a temperature-metering device to measure the return water tem­perature entering the boiler. Compare this measured temperature with the display temperature (INFO Mode display, “2” is the first digit fol­lowed by the temperature.)
- Replace the return temperature sensor if the temperature compar­ison is largely varied by more than 10ºF.
b- 25
High Temperature Limit, Boiler Supply
Replace the control module if the sensor replacement does not resolve the problem.
If the primary boiler supply water temperature rate of increase is deemed too quick, the burner will shut down for a 10 minute period. If the condition is not corrected during the next cycle, the burner shut down period of 10 minutes will increase an additional minute. The boiler will continue for 5 cycles until a “hard” lockout will occur.
This problem will occur if the flow rate on the boiler is too low or if there is no flow. Check for the following conditions:
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Installation Manual or per other approved/recognized designed configurations.
Verify and ensure the boiler space heating CH circulator is operating properly.
- Check and verify 120V at the circulator wiring in the circulator junc­tion box. If no voltage is measured, check circulator wiring and connections.
- Check and verify 120V at the MCBA control module along termi­nals X1-4 and X1-3. If no voltage is measured, replace control module. Check circulator wire harness and replace if needed if voltage is measured at the control module.
10
Page 13
Soft Lockout Error Code
Code
b- 25
b- 26
Error Condition
High Temperature Limit, Boiler Supply (continued)
LWCO Device
Correcting Error Condition
Verify and ensure the external DHW circulator is operating properly.
- Check and verify 120V at the circulator wiring in the circulator junction box. If no voltage is measured, check circulator wiring and connections.
- Check and verify 120V at the 120V terminal strip, terminals 4 and 5 inside the boiler enclosure. Check circulator wire harness and replace if needed if voltage is measured at the control module.
Verify pump is properly sized for the flow rate required based on the head loss of the system. Reference the installation manual for pump curves and boiler pressure drop. Consult the circulator manufacturer for additional pump curve data or for assistance in sizing a circulator properly.
If the LWCO device is determined to be open by the control module the boiler will remain in a shut down mode until the condition is cor­rected. Once the condition is corrected the boiler will remain in the shut down mode for an additional 150 seconds before startup.
- Check the pressure gauge on the boiler and ensure the system is at minimum 10 psig.
- Ensure proper operation of the boiler make up system and fill valve.
Check continuity across the LWCO terminals for closed contacts if the boiler system pressure gauge reads 10 psig or greater.
- Replace the LWCO device if the continuity shows an open circuit and the system pressure is 10 psig or greater.
- Check the wiring and contacts from the LWCO to the control mod- ule terminals if the continuity check shows a close circuit. Replace the low voltage wiring harness if needed.
- Replace control module if the replacement of the wiring harness does not resolve the problem.
b- 28
b- 29
Blower Assembly
Blower Assembly
Will occur if during the ignition sequence the blower does not start. The boiler display will indicate a status code of 5 during the ignition sequence.
Disconnect the connector at the blower. Restart the boiler sequence and check for 35Vdc at the connector between the black and white wires (pin 1 & 5).
- If 35Vdc is not present at the connector, inspect the wiring har­ness and replace if necessary. Replace the control module if wire harness replacement does not resolve the problem.
-- If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure a secure connection. Replace the blow­er assembly if problem is not resolved.
The control module is detecting the blower in operation when it should not be.
Check and verify the wiring from the blower to the control module is correct as shown in the appliance wiring schematic, page 22 and 23.
- Replace the wiring harness from the control module to the blower. Replace the blower if the replacement of the wiring harness does not resolve the problem. Replace control module if blower replacement does not resolve the problem.
11
Page 14
Soft Lockout Error Code
Code
b- 30
Error Condition
High Temperature Limit, Boiler Supply and Return Temperature Differential is greater than 72ºF
Correcting Error Condition
If the primary boiler water temperature differential between the supply and the return is too high (greater than 72ºF), the burner will shut down for a 150 sec­ond period. The circulator will continue circulating until the start of the next cycle. If the condition is not corrected during the next cycle, the burner shut down period of 150 seconds will increase an additional minute. The boiler will continue for 22 cycles until a “hard “ lockout will occur.
This problem will occur if the flow rate and demand on the boiler is too low. Check for the following conditions:
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Installation Manual or per other approved/recognized designed configurations.
- Ensure the piping system pressure drop is within the flow rate parameters of the circulator.
Verify and ensure the boiler space heating CH circulator is operating properly.
- Check and verify 120V at the circulator wiring in the circulator junction box. If no voltage is measured, check circulator wiring and connections.
- Check and verify 120V at the MCBA control module along termi­nals X1-4 and X1-3, see page 22. If no voltage is measured, replace control module. Check circulator wire harness and replace if needed if voltage is measured at the control module.
b- 35
Flue Temperature Sensor
Verify and ensure the external DHW circulator is operating properly.
- Check and verify 120V at the circulator wiring in the circulator junction box. If no voltage is measured, check circulator wiring and connections.
- Check and verify 120V at the 120V terminal strip between termi­nals 4 and 5 inside the boiler enclosure. Check circulator wire harness and replace if needed if voltage is measured at the con­trol module.
The control module detects a short or jumped out condition of the flue tem­perature sensor. This code will also appear briefly prior to a “hard” lockout if the flue gas temperature exceeds 250ºF. The burner will remain off until the condition is corrected.
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
12
Page 15
Soft Lockout Error Code
Code
b- 40
b- 52
Error Condition
Flue Temperature Sensor
Flue Temperature Sensor
Correcting Error Condition
The control module detects the flue temperature sensor as “open”, which is typically an improper or missing connection at the sensor.
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
The control module detects the flue temperature greater than 241ºF, less than 250ºF. Burner off for 150 seconds.
This is an indication the heat exchanger flue ways may need clean­ing. Reference the Maintenance section of the installation manual for procedures on cleaning the flue side of the heat exchanger.
Isolate the boiler from the boiler system piping and drain the boiler heat exchanger. Flush the boiler heat exchanger several times, checking the discharge water for signs of scale or sediment.
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
b- 65
Blower Assembly
The control module does not detect proper blower operation during a call for heat.
Disconnect the 35Vdc connector at the blower. Restart the boiler sequence and check for 35Vdc at the connector between the black and white wires (pin 1 & 5).
- If 135Vdc is not present at the connector, inspect the wiring har­ness and replace if necessary. Replace the control module if the wire harness replacement does not resolve the problem.
- If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure a secure connection. Replace the blow­er assembly if problem is not resolved.
13
Page 16
Hard Lockout Error Code
The boiler will display a Hard Lockout with an E as the first digit on the left of display followed by a two-digit code. The boiler must be manually reset by pressing the RESET button on the display once the condition has been corrected. A Hard Lockout will occur when boiler conditions, that are considered critical in terms of safety, are not met or exceeded.
Code
E- 00
E- 02
Error Condition
Flame Detection Error
Failed Ignition Error
Correcting Error Condition
This error will occur if the control module detects a burner flame (flame signal) prior to the ignition sequence.
This problem maybe related to the burner operating too hot due to poor combustion. The flame pattern and combustion should be test­ed at both high fire and low fire inputs. The flame should be com­pletely on the burner head and blue without yellow tips during high fire. Reference page 5 regarding high and low fire input procedures. Reference page 20 for combustion requirements.
- If the flame is not deemed acceptable and the application is propane, check and verify the propane orifice for proper size (ref­erence page 20 for orifice sizes). Ensure the propane orifice is properly seated in the gas valve gasket.
Inspect the burner head through the burner sight port during shut down sequence of the boiler.
- If the flame remains after the shut down sequence, the gas valve maybe leaking. Check and verify the gas pressure is less than 13 inches w.c. If the gas pressure is less than 13 inches w.c., replace the gas valve.
This error will occur if the boiler has failed to establish flame detection during the ignition sequence. The lockout will occur after 5 tries.
If no ignition spark occurs during the ignition sequence:
- Check the ignition electrode cable, the electrode boot connector and all connections, ensure all are in good condition. Replace if damaged.
- Inspect the insulation of the electrode cable and the electrode igniter; ensure there is no damage. Replace as needed.
- Check the ground lead for a secure connection from the control module ground to the burner mounting plate. Use a ground con­tinuity check to verify a good ground.
If there is an ignition spark during the ignition sequence, but no flame:
- Verify the manual shutoff valve on the gas supply piping is in the OPEN position.
- Check and verify the gas pressure at the inlet of the valve during ignition sequence. Ensure the gas pressure maintains a mini­mum 5 inches w.c during ignition sequence. Note: All gas appli­ances within the building should be operating during this meas­urement.
- Check and verify all gas piping is free of obstructions and has been purged of all air.
- Check the gas meter for indications of gas flow during the ignition sequence.
- Remove the ignition electrode to inspect for damage. Clean any white oxides off the electrode if necessary. Replace the electrode if damaged or will not clean.
- Replace the gas valve rectifier cable.
- Remove and inspect the gas valve and venturi gas ports. Ensure ports are free of obstructions.
14
Page 17
Hard Lockout Error Code
Code
E- 02
Error Condition
Failed Ignition Error (continued)
Correcting Error Condition
- If the above items have been completed and verified, replace the gas valve.
Flame is established during the ignition sequence, but not maintained. This problem may be due to low flame signal detection by the control module.
- Inspect the flame pattern on the burner head during high and low fire inputs. Inspect and clean the burner head if necessary. Replace the burner head if damage. Reference page 5 regarding high and low fire input procedures.
- Check the input rate of the boiler at the gas meter during high fire input. If the gas meter measured rate is not at or below 15% of the boiler rating, replace the gas valve.
Note: The length of venting and combustion air piping will affect the
measure boiler rating.
- Check the ground lead for a secure connection from the control module ground to the burner mounting plate. Use a ground con­tinuity check to verify a good ground.
- Remove the ignition electrode to inspect for damage. Clean any white oxides off the electrode if necessary. Replace the electrode if damaged or will not clean.
- If the above items have been completed and verified, replace the control module.
E- 03
E- 04
E- 05
E- 06
E- 07
Gas Valve Harness
Loss of Power
Internal Failure
Internal Failure
Internal Failure
Ensure gas valve rectifier cable is properly connected to the gas valve and secured.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the rectifier cable.
This error will occur if power to the boiler is lost after a lockout has occurred. The boiler must be manually reset and the original lockout code will be lost.
This error will also occur if the service technician tries to reset a hard lockout by turning the boiler OFF and then ON as an attempt to reset the boiler.
Verify polarity and proper ground on incoming 120V power connections
This error may occur in rare cases if there is power interruption, surge or “Dirty” voltage. An uninterruptible power supply may be installed on the incoming voltage to the boiler.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
E- 08
E- 09
Internal Failure
Internal Failure
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
15
Page 18
Hard Lockout Error Code
Code
E- 11
E- 12
E- 13
E- 14
E- 15
Error Condition
Internal Failure
External Limit Lockout
Internal Failure
Internal Failure
Internal Failure
Correcting Error Condition
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
An external limit control connected at the 24V terminal strip, between terminals 13 and 14 is open, breaking the circuit. Determine reason for the limit to be open and correct condition.
- If no external limit is used, then check and verify connection of the factory applied jumper across terminals 13 and 14.
- If the external limit is closed, then check the boiler internal wiring connections and repair or replace if necessary. Remove the exter­nal limit and apply a temporary jumper across terminals 13 and 14 and verify operation.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
E- 16
E- 17
E- 18
Internal Failure
Internal Failure
High Temperature Limit, Supply Temperature
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
This error will occur if the boiler supply water temperature exceeds 212ºF.
The following items should be checked:.
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Installation Manual or per other approved/recognized designed configurations.
Use a temperature-metering device to measure the supply water tem­perature leaving the boiler. Compare this measured temperature with the display temperature (INFO Mode display, “1” is the first digit fol­lowed by the temperature.)
- Replace the supply temperature sensor if the temperature com­parison is largely varied by more than 10ºF.
- Replace the control module if the sensor replacement does not resolve the problem.
16
Page 19
Hard Lockout Error Code
Code
E- 19
Error Condition
High Temperature Limit, Return Temperature
Correcting Error Condition
This error will occur if the boiler return water temperature exceeds 212ºF.
This problem rarely occurs unless the boiler experiences an Error Code 18 and the system is charged with a water temperature in excess of 212ºF. The following items should be checked:
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Installation Manual or per other approved/recognized designed configurations.
- Ensure the boiler piping is correct and the water flow is not reversed or pipes are cross-connected.
Use a temperature-metering device to measure the return water tem­perature leaving the boiler. Compare this measured temperature with the display temperature (INFO Mode display, “2” is the first digit fol­lowed by the temperature.)
- Replace the return temperature sensor if the temperature compar­ison is largely variedby more than 10ºF.
- Replace the control module if the sensor replacement does not resolve the problem.
E- 25
High Temperature Limit, Supply Temperature rate of increase
This error will occur if the boiler supply water temperature rate of increase is deemed too rapid. The control module will display a soft lockout of b_25 and initiate a recycle sequence. After 5 cycles the boiler will go into a hard lockout.
This problem will occur if the flow rate and demand load on the boiler are too low. Check for the following conditions:
- Verify the boiler and heating system are filled with water and the LWCO is operating properly.
- Ensure the boiler and heating system have been properly purged and there is no entrapped air.
- Inspect and verify heating system piping and its components. Ensure piping is per the recommendations given in the Installation Manual or per other approved/recognized designed configurations.
Verify and ensure the boiler central heating CH circulator is operating properly.
- Check and verify 120V at the circulator wiring in the circulator junc­tion box. If no voltage is measured, check circulator wiring and connections.
- Check and verify 120V at the MCBA control module along termi­nals X1-4 and X1-3. If no voltage is measured, replace control module. Check circulator wire harness and replace if needed if voltage is measured at the control module.
Verify and ensure the external DHW circulator is operating properly.
- Check and verify 120V at the circulator wiring in the circulator junc­tion box. If no voltage is measured, check circulator wiring and connections.
- Check and verify 120V at the 120V terminal strip between termi­nals 4 and 5 inside the boiler enclosure. Check circulator wire har­ness and replace if needed, if voltage is measured at the control module.
17
Page 20
re rate
,
Hard Lockout Error Code
Code
E- 25
E- 28
Error Condition
High Temperature Limit, Supply Temperature rate of increase
Blower Assembly
Blower AssemblyE- 29
Correcting Error Condition
Verify pump is properly sized for the flow rate required based on the head loss of the system. Reference the installation manual for pump curves and boiler pressure drops. Consult the circulator manufacturer for additional pump curve data or for assistance in sizing a circulator properly.
This error will occur if during the ignition sequence the blower does not start. The boiler display will indicate a status code of 5 during the ignition sequence for 4 minutes before locking out.
Disconnect the connector at the blower. Restart the boiler sequence and check for 35Vdc at the connector between the black and white wires (pin 1& 5).
- If 35Vdc is not present at the connector, inspect the wiring harness and replace if necessary. Replace the control module if wire har­ness replacement does not resolve the problem.
- If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure a secure connection. Replace the blower assembly if problem is not resolved.
The control module is detecting the blower in operation when it should not be.
Check and verify the wiring from the blower to the control module is correct as shown in the appliance wiring schematic, page 22.
- Replace the wiring harness from the control module to the blower. Replace the blower if the replacement of the wiring harness does not resolve the problem. Replace control module if blower replace­ment does not resolve the problem.
E- 31
E- 32
E- 36
Boiler Supply Temperature sensor
Boiler Return Temperature sensor
Boiler Supply Temperature sensor
The control module detects a short or jumped out condition of the boiler supply (outlet) temperature sensor.
Inspect the boiler supply temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
The control module detects a short or jumped out condition of the boiler return (inlet) temperature sensor.
Inspect the boiler return temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
The control module detects the boiler supply (outlet) temperature sensor as an open circuit.
Inspect the boiler supply temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
18
Page 21
Hard Lockout Error Code
Code
E- 37
E- 52
Error Condition
Boiler Return Temperature sensor
Internal FailureE- 44
Flue Temperature Sensor
Correcting Error Condition
The control module detects the boiler return (inlet) temperature sensor as an open circuit.
Inspect the boiler return temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replacement of sensor and wiring does not resolve the problem, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
The control module detects the flue temperature exceeding the 250ºF limitation of the boiler.
• This is an indication the heat exchanger flue ways may need cleaning. Reference the Maintenance section of the installation manual for procedures on cleaning the flue side of the heat exchanger.
• Isolate the boiler from the boiler system piping and drain the boiler heat exchanger. Flush the boiler heat exchanger several times, checking the discharge water for signs of scale or sediment.
• Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition, replace as needed.
- Replace the sensor and wiring if problem persists. If replace­ment of sensor and wiring does not resolve the problem, replace the control module.
E- 60
E- 61
E- 65
Internal Failure
Internal Failure
Blower Assembly
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
Reset the boiler control module and retry ignition sequence and boiler opera­tion. If problem continues, replace the control module.
The control module does not detect proper blower operation during a call for heat.
Disconnect the 35V dc connector at the blower. Restart the boiler sequence and check for 35Vdc at the connector between the black and white wires (pin 1 & 5).
- If 35Vdc is not present at the connector, inspect the wiring harness and replace if necessary. Replace the control module if the wire harness replacement does not resolve the problem.
- If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure a secure connection. Replace the blower assembly if problem is not resolved.
19
Page 22
Combustion Test / Settings
WARNING
The installation and startup of the PRESTIGE should be performed by a qualified installer / service technician. The startup procedures should include a complete combustion test. The complete combustion test must also be performed after any adjustments to the factory settings on the burner. Failure to comply with these require- ments can result in severe personal injury, death or substantial property damage.
Combustion Test Guidelines
The combustion test should be conducted using an electronic combustion analyzer or at a minimum a “Fyrite” type CO2 analyzer.
The combustion test sample can be taken from the test port located on the vent adapter of the PRESTIGE.
Ensure the vent and combustion air piping are completely installed prior to startup and conducting a combus­tion test.
The combustion test should be conducted, at a minimum, when the unit is at high fire input.
Combustion Parameters
Natural Gas Propane
O2 Min 2.30% 2.70% O2 Max. 5.30% 4.70%
CO2 Min 8.80% 10.70% CO2 Max 10.50% 12.00% CO Max 100 ppm 100 ppm
Propane Orifices
Model Orifice Size
Solo 110 0.204#52 Solo 175 0.221#56
Solo 250 0.250#64
20
Page 23
Combustion Test / Settings
Combustion Adjustment
WARNING
To pe rform the following procedure it is essential the service technician reads and follows the procedures closely. After any adjustments are completed it is essential to perform a combustion check before proceeding with further steps. Failure to comply with these procedures can result in personal injury, death or substantial property damage.
If the O2 level measured during the combustion test is below 2.3% for natural or 2.7% for propane:
OR
If the CO2 level measured during the combustion test is above 10.5% for natural or 12.0% for propane:
Adjust the gas valve throttle screw, a brass screw within a sleeve located on the upper portion of the venturi as follows:
1. Ensure the PRESTIGE is OFF and no “calls for heat” are initiated.
2. Using a flat head screwdriver, turn the throttle screw clockwise (inward) a 1/ note the initial start point of the screw prior to any adjustments.
3. Place the PRESTIGE back into service and conduct a combustion test.
4. If necessary, repeat the adjustment steps until the desired combustion level is met. NEVER adjust the throttle screw more than full turns from its initial start point.
4 of a full turn. It is important to
WARNING
Adjusting the throttle screw clockwise (inward) decreases the volume of gas injected into the burner. Adjustments beyond 2 full turns clockwise will greatly affect the operation of the burner and result in unstable combustion conditions.
WARNING
DO NOT adjust the throttle screw counter-clockwise beyond the initial factory set point. Adjustments counter- clockwise beyond the factory set point will increase the volume of gas injected into the burner, sible unstable combustion conditions and potential dangerous levels of CO.
resulting in pos-
21
Page 24
Internal Wiring
Note:
- If any of the original wire as supplied with
the appliance must be replaced, it must be
replaced with type T wire or it’s equivalent.
- The wiring for 120V field connections to the
boiler shall have a minimum size of 14 AWG
and a temperataure rating of at least 190 F
(90 C).
BK - Black
Wire Color Code
Fig. 2: Prestige SOLO 110 Boiler Factory Wiring
W-White
G-Green
BL -Blue
R-Red
O - Orange
V - Violet
Y-Yellow
BR - Brown
1 - Incoming Supply L
2 - Incoming Supply N
3 - Incoming Supply G
4 - DHW Circulator L
5 - DHW Circulator N
120V WireTerminal Key
6 - DHW Circulator G
7 - Thermostat (T-T)
8 - Thermostat (T-T)
9-Outdoor Sensor
10 - Outdoor Sensor
11 - D HW T her most at
12 - DHW Thermostat
13 - External Limit - Manual Reset
14 - External Limit - Manual Reset
24V WireTerminal Key
15 - External Limit - Auto Reset
16 - External Limit - Auto Reset
17 - 0-10v Input Controller
19 - Flame Signal
18 - 0-10v Input Controller
22
Page 25
Internal Wiring
Fig. 3: Prestige SOLO 175 and Solo 250 Boiler Factory Wiring
23
Page 26
Replacement Parts
9
8
7
6
5
2
4
1
7
Fig. 4: Prestige Jacket Components
Item Part No. Description
1 PSRKT21 Wall Mounting Bracket with Hardware
2 PSCS01 Display/Control Panel
3 PSJKT01B Connection Flange Panel - Solo 110
4
5 PSJKT01F Front Jacket Panel
6
7 PSJKT01S Side Jacket Panel (Left or Right)
8
9
10 PSJKT03 Control Cover Panel
2
10
PSJKT02B Base Panel - Solo 110
PSJKT03B Base Panel - Solo 175 & 250
PSJKT01R Rear Jacket Panel - Solo 110
PSJKT02R Rear Jacket Panel - Solo 175 & 250
PSJKT01T Top Jacket Panel - Front - Solo 110
PSJKT03T Top Jacket Panel - Front - Solo 175 & 250
PSJKT02T Top Jacket Panel - Access - Solo 110
PSJKT04T Top Jacket Panel - Access - Solo 175 & 250
3
24
Page 27
Replacement Parts
2
4
1
4
3
9
10
11
5
7
6
Fig. 5: Prestige Solo 110 Internal Components
Item Part No. Description
1 PSRKIT01 Heat Exchanger Body
2 PSRKIT02 Vent Outlet Adapter
3 PSRKIT03 Combustion Air Inlet Adapter
4 PSRKIT04 NTC Sensor (NTC1, NTC2 and NTC5)
5 PGRKIT20 LWCO Pressure Device
6 PSRKIT05 Condensate Drain Assembly
7 PSRKIT06 Boiler Piping - Return Assembly
8 PSRKIT07 Boiler Piping - Supply Short Assembly
9 PSRKIT08 Boiler Piping - Supply Long Assembly
10 HMVCIR02 Circulator
8
11 -- Pressure Gauge Fitting
25
Page 28
Replacement Parts
3
2
8
4
1
5
9
6
Fig. 6: Prestige Solo 175/250 Internal Components
Item Part No. Description
PSRKIT25 Heat Exchanger Body SOLO 175
1
PSRKIT26 Heat Exchanger Body SOLO 250
2 PSRKIT27 Vent Outlet Adapter
3 PSRKIT03 Combustion Air Inlet Adapter
4 PSRKIT04 NTC Sensor (NTC1, NTC2 and NTC5)
5 PGRKIT20 LWCO Pressure Device
6 PSRKIT05 Condensate Drain Assembly
7 PSRKIT28 Boiler Piping - Return Assembly
8 PSRKIT29 Boiler Piping - Supply
9 -- Pressure Gauge Fitting
4
4
7
26
Page 29
Replacement Parts
7
8
9
6
5
4
3
2
Fig. 7: Prestige Burner Components
Item Part No. Description
1
2
3
4 PSRKIT13 Blower with Gasket
5 PGRKIT01 Gas Valve
6 -- Venturi
7 PSRKIT14 Ignition Cable
8 PSRKIT15 Igniter with Gasket
9 PSRKIT16 Sight Glass Assembly (Glass, Gasket and Bracket)
10 -- Propane Orifice - Not Shown
11 -- Burner Plate Gasket - Not Shown
12 PGRKIT15 Gas Valve Rectifier Plug - Not Shown
1
PSRKIT09
Combustion Chamber Insulation - Solo 110
PSRKIT30 Combustion Chamber Insulation - Solo 175 & 250
PSRKIT10 Burner Head with Gasket - Natural - Solo 110
PSRKIT11 Burner Head with Gasket - Propane - Solo 110
PSRKIT31 Burner Head with Gasket - Natural / Propane - Solo 175& 250
PSRKIT12 Burner Plate - Solo 110
PSRKIT32 Burner Plate - Solo 175 & 250
27
Page 30
Replacement Parts
1
3
2
Fig. 8: Prestige Electronic Components
Item Part No. Description
1 PSRKIT18 Prestige Control Module
2 PSRKIT19 Transformer with Surge Protection
3 PSRKIT20 Prestige Control Module Display
4 PSRKIT17 Pressure Gauge - Not shown
28
Page 31
Notes
For additional Technical Assistance Contact:
Triangle Tube Engineering Department
Tel: (856) 228-8881
Fax: (856) 228-3584
E-mail: Eng@TriangleTube.com
29
Page 32
Additional quality water heating equipment available from Triangle Tube/Phase III
Heat Master Commercial Water Heaters
- Stainless steel construction
- Oil and Gas fired
- A unique design that eliminates the problem of scaling found with traditional water heaters
- Inputs ranging from 165,000 BTU/hr to 390,000 BTU/hr
- Capable of 180º continuous production
- 5 year non-prorated warranty
Delta ELITE & PERFORMANCE Combination Heaters
- Heat and hot water in one footprint
- Up to 292 gph domestic hot water
- Completely piped and wired from the factory
- Zero clearance to combustibles
- Available in direct vent
- Limited LIFETIME warranty
- Exclusive “tank-in-tank” design
Phase III Indirect Fired Water Heaters
- Exclusive “tank-in-tank” design
- Stainless steel construction
- Available in 8 sizes and 2 models
- Limited LIFETIME residential warranty
- 15 year limited commercial warranty
- Self cleaning/self descaling design
Maxi-flo Pool and Spa Heat Exchangers
- Construction of high quality corrosion resistant stainless steel (AISI 316)
- Specially designed built-in flow restrictor to assure maximum heat exchange
- Compact and light weight
- Available in 5 sizes that can accommodate any size pool or spa
Freeway Center - 1 Triangle Lane Blackwood, NJ 08012 Tel: (856) 228 8881 - Fax: (856) 228 3584
E-mail: Sales@triangletube.com
Member of
Group
Loading...