Kit Part Number
Kit numbers vary based on boiler size. Additional differ­ences are needed at higher altitudes. Use the table be­low to confirm the correct replacement kit is installed on the boiler.
(0 - 5,000 ft)
PA 80 PARKIT141 PARKIT151
PA 110 PARKIT142 PARKIT152
PA Excellence PARKIT142 PARKIT152
PA 155 PARKIT143 PARKIT153
PA 175 PARKIT144 PARKIT154
PA 250 PARKIT145 PARKIT155
PA 299 V2* PARKIT146 PARKIT156
PA 399 V2* PARKIT147 PARKIT157
PA 299 V1* PARKIT148 PARKIT158
PA 399 V1* PARKIT149 PARKIT159
Table 1 - Kit Numbers
*See paragraph 1.1 for more details.
Hi Altitude (5,000 + ft)
!
DANGER
Indicates the presence of a hazardous situa­tion which, if ignored, will result in substantial property damage, serious injury, or death.
WARNING
!
Indicates a potentially hazardous situation which, if ignored, can result in serious injury or substantial property damage.
NOTICE
Indicates special instructions on installation, opera­tion or maintenance, which are important to equip­ment but not related to personal injury hazards.
1.1. V1 and V2 PA299 and PA399 Boilers
There are two different blower/venturi arrangements that result in two different required ignition kits. The separate blower and venturi (V2) configuration ap­plies to PA299s and PA399 with serial numbers after PA11700. Units with serial numbers below PA117000 have a single piece blower venturi (V1). Some V1 models may have been converted to the V2 config-
uration as well.
Before installing the ignition kit, confirm your blow­er/venturi configuration. See Engineering Bulletin
dated Oct. 24, 2018 for more information.
WARNING
!
Installation of the wrong replacement kit will cause the improper operation of the boiler re­sulting in substantial property damage, serious
injury, or death.
Revision Date: 5/16/2019 2019-12 Prestige Igniter Replc.
1.2. Purpose
This kit (see Fig. 1 for details) replaces the existing ignit­er and its wiring, as well as the printed circuit board and the front cover of the control box on all Prestige boilers .
NOTICE
This modification disables the Alarm Relay function which is used in several system con­figurations. Therefore, to allow the heating sys­tem configuration to be operational, some wire connections must be modified and some CTRL­Max settings changed, as required. Please refer
to paragraph 1.6 for more information.
1
Page 2
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
Bk. Black Br. Brown R. Red V. Violet W. White Gr. Green
1
2
V
3
Gr
Br
W
Bk
5
F00
123456
123
P13
P14
5AT Fuse
5AT Fuse
5AT Fuse
F01
X5
123
456
X9
X18
X7
X4
X6
123121234123456
4
12
12 3
4
X10
X12
7 8 9 10 11
1 2 3 4 5
12
6
X1
6 7 8 9 10
1 2 3 4 5
X3
8 9 10 11 12
1 2 3 4 5
13
6
14
7
X2
6 7 8 9 10
1 2 3 4 5
X11
4 5 6
1 2 3
X15
3 4
X16
1 2
Fig. 1 - Prestige Solo & Excellence - Ignition Kit
Item Description Qty
Igniter 1
1
2 Bracket, spark generator 1
3
4 Printed circuit board, ACVMax 1
5 Cover, front, control box 1
6 “PB” Sticker, S/N adaptation (not shown) 1
7 Combustion Chamber Insulation/gasket (not shown) 1
2
Screws, igniter 2
Gasket, igniter 1
Spark generator 1
Wiring, spark generator 1
Connector, Fast-on (not illustrated) 2
Page 3
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
1
2
1.3. Initial task
Write down all the appliance settings and the chosen configuration for reference before bringing any change to the appliance. A reference table is provided on the last page of this document.
1.4. Boiler preparation
1.4.1 Required Tools and Material
Flathead and Phillips Screwdriver
Torx 20 Wrench
1.4.2 Combustion Chamber Insulation
1. The Ignition kit is shipped with a new combustion chamber 2in1 insulation/gasket. This may need to be installed with the new ignition kit. Boilers with serial number before those listed in the table below need to be replaced.
Model Serial Number
PA80 PA132660
PA110 PA131779
PA155 PA13163
PA175 PA127120
PA250 PA137281
PA299 PA127280
PA399 PA128691
PA Excellence PA131819
6. Shut off the gas supply to the boiler at the main manual shut off valve.
7. Remove boiler front panel to access the electronic board and the burner (See Fig. 2).
x 3
Fig. 2 - Prestige Solo & Excellence - Front Panel Removal
8. Disconnect the black ignition cable from the front of the electronic box.
9. Open the front cover of the electronic box (See Fig. 3). Discard the cover.
2. If the Prestige serial number is after the listed num­ber above, no change is required to the insulation/ gasket.
3. Refer to the installation manual for installation pro­cedure.
1.4.3 Procedure
4. Turn the boiler off by pressing the power switch
5. Disconnect electrical power at the external electric box
DANGER
Avoid electrical shock by disconnecting the electrical supply prior to performing any operation
on the internal parts of the boiler.
Before any operation on the internal components of the appliance, allow the appliance to cool down to room temperature. Some components
can be very hot.
Failure to comply will result in substantial property
damage, serious injury, or death.
Fig. 3 - Prestige Solo & Excellence - Removal of Control Box
Front Cover
10. Disconnect the igniter wiring from the igniter. Discard.
11. Using the Torx wrench, release two screws and remove the igniter and gasket from the burner mounting plate. Discard all.
NOTICE
If the gasket is stuck on the igniter support, use a flat head tool and release it carefully from the
surface. Be careful not to scratch the surface.
3
Page 4
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
1.5. Kit installation
1.5.1 Required tools and material
Wrench, Torx, 25
Wrench, 10 mm
1.5.2 Installation of Igniter and Spark Generator
1. Install the new igniter, with its new gasket, on the burner mounting plate support (See Fig. 4).
2. Tighten 2 igniter screws by hand, then torque screws between 13 and 18 lbf-in.
NOTICE
Do not exceed the recommended max. torque value for the igniter attachment screws to pre-
vent the igniter stems from distorting.
3. Connect the ignition wire to the spark generator (1). Slide the protection sleeve (2) over the connector (See Fig. 5).
8. Connect the spark generator connector (C) to the new igniter.
C
Fig. 6 - Prestige Solo & Excellence - Spark Generator Installation
B
A
Fig. 4 - Prestige Solo & Excellence - New igniter Installation
4. Remove the blower clamp screw (A). Retain for rein­stallation. (See Fig. 6).
2
1
Fig. 5 - Prestige Solo & Excellence - Ignition Wire Connection
5. Locate the spark generator with bracket (B) on the blower clamp (A), aligning bracket hole with blow-
er clamp hole. (See Fig. 6).
6. Reinstall the blower clamp screw (A) to secure the spark generator bracket to the blower clamp. Torque screw between 62 and 71 lbf-in.
7. Install the igniter cable boot so that the cable is smooth with no sharp bends and doesn’t curl on
itself. See Fig. 7 & Fig. 8.
Fig. 7 - Prestige Solo 155 to 399 - Igniter Kit Installed
OK NO
Fig. 8 - Prestige Solo & Excellence - Igniter Cable Installation
1.5.3 Printed Circuit Board replacement
1. Disconnect violet wire (ionization current return) (See Fig. 13) from circuit board ground connection.
Discard the wire.
2. Disconnect all wire terminals from the board.
3. Remove the circuit board and discard according to
applicable local regulations (See Fig. 9).
4. Install new circuit board, making sure it is secured in
the retaining clips (See Fig. 10).
4
Page 5
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
1
2
2
NEW
Fig. 9 - Prestige Solo & Excellence - Removal of old PCB
F00
123456
12
12 34123
456
123
X12
X9
P14
P13
CLICK
X10
5AT Fuse
5AT Fuse
7 8 9 10 11
1 2 3 4 5
5AT Fuse
12
6
X1
6 7 8 9 10
1 2 3 4 5
X3
8 910 11 12
1 2 3 4 5
13
6
14
7
X2
6 7 8 9 10
1 2 3 4 5
X11
4 5 6
1 2 3
X18
X15
X7X4X6
X5
34
X16
12
123121234123456
NEW
Fig. 10 - Prestige Solo & Excellence - Installation of new PCB
5. Reconnect all wire terminals to the new circuit board terminals, except P14, 1&2 (See Fig. 13).
6. Route the wiring over the top of the control box.
7. Connect the spark generator power supply con­nector to the free receptacle of the P14 terminal
(pins 1&2) of the PCB (See Fig. 14).
1
New connection
location
Fig. 11 - Prestige Solo & Excellence - Installation of new Front Cover
1.5.4 Follow-up Tasks
1. Perform any required configuration change in the wir­ing and CTRLMax setup according to Paragraph 1.6.
2. Reinstall the boiler front panel.
3. On the rating plate of the appliance, cover the “PA” of the Serial Number with the “PB” sticker provid­ed with the kit. This will indicate that the boiler has been upgraded with the ignition kit, for future ref-
erence. See Fig. 12.
PB
Stick here
8. Connect the violet ground wire to the ground con­nection on the PCB, and on the ground lug located
on the igniter bracket (See Fig. 14).
9. Connect the green ground wire from the spark generator to the ground tab located at the bottom
right hand side of the chassis (See Fig. 14).
10. Protect the bare pins of former P14 connector using 2 Fast-on connectors.
11. Route the wiring (unconnected former P14 con-
nector included) in the plastic retaining clip located at the rear of the control box.
12. Install the new control box front cover (See Fig. 11).
13. Connect the brown ionization cable at the front of
the control box (See Fig. 11).
14. Reuse the Control Board box to ship the old control board to Triangle Tube and using the preprinted shipping label.
Fig. 12 - Prestige Solo & Excellence - Rating Plate Correction
1.5.5 Testing
1. Start up the boiler, refer to the Installation Manual of your appliance for the correct procedure and settings.
2. Should hard ignition still occur, please check the condition of the combustion chamber 2-in-1 insu­lation. Refer to the Installation Manual of your ap­pliance for the correct removal procedure. (See Fig. 15 and refer to following step).
3. Replace the combustion chamber 2-in-1 insulation if:
There are released stitches around the igniter location hole (See Fig. 15, Detail B).
The insulation cloth shows frayed areas around the igniter location hole (See Fig. 15Detail A)
Refer to the installation manual of your appliance for part reference and installation procedure.
5
Page 6
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
7 8 9 10 11
1 2 3 4 5
X12
X9
P14
123
4
123
456
P13
123
F00
X10
12
V
W
Bk
56
34 12
5AT Fuse
5AT Fuse
5AT Fuse
7 8 9 10 11
1 2 3 4 5
12
6
X1
X12
X9
P14
123
4
123
456
P13
123
F00
X10
12
V
Gr
Br
GND
56 34
12
W Bk
5AT Fuse
5AT Fuse
5AT Fuse
8 9 10 11 12
1 2 3 4 5
13
6
14
7
X2
6 7 8 9 10
1 2 3 4 5
X3
7 8 9 10 11
1 2 3 4 5
12
6
X1
X12
X9
P14
123
4
123
456
P13
123
F00
X10
12
V
V
Bk
W
Bk
56
34 12
5AT Fuse
5AT Fuse
5AT Fuse
8 9 10 11 12
1 2 3 4 5
6 7 8 9 10
1 2 3 4 5
X3
7 8 9 10 11
1 2 3 4 5
12
6
X1
X12
X9
P14
123
4
123
456
P13
123
F00
F01
X10
12
V
Gr
Br
Br
GND
56 34
12
W Bk
5AT Fuse
5AT Fuse
5AT Fuse
Protect bare pins with Fast-on connectors, then store connector and wiring at the rear of control box with retaining clips.
Fig. 13 - Prestige Solo & Excellence- PCB Wiring - Pre modication
6
Fig. 14- Prestige Solo & Excellence - PCB Wiring - Post Modiciation
Bk. Black Br. Brown R. Red V. Violet W. White Gr. Green
Page 7
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
A B
Fig. 15 - Prestige Solo & Excellence - Combustion chamber 2-in-1 Insulation Damages
7
Page 8
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
1.6. Configuration Changes
1.6.1 Wiring
Following the printed circuit board replacement and wiring changes, the ALARM relay function is no longer available for the configurations that use it. Therefore, anything wired to the Alarm relay needs to be rewired to a different relay if required (see table below).
NOTICE
In some configurations, the Error function will no longer be available. Please contact your
Triangle Tube assistance.
Preset cong
1 18
Page * Connected toReconnect
to
ACVMax setup (Flexible
1.6.2 CTRLMax Setup
Additionally, the setting of the relevant Flex relays needs to be adapted through the Installer menu, as indicated on the next page.
Remark
pump cong)
2 19
3 20
4 21
5 22
6 23
8 25
10/11** 24** ALARM Pump 3
7 - Error function not available anymore
9 26 Error function not available anymore
10 27
11 28
12 29
13 30 Error function not available anymore
* refer to the manual “Prestige Control Application Supplement - ACVMax”, 2015-10
** The configuration mentioned on this page in the manual is mistakenly identified 7. It should be 11 (or possibly 10)
ALARM FLAME
These configurations are no longer available (no available relay for the motor open function that was implemented by the Error relay). Please contact your TTP assistance.
Flex. Relay 5 to be set to ERR :
FLAME: OFF
ERROR: ON
Flex Relay 3 to be set to
MIX OPEN:
MIX OPEN: ON
ONLY if no additional pump is con­nected to Flex Relay 3 (P3).
If a pump is connected, please con­tact your TTP assistance.
8
Page 9
PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS
O
O
1.6.3 Alarm relay function moved to the Flex relay 5 (Flame)
Boiler Settings
Boiler Settings
Prestige Model Solo
Lockout Temp. 105°C
Modbus Address 1
Pump settings
Pump Settings
Current Pump Cong M odied
Preset Pump Cong
Flexible Pump Cong
Flexible Pump Cong
Flex. Relay 1 (CH)
Flex. Relay 2 (DHW)
Flex. Relay 3 (P3)
Flex. Relay 4 (ERR)
Flex. Relay 5 (Flame)
Flex. Relay 6 (P4)
Flex. Relay 5 (Flame)
CH1 / CV1 O
CH2 / CV2
DHW / ECS / SWW O
MIX OPEN O
MIX CLOSE O
ERROR On
FLAME O
1.6.4 Alarm Relay function moved to the Flex Relay 3 (P3)
Flexible Pump Cong
Flex. Relay 1 (CH)
Flex. Relay 2 (DHW)
Flex. Relay 3 (P3)
Flex. Relay 4 (ERR)
Flex. Relay 5 (Flame)
Flex. Relay 6 (P4)
Flex. Relay 3 (P3)
CH1 / CV1 O
CH2 / CV2
DHW / ECS / SWW O
MIX OPEN On
MIX CLOSE O
ERROR O
FLAME O
Flexible Relay 5 (Flame)
CH2 / CV2 O
DHW / ECS / SWW O
MIX OPEN O
MIX CLOSE O
ERROR On
FLAME O
Save & Exit
Flexible Relay 5 (Flame)
CH2 / CV2 O
DHW / ECS / SWW O
MIX OPEN O
MIX CLOSE O
ERROR On
FLAME O
Save & Exit
1.6.5 Configuration Record
Preset Pump
Config
Pre-Mod
Configuration
Post-Mod
Configuration
Flex Relays Functions
Flex Relay 1Flex Relay 2Flex Relay 3Flex Relay 4Flex Relay 5Flex Relay