5.8. Storage Tank Installation ............................................................................................................. 30
CHAPTER 6 - INSTALLING VENT/COMBUSTION AIR & CONDENSATE DRAIN ..........38
6.1. Installing Vent and Combustion Air ............................................................................................ 38
6.2. Installing Condensate Drain Assembly into INSTINCT Solo Units ........................................... 38
CHAPTER 7 - GAS PIPING ................................................................................................ 40
7.1. Gas Supply Piping Connection ....................................................................................................40
7.2. Natural Gas .................................................................................................................................... 41
9.2. CTRLMax Menu Structure ........................................................................................................... 52
9.3. Home Screen ................................................................................................................................ 53
9.4. Status Line Messages .................................................................................................................. 54
9.5. Main Menu .................................................................................................................................... 55
9.6. EZ Setup ....................................................................................................................................... 55
9.7. Heating EZ Setup
9.7.1 Select CH Demand (No outdoor sensor connected) ...................................................... 56
IMPORTANT SAFETY INFORMATION FOR
THE HOMEOWNER AND THE INSTALLER
DANGER
SAFETY
This manual contains important information with respect to the
installation, starting up and maintenance of the appliance.
This manual must be provided to the Homeowner, who will
keep it in a safe place for future reference.
Triangle Tube accepts no liability for any damage,
injury, or loss of life resulting from incorrect
installation, alteration of any factory supplied
parts, or the use of parts or ttings not specied by
Triangle Tube. If there is a conict or doubt about the
proper installation of the unit or any factory supplied
replacement parts please contact Triangle Tube
Technical Support.
DEFINITIONS
The following terms are used throughout this manual
to bring attention to the presence of potential hazards
or to important information concerning the product.
DANGER
Indicates the presence of a hazardous situation which, if ignored, will result in substantial
property damage, serious injury, or death.
WARNING
Indicates a potentially hazardous situation
which, if ignored, can result in substantial
property damage, serious injury, or death.
CAUTION
Indicates a potentially hazardous situation
which, if ignored, can result in minor property
damage, or injury.
NOTICE
Indicates special instructions on installation,
operation or maintenance, which are important to the equipment but not related to person-
al injury hazards.
BEST PRACTICE
Indicates recommendations made by Triangle
Tube for the installers, which will help to ensure
optimum operation and longevity of the equip-
ment.
• Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of
the control system which has been under water.
• Avoid electrical shock when servicing the
appliance, by disconnecting the electrical supply
prior to performing maintenance.
• Failure to comply with these instructions will
result in substantial property damage, serious
injury, or death.
WARNING
• What to do if you smell gas:
- Do not try to light any appliance
- Do not touch any electrical switch; do not use
any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
- If you cannot reach your gas supplier, call the
fire department.
• Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
• Prior to installing this product, the qualified
installer must read all instructions included in
this manual and all accompanying manuals/
documents with this appliance.
• All installation steps required in these manuals
must be performed in the proper order given.
• This product must be maintained / serviced and
inspected annually by a qualified service technician.
• A byproduct of any gas fired appliance is carbon
monoxide. Triangle Tube requires the installation
of a minimum of two (2) hard-wired carbon
monoxide detectors with an alarm and battery
back-up; one in the mechanical room where
the boiler is located and another installed in
the living area outside the bedroom(s) for all
installations. Consult the local authority having
jurisdiction for any additional carbon monoxide
detector requirements in your area. See
Section
2.8 on page 10 for additional carbon monoxide
detector requirements in Massachusetts.
• Failure to comply with these instructions can
result in substantial property damage, serious
injury, or death.
xi
Page 12
SAFETY
PRODUCT AND SAFETY INFORMATION
WARNING
DANGER
HOT WATER CAN SCALD!
Water temperature over 125ºF can cause se-
vere burns instantly or death from scalds.
• Children, disabled and elderly are at
highest risk of being scalded.
Ū Never leave them unattended in or
near shower, bathtub or sink.
Ū Never allow small children to use a hot
water faucet or draw their own bath.
• To avoid any potential scald hazard or if
codes require specific water temperatures
at the hot water faucet, the installer must:
Ū Install a thermostatic mixing valve at
this appliance and ensure it is working
property AND
Ū Set the domestic hot water tempera-
ture to the lowest temperature which
satisfies your hot water needs.
Ū Feel and adjust water temperature be-
fore bathing or showering.
Ū Water drained from the system drain
valves may be extremely hot.
TO AVOID INJURY:
• Make sure all connections are tight.
• Direct water flow away from any person.
• Failure to comply with these instructions
will result in substantial property damage,
serious injury, or death.
• Should overheating occur or if the gas supply fails
to shut off, turn OFF the manual gas control valve
external to the appliance.
• Do not add cold make up water when the
appliance is hot. Thermal shock can potentially
cause cracks in the heat exchanger.
• Failure to comply with these instructions can
result in substantial property damage, serious
injury, or death.
Protection must be taken against excessive pressure!
TO PROTECT AGAINST EXCESSIVE PRESSURE:
• Verify that a field supplied 150 psi pressure
relief valve is installed in the recommended
location for Combi models using the domestic hot water function (DHW Side).
• Verify the 30 psi relief valve supplied is in-
stalled in the location provided (CH Side). In
installations where the CH pressure exceeds
30 psi, a 50 psi relief valve (not included) can
be installed in lieu of the 30 psi relief valve.
• To avoid injury, install the relief valves in com-
pliance with local code requirements.
Failure to comply with these instructions can
result in substantial property damage, seri-
• It is prohibited to carry out any modifications to
the appliance without prior written consent from
Triangle Tube.
• Faulty parts must only be replaced by genuine
Triangle Tube factory parts.
• Failure to comply with these instructions can result
in minor property damage, or injury.
• The Instinct appliance is supplied with an acoustic
dampening foam rubber insert located in the
appliance air inlet. DO NOT remove this on installation.
WARNING
ous injury, or death.
CAUTION
NOTICE
WARNING
Bacteria can develop in the domestic water
system if certain minimum water temperatures are not maintained. Failure to maintain
at least 140°F [60°C] domestic hot water temperature or use the Antilegionella function
can result in bacteria development, which
can result in serious injury, or death.
xii
• The homeowner is only permitted to carry out the basic
set-up operations (EZ Setup) after he has received all
relevant instructions from the installer. Any other setup must be carried out by a qualified installer.
• In case of any anomaly, please call your qualified
service technician.
• Make sure to reference the unit’s model number and
serial number from the rating label when inquiring
about service or troubleshooting.
• Triangle Tube reserves the right to change the
technical characteristics, components and features of
its products without prior notice. Check for an updated
version of this manual at www.triangletube.com.
Page 13
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.1. INSTINCT boilers - Code Compliance
The INSTINCT units must be installed by a qualied installer in accordance with the following:
• All applicable local, state, national and provincial codes, ordinances, regulations and laws.
• For installations in Massachusetts, code requires the INSTINCT to be installed by a licensed
plumber or gas tter, and if antifreeze is utilized,
the installation of a reduced pressure back-ow
preventer device is required in the boiler’s cold
water ll or make up water supply line.
• For installation in Massachusetts, all direct vented
appliances must comply with the guidelines as
outlined in Section 2.8 on page 10.
• The National Fuel Gas Code (NFPA54/ ANSI Z 223.1).
• National Electric Code (ANSI/NFPA 70).
• For installations in Canada - Installation Code for
Gas Burning Equipment (CAN/CSA B149.1), Canadian Electrical Code Part 1 (CSA C22.1).
• Standards for Controls and Safety Devices for
Automatically Fired Boilers (ANSI/ASME CSD-1),
when required.
NOTICE
The Instinct gas manifold and gas controls
meet the safe lighting and other performance
requirements as specified in ANSI Z21.13.
Where recommendations in this manual dier from local or national codes, the local or national codes take
precedence.
1.1.1 Code Restrictions
The single wall heat exchanger in the INSTINCT Combi
water heater complies with National Standard Plumbing Code, provided that:
• Boiler water (including additives) is practically
non-toxic, having toxicity rating or class of 1, as listed
in Clinical Toxicology of Commercial Products, and
• Boiler water pressure is limited to maximum 30
psig by approved relief valve.
Single wall heat exchangers are permitted under the
Uniform Plumbing Code - Paragraph L3.2. and L3.3 if
they satisfy all of the following requirements.
• The heat transfer medium is potable water or
contains only substances which are recognized
as safe by the U.S. Food and Drug Administration.
• The pressure of the heat transfer medium is
maintained less than the normal minimum operating pressure of the potable water system
• The equipment is permanently labeled to indicate that only additives recognized as safe by
the FDA shall be used in the heat transfer medium.
Other heat exchanger designs may be permitted where
approved by the Administrative Authority.
1.1.2 Operating Restrictions
• Maximum INSTINCT Combi DHW outlet temperature is 149ºF, when mixing valve is installed.
• Maximum boiler water temperature rating is 210ºF.
• Maximum DWH working pressure is 150 psig.
• Maximum boiler (CH) working pressure is
50 psig.
• Water quality limitations (based on E.P.A National Secondary Drinking Water Regulations):
Ū Chloride, less than 150 ppm or mg/lŪ pH value min. 6, max. 8 Ū Total hardness 3 - 7 grains/gallon or 50-120
ppm or mg/l.
Ū Total Dissolved Solids (TDS), less than 120
ppm or mg/l.
Ū Iron less than 0.3 ppm or mg/l.Ū Aluminum, less than 0.2 ppm or mg/l.Ū Copper, less than 1 ppm or mg/l.Ū Manganese, less than 0.05 ppm or mg/l.
Ū Zinc, less than 5 ppm or mg/l.
BEST PRACTICE
In hard water areas (more than 7 grains of
hardness) soften the cold domestic supply wa-
ter to the appliance to prevent scaling.
NOTICE
• Any water conditioning system must be installed and maintained in accordance with
manufacturer’s specifications.
• Do not install the INSTINCT Combi in any
application if the boiler piping contains
non-oxygen barrier tubing or if the boiler
piping is considered an “open system”. Exposing the internal circulator to oxygen
contamination will lead to premature fail-
ure and denial of the warranty.
CHAPTER 1
1
Page 14
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
CHAPTER 1
1.2. Determining Product Location
NOTICE
The INSTINCT is certified for indoor, condi-
tioned space installations ONLY.
Before locating the INSTINCT check for convenient locations to:
• Heating system piping
• Venting
• Gas supply piping
• Electrical service
Ensure the INSTINCT location allows the combustion air/
vent piping to be routed directly through the building
and terminate properly outside with a minimum amount
of length and bends.
Ensure the area chosen for the installation of the INSTINCT
is free of any combustible materials, gasoline, or other
ammable liquids.
WARNING
Failure to remove or maintain the area free
of combustible materials, gasoline, or other flammable liquids or vapors can result in
substantial property damage, serious injury,
or death.
Ensure the INSTINCT and its controls are protected from
dripping or spraying water during normal operation or
service.
The INSTINCT should be installed in a location so that
any water leaking from the boiler, piping connections,
or relief valve will not cause damage to the surrounding
area or any lower oors in the structure.
1.3. Boiler Freeze Protection Feature
The CTRLMax boiler management system has a freeze
protection feature built in. This feature monitors the
boiler water temperature and responds as follows when
no call for heat is present:
• 46ºF [8ºC] Pump outputs congured to respond to
a CH1 Call are enabled.
• 42ºF [6ºC] Pump outputs congured to respond to
a CH1 or CH2 Call are enabled, Burner operates at
low re.
• 60ºF [15ºC] Freeze protection ends. Burner & all pumps
turn o after completing CH Post Pump Time.
CAUTION
• The boiler freeze protection feature is disabled during a hard lockout. The burner
will not fire, but the circulators will operate.
• The boiler freeze protection feature is designed to protect the boiler, not the heating
system. The boiler should be installed in a
primary/secondary piping arrangement if it
is installed in an unheated space or exposed
to water temperatures of 46ºF or less. Refer
to Chapter 4 for primary/secondary piping
and Chapter 10 for antifreeze guides.
• Failure to comply can result in minor prop-
erty damage, or injury.
1.4. Boiler Replacement
If the INSTINCT is replacing an existing boiler, the following items should be checked and corrected prior to
installation:
• Boiler piping leaks and corrosion.
• Proper location and sizing of the expansion
tank on the boiler heating loop.
• The existing vent system is appropriate for the
INSTINCT and it is correctly installed. Refer to
the INSTINCT Vent Supplement for the vent system requirements.
• Amount and quality of propylene glycol within
the system, if applicable.
2
Page 15
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.5. Recommended Clearances
The INSTINCT is approved for zero clearance to combustibles, excluding vent and boiler piping.
• Boiler piping must be a minimum 1/4 inch from
combustible materials.
• Reference the INSTINCT Vent Supplement for
vent pipe clearance requirements.
BEST PRACTICE
It is recommended that the following clearances
be maintained for serviceability:
• Top boiler jacket - 24 inches [610 mm].
• Front - 24 inches [610 mm].
• Bottom boiler piping - 24 inches [610 mm].
• Rear - 0 inches
• Sides - 6 inches [153 mm]
NOTICE
When maintaining less than recommended
service clearances, some product labeling, including the rating label, may become hidden
and unreadable.
1.6. Residential Garage Installations
When installing the INSTINCT in a residential garage,
the following special precautions per NFPA 54/ANSI
Z223.1 must be taken:
• Mount the unit a minimum 18 inches [458 mm]
above the oor level of the garage. Ensure the
burner and ignition devices / controls are no less
than 18 inches [458 mm] above the oor level.
• Locate or protect the unit in a manner so it cannot be damaged by a moving vehicle.
CHAPTER 1
WARNING
• If the recommended clearances listed above cannot be maintained
or the enclosure in which the boiler is installed is less than 70 cubic
feet, the space must be ventilated.
See Section 2.2 on page 6.
• When installing the INSTINCT in a confined space, sufficient air must be provided
to allow, under normal operating conditions, proper air flow around the product
to maintain ambient temperatures within
safe limits to comply with the National Fuel
Gas Code (NFPA 54 / ANSI Z223.1)
• Failure to comply with these instructions
can result in substantial property dam-
age, serious injury, or death.
3
Page 16
INTENTIONALLY LEFT BLANK
Page 17
CHAPTER 2 - COMBUSTION AIR & VENTING
2.1. Combustion Air Contamination
WARNING
If the INSTINCT combustion air inlet is located
in an area likely to cause or contain contamination, or if products which could contaminate
the air cannot be removed, the combustion air
must be repiped and terminated at another location. Contaminated combustion air will damage the unit and its burner system, and can
result in substantial property damage, serious
injury, or death.
DANGER
• Do not operate the INSTINCT if the combustion air inlet is located near a laundry
room or pool facility. These areas will al-
ways contain hazardous contaminants.
• Pool, laundry, common household, and
hobby products often contain fluorine or
chlorine compounds. When these chemicals pass through the burner and vent
system, they can form strong acids. These
acids will corrode the heat exchanger,
burner components, and vent system,
causing serious damage and possible
flue gas spillage or water leakage into
the surrounding area.
• Please read the information listed below.
If contaminating chemicals are located
near the area of the combustion air inlet,
the installer must pipe the combustion
air inlet to an area free of these chemicals,
as indicated in Chapter 6 on page 38.
• Failure to comply with these instructions
will result in substantial property dam-
age, serious injury, or death.
• The INSTINCT boiler is classified as a
Category IV appliance. This utilizes uncontaminated indoor or outdoor air for
applicance combustion. A direct vent
installation uses the outdoor air. Air supply, combusiton chamber, heat exchanger and evacuation of POC (products of
combustion) for this type of appliance is
sealed with respect to the room in which
the appliance is installed.
• An in-direct installation uses uncontaminated indoor air for appliance combustion.
• When the air for combustion is taken
from the room air grilles must be installed
by the contractor. The air grilles should
be sized in accordance with ANSI Z223.1/
NFPA54 and/or Natural Gas and Propane
Installation Code CAN/CSA B149.1.
• The grille providing air when taking air
directly from the room should be clearly labelled; "AIR SUPPLY, DO NOT COVER
OR RESTRICT. FAILURE TO PROVIDE ADEQUATE AIR FOR COMBUSTION COULD
RESULT IN SERIOUS INJURY, OR DEATH."
Potential contaminating products
• Spray cans containing chloro/uorocarbons
• Permanent Wave Solutions
• Chlorinated wax
• Chlorine based swimming pool chemicals /
cleaners
• Calcium Chloride used for thawing ice
• Sodium Chloride used for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid / muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
• Adhesives used to fasten building products and
other similar products
Areas likely to contain these products
• Dry cleaning / laundry areas and establishments
• Beauty salons
• Metal fabrication shops
• Swimming pools and health spas
• Refrigeration Repair shops
• Photo processing plants
• Auto body shops
• Plastic manufacturing plants
• Furniture renishing areas and establishments
• New building construction
• Remodeling areas
• Garages with workshops
CHAPTER 2
5
Page 18
CHAPTER 2 - COMBUSTION AIR & VENTING
CHAPTER 2
2.2. Ventilation and Combustion Air Requirements - Direct Vent
A Direct Vent appliance utilizes uncontaminated outdoor air piped directly to the appliance for combustion.
For Direct Vent installations involving only the INSTINCT, in which the minimum service clearances are
maintained as listed in Section 1.5 on page 3, no
ventilation openings are required, but may be necessary to equalize the air pressure with the outside.
For Direct Vent installations involving only the INSTINCT,
in which the minimum service clearances are not maintained as listed in Section 1.5 on page 3, the space
/ enclosure must provide two openings for ventilation.
The openings must be sized to provide 1 square inch of
free area per 1,000 BTUH of boiler input. The openings
shall be placed 12 inches from the top of the space and
12 inches from the oor of the space.
For installations in which the INSTINCT shares the
space with air movers (exhaust fan, clothes dryers,
replaces, etc.) and other combustion equipment (gas
or oil) the space must be provided with adequate air
openings to provide ventilation and combustion air
to the equipment. To properly size the ventilation /
combustion air openings, the installer must comply
with the National Fuel Gas Code (NFPA 54 / ANSI
Z223.1) for installations in the U.S. or CAN/CSA B149.1
for installations in Canada.
WARNING
The space must be provided with ventilation
/ combustion air openings properly sized for
all make-up air requirements (exhaust fans,
clothes dryers, fireplaces, etc.) and the total
input of all appliances located in the same
space as the INSTINCT, excluding the input
of a Direct Vent INSTINCT which uses combustion air directly from the outside, thus
additional free area for the openings is not
required. Failure to provide or properly size
the openings can result in substantial prop-
erty damage, serious injury, or death.
2.3. Ventilation and Combustion Air Requirements - Category IV
A Category IV appliance utilizes uncontaminated indoor
or outdoor air surrounding the appliance for combustion.
BEST PRACTICE
In order to reduce the potential risks associated
with indoor contaminates (see list in Section
2.1 on page 5), flammable vapors and tight
housing construction with little or no infiltration
air, it is recommended to pipe uncontaminated
combustion air directly from the outdoors to
the appliance. This practice also promotes higher system efficiency by reducing heated indoor
air from being exhausted from the house and
replaced by cold infiltration air into the house.
For installations in which the INSTINCT shares the
space with air movers (exhaust fan, clothes dryers,
replaces, etc.) and other combustion equipment (gas
or oil) the space must be provided with adequate air
openings to provide ventilation and combustion air
to the equipment. To properly size the ventilation /
combustion air openings, the installer must comply
with the National Fuel Gas Code (NFPA 54 / ANSI
Z223.1) for installations in the U.S. or CAN/ CSA B149.1
for installations in Canada.
WARNING
The space must be provided with ventilation
/ combustion air openings properly sized for
all make-up air requirements (exhaust fans,
clothes dryers, fireplaces, etc.) and the total input of all appliances, including the INSTINCT when located in the same space. Failure to provide or properly size the openings
can result in substantial property damage,
serious injury, or death.
6
Page 19
CHAPTER 2 - COMBUSTION AIR & VENTING
DHW Demand
DHW
186°F
156°F
Target = 186°F
Ion-ic
2.4. Methods of Accessing Combustion Air
Into A Space - Category IV
2.4.1. Indoor Combustion Air
NOTICE
• The methods listed in this chapter for accessing
Indoor Combustion Air assume that the infiltra
tion rate is adequate and not less than .40 ACH.
• For infiltration rates less than .40 ACH, reference the National Fuel Gas Code (NFPA 54 /
ANSI Z223.1) for additional guidance.
• Indoor combustion air vent supply must be
installed with a minimum equivalent vent
length of 10 feet. Refer to Vent Supplement
for further guidance.
Opening Size and Location
Openings used to connect indoor spaces shall be sized and
located in accordance with the following, see Fig. 1 below :
• Combining spaces on the same story. Each opening
shall have a minimum free area of 1 sq. in./1000 Btu/hr
of the total input rating of all gas utilization equipment
in the space, but not less than 100 sq. inches. One
opening shall commence within 12 inches of the top,
and one opening shall commence within 12 inches
of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches.
Gas Vent
-
2.4.2. Outdoor Combustion Air
BEST PRACTICE
Isolating the combustion appliance room from
the rest of the building and bringing in uncontaminated outside air for combustion and ven-
tilation is always preferred.
Opening Size and Location
The minimum dimension of air openings shall be not
less than 3 inches
Openings used to supply combustion and ventilation
air shall be sized and located in accordance with the
following:
• One Permanent Opening Method . One permanent
opening, commencing within 12 in. of the top of
the enclosure, shall be provided as shown in Fig. 2 below. The equipment shall have clearances of
at least 1 inch from the sides and 6 in. from the
front of the appliance. The opening shall directly
communicate with the outdoors or shall communicate through a vertical or horizontal duct to the
outdoors or spaces that freely communicate with
the outdoors and shall have a minimum free area
of the following:
• 1sq. in./3000 Btu/hr of the total input rating of
all equipment located in the enclosures, and
• Not less than the sum of the areas of all vent
connectors in the space.
CHAPTER 2
Openings
Fig. 1 - All Combustion Air from adjacent Indoor Spaces
through Indoor Combustion Openings
• Combining spaces in dierent stories. The volumes of
spaces in dierent stories shall be considered as communicating spaces where such spaces are connected
by one or more openings in doors or oors having a
total minimum free area of 2 sq. in./1000 Btu/hr of total input rating of all gas utilization equipment.
Gas Vent
Alternate
opening
location
Ion-ic
186°F
DHW
156°F
Target = 186°F
DHW Demand
Fig. 2 - All Combustion Air from Outdoors
Through One Permanent Air Opening
Opening
7
Page 20
CHAPTER 2 - COMBUSTION AIR & VENTING
CHAPTER 2
• Two Permanent Opening Method. Two permanent
openings, one commencing within 12 in. of the top
and one commencing within 12 in. of the bottom
of the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces that freely communicate with
the outdoors, as follows:
• Where directly communicating with the outdoors or where communication to the outdoors
is through vertical ducts, each opening shall
have a minimum free area of 1 sq. in./4000 Btu/
hr of total input rating of all equipment in the
enclosure. See Fig. 3 below.
Ventilation louvers
Outlet air
Inlet air duct
(ends 1ft (30 cm)
above oor)
(each end of the attic)
Gas Vent
Ion-ic
186°F
DHW
156°F
Target = 186°F
DHW Demand
• Where communicating with the outdoors is
through horizontal ducts, each opening shall have
a minimum free area of not less than 1 sq.in./2000
Btu/hr of total input rating of all equipment in the
enclosure. See Fig. 4 below.
2.4.3 Combination of Indoor and Outdoor
Combustion Air
Indoor Openings. Where used, openings connecting the interior spaces shall comply with Section 2.4.1 on page 7.
Outdoor Opening(s) Location. Outdoor opening(s) shall
be located in accordance with Section 2.4.2 on page 7.
Outdoor Opening(s) Size. Outdoor opening(s) shall be
calculated in accordance with the following:
• The ratio of the interior spaces shall be the avail-
able volume of all communicating spaces divided
by the required volume.
• The outdoor size reduction factor shall be 1 minus
the ratio of interior spaces.
• The minimum size of outdoor opening(s) calculat-
ed in accordance with the above outdoor air chapter multiplied by the reduction factor. The minimum dimension of air openings shall not be less
than 3 in.
Fig. 3 - All Combustion Air from Outdoors Through
Ventilated Attic
Gas Vent
Outlet air duct
Ion-ic
186°F
DHW
156°F
Target = 186°F
DHW Demand
Inlet air duct
Fig. 4 - All Combustion Air from Outdoors Through
Horizontal Ducts
2.5. Combustion Air and Vent Piping
The INSTINCT requires a Category IV venting system,
which is designed for pressurized venting and condensate.
The INSTINCT is certied as a Category IV or Direct Vent
(sealed combustion) appliance. A Category IV appliance
utilizes uncontaminated indoor or outdoor air surrounding the appliance for combustion. A Direct Vent appliance utilizes uncontaminated outdoor air piped directly
to the appliance for combustion.
DANGER
Do not install the INSTINCT into a common
vent with any other gas or oil appliances.
This will cause flue gas spillage or appliance
malfunction, which will result in substantial
property damage, serious injury, or death.
DANGER
It is essential that the supply of air for combustion is not blocked or restricted - this
could result in serious injury, or death.
8
Page 21
CHAPTER 2 - COMBUSTION AIR & VENTING
BEST PRACTICE
In order to reduce the potential risks associated with indoor contaminates (see list in Section
2.1 on page 5), flammable vapors and tight
housing construction with little or no infiltration
air, it is recommended to pipe uncontaminated
combustion air directly from the outdoors to the
appliance. This practice also promotes higher
system efficiency by reducing heated indoor air
from being exhausted from the house and re-
placed by cold infiltration air into the house.
DANGER
Verify installed combustion air and vent piping are sealed gas tight and meet all provided
instructions and applicable codes, failure to
comply will result in serious injury, or death.
WARNING
Failure to properly support the vent system
can cause the venting system to fail, resulting in substantial property damage, serious
injury, or death.
NOTICE
Install combustion air and vent pipe as detailed
in the INSTINCT Vent Supplement included in
the boiler installation envelope. Refer to optional vent kit instructions for additional vent
installation instructions.
2.6. Removal of an Existing Boiler from a
Common Vent System
BEST PRACTICE
When an existing boiler is removed from a common venting system, the common venting system
is likely to be too large for proper venting of the remaining appliances. At the time of removal of an
existing boiler, the following steps shall be followed
with each appliance remaining connected to the
common venting system placed in operation, while
the other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deciencies which could cause an unsafe condition.
3. Insofar as is practical:
• Close all exterior building doors and windows
and all doors between the space in which the
appliances remaining connected to the common venting system are located and other
spaces of the building.
• Turn on clothes dryers and any appliance not
connected to the common venting system.
• Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at
maximum speed.
• Do not operate a summer exhaust fan.
• Close replace dampers.
4. Place in operation the appliance being inspected.
• Follow the lighting instructions.
• Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
ame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, replace
dampers, and any other gas-burning appliance to
their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms
with the National Fuel Gas Code (NFPA 54 / ANSI
Z223.1) for installations in the U.S. or CAN/CSA B149.1
for installations in Canada. When resizing any portion of the common venting system, the common
venting system should be resized to approach the
minimum size as determined using the appropriate
tables in Chapter 13 of the National Fuel Gas Code
(NFPA 54 / ANSI Z223.1) for installations in the U.S. or
CAN/CSA B149.1 for installations in Canada.
DANGER
Do not install the INSTINCT into a common
vent with any other gas or oil appliances. This
will cause flue gas spillage or appliance malfunction, resulting in substantial property
damage, serious injury, or death.
CHAPTER 2
9
Page 22
CHAPTER 2 - COMBUSTION AIR & VENTING
CHAPTER 2
2.7. Carbon Monoxide Detector Installation
Triangle Tube requires the installation of a minimum
of two (2) hard wired carbon monoxide detectors with
an alarm and battery back-up in the mechanical room
where the INSTINCT is located and another installed in
the living area outside the bedroom(s) for all installations.
Each carbon monoxide detector shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
Consult the local authority having jurisdiction for any additional carbon monoxide detector requirements in your
area. See Section 2.8 on page 10 for additional carbon
monoxide detector requirements in Massachusetts.
WARNING
A byproduct of any gas fired appliance is carbon monoxide. Failure to install carbon monoxide detectors with alarms can result in seri-
ous injury, or death.
2.8. Commonwealth of Massachusetts Installation Requirements
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure
used in whole or in part for residential purposes, including those owned or operated by the Commonwealth
and where the side wall exhaust vent termination is
less than seven (7) feet above nished grade in the area
of the venting, including but not limited to decks and
porches, the following requirements shall be satised:
2.8.1 Installation of Carbon Monoxide Detectors.
1. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or
gastter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the oor level where the gas equipment is
to be installed.
2. In addition, the installing plumber or gastter shall
observe that a battery operated or hard wired carbon
monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled
equipment.
3. It shall be the responsibility of the property owner to
secure the services of qualied licensed professionals
for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vent-
ed gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up
may be installed on the next adjacent oor level.
b. In the event that the requirements of this sub-
division can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above
requirements; provided, however, that during
said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall
be installed.
2.8.2 Approved Carbon Monoxide Detectors.
Each carbon monoxide detector as required in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
2.8.3 Signage
A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in
line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment.
The sign shall read, in print size no less than one half
(1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
2.8.4 Inspection.
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board;
and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
10
Page 23
CHAPTER 2 - COMBUSTION AIR & VENTING
2.8.5 Manufacturer Requirements - Gas Equipment Venting System Provided.
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer for installation of the equipment and the venting
system shall include:
1. Detailed instructions for the installation of the venting
system design or the venting system components;
and
2. A complete parts list for the venting system design
or venting system.
2.8.6 Manufacturer Requirements - Gas Equipment Venting System Not Provided.
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does
not provide the parts for venting the ue gases, but
identies “special venting systems”, the following requirements shall be satised by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion of the installation.
CHAPTER 2
11
Page 24
INTENTIONALLY LEFT BLANK
Page 25
CHAPTER 3 - UNIT PREPARATIONS
3.1. Handling Instructions
The INSTINCT is generally easier to handle and maneuver once removed from the shipping carton.
To remove the shipping carton:
NOTICE
Use care not to drop, bump or rotate the boiler
upside down, as damage to the boiler will result.
1. Remove any shipping straps.
2. Slide the cardboard sleeve from the unit.
3. Remove the wall mounting template.
4. Remove the accessory boxes.
5. Remove upper and lower cardboard end pieces.
6. Remove the boiler from the cardboard tray.
7. Discard all packing materials and recycle where
possible.
3.2. Wall Mounting Installation
The INSTINCT should be wall mounted using the wall
mounting template and bracket provided with the boiler. The INSTINCT is not designed for oor installation.
The INSTINCT is not to be installed on carpeting
WARNING
The wall used for mounting the INSTINCT
must be vertically plumb and capable of sup-
porting at minimum:
• 101 pounds [46 kg] for the INSTINCT Solo 110
• 137 pounds [62 kg] for the INSTINCT Solo 155
• TBC pounds [TBC kg] for INSTINCT Solo 199
• 154 pounds [70 kg] for INSTINCT Combi 155
• TBC pounds [TBC kg] for INSTINCT Combi 199
Note. All weights above include INSTINCT
water volumes.
Failure to comply with these requirements
can result in substantial property damage,
serious injury, or death.
CHAPTER 3
Venturi
3/4" Elbow
Auto Air Vent
Reduced Tee
Pressure Gauge
Union
3.3. Accessory Box
Unpack and check the the list of all accessories as
shown in Fig. 5 below.
Bird Screens (x2)
Screws (x4) / Anchors (x4)
Pressure Relief ValveSensor DHW
Gas Valve to Venturi Gaskets (x2)
Fig. 5 - Accessory Box Contents
13
Page 26
CHAPTER 3 - UNIT PREPARATIONS
CHAPTER 3
3.4. Wall Mounting Guidelines
The wall-mounting bracket is designed for stud spacing
of approximate 12 inch or 16 inch on centers. For unconventional stud spacing, a solid / secure mounting
surface must be provided for installation of the bracket.
1. For applications using wood studs, install the bracket using the lag screws provided with the boiler.
Ensure both lag screws are installed securely in the
studs.
2. For applications using metal studs, install the bracket to the studs using 3/16” toggle bolts and washers.
3. DO NOT mount or attempt to mount the wall
bracket to hollow sheet rock or lath walls using
anchors. Only install boiler to studs or equivalent
wood structure.
4. For applications using solid walls (rock, concrete,
brick, cinder block, etc.), install the wall bracket using anchors (double expansion shields) and bolts
with washers provided with the boiler.
5. The boiler is too heavy and bulky for a single person
to lift and attempt to mount; a minimum of 2 people are required for mounting the boiler.
3.5. Stud Walls - Installation
1. Locate the studs in the general area of the boiler
installation.
2. Place the wall-mounting bracket on the wall centering the mounting slots with the stud centers
and ensuring the upper edge of the bracket is away
from the wall.
3. Level the bracket, while maintaining it’s centering
with the studs and use a pencil to mark the location
of the mounting slots.
4. Remove the bracket from the wall and drill a 1/4” diameter by 3” deep hole in the center of each mark.
For applications using metal studs and 3/16” toggle
bolts, drill the required clearance hole.
5. Reposition the bracket on the wall and align with
the mounting slots/holes. Insert the two lag screws
provided (or toggle bolts for metal studs) through
the mounting slots/holes and loosely tighten.
6. Level bracket and tighten screws (bolts for metal
studs) securely making sure not to over-tighten to
avoid damaging drywall or plaster.
3.6. Wall Bracket Installation - Solid Walls
WARNING
Use extreme care not to drop the boiler or
cause bodily injury while lifting or mounting the boiler onto the wall bracket. Once
mounted, verify that the boiler is securely
attached to the bracket and wall. Failure to
comply with the above guidelines can result
in substantial property damage, serious inju-
ry, or death.
1. Locate the general area of the boiler installation.
2. Place the wall-mounting bracket on the wall ensuring
the upper edge of the bracket is away from the wall.
3. Level the bracket and use a pencil to mark the location of the mounting slots on the wall.
4. Remove the bracket from the wall and drill a 5/8”
diameter by 1-3/8” deep hole in the center of each
mark.
5. Install the provided anchors ush or slightly recessed
in the drilled holes with threaded side facing down.
6. Reposition the bracket on the wall and align with
the mounting slots/holes. Insert the two bolts with
washers through the mounting slots/holes and
loosely tighten.
7. Level bracket and tighten bolts securely.
3.7. Boiler Mounting
1. Obtain assistance in lifting the boiler onto the wall
bracket.
2. Install the boiler making sure the boiler mounting
lip located along the upper edge of the rear jacket
panel engages the wall-mounting bracket. Ensure
the boiler is seated properly and is secure.
14
Page 27
CHAPTER 4 - BOILER PIPING
4.1. General Piping Requirements
• All plumbing must meet or exceed all local, state
and national plumbing codes.
• Support all piping using hangers. DO NOT support
piping by the unit or its components.
• Use isolation valves to isolate system components.
• Install unions for easy removal of the INSTINCT
from the system piping.
WARNING
Use a two-wrench method when tightening
field piping onto the boiler piping connections.
Use one wrench to prevent the boiler connections from turning and the second to tighten
field piping. Failure to support the boiler piping connections could damage piping, causing
a leak, resulting in substantial property dam-
age, serious injury, or death.
3/4" Street Elbow
Air Vent
Pressure relief valve
(supplied with boiler)
4.2. Pressure Relief Valve
1. The INSTINCT is supplied with a 30 psi pressure relief valve and must be piped using the PRV connec-
tion as shown in Fig. 5below.
NOTICE
In installations where the CH pressure exceeds
30 psi, a 50 psi relief valve (not included) can be
installed in lieu of the 30 psi relief valve.
2. To avoid potential water damage to the surrounding area or potential scalding hazard due to the operation of the relief valve, the discharge piping:
• Must be connected to the discharge outlet of the
relief valve and directed to a safe place of disposal.
• Length should be as short and direct as possible.
The size of the discharge line must not be reduced,
maintain the same size as the outlet of the relief
valve.
• Must be directed downward towards the oor
at all times. The piping should terminate at
least 6 inches [153 mm] above any drain connection to allow clear visibility of the discharge.
• Must terminate with a plain end, not with a threaded
end. The material of the piping must have a serviceable temperature rating of 250ºF or greater.
• Must not be subject to conditions where freez-
ing could occur.
• Must not contain any shut-o valves or ob-
structions. No shut-o valve should be piped
between the boiler and relief valve.
WARNING
Failure to comply with the guidelines on
installing the pressure relief valve and discharge piping can result in substantial prop-
erty damage, serious injury, or death.
CHAPTER 4
Drain
piping
directed to
a suitable
place of
drainage
This boiler is supplied with a special automatic air vent that will provide reliable operation
in purging air from the boiler. The hygroscopic
cap supplied with the automatic air vent MUST
remain tight at all times on the air vent body.
The hygroscopic cap has a membrane which
expands upon contact with water and seals
the air vent until the membrane dries up due to
new air forming in the air vent.
1. Make sure to fully tighten the cap on the air vent
during initial installation.
2. Never loosen the hygroscopic cap to allow air to escape
the air vent. Air will exit with the cap fully tightened in
place.
3. If the hygroscopic cap is not fully tightened, water
may leak from the cap. Simply tighten the cap securely.
4.4. Low Water Cutoff Device
• The INSTINCT is equipped with a factory installed
pressure sensor type Low Water Cut O (LWCO).
• The minimum operating system pressure is 10 psi.
In the event that the pressure falls below 10 psi the
burner will deactivate until proper pressure has
been restored.
• Check local codes if a Low Water Cuto is required.
If so, determine if this device meets their requirements.
NOTICE
The INSTINCT control system also senses the
water temperatures entering and exiting the
heat exchanger to provide protection against
low water conditions. Where local codes and
jurisdiction do not accept a pressure device for
low water protection, the jurisdiction may accept this INSTINCT integral control function as
If a separate Low Water Cut O (LWCO) is required by
the local jurisdiction or when the boiler is installed
above the system piping, the following guidelines
must be followed:
• The LWCO must be designed for water installations,
electrode probe-type is recommended.
• The LWCO must be installed in a tee connection on
the boiler supply piping above the boiler.
• Wiring of the LWCO to the INSTINCT is done directly
onto the low voltage terminal strip. Reference Fig. 30 on page 46 for available external limit (manual
or auto reset) terminals.
If the installation is to comply with ASME or Canadian
requirements, an additional high temperature limit
may be required. Consult local code requirements to
determine compliance. The limit should be installed as
follows:
• Install the limit in the boiler supply piping between
the boiler and any isolation valve.
• Consult heat exchanger for maximum temperature
set point.
• For wiring of the limit, reference Fig. 30 on page
46. Wire the limit to the manual reset terminals
on the low voltage terminal strip. An open manual
reset limit will require a manual reset of the control.
4.6. Backflow Preventer
• Use a backow preventer valve in the make-up water supply to the unit as required by local codes.
4.7. INSTINCT Solo Boiler System Piping
BEST PRACTICE
• It is recommended on all piping applica-
tions to utilize a primary/secondary piping
arrangement as a means to provide freeze
protection of the boiler, which is an integral
function of the boiler control. Maintain at
least the minimum boiler flow rate shown
in the Graphs of Chapter 19 on page 101.
For other piping arrangements, contact
Triangle Tube Technical Support or consult other approved/recognized design ar-
rangements.
• On piping applications utilizing a single zone
or other recognized piping design arrangements, it is recommended that the installer
uses flow/check valves with weighted seats at
or near the INSTINCT Solo to prevent gravity
circulation.
CHAPTER 4
Cold
Water
Fill
System
Supply
Boiler
Supply
Fig. 8 - INSTINCT Solo Near Boiler Piping - Diaphragm Expansion Tank
Boiler
Return
12"
Max
System
Return
17
Page 30
CHAPTER 4 - BOILER PIPING
Boiler
Supply
Boiler
Return
System
Supply
Cold
Water
Fill
System
Return
12"
Max.
CHAPTER 4
4.7.1 Expansion Tank and Makeup Water
Ensure the expansion tank is properly sized for the boiler volume:
• 2 gallons [8 L] for the INSTINCT Solo 110
• 3 gallons [12 L] for the INSTINCT Solo 155
• 4 gallons [15 L] for INSTINCT Solo 199
the system water volume, and the system water temperature.
CAUTION
Undersized expansion tanks will cause system
water to be lost through the pressure relief
valve and cause additional makeup water to be
added to the system. Eventual boiler heat exchanger failure can result due to this excessive
makeup water addition.
The expansion tank must be located as shown in Fig.
8 on page 17 and Fig. 9 below, when using a prima-
ry/secondary piping arrangement or as per recognized
design methods. Refer to the expansion tank manufacturer for additional installation details.
Connect the expansion tank to an air separator only if
the air separator is located on the suction side (inlet)
of the system circulator. Always locate and install the
system ll connection at the same location as the expansion tank connection to the system.
4.7.2 Diaphragm Expansion Tank
Always install an automatic air vent on top of the air
separator to remove residual air from the system.
4.7.3 Closed-Type Expansion Tank
It is recommended to pitch any horizontal piping upwards toward the expansion tank 1 inch per 5 feet of
piping. Use 3/4” piping to the expansion tank to allow
air within the system to rise.
NOTICE
DO NOT install automatic air vents on a closedtype expansion tank system. Air must remain
in the system and be returned to the expansion
tank to provide an air cushion. An automatic air
vent would cause air to be vented from the system resulting in a water-logged expansion tank.
4.7.4 Circulator
A circulator with ow check must be utilized with the
INSTINCT Solo. The circulator, when wired directly to
the INSTINCT, will allow for domestic hot water priority
and provide circulation for the freeze protection feature
of the boiler control. See the Graphs in Chapter 19 on page 101 for pressure drop and minimum ow rate
through the boiler.
18
System
Supply
Boiler
Supply
Fig. 9 - Near Boiler Piping - Closed Type Expansion Tank
Boiler
Return
12" Max
System
Return
Cold
Water
Fill
Page 31
CHAPTER 4 - BOILER PIPING
4.7.5 Sizing Primary Piping
See Fig. 12 on page 24 through Fig. 14 on page 26,
for recommended piping arrangements based on various applications. Size the piping and system components required in the space heating system using recognized design methods.
4.7.6 Domestic Hot Water System Piping
See Fig. 12 on page 24 through Fig. 14 on page 26
for recommended piping to a DHW system. This recommended piping conguration ensures priority is given
to the production and recovery of DHW.
The piping for DHW is separate from the boiler system
piping and does not require a primary / secondary piping conguration.
To wire the DHW circulator to the boiler control module, reference Chapter 8 on page 45.
4.7.7 System Piping – Zone Circulators
Connect the INSTINCT Solo to the system piping as
shown in Fig. 13 on page 25 when zoning with zone
circulators.
The installer must provide a separate circulator for each
zone of space heating.
4.7.9 System Piping – Through Boiler
Primary / secondary piping is preferred, but is not required
for smaller systems (1 to 3 zones) provided that at least the
minimum ow rate through the boiler is maintained at all
times. The circulator must be sized to overcome the pressure drop through the system as well as the INSTINCT Solo.
See the Graphs in Chapter 19 on page 101 for pressure
drop and minimum ow rate through the boiler.
Fig. 13 on page 25 illustrates a multiple zone valve
system with a single system/boiler circulator. A by-pass
loop with a pressure dierential valve must be installed
on the system piping.
Fig. 14 on page 26 illustrates a single zone system
utilizing the boiler circulator as the system circulator.
4.7.10 System Piping – Radiant Heating
The heat exchanger design of the INSTINCT Solo allows
operation in a condensing mode. This feature requires
no regulation of the return water temperature back to
the boiler in radiant heating applications. The design and
construction of the INSTINCT Solo heat exchanger allows
the installation of the boiler on systems with non - oxygen
barrier tubing.
NOTICE
CHAPTER 4
NOTICE
To ensure an adequate flow rate through the
INSTINCT Solo, the boiler supply and return piping size must be a minimum of 1 inch for the
INSTINCT Solo 110, 1-1/4 inch for the INSTINCT
Solo 155/199.
4.7.8 System Piping – Zone Valves
Connect the INSTINCT Solo to the system piping when
zoning with zone valves.
NOTICE
To ensure an adequate flow rate through the
INSTINCT Solo, the boiler supply and return piping size must be a minimum of 1 inch for the
INSTINCT Solo 110, 1-1/4 inch for the INSTINCT
Solo 155/199.
DO NOT install a SMART indirect water heater along
with the INSTINCT Solo in systems with non-oxygen
barrier tubing. Failure to comply will result in prema-
ture failure of the SMART indirect water heater.
The boiler water supply temperature can be maintained
by the INSTINCT Solo, potentially eliminating the need for
a mixing system to achieve the desired temperature if all
zones of heat require the same temperature setpoint.
It is recommended to install a high temperature limit to ensure that the primary supply temperature does not exceed
the maximum allowable temperature for the radiant tubing.
NOTICE
The addition of a high temperature limit is important if the INSTINCT Solo is connected to a
domestic hot water system, which requires a
high primary supply water temperature.
Size the system piping and circulator to provide the
ow needed for the radiant system.
NOTICE
To ensure an adequate flow rate through the INSTINCT Solo, the boiler supply and return piping
size must be a minimum of 1 inch for the INSTINCT
Solo 110, 1-1/4 inch for the INSTINCT Solo 155/199.
19
Page 32
CHAPTER 4 - BOILER PIPING
N G L
CHAPTER 4
L N G L N G L N G L N G
+
Boiler 1 (Master)
Boiler 1 (Master)
ModbusDHW Sensor
- G
3 2
or
aquastat
Sensor
CH1CH2
1 4 3 2 1 2 11
+
Signal
-
Modulation
X5X6X4X7
System Outdoor
6 5 4 3 2
ThermostatThermostatSensor
ZV1
DHW PUMP
SUPPLY CH PUMP
FLAME
DHW PUMP
DHW PUMP
CH
SUPPLY CH PUMP
FLAME
+
ModbusDHW Sensor
- G
3 2
Boiler 2 (Slave)
Boiler 2 (Slave)
or
aquastat
Sensor
Outdoor
CH1CH2
13 2 1 2 11
+
Signal
-
Modulation
X5X6X4X7
Sensor
System
6 5 4 3 24
ThermostatThermostat
L N G L N G L N G L N G
Slave
Slave
Cascade
Cascade
Boiler 3 (Slave)
Boiler 3 (Slave)
Back of Display Panel
Back of Display Panel
Master
Master
Cascade
Cascade
1
23
1 2
X16
3 4
X7
X15
1 2 3
4 5 6
Main Control Board
Main Control Board
P3DHW
P3CH DHW
DHW S
ensor
HW Sen
sor
D
Out
door S
ensor
Outd
oor Se
nsor
From Zone Panel
Heating Call
Master
Master
Cascade
Cascade
ystemem S
ensor
S
Syst
Sens
or
Main Control Board
Main Control Board
ZV2
ZV3
123
1 2
X16
3 4
X7
X15
1 2 3
4 5 6
ZV4
SUPPLY CH PUMP
FLAME
L N G L N G L N G L N G
Slave
Slave
Cascade
+
Modbus
- G
3 2
or
aquastat
DHW Sensor
Sensor
Outdoor
CH1CH2
1 4 3 2 1 2 11
+
Signal
-
Modulation
X5X6X4X7
Sensor
System
5 4 3 2
6
ThermostatThermostat
Cascade
Back of Display Panel
Back of Display Panel
CH
CH
DHW
DHW
P3
P3
Sensor
System
Sensor
System
Optional Extra Required: Lead from X15 on 1 boiler to X16 on the next boiler
Optional Extra Required: Lead from X15 on 1 boiler to X16 on the next boiler
20
Fig. 10 - 3 Boiler Cascade, 1 System Pump, 1 CH Pump and 1 DHW Pump (Manual Pump Conguraiton)
Page 33
Boiler
Supply
Boiler
Return
System
Supply
Cold
Water
Fill
System
Return
12"
Max.
CHAPTER 4 - BOILER PIPING
4.7.11 System Piping – Special Application
If the boiler is used in conjunction with a chilled water/
medium system, the boiler and chiller must be piped in
parallel. Install ow/check valves to prevent the chilled
medium from entering the boiler.
If the boiler is used to supply hot water to the heating
coils of an air handler where they may be exposed to
chilled air circulation, install ow/check valves or other
automatic devices to prevent gravity circulation of the
boiler water during cooling cycles.
4.7.12 System Piping – Multiple Units Installation
Use a balanced manifold system as the primary / secondary connection to the space heating piping.
For the space heating piping, refer to the applications
mentioned in this manual or use recognized design
methods.
4.8. INSTINCT Combi Boiler System Piping
BEST PRACTICE
It is recommended on all piping applications
to utilize a primary/secondary piping arrangement as a means to provide freeze protection of
the boiler, which is an integral function of the
boiler control. Maintain at least the minimum
boiler flow rate shown in the Graphs of Chapter 19 on page 101. For other piping arrangements, contact Triangle Tube Technical Support
or consult other approved/recognized design
arrangements.
On piping applications utilizing a single zone or
other recognized piping design arrangements,
it is recommended that the installer uses flow/
check valves with weighted seats at or near the
INSTINCT Combi to prevent gravity circulation.
CHAPTER 4
System
Supply
Boiler
Supply
Fig. 11 - INSTINCT Combi Near Boiler Piping - Diaphragm Expansion Tank
Boiler
Return
12" Max.
System
Return
Cold
water ll
21
Page 34
CHAPTER 4 - BOILER PIPING
CHAPTER 4
4.8.1 Expansion Tank and Makeup Water
Ensure the expansion tank is properly sized for the boiler volume:
• 3 gallons [12 L] for the INSTINCT Combi 155
• 4 gallons [15 L] for the INSTINCT Combi 199
the system water volume, and the system water temperature.
CAUTION
Undersized expansion tanks will cause system
water to be lost through the pressure relief
valve and cause additional makeup water to
be added to the system. Eventual boiler heat
exchanger failure can result due to this exces-
sive makeup water addition.
The expansion tank must be located as shown in Fig. 11
on page 21 when using a primary/secondary piping
arrangement. Refer to the expansion tank manufacturer for additional installation details.
Connect the expansion tank to an air separator only if
the air separator is located on the suction side (inlet)
of the system circulator. Always locate and install the
system ll connection at the same location as the expansion tank connection to the system.
4.8.3 Circulator
The INSTINCT Combi is supplied with a Boiler circulator
that provides circulation for central/space heating(CH)
and Domestic Hot Water (DHW) production. See the
Graph 1 on page 112 .
4.8.4 Sizing Primary Piping
See Fig. 12 on page 24 through Fig. 14 on page 26,
for recommended piping arrangements based on various applications. Size the piping and system components required in the space heating system using recognized design methods.
4.8.5 System Piping – Zone Circulators
Connect the INSTINCT Combi to the system piping as
shown in when zoning with zone circulators.
The installer must provide a separate circulator for each
zone of space heating.
NOTICE
To ensure an adequate flow rate through the
INSTINCT Combi, the boiler supply and return
piping size must be a minimum of 1-1/4 inch
for the INSTINCT Combi 155/199.
CAUTION
The expansion tank must be located directly on
the INSTINCT Combi return pipe, before the return check valve. Incorrect expansion tank location will cause system water to be lost through
the pressure relief valve and cause additional
makeup water to be added to the system. Eventual boiler heat exchanger failure can result due
to this excessive makeup water addition.
4.8.2 Diaphragm Expansion Tank
Always install an automatic air vent on top of the air
separator to remove residual air from the system.
4.8.6 System Piping – Zone Valves
Connect the INSTINCT Combi to the system piping as
shown in Fig. 12 on page 24 when zoning with zone
valves.
NOTICE
To ensure an adequate flow rate through the
INSTINCT Combi, the boiler supply and return
piping size must be a minimum of 1-1/4 inch
for the INSTINCT Combi 155/199.
22
Page 35
CHAPTER 4 - BOILER PIPING
4.8.7 System Piping – Through Boiler
Primary / secondary piping is preferred, but is not required for smaller systems (1 to 3 zones) provided that
at least the minimum ow rate through the boiler is
maintained at all times. The internal circulator must be
able to overcome the pressure drop through the system as well as the INSTINCT Combi. See the Graphs on page 112 for pressure drop and minimum ow rate
through the boiler.
Fig. 13 on page 25 illustrates a multiple zone valve
system with a single system/boiler circulator. A by-pass
loop with a pressure dierential valve must be installed
on the system piping.
Fig. 14 on page 26 illustrates a single zone system
utilizing the boiler circulator as the system circulator.
4.8.8 System Piping – Radiant Heating
The heat exchanger design of the INSTINCT Combi allows operation in a condensing mode. This feature requires no regulation of the return water temperature
back to the boiler in radiant heating applications. The
INSTINCT CANNOT be installed with non-oxygen barrier tubing.
The boiler water supply temperature can be maintained by the INSTINCT Combi, potentially eliminating
the need for a mixing system to achieve the desired
temperature if all zones of heat require the same temperature setpoint.
It is recommended to install a high temperature limit to
ensure that the primary supply temperature does not
exceed the maximum allowable temperature for the
radiant tubing.
NOTICE
To ensure an adequate flow rate through the
INSTINCT Combi, the boiler supply and return
piping size must be a minimum of 1-1/4 inch
for the INSTINCT Combi 155/199.
4.8.9 System Piping – Special Application
If the boiler is used in conjunction with a chilled water/
medium system, the boiler and chiller must be piped in
parallel. Install ow/check valves to prevent the chilled
medium from entering the boiler.
If the boiler is used to supply hot water to the heating
coils of an air handler where they may be exposed to
chilled air circulation, install ow/check valves or other
automatic devices to prevent gravity circulation of the
boiler water during cooling cycles.
4.9. Optional System Piping and Cascading
CHAPTER 4
Several additional congurations (mixing device, cascading, etc.) are possible with INSTINCT Solo and Combi Units, provided an optional wiring kit is used. Please
refer to Fig. 10 on page 20 for more information.
NOTICE
The addition of a high temperature limit is important if the INSTINCT Combi is connected to
a domestic hot water system, which requires a
high primary supply water temperature.
Size the system piping and circulator to provide the
ow needed for the radiant system.
23
Page 36
CHAPTER 4
CHAPTER 4 - BOILER PIPING
PRESET PUMP CONFIGURATION INSTINCT COMBI
Heat CallDHW PumpCH PumpFlame
CH1OFFONON
CH2OFFONON
DHWONONOFF
NOTICE
• Consult the INSTINCT CTRLMax Control Supplement for information on setting the
required Preset Pump Configuration.
Low Voltage Terminals
Low Voltage Terminals
CH2
System
Thermostat
6 5
Modulation
Sensor
Signal
-+
4 3
2 1
Dry Contact
Dry Contact
Zone Valve
ZoneValve
End Switches
EndSwitches
CH1
CH2
Thermostat
Thermosta
t
4 3
Z.V.
External Limit
ExternalLimit
Terminals
Terminals
Manual Auto
Outdoor
DHW
Sensor or
Aquastat
2 1
DHW Sensor
DHW Sensor
Modbus
+ G 3 2 1
Sensor
2 1
X6X5
OutdoorSensor
Outdoor Sensor
ManualAuto
X7X4
Z.V.
Line Voltage Terminals
LineVoltageTerminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
24
Fig. 12 - INSTINCT Combi System Piping - Zoning w Valves
Page 37
CHAPTER 4 - BOILER PIPING
PRESET PUMP CONFIGURATION INSTINCT COMBI
Heat CallDHW PumpCH PumpFlame
CH1OFFONON
CH2OFFONON
DHWONONOFF
Consult the INSTINCT CTRLMax Control Supplement for information on setting the re-
Low Voltage Terminals
Low Voltage Terminals
CH2
System
Modulation
CH1
Outdoor
Thermostat
Sensor
6 5
4 3
Dry Contact
Dry Contact
Zone Valve End
Zone Valve
Switches
End Switches
Signal
-+
2 1
CH2
Thermostat
Thermosta
t
4 3
Sensor
2 1
X6X5
NOTICE
quired Preset Pump Configuration.
External Limit
ExternalLimit
DHW
Sensor or
Aquastat
2 1
Modbus
+ G 3 2 1
X7X4
Terminals
Terminals
Manual Auto
ManualAuto
LineVoltageTerminals
Line Voltage Terminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
CHAPTER 4
DHW Sensor
DHW Sensor
OutdoorSensor
Outdoor Sensor
Z.V.
Z.V.
Fig. 13 - INSTINCT Combi - System Piping - Multi Zone Valve - Single Circulator
25
Page 38
Low Voltage Terminals
OutdoorSensor
DHW Sensor
CH2
Thermostat
6 5
System
Sensor
4 3
Modulation
Signal
-+
2 1
CH2
Thermosta
t
CH1
Thermostat
4 3
Outdoor
Sensor
2 1
DHW
Sensor or
Aquastat
2 1
Modbus
+ G 3 2 1
X7X4
X6X5
ExternalLimit
Terminals
Manual Auto
68
Line Voltage Terminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
CHAPTER 4 - BOILER PIPING
PRESET PUMP CONFIGURATION INSTINCT COMBI
Heat CallDHW PumpCH PumpFlame
CH1OFFONON
CH2OFFONON
DHWONONOFF
Consult the INSTINCT CTRLMax Control Supplement for information on setting the re-
NOTICE
quired Preset Pump Configuration.
CHAPTER 4
Low Voltage Terminals
External Limit
Terminals
Line Voltage Terminals
Manual Auto
DHW Sensor
Outdoor Sensor
26
Fig. 14 - INSTINCT Combi - System Piping - Single Zone with Single Circulator
Page 39
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
5.1. Domestic Piping Pressure Relief Valve
CAUTION
To reduce risk of excessive pressures and
temperatures in the water heater, install temperature and pressure protective equipment
required by local codes, but no less than a combination temperature and pressure relief valve
certified by a nationally recognized testing laboratory that maintains periodic inspection of
production of listed equipment or materials, as
meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water
Supply Systems, ANSI Z21.22. This valve must
be marked with a maximum working pressure
of the water heater.
Failure to comply with this instruction can re-
sult in minor property damage, or injury.
The INSTINCT Combi domestic circuit must be protected with a pressure relief valve (150 psi).
5.1.1 Standard Installation
Install pressure relief valve as shown in Fig. 15.
Pressure relief valve
(eld supplied
5.1.2 Pressure Relief Valve - Standard Installations
The domestic water heater (if utilized) shall have a
eld supplied pressure relief valve installed within 6”
[152mm] of the DHW hot outlet connection with the
relief valve spindle installed in the vertical position.
The domestic water heater (if utilized) requires a eld
supplied pressure relief valve identied with the ASME
V or HV symbol and set to relieve at or below 150 psi
[10 bar] of domestic water pressure and a minimum relieving capacity of 199,000 Btu/hr with 3/4” NPT threads.
For safe operation of the domestic water heater, the relief valve must not be removed from its designated location of installation or plugged.
1. The INSTINCT is not supplied with a 150 psi [10bar]
pressure relief valve and must be piped using a
pressure relief valve connected as shown in Fig. 15
on page 27
2. To avoid potential water damage to the surround-
ing area or potential scalding hazard due to the operation of the relief valve, the discharge piping:
• Must be connected to the discharge outlet of
the relief valve and directed to a safe place of
disposal.
• Length should be as short and direct as possible. The size of the discharge line should not be
reduced, maintain the same size as the outlet of
the relief valve.
• Should be directed downward towards the
oor at all times. The piping should terminate
at least 6 inches [152mm] above any drain connection to allow clear visibility of the discharge.
• Should terminate with a plain end, not with a
threaded end. The material of the piping should
have a serviceable temperature rating 250°F
[121°C] or greater.
• Should not be subject to conditions here freezing could occur.
• Should not contain any shut-o valves or obstructions. No shuto valves should be piped
between the appliance and relief valve.
CHAPTER 5
Domestic connection
with Tee tting
Fig. 15 - Standard Installation of the Pressure Relief Valve
Domestic
Hot Water
Supply
WARNING
Failure to comply with the guidelines on
installing the pressure relief valve and discharge piping can result in substantial prop-
erty damage, serious injury or death.
27
Page 40
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
CHAPTER 5
5.1.3 Pressure Relief Valve Discharge Piping
Pressure relief valve discharge piping must be:
• Made of material serviceable for temperatures
of 250ºF or greater.
• Directed so that hot water ows away from all
persons.
• Directed to a suitable place for disposal.
• Installed so as to allow complete draining of the
pressure relief valve and discharge line.
Pressure relief valve discharge piping must not be:
• Excessively long. Using more than 2 elbows or
15 feet of piping can reduce discharge capacity.
• Directly connected to a drain. Terminate discharge piping within 6” from drain. Refer to local codes.
• Plugged, reduced or restricted.
• Subject to freezing.
WARNING
Do not install any valve between pressure relief valve and tank connection or on
pressure relief valve discharge piping. Do
not plug pressure relief valve or discharge
piping. Improper placement and piping of
T&P relief valve can cause severe personal in-
jury, death or substantial property damage.
5.2. Thermal Expansion
If a backow preventer, check valve or pressure reducing valve is piped on cold water supply piping of water
heater, install an expansion tank on cold water supply
line to prevent thermal expansion from repeatedly forcing open pressure relief valve.
NOTICE
The pressure relief valve is not intended for constant duty, such as relief of pressure due to repeated normal thermal expansion. Correct this
condition by installing a properly sized expansion tank in the domestic water system. Refer
to expansion tank manufacturer’s installation
instructions for proper sizing.
28
Page 41
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
5.3. Water Hammer
Dishwashers, clothes washers and fast-closing positive
shut-o valves incorporated in the system all contribute to creating water shock. Install a water hammer arrester to prevent damage to pipes and appliances. See
device manufacturer’s instructions for application and
installation.
NOTICE
Water hammering within the domestic piping
system can cause premature failure of the domestic circuit of the boiler. This type of failure is
NOT covered under warranty.
5.4. Vacuum Breaker
Installing a vacuum breaker on the domestic cold water inlet will prevent damage to the domestic circuit if
a negative pressure is developed in the domestic supply line. See manufacturer’s instructions for application
and installation of the vacuum breaker.
5.5. Hydro-Block
The domestic circuit provides domestic hot water
through a hydro-block. It is made of a plate-to-plate
heat exchanger and connections to the primary and
domestic piping. Water heated in the primary circuit
(central heating) ows into the plate-to-plate heat exchanger, which in turn heats the domestic water owing through it in its own circuit. Refer to Fig. 16 below
for ow diagram.
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
CHAPTER 5
5.6. General Piping
• For domestic water piping diagrams, see Fig. 17 on
page 31.
• All plumbing must meet or exceed all local, state
and national plumbing codes.
• Use pipe dope or tape suitable for potable water
systems.
• Use isolation valves to isolate system components.
• Use dielectric unions or couplings to protect hot
and cold water ttings from corrosion when connecting dissimilar materials such as copper and galvanized iron pipe.
• When the water supply pressure is higher than 70
psig, it is recommended to install a pressure reducing valve on cold water supply line to prevent water loss through T&P relief valve.
5.7. Thermostatic Mixing Valve
A thermostatic mixing valve must be installed in the
DHW circuit.
The operating range of the thermostatic mixing is 85ºF
[30ºC] to 150ºF [65ºC].
For applications with a domestic recirculation loop, the
recirculation pump should be controlled by an aquastat.
The maximum recommended setting of the aquastat is
10ºF lower than the thermostatic mixing valve setting.
If any adjustment needs to be made to the valve’s temperature setpoint, refer to the manufacturer’s instructions included with the valve.
5.8. Storage Tank Installation
For applications requiring high domestic hot water ow
rates for a short period of time (dump load), the installer may install a storage type tank (see Fig. 18 on page
32) in the domestic piping.
The installer must :
1. Relocate the thermostatic mixing valve from the INSTINCT to the outlet of the storage tank.
2. Remove domestic restrictor at the inlet of the domestic ow sensor.
3. Provide recirculation from the storage tank back to
the INSTINCT using a bronze or stainless steel circulator.
DANGER
For proper operation of the thermostatic
mixing valve and to prevent potential scalding hazards, the recirculation loop should be
controlled by an aquastat. DO NOT use con-
tinuous recirculation.
Failure to comply with this instruction will re-
sult in serious injury, or death.
30
Page 43
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
PRESET PUMP CONFIGURATION 5 - INSTINCT COMBI UNITS
Heat CallFlameCH PumpDHW Pump
CH1ONONOFF
CH2ONONOFF
DHWOFFONON
NOTICE
Consult the INSTINCT CTRLMax Control Supplement for information on setting the re-
quired Preset Pump Configuration.
Low Voltage Terminals
CH2
System
Sensor
4 3
Modulation
Signal
-+
2 1
Thermostat
6 5
CH1
CH2
Thermostat
Thermosta
t
4 3
External Limit
Terminals
Outdoor
DHW
Sensor or
Aquastat
2 1
Modbus
+ G 3 2 1
DHW Sensor
Sensor
2 1
X6X5
Outdoor Sensor
Manual Auto
X7X4
DHW
Line Voltage Terminals
Line Voltage Terminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
12" min Heat Trap
12" min
HeatTrap Loop
Loop (Optional)
(Optional)
CHAPTER 5
Outlet
Fig. 17 - INSTINCT Combi System Piping - Single Zone System with Single System/Boiler Circulator
31
Page 44
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
PRESET PUMP CONFIGURATION 5 - INSTINCT COMBI UNITS
Heat CallFlameCH PumpDHW Pump
CH1ONONOFF
CH2ONONOFF
DHWOFFONON
NOTICE
Consult the INSTINCT CTRLMax Control Supplement for information on setting the re-
quired Preset Pump Configuration.
External Limit
X7X4
ExternalLimit
Terminals
Terminals
Manual Auto
ManualAuto
Line Voltage Terminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
Low Voltage TerminalsLine Voltage Terminals
Low Voltage Terminals
CH2
System
Sensor
4 3
Modulation
Signal
-+
2 1
Thermostat
6 5
CH1
CH2
Thermostat
Thermosta
t
4 3
X6X5
Outdoor
Sensor
2 1
DHW
Sensor or
Aquastat
2 1
Modbus
+ G 3 2 1
CH PUMP
DHW PUMP
CHAPTER 5
DHW
DHW
Outlet
Outlet
OutdoorSensor
Outdoor Sensor
DHW Sensor
DHW Sensor
Storage
Storage
Tank
Tank
12" min heat trap
12" min
loop (optional)
HeatTrap Loop
(Optional)
32
Fig. 18 - INSTINCT Combi System Piping - Domestic piping - Storage tank installation
Page 45
TITLE
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
External Limit
CH2
Thermostat
6 5
Low Voltage Terminals
LowVoltageTerminals
System
Sensor
4 3
Modulation
Signal
-+
2 1
CH1
CH2
Thermostat
Thermosta
t
4 3
X6X5
Outdoor
Sensor
2 1
Sensor or
Aquastat
2 1
DHW
Modbus
+ G 3 2 1
X7X4
External Limit
Terminals
Terminals
ManualAuto
AutoManual
Line Voltage Terminals
Line Voltage Terminals
Outdoor Sensor
Outdoor Sensor
DHWSensor
DHW Sensor
SLAVE
MASTER
1 2 3 4
EXPANSION
RESETNORMAL
PLUG IN CARDS
MODE
L N G L N G L N G L N G
FLAME POW ER SUPPLY
CH PUMP
120V/15A
Service
Zone 1
Thermostat
Zone 2
Thermostat
Thermostat
6868
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
Zone 3
68
ZONE4ZONE3ZONE2ZONE1
DHW PUMP
DHWCH
ZONE 4
PRIORITY
ON
OFF
CHAPTER 5
X X
END
ZRZC
SWITCH
FUSE 1 AMP
Zone 1
Thermostat
Fig. 19 - Multiple Zones - Panel Wiring with Circulators
ZONE2ZONE1
120 VOLT CIRCULATORS
Zone 2
Thermostat
ZONE3
Zone 3
Thermostat
ZONE4
120 VAC
POWER
INPUT
INPUT
(H & N)
33
Page 46
CHAPTER 5 - INSTINCT COMBI UNITS - DOMESTIC PIPING
External Limit
Low Voltage Terminals
LowVoltageTerminals
CH2
System
Sensor
4 3
Modulation
Signal
-+
2 1
Thermostat
6 5
CH1
CH2
Thermostat
Thermosta
t
4 3
X6X5
Outdoor
Sensor
2 1
DHW
Sensor or
Aquastat
2 1
Modbus
+ G 3 2 1
X7X4
External Limit
Terminals
Terminals
ManualAuto
AutoManual
Line Voltage Terminals
Line Voltage Terminals
CHAPTER 5
L N G L N G L N G L N G
FLAME POWER SUPPLY
120V/15A
DHWSensor
DHW Sensor
Outdoor Sensor
Outdoor Sensor
Zone 1
Thermostat
68
PLUG-IN
Factory
Installed
Transformer
Factory
Installed
Transformer
POWER
CONTROLS
POWER IN
MODE
RESETNORMAL
ENDSW
B
PUMP
N/ON/ CCOM
ZONE 4 RELAY
1 2 3 4
SLAVE
MASTER
EXPANSION
ENDSW
A
BOILER
CARDS
FUSE 7 AMP MAX
ZONE 1
1 2 3 4
T T
ZONE 1
Service
Zone 2
Thermostat
68
T T
ZONE 2
FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
ZONE 2
1 2 3 4
CH PUMP
Internal
Circulator
Thermostat
ZONE 3
1 2 3 4
DHW PUMP
Zone 3
68
T T
ZONE 3
T T
ZONE 4
ZONE 4
1 2 3 4
ZONE 4
PRIORITY
ON
OFF
34
System
Motor
1
2
End Switch
3
4
Zone 1
Zone Valve
Motor
1
2
End Switch
3
4
Zone 2
Zone Valve
Motor
1
2
End Switch
3
4
Zone 3
Zone Valve
Circulator
Fig. 20 - INSTINCT Combi System Piping - Multiple Zones - Panel Wiring with Valves
Page 47
CHAPTER 5 - INSTINCT SOLO UNITS - DOMESTIC PIPING
External Limit
X7X4
ExternalLimit
Terminals
Terminals
AutoManual
ManualAuto
Line Voltage Terminals
LineVoltageTerminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
Low Voltage Terminals
Low Voltage Terminals
CH2
System
Modulation
CH1
Thermostat
Sensor
6 5
4 3
Dry Contact
Dry Contact
Signal
-+
2 1
CH2
Thermostat
Thermosta
t
4 3
X6X5
Outdoor
Sensor
2 1
OutdoorSensor
Outdoor Sensor
DHW
Sensor or
Aquastat
2 1
DHW Sensor
Modbus
+ G 3 2 1
DHW Sensor
DHW
Z.V.
Z.V.
DHW
Hot
Hot
DHW
smart
DHW
Cold
Cold
CHAPTER 5
Fig. 21 - INSTINCT Solo System Piping - Multi Zone System with Single System/Boiler Circulator
35
Page 48
TITLE
CHAPTER 5 - INSTINCT SOLO UNITS - DOMESTIC PIPING
External Limit
Modbus
X7X4
External Limit
Terminals
Terminals
AutoManual
ManualAuto
Line Voltage Terminals
Line Voltage Terminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
Low Voltage Terminals
Low Voltage Terminals
CH2
System
Modulation
CH1
Outdoor
Thermostat
6 5
Sensor
4 3
Signal
-+
2 1
CH2
Thermostat
Thermosta
4 3
t
X6X5
Sensor
2 1
Outdoor Sensor
DHW
Sensor or
Aquastat
2 1
+ G 3 2 1
DHW Sensor
DHW Sensor
Outdoor Sensor
CHAPTER 5
DHW
68
DHW
Hot
Hot
DHW
DHW
Cold
Cold
smart
36
Fig. 22 - INSTINCT Solo System Piping - Indirect Water Heater installation
Page 49
CHAPTER 5 - INSTINCT SOLO UNITS - DOMESTIC PIPING
TITLE
NOTICE
Cascading is only available on Solo Boilers.
System
Return
12"
Max.
P G
System
Supply
CHAPTER 5
Fig. 23 - Instinct Solo - Cascade Piping
37
Page 50
CHAPTER 6 - INSTALLING VENT/COMBUSTION AIR & CONDENSATE DRAIN
6.1. Installing Vent and Combustion Air
DANGER
The INSTINCT must be vented and supplied
with combustion air as shown in the IN
Vent Supplement, included in the installation envelope. Refer to instructions for parts
list and method of installation.
Once installation is completed, inspect the
vent and combustion air system thoroughly
to ensure systems are airtight, properly supported, and comply with the instructions given in the venting supplement and are within
all requirements of applicable codes. Failure
to comply with the venting and combustion
air piping installation requirements will result in substantial property damage, serious
injury, or death.
STINCT
NOTICE
Contact Triangle Tube for other venting options
including PVC Concentric Vent/Air Termination
and Stainless Steel or PVC Flush Mount Horizontal Terminations. Refer to the instructions includ-
ed with these kits for method of installation.
2. Install the condensate drain assembly on the boiler
condensate drain by pushing the condensate drain
assembly up until it stops.
3. Tighten the condensate drain assembly retaining nut.
WARNING
• Ensure installation of the condensate
drain assembly included the seals. Failure
to comply could result in the assembly
dislocating from the boiler. Dislocation of
the condensate drain assembly can result
in property damage, serious injury, or
• Ensure the condensate drain assembly
contains the plastic ball. Do not install
the condensate drain assembly if the ball
is lost or missing, replace the entire assembly. Installing the condensate drain
assembly without the plastic ball can result in substantial property damage, seri-
4. Remove the compression nut and rubber seal from
the condensate drain assembly drain outlet.
5. Slide the compression nut and rubber seal over the
3/4” x 2’ exible tube provided.
death.
ous injury, or death.
CHAPTER 6
6.2. Installing Condensate Drain Assembly
into INSTINCT Solo Units
NOTICE
The condensate drain assembly is factory-in-
stalled in the INSTINCT Combi units.
1. Locate the condensate drain assembly and ensure
the seals are installed as shown in Fig. 24 on page
39.
NOTICE
The installer may want to fill the condensate
drain assembly with water prior to assembling
on the unit.
WARNING
Do not operate the boiler without the factory-supplied condensate drain assembly
installed. Operation of the boiler without
the condensate drain assembly installed can
result in property damage, serious injury, or
death.
NOTICE
The use of 3/4” PVC or CPVC pipe is also acceptable. If 3/4” pipe is used, deburr and chamfer
pipe to allow mating onto the drain assembly.
6. Thread the rubber seal into the compression nut to ease
installation of the tube to the condensate drain assembly.
7. Seat the tube onto the condensate drain assembly
and tighten the compression nut. Hand tight only!
NOTICE
• The installer may opt to use 13/16” ID tubing in lieu of provided tube.
• The drain line materials must be an ap-
proved material by the authority having
jurisdiction. In absence of such authority,
PVC and CPVC piping must comply with
ASTM D1785 or D2845. The cement and
primer used on the piping must comply
with ASME D2564 or F493. For installations
in Canada, use ULC certified PVC or CPVC
pipe, fittings and cement/primer.
38
Page 51
CHAPTER 6 - INSTALLING VENT/COMBUSTION AIR & CONDENSATE DRAIN
8. Route the tube from the condensate drain assembly to a oor drain or condensate pump.
NOTICE
When selecting and installing a condensate
pump, ensure the pump is approved for use
with condensing appliances. The pump should
be equipped with an overflow switch to prevent
property damage from potential condensate
spillage.
9. The INSTINCT will typically produce a condensate
that is considered slightly acidic with a pH content
below 4.0. Install a neutralizing lter if required by
authority having jurisdiction.
WARNING
The condensate drain assembly must remain
filled with water. Extended periods of non
use or high temperature operation may allow
the water to evaporate. Periodically check
the water level in the condensate drain assembly and fill with water as necessary. Failure to keep the condensate drain assembly
full of water can result in substantial proper-
ty damage, serious injury, or death.
CAUTION
The drain assembly must remain unobstructed
and allow unrestricted flow of condensate. The
condensate should not be subject to conditions
where freezing could occur. If the condensate is
subjected to freezing or becomes obstructed , it
can leak, resulting in potential water damage
to the boiler and surrounding area.
RETAINING NUT
RETENTION
CLIP
FOR SOLO
MODELS ONLY
PLASTIC BALL
NOT SHOWN
CONDENSATE
DRAIN ASSEMBLY
SEALS
FILL PLUG WITH VACCUM
BREAK PORT
COMPRESSION NUT
WITH RUBBER SEAL
Flexible tubing
(or 3/4 PVC/
CPVC Piping to
Drain)
Fig. 24 - Condensate Drain Assembly
RETENTION
CLIP
FOR SOLO
MODELS ONLY
CHAPTER 6
39
Page 52
CHAPTER 7 - GAS PIPING
7.1. Gas Supply Piping Connection
NOTICE
The gas supply piping must be installed in accordance to all applicable local, state, national
codes, and utility requirements.
1. Install a 3/4” NPT for INSTINCT pipe union at the gas
nipple, for ease of service.
nstall a manual shuto valve in the gas supply piping as
2. I
shown in Fig. 25 on the right. For installations in Canada, the
installer must tag and identify the main shuto valve.
3. Install a sediment trap (drip leg) on the gas supply
line prior to connecting to the INSTINCT gas train
as shown in Fig. 25 on the right.
4. Support the gas piping using hangers. Do not support the piping by the unit or its components.
5. Purge all air from the gas supply piping.
6. Before placing the INSTINCT into operation, check
and test all connections for leaks.
• Close the manual shuto valve during any pres-
sure test with less than 13”w.c..
• Disconnect the INSTINCT and its gas valve from
the gas supply piping during any pressure test
greater than 13”w.c..
Union Fitting
Gas Flow
External Manual
Gas Shut O
Ion-ic
186°F
DHW
156°F
Target = 186°F
DHW Demand
Cap
Fig. 25 - Recommended Gas Supply Piping
Valve (Must Be
Within 6” of the
Boiler )
Tee Fitting
Sediment Trap
Min. Length of 3"
CHAPTER 7
WARNING
Do not check for gas leaks with an open flame.
Use a gas detection device or bubble test. Fail
-
ure to check for gas leaks can cause substan-
tial property damage, serious injury, or death.
7. Use pipe dope compatible with natural and propane gases. Apply sparingly only to the male
threads of pipe joints so that pipe dope does not
block gas ow.
WARNING
• Failure to apply pipe dope as detailed
above can result in substantial property
damage, serious injury, or death.
• Use a two-wrench method when tightening field piping onto the boiler piping
connections. Use one wrench to prevent
the boiler connections from turning and
the second to tighten field piping. Failure
to support the boiler piping connections
could damage piping, causing a leak, resulting in substantial property damage,
serious injury, or death.
40
Page 53
CHAPTER 7 - GAS PIPING
7.2. Natural Gas
7.2.1 Pipe Sizing
Refer to Table 2 below for schedule 40 metallic pipe
length and diameter requirements for natural gas,
based on rated INSTINCT input (divide by 1,000 to obtain cubic feet per hour).
• Table 1 is based on Natural Gas with a specic gravity of 0.60 and a pressure drop through the gas piping of 0.30”w.c..
• For additional gas pipe sizing information, refer to
National Fuel Gas Code (NFPA 54 / ANSI Z223.1)
for installations in the U.S. or CAN/CSA B149.1 for
installations in Canada.
7.2.2 Supply Pressure Requirements
1. Pressure required at the gas valve inlet supply pres-
sure port:
• Maximum 13”w.c. at ow or no ow conditions
to the burner.
• Minimum 5”w.c. during ow conditions to the
burner. Must be veried during start up and
with all other gas appliances operating within
the building.
2. Install 100% lockup gas pressure regulator in the
gas supply line if inlet pressure can exceed 13”w.c
at any time. Adjust the lockup pressure regulator
for 13”w.c maximum.
WARNING
DO NOT adjust or attempt to measure gas
valve outlet pressure. The gas valve is factory-set for the correct outlet pressure. This setting is suitable for natural gas and propane
and requires no field adjustment. Attempts
by the installer to adjust or measure the gas
valve outlet pressure can result in damage to
the valve, causing substantial property dam-
age, serious injury, or death.
•
WARNING
The INSTINCT is factory equipped with the required natural gas venturi. The natural gas
venturi must never be modified or replaced
with a different size venturi. Failure to use the
required natural gas venturi can result in substantial property damage, serious injury, or
Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas Per Hour (based
on 0.60 specific gravity, 0.30” w.c. pressure drop)
CHAPTER 7
41
Page 54
CHAPTER 7 - GAS PIPING
7.3. Propane Gas
7.3.1 Pipe Sizing
WARNING
• The unit was shipped with a propane conversion kit which is located on the top of
the unit in the instructions packet. This
kit includes all the necessary parts and
instruction to perform the conversion
from natural to propane gas. If this conversion kit is missing, please contact Triangle Tube Technical Support for missing
kit before installing unit.
• Prior to start up, ensure the unit is set to
fire propane. Check the rating label for
the type of fuel. Check the gas valve for
propane conversion label. If there is a
conflict or doubt on the burner set up, re
move the gas valve and check for the pro-
pane orifice, see Fig. 17 on page 31
Fig. 27 on page 43 and Fig. 28 on page 44.
• Failure to ensure proper burner setup can
result in substantial property damage,
serious injury, or death.
-
and
7.3.2 Supply Pressure Requirements
1. Adjust the propane supply regulator provided by
the gas supplier for 13”w.c. maximum pressure
2. Pressure required at the gas valve inlet supply pressure port:
• Maximum 13”w.c. at ow or no ow conditions
to the burner
• Minimum 8”w.c. during ow conditions to the
burner. Must be veried during start up and
with all other gas appliances operating within
the building.
WARNING
DO NOT adjust or attempt to measure gas
valve outlet pressure. The gas valve is factory-set for the correct outlet pressure. This setting is suitable for natural gas and propane
and requires no field adjustment. Attempts
by the installer to adjust or measure the gas
valve outlet pressure can result in damage to
the valve, causing substantial property dam-
age, serious injury, or death.
CHAPTER 7
• Operating a natural gas INSTINCT boiler
on propane will create excessive and dangerious carbon monoxide levels which
could cause serious injury, or death.
Contact the local propane gas supplier for recommended sizing of piping, tanks and 100% lockup gas regulator.
Note: Propane conversion venturis have an additional yellow label to identify use for propane
The propane gas venturi assembly must never
be modified or replaced with a different assembly. See the below chart for the full specification. Failure to use the required propane gas
venturi assembly can result in substantial prop-
ELECTRICAL SHOCK HAZARD. For your safety, disconnect electrical power supply to the
unit before servicing or making any electrical
connections to avoid possible electric shock
hazard. Failure to do so can cause serious in-
jury, or death.
CAUTION
Prior to servicing, label all wires before disconnecting. Wiring errors can cause improper and
dangerous operation. Verify proper wiring and
operation after servicing.
8.1.1 General Requirements
• Wiring must be N.E.C Class 1.
• If original wiring as supplied with the unit must
be replaced, use only Type T 194ºF [90ºC] wire or
equivalent as a minimum.
• The INSTINCT Solo must be electrically grounded
as required by National Electrical Code (ANSI/NFPA
70) for installations in the U.S., or the Canadian Electrical Code Part 1(CSA C22.1) for installations in Canada.
8.1.2 Fuse Locations
• The CTRLMax control module contains 3 internal
replaceable 5A fuses as shown in Fig. 29 below.
• The top two fuses protect the INSTINCT as well as
the CH, DHW, and Flame outputs.
• Spare fuses are located on the back of the control
module enclosure.
• A 2.5A fuse is also located on the terminal strip, to
protect the output. Refer to Fig. 32 on page 48.
Location of fuses
Fig. 29 - CTRLMax Control Module Fuse Location
CHAPTER 8
45
Page 58
InsnctSolo WiringDiagram
CHAPTER 8 - WIRING
Spark Generator
Spark Generator
Gas Valve
Ignitor
Ignitor
GND
GND
Gas Valve
3
1
1
5
1
Blower
Blower
3
1
R
W
V
BK
5
Key
W = White
BK = Black
R = Red
G= Green
O = Orange
Y = Yellow
BL = Blue
GND
GND
G
W
BK
1 6 3
1
P13
W
BK W BK
P14 1 6 X9 1 4
X12
X10
1
O
1
X1
X3
12
10
Flue
Y
1
Y
R
R
Temperature
Sensor
Supply
Temperature
Sensor
Flue
Temperature
Temperature
Sensor
BL
Supply
Temperature
Sensor
BL
Return
Sensor
Return
Temperature
Sensor
BK
BR
O
1
BR
X2
R
14
O
Y
W
BK
R
3
Manual ResetLimit
Manual Reset Limit
Auto ResetLimit
Auto Reset Limit
Pressure
Water
Sensor
Water
Pressure
Sensor
CHAPTER 8
BK
GND
BK
W
W
BK
W
GND
G
W
BK
46
G
N
L
G
N
L
G
N
L
G
N
L
DHW
Pump
CH
Pump
Power
Supply
Flame
DHW
Pump
CH
Pump
Power
Supply
Flame
X11
X5 1 6X6 1 4
CH2Thermostat
System Sensor
X4
1
Outdoor Sensor
CH1 Thermostat
Modulation Signal
System Sensor
CH2 Thermostat
Modulaon Signal
CH1Thermostat
Outdoor Sensor
DHW Aquastat/Sensor
X7
1 3
DHW Aquastat/Sensor
ModBus
X16
4
Cascade Master
Modbus
Fig. 30 - INSTINCT Solo Boiler Factory Wiring
X15
1
10
6
1
Y
Y
Y
Y
Y
1
Cascade Slave
Cascade Master
Cascade Slave
User
Interface
User
Interface
Page 59
InsnctCombiWiringDiagram
CHAPTER 8 - WIRING
Ignitor
Ignitor
Spark Generator
GND
SparkGenerator
GND
3
Gas Valve
1
1
Gas Valve
Blower
5
Blower
1
Key
1
R
W
V
BK
5
3
W = White
BK = Black
R = Red
G= Green
O = Orange
Y = Yellow
BL = Blue
W
BK
BK
W
BK
GNDG
BK
W
BK W BK
P14 1 6 X9 1 4
X12
X3
R
X1
12
O
X2
14
10
X10
1
1
1
1
BR
O
BK
R
W
Flue
Y
Y
R
R
BR
Y
Temperature
Temperature
Sensor
Supply
Temperature
Temperature
Sensor
Manual Reset Limit
Auto Reset Limit
O
W
BK
3
R
BK
3
Diverter
Valve
Flue
Sensor
Supply
Sensor
Manual ResetLimit
AutoResetLimit
Return
Temperature
Sensor
BL
Water
Pressure
Sensor
DHW
Flow
Sensor
Diverter
Pressure
Valve
Return
Temperature
Sensor
BL
Water
Sensor
DHW
Flow
Sensor
BK
GND
W
G
BK
1 6 3
1
P13
1
X11
10
G
DHW
DHW
N
Pump
Pump
L
G
CH
CH
CH2 Thermostat
N
Pump
Pump
Power
Supply
Flame
L
GNL
G
N
L
Power
Supply
Flame
W
W
Modulation Signal
CH2 Thermostat
X5 1 6 X6 1 4
Outdoor Sensor
CH1 Thermostat
ModulaonSignal
X4
X7
1
Modbus
CH1 Thermostat
Outdoor Sensor
DHW
Sensor
ModBus
DHW
Sensor
X15
X16
4
1 3
6
1
Y
Y
Y
Y
Y
1
User
Interface
User
Interface
CHAPTER 8
Fig. 31 - INSTINCT Combi Boiler Factory Wiring
47
Page 60
CHAPTER 8 - WIRING
8.2. External Wiring
8.2.1 General Requirements
All eld wiring must comply with:
• National Electrical Code (ANSI/NFPA 70) for installations in the U.S., and any other national, state, provincial or local codes or requirements.
• Canadian Electrical Code Part 1 (CSA C22.1) for installations in Canada.
NOTICE
If local electrical codes require an additional service
switch, the installer must provide and install a fused
disconnect or minimum 15 amp service switch.
8.3. External Wiring - INSTINCT Solo Units
8.3.1 Circulator Wiring
CHAPTER 8
WARNING
ELECTRICAL SHOCK HAZARD. For your safety,
disconnect electrical power supply to the unit
before servicing or making any electrical connections to avoid possible electric shock hazard.
Failure to do so can cause serious injury, or death.
NOTICE
The low voltage terminals are located at the
bottom of the CTRLMax control module. The
line voltage terminals are located in the lower
left corner as shown in Fig. 21 below.
8.2.2 Line Voltage Connections
1. Connect a dedicated 120 VAC/15A service to the
line voltage terminals located internally in the lower left corner, as shown in Fig. 32 below.
2. Route the incoming 120 VAC power wires through one
of the provided openings in the bottom jacket panel.
3. The unit is provided with a service switch located
on the front panel, check local code requirements
for compliance.
2.5A Fuse
1. The circulator connections used will depend on the
systems piping layout. See Fig. 17 on page 31 and Fig. 18 on page 32 for common system pip-
ing applications and associated circulator wiring.
Consult the Fig. 10 on page 20 and the INSTINCT
CTRLMax Control Supplement for additional options.
NOTICE
The circulator output is protected by fuses on
the CTRLMax control module. The total combined amp draw of the CH, DHW, and Flame
outputs must not exceed 4 amps at any time
for the INSTINCT 110 and 155 units, or 3 amps
at any time for the INSTINCT 199 units. Use an
isolation relay to lower the total combined amp
draw if exceeding this limits.
2. Connect the CH circulator wiring to the line voltage
terminals located internally in the lower left corner, as
shown in Fig. 32 on the left. This circulator is typically
used to supply heat to the central/space heating loop.
3. Connect the DHW circulator wiring to the line voltage terminals located internally in the lower left
corner, as shown in Fig. 32 on the left. This circulator
is typically used to supply heat to an indirect hot
water heater.
4. Connect the system pump wiring to the line voltage terminals located internally in the lower left
corner, as shown in Fig. 32 on the left.
48
Fig. 32 - Terminal Strip Location
Page 61
CHAPTER 8 - WIRING
8.3.2 Low Voltage Connections
Line and Low Voltage wiring should be separated to
prevent possible electrical noise on the low voltage
circuits. Line and Low Voltage wiring should use separate electrical knockouts on the INSTINCT cabinet and
should remain separated inside the INSTINCT.
NOTICE
CH and DHW call connections to the INSTINCT require a dry contact with no external
voltage present. Ensure no external voltage is
present on each set of wires before connecting
to the INSTINCT. If external voltage is present,
the use of an isolation relay is required to pre-
vent damage to the CTRLMax controller.
8.3.3 Thermostat Wiring
The CTRLMax control has two thermostat call inputs for
multiple zone / temperature systems. This allows each
call to have its own outdoor reset curve and maximizes
the eciency of the system.
NOTICE
Simultaneous CH1 and CH2 calls will result
in the INSTINCT operating at the highest target
temperature.
8.3.4 Outdoor Sensor Wiring
The Outdoor Reset function and Warm Weather Shutdown (WWSD) features require the connection of the
included outdoor temperature sensor. See Chapter 12 on page 75 for outdoor sensor installation and setup.
8.3.5 Domestic Hot Water Wiring
The Domestic Hot Water terminals can accept either a
call from an aquastat (thermostat) or temperature sensor. Use of the included indirect water heater sensor is
recommended.
1. Connect the DHW aquastat or temperature sensor
wires to low voltage terminals X4-1&2 located at the
bottom of the CTRLMax control module as shown
in Fig. 33 on page 49.
8.3.6 Additional Boiler Limits
Additional boiler limits (High Temperature Limit, LWCO,
etc.) can be wired into either the Manual Reset Limit or
Auto Reset Limit terminals of the INSTINCT. These limit connections will provide a “hard” lockout requiring a
manual reset of the INSTINCT or a “soft” lockout in which
the INSTINCT will automatically reset when the limit resets.
A Manual Reset External Limit Open (E87) lockout will
occur anytime the manual reset terminals are open. An
Auto Reset External Limit Open (76) lockout will not occur until just before ignition when the auto reset terminals are open. The Auto Reset terminals should be used
for any type of burner interlock such as a combustion air
louver or water ow proving switch.
Low voltage
connections
Fig. 33 - Low Voltage Connections
External limit
Terminals
NOTICE
• The Manual Reset Limit and Auto Reset
Limit terminals are located on the lower
right corner of the CTRLMax control module housing.
• Manual Reset Limit and Auto Reset Limit
connections to the INSTINCT require a dry
contact with no external voltage present.
Ensure no external voltage is present on
each set of wires before connecting to the
INSTINCT. If external voltage is present, the
use of an isolation relay is required to pre-
vent damage to the CTRLMax controller.
CHAPTER 8
49
Page 62
CHAPTER 8 - WIRING
1. Remove the factory-installed brown jumper wire at
the Manual Reset Limit terminals that will accept
the additional boiler limit.
2. Remove the factory-installed orange jumper wire at
the Auto Reset Limit terminals that will accept the
additional boiler limit.
3. Connect the external limit wires to the Manual Reset
Limit or Auto Reset Limit low voltage terminals located on the lower right corner of the CTRLMax control
module housing as shown in Fig. 33 on page 49.
8.3.7 External Modulation Control
The INSTINCT ring rate can be controlled by an external modulating boiler controller. See Chapter 13 on page 77 for external modulation signal wiring and
setup.
8.3.8 System Sensor Wiring
An optional system temperature sensor can be placed
on the central heating loop to control the temperature
in the central heating loop instead of the boiler loop.
When connected, the INSTINCT will automatically modulate to maintain the target temperature in the central
heating loop. The boiler supply temperature sensor will
continue to be used as a high temperature limit.
8.3.9 Cascade Wiring - Optional
The CTRLMax control includes the ability to operate up
to six Solo boilers together as one without the need for
external controllers. Consult the Fig. 10 on page 20
for more information.
8.3.10 Modbus
The CTRLMax control includes the ability to communicate with building management systems (BMS) through
a Modbus interface. Consult the INSTINCT CTRLMax
Control Supplement for more information.
Modbus communication will only occur if the external
device is properly wired to the INSTINCT as follows:
Locate the system temperature sensor where
it can accurately measure the supply temperature
to the heating system. Inaccurate system temperature readings could lead to overheating or
under heating resulting in property damage.
1. Connect the system temperature sensor wires to
low voltage terminals X5-3&4 located at the bottom
of the CTRLMax control module as shown in Fig. 33
on page 49.
50
Page 63
CHAPTER 9 - CTRLMAX OPERATION
The CTRLMax Boiler Management System is designed
to be exible yet easy to use. CTRLMax monitors and
controls the INSTINCT to provide heat as eciently as
possible. CTRLMax includes many advanced features:
• Two central/space heating (CH) call inputs with
separate outdoor reset curves.
• Domestic Hot Water (DHW) call input with optional
priority in INSTINCT Solo units and DHW priority in
INSTINCT Combi units.
• EZ Setup feature allows the installer to quickly customize CTRLMax for each installation.
• Optional cascade function (Solo models only), using
an optional wiring kit, allows up to six INSTINCT boilers to operate together in a single heating system.
Refer to Fig. 10 on page 20 for more information.
• Modbus interface for integrating with building
management systems.
All CTRLMax features are easy to use through a graphical display where information is presented either graphically or in plain English, so code charts are not required.
Fig. 34 below shows an CTRLMax display example of
the INSTINCT red for a domestic hot water demand.
9.1. CTRLMax Navigation
The CTRLMax navigation is performed through soft keys
that react to the touch and emit a short beep when tapped.
NOTICE
Exert a light and short touch (tap) on the soft
keys to activate their function. Holding the
touch too long will not generate any reaction
from the CTRLMax, unless it is a combination of
soft keys meant to be touched simultaneously
for a determined duration, as instructed in this
manual. The arrow keys can also be held longer
to increase or decrease values faster.
Navigation is performed through four arrow soft keys
, , with a center soft key (OK /Reset func-
tions) for making selections and entering information.
The installing contractor is provided with full access
to all available features after simultaneously touching
the
code. Reference the INSTINCT CTRLMax Control Supplement for Installer level functions
The Main Menu can be entered from the Home Screen
and soft keys for 3 seconds and entering a
,
Instinct
DHW
DHW Demand
Fig. 34 - CTRLMax User Interface
by touching the center soft key
To shut down the unit, touch the
DANGER
When touching the
shuts down but is not isolated from power
supply. Therefore, live current is still present
in the unit. For your safety, disconnect electrical power supply to the unit before servicing or making any electrical connections to
avoid possible electric shock hazard. Failure
to do so can cause serious injury, or death.
.
soft key.
soft key, the unit
NOTICE
• When shutting down using the
the appliance will not react to any heat demand. However, the basic appliance protection functions (such as frost protection, etc.)
remain active.
• In addition, the arrow soft keys are no longer
soft key,
illuminated, and the
dimmed.
soft key lighting is
CHAPTER 9
51
Page 64
CHAPTER 9 - CTRLMAX OPERATION
The menu system utilizes icons to represent each selection. The current selected menu is displayed as a reversed image with a text description shown at the top
of the display. Menus can be entered by selecting the
the desired icon (highlights) using the arrow soft keys
and touching the
soft key.
Home Screen
INSTINCT
186°F
DHW
156°F
Target = 186°F
DHW Demand
EZ Setup
CH / DHW Operation
The Home Screen icon
at the bottom of each screen
returns to the Home Screen when selected. The Previous Screen icon
at the bottom of each screen re-
turns to the previous screen when selected.
9.2. CTRLMax Menu Structure
Select Language
Boiler Information
CHAPTER 9
Heating Enabled
Heating EZ SetupDHW EZ Setup
Select Language
English
Français
Nederlands
Español
Italiano
Deutsch
Boiler Information
EZ Setup ResetDisplay EZ Setup
Lockout History
a
b
b
c
b
d
b
e
b
a
b
b
c
b
d
b
e
b
f
f
b
e
b
d
b
a
b
c
c
b
b
d
b
b
e
a
f
f
e
b
d
b
a
b
b
c
b
c
b
d
b
b
e
a
f
f
b
e
b
d
b
c
b
b
a
f
f
b
e
b
d
b
a
b
c
c
b
b
b
d
b
e
a
f
f
e
b
d
b
a
b
b
c
b
c
b
d
b
b
e
a
f
f
b
e
b
d
b
c
b
b
a
52
Page 65
CHAPTER 9 - CTRLMAX OPERATION
9.3. Home Screen
The Home Screen presents status information in a very
user friendly way so that the current state of the boiler
can be quickly accessed.
• Screen backlight - it will illuminate when any soft
key is touched, and remain illuminated for ve minutes.
• Screen brightness - it can be adjusted at the
Home screen by touching and holding simulta-
neously the
Touch the
crease the contrast. Touch
and soft keys for 2 seconds.
and soft key to increase or de-
to end the process.
Main Icons of CTRLMax display
• Central Heating - indicates information related
to central/space heating.
•
•
•
•
•
•
•
•
DHW - indicates information related to Domes-
tic Hot Water.
Home - to go back to the home screen.
Back - to go back to the previous screen.
Warm Weather Shutdown - displays on the
home screen when the outdoor temperature
reaches the Warm Weather Shutdown temperature.
Reset - to reset the system to the factory settings.
Settings - to access controller settings (lan-
guage, units, etc.).
Easy Setup - to quickly adjust the most com-
mon settings.
CH/DHW operation - to enable/disable the
central/space heating or Domestic Hot Water functions
The model is indicated at the top of the screen.
The INSTINCT is represented in the center of the Home Screen. Basic operating infor-
mation such as supply and return temperatures are displayed as well as current burner
Radiator icon: indicates that a central heating
call has been received. A small number 1 or 2
indicates which CH calls are active
A ame symbol is displayed when the unit is red. The
ame size changes to indicate the current ring rate.
Basic information: The user can toggle
through items using the
keys to view Target, Supply, Return, Domestic,
Outdoor, System and Mix Zone temperatures,
DHW ow.
and soft
•
status.
INSTINCT Combi
186°F
156°F
Target = 186°F
DHW Demand
Information - to get information on the boiler.
Faucet icon: indicates that a DHW call has been
received.
Circulator icons: indicate which circulators are currently
DHW
powered.
Status line: displays the current operating state of
the boiler. See Section 9.4 on page 54.
53
CHAPTER 9
Page 66
CHAPTER 9 - CTRLMAX OPERATION
9.4. Status Line Messages
Standby - Indicates that the INSTINCT is ready to re-
spond when a demand is received.
CH Demand - A central heating call has been received.
DHW Demand - A domestic hot water call has been
received.
CH/DHW Demand - Central heating and domestic hot
water calls are being received simultaneously. Both calls
are being satised simultaneously because domestic
hot water priority has been disabled.
DHW Priority - Central heating and domestic hot water calls are being received simultaneously. Domestic
hot water call is being satised rst because it has priority over central heating calls.
Priority Timeout - Central heating and domestic hot water calls are being received simultaneously. The domestic
hot water priority time limit has been exceeded. Priority
will now switch back and forth between central heating
and domestic hot water calls until one call is satised.
External Demand - An external modulation call has
been received.
Slave Operation - The INSTINCT is a slave in a cascade
system.
Manual Operation - The burner or circulators have
manually been enabled in the Installer Menu.
DHW Setpoint Reached - The burner is not red because the supply/system water temperature exceeds the
setpoint. The domestic circulator(s) continue(s) to operate and the burner will re again once the supply/system
water temperature drops below the setpoint.
CH Post Pump - The central heating circulator(s) is/are
running to remove heat from the INSTINCT at the completion of a call.
DHW Post Pump - The domestic hot water circulator(s)
is/are running to remove heat from the INSTINCT at the
completion of a call.
Freeze Protection - The burner is red because the
freeze protection feature has been activated. Freeze
protection will end once the supply/system water temperature is raised to 60°F [16°C].
Boiler Protection - The burner ring rate is being reduced because of an excessive dierence between the
boiler supply and return temperatures. The ring rate
will begin increasing once the temperature dierence
is less than 45°F [25°C].
Low Water Pressure - The system pressure has dropped
to 10.1 psi. The INSTINCT will still respond to calls until
the pressure drops below 7.2 psi. Increase system pressure to 14.5 psi to clear Low Water Pressure warning
Lockout Description - The lockout which currently
has the INSTINCT shut down is displayed
CHAPTER 9
CH Burner Delay - The burner will not re until the call
blocking time has elapsed.
DHW Burner Delay - The burner will not re until the
call blocking time has elapsed.
CH Setpoint Reached - The burner is not red because
the supply/system water temperature exceeds the setpoint. The central heating circulator(s) continue(s) to
operate and the burner will re again once the supply/
system water temperature drops below the setpoint.
54
Page 67
CHAPTER 9 - CTRLMAX OPERATION
9.5. Main Menu
The Main Menu can be entered from the Home Screen
by touching the
The menu system utilizes icons to represent each se-
lection.
The currently selected menu is displayed as an inversed im-
age with a text description shown at the top of the display.
Menus can be entered by scrolling through the icons
using the arrow soft keys, highlighting the desired icon
and touching the
soft key.
soft key.
INSTINCT Combi
186°F
Target = 186°F
9.6. EZ Setup
The EZ Setup menus provide a simple way to quickly customize CTRLMax for each installation. EZ Setup
prompts the user to make selections which allows the
INSTINCT to be setup very quickly without searching
through long lists of settings and manually making adjustments.
DHW
156°F
The EZ Setup menu can
be accessed by selecting
this icon.
The Boiler Information
Menu can be accessed
by selecting this icon.
DHW Demand
Touch center soft key
EZ Setup
Currently selected menu
The CH / DHW Operation
Menu can be accessed by
selecting this icon.
The Home Screen icon at
the bottom of each screen
returns to the Home Screen
when selected.
The Previous Screen icon at the
bottom of each screen returns to
the previous screen when selected.
CHAPTER 9
55
Page 68
CHAPTER 9 - CTRLMAX OPERATION
9.7. Heating EZ Setup
Heating EZ Setup allows the installer to quickly customize the central heating settings for the application.
9.7.1 Select CH Demand (No outdoor sensor connected)
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
CH1 Setpoint
140°F
68°F188°F
CH2 Setpoint
68°F188°F
140°F
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Select CH Demand prompts the installer to select how a CH Demand is generated.
Thermostat & Setpoint - A central heating call from a thermostat
or zone panel will enable the INSTINCT and the setpoint will be xed
for central heating calls. After Thermostat & Setpoint is selected, the
CH1 Setpoint screen appears. (see below).
Constant & Setpoint - The INSTINCT will maintain setpoint without
an external CH call from a thermostat or zone panel. The setpoint
will be xed for CH calls. After Constant & Setpoint is selected, the
CH1 Setpoint screen appears.
CH1 Setpoint prompts to enter the xed setpoint for a CH1 heating
call when a Setpoint option is chosen in Select CH Demand.
Touch the
then touch
or soft keys to adjust the temperature setpoint
to store the setting. The CH2 Setpoint screen then
appears.
CH2 Setpoint prompts to enter the xed setpoint for a CH2 heating
call when a Setpoint option is chosen in Select CH Demand.
Touch the
then touch
or soft keys to adjust the temperature setpoint
to store the setting and complete the Heating EZ
Setup.
CHAPTER 9
56
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
Press OK to return to EZ Setup Menu
Press OK to return to EZ Setup Menu
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
CH1 Default: 140°F [60°C]
CH2 Default: 140°F [60°C]
0 - 10V Modulation Signal - This option allows the INSTINCT ring
rate to be controlled by an external control system.
Refer to Chapter 13 on page 77 for more information.
Page 69
CHAPTER 9 - CTRLMAX OPERATION
9.7.2 Select CH Demand (Outdoor sensor connected)
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Outd. Curve
Constant & Outdoor Curve
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH1 Reset Curve
140°F
MAX
Select CH2 Reset Curve
80°F
140°F
18°C
Current Settings
80°F
Select CH Demand
Thermostat & Outd. Curve
Constant & Outdoor Curve
Constant & Setpoint
0 - 10 V Modulation Signal
-12°C
Warm Weather Shutdown
O
18°C
-12°C
Current Settings
O25°C
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Select CH Demand prompts the installer to select how a CH Demand is generated.
Thermostat & Outd. Curve – A central heating call from a thermostat or zone panel will
enable the INSTINCT and the setpoint will vary with the outdoor temperature for central
heating calls. After Thermostat & Outd. Curve is selected, the Select CH1 Reset Curve
screen appears (see below).
Constant & Outdoor Curve - The INSTINCT will maintain setpoint without an external CH call from
a thermostat or zone panel. The setpoint will vary with the outdoor temperature for central heating
calls. After Constant & Outdoor Curve is selected, the Select CH1 Reset Curve screen appears
Select CH1 Reset Curve prompts to select an outdoor reset curve for a CH1 heating
call when an Outdoor Curve option is chosen in Select CH Demand. Outdoor reset curve
presets are available to cover most applications. The outdoor reset curve can also be
adjusted to any desired settings in the Installer Menu.
Touch the
system, then touch
or soft keys to select the outdoor reset curve appropriate for the type of heating
to store the setting. The Select CH2 Reset Curve screen then appears.
Default: Radiators 2
Select CH2 Reset Curve prompts to select an outdoor reset curve for a CH2 heating call
when an Outdoor Curve option is chosen in Select CH Demand. Outdoor reset curve presets are available to cover most applications. The outdoor reset curve can also be adjusted
to any desired settings in the Installer Menu.
or soft keys to select the outdoor reset curve appropriate for the type of heating
to store the setting. The Warm Weather Shutdown screen then appears.
Default: Radiators 2
Warm Weather Shutdown prompts to enter an optional outdoor temperature at which to
disable the central heating function and any circulator placed into constant circulation with
the Pump Permanent Circulation setting. The INSTINCT will continue to respond to a domestic hot water call or a 0- 10V Modulation Signal when the outdoor temperature exceeds the
Warm Weather Shutdown Temperature setting.
Touch the
touch the
The Warm Weather Shutdown icon (
or soft keys to adjust the Warm Weather Shutdown Temperature then
soft key to store the setting and complete Heating EZ Setup.
) is displayed on the home screen when the out-
door temperature reaches the Warm Weather Shutdown temperature.
Default: OFF.
CHAPTER 9
57
Page 70
CHAPTER 9 - CTRLMAX OPERATION
9.8. Domestic Hot Water EZ Setup
- INSTINCT Solo Units
Domestic Hot Water EZ Setup allows the installer to quickly customize the Domestic Hot Water settings for the application
EZ Setup
DHW EZ Setup
Select DHW Demand
Thermostat
Sensor
DHW
Boiler Setpoint
168°F
96°F188°F
Select DHW Demand prompts the installer to select how a DHW
Demand is generated.
When Thermostat is selected in Select DHW Demand, a domestic
hot water call from an aquastat or dry contact switch will enable the
INSTINCT with a xed setpoint for a domestic hot water call. After
Thermostat is selected, the DHW Boiler Setpoint screen appears.
Default: Thermostat
DHW Boiler Setpoint prompts to enter the xed boiler setpoint
temperature during a domestic hot water call.
Touch the
then touch
or soft keys to adjust the temperature setpoint
to store the setting. The DHW Priority Timeout
screen then appears (see below).
Default: 168°F [75°C].
CHAPTER 9
EZ Setup
DHW EZ Setup
Select DHW Demand
Thermostat
Sensor
DHW Storage Setpoint
140°F
68°F168°F
DHW Priority Timeout
O 120 min.
O
EZ Setup Complete
DHW EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
When Sensor is selected in Select DHW Demand, use of an (optional)
Indirect Water Heater Sensor is required. The INSTINCT monitors the
DHW storage temperature and generates a DHW call whenever the
temperature drops below the DHW storage setpoint by 6°F [3°C].
DHW Storage Setpoint prompts to enter the DHW Storage Setpoint temperature.
Touch the
touch
or soft keys to adjust the temperature setpoint then
to store the setting. The DHW Priority Timeout screen
then appears.
Default: 140°F [60°C].
NOTICE
The DHW Boiler Setpoint will automatically be set 28°F
[15°C] higher than the DHW Storage Setpoint setting
DHW Priority Timeout prompts to enter an optional time limit that
a domestic hot water call has priority over central heating call.
Touch the
then touch
Defau
or soft keys to adjust the timeout value, if required,
to store the setting and complete the DHW EZ Setup.
lt: O
58
Page 71
CHAPTER 9 - CTRLMAX OPERATION
9.9. Domestic Hot Water EZ Setup - INSTINCT Combi Units
Domestic Hot Water EZ Setup allows the installer to quickly customize the Domestic Hot Water settings for the application
EZ Setup
DHW EZ Setup
DHW Setpoint
68°F168°F
140°F
DHW
Warmstart Temperature
125°F
86°F
O
Warmstart Hysteresis
936°F
140°F
DHW
30°F
EZ Setup Complete
DHW EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
DHW EZ Setup prompts the installer to select the DHW setpoint.
DHW Setpoint prompts to enter the xed setpoint temperature
during a domestic hot water call.
Touch the
then touch
or soft keys to adjust the temperature setpoint
to store the setting. The DHW Warmstart Tempera-
ture screen then appears .
Default: 140°F [60°C].
DHW Warmstart Temperature prompts to enter the DHW tem-
perature in case you want to speed up the delivery of DHW in summer conditions.
Touch the
or soft keys to adjust the temperature then touch
to store the setting. At the minimum temperature (86°F), this
function is OFF. The DHW Warmstart Hysteresis screen then appears .
Default: 125°F [52°C].
DHW Warmstart Hysteresis prompts to enter the DHW hysteresis
value, comprised between 9°F (5K) and 36°F (20K).
Touch the
touch
or soft keys to adjust the hysteresis value, then
to store the setting.
Default: 30°F (17k).
9.10. Altitude Setup
INSTINCT Combi
88°F
ENTER ACCESS CODE
84°F
Target = - -
Standby
CH & DHW Settings
0 5 [4]
CH Settings
Boiler Settings
Boiler Settings
ModelInstinct Combi
Lockout Temp.
Modbus Address
Pump Settings
Ignition level
Mix zone high limit
210ºF [99ºC]
Boiler Settings
1
Pump Settings
300rpm
Ignition level
Mix zone high limit
WP di trigger
Appliance setting
Altitude0ft
3000 rpm
114ºF
Altitude
114ºF
0cpsi
4920ft
0ft19680ft
Altitude must be correctly set to allow reliable operation of the
boiler.
From the home screen touch the
or soft keys simultaneously for 5
seconds and “Enter Access Code” screen will be shown.
Touch the
or soft keys to set the access code to 054. Touch
and the CH & DHW Settings creen will be shown.
Touch
and the CH Setting screen will be shown. Touch the
soft key and the “Boiler Settings” (list) screen will be shown.
Touch the
Touch
Touch the
the
soft key until the “Altitude” option is highlighted.
and the Altitude screen will be shown.
soft key until the correct altitude is shown, then touch
soft key to highlight the home icon. Touch to conrm.
Note. The altitude moves in steps of 984 ft (300m).
CHAPTER 9
59
Page 72
CHAPTER 9 - CTRLMAX OPERATION
9.11. EZ Setup Reset
EZ Setup
EZ Setup Reset
EZ Setup Reset
Press OK to restore factory settings,
any other button to keep current
settings.
9.12. Display EZ Setup
EZ Setup
EZ Setup Reset allows reset of all EZ Setup settings back to the original factory defaults. See Chapter 13 on page 77 for the list of settings reset by this function.
Follow the on-screen instructions to reset all EZ Setup settings.
Display EZ Setup allows language (English, French, Dutch, Spanish,
Italian, German, Czech) and temperature units selection.
CHAPTER 9
Display EZ Setup
Select Language
English
Français
Nederlands
Español
Italiano
Deutsch
Fahrenheit
Celsius
Select Unit
Touch the
touch
Touch the
then touch
or soft keys to select the required language then
to store the setting. The Select Unit screen then appears.
or soft keys to select the required temperature units
to store the setting.
60
Page 73
CHAPTER 9 - CTRLMAX OPERATION
Heating Enabled
9.13. CH/DHW Operation
CH / DHW Operation
Heating Enabled
9.14. Boiler Information
Boiler Information
Boiler Information
a
b
b
c
b
d
b
e
b
f
f
b
e
b
d
b
a
b
c
c
b
b
d
b
b
e
a
f
f
e
b
d
b
a
b
b
c
b
c
b
d
b
b
e
a
f
f
b
e
b
d
b
c
b
b
a
Boiler Information
Boiler Status Standby
Heating Call No
DHW Call No
Boiler Firing Rate --
Ionization current 0μA
Boiler Setpoint --
CH/DHW Operation provides a simple way to enable/disable either
the CH or the DHW function of the INSTINCT.
Touch the
touch
or soft keys to select the CH or DHW icon, then
to toggle between the enabled/disabled status. The sta-
tus is displayed at the top of the screen.
Using the arrow keys, select the HOME or RETURN icon at the bottom of the screen to go back either to the home page or to the
previous screen.
Default :
Boiler Information provides real time operating information of the
INSTINCT. Each line contains an information item followed by its current value. Six lines are displayed on the screen at one time.
Some information items include a logging function which records one
sample every 12 minutes to produce a graph of the last 24 hours. Select the information item in Boiler Information then touch the
soft
key to view its graph. The following items have a logging function:
• Boiler Firing Rate
• Ionization Current
• Boiler Setpoint
• Boiler Supply Temperature
• Boiler Return Temperature
• Boiler Flue Temperature
• Outdoor Temperature
• DHW Storage Temperature
• External Modulation Signal
• Pressure
Touch the
or soft keys to scroll through the items.
CHAPTER 9
61
Page 74
CHAPTER 9 - CTRLMAX OPERATION
9.14.1 Information Items
Information ItemDescription
Boiler Status
Heating CallDisplays if a central heating call is present.
DHW CallDisplays if a domestic hot water call is present.
Boiler Firing RateDisplays the current ring rate of the INSTINCT.
Ionization CurrentDisplays the current ame ionization current from the ignitor.
Boiler SetpointDisplays the current setpoint of the INSTINCT.
Supply Temp.Displays the current supply temperature of the INSTINCT.
Return Temp.Displays the current return temperature to the INSTINCT.
Boiler Flue Temp.Displays the current ue temperature of the INSTINCT.
Outdoor Temp.Displays the current outdoor temperature.
DHW Storage Temp.
External Modulation Signal
Displays the current operating state of the INSTINCT. This is the same as the status line on the home screen.
Displays the current DHW storage temperature when Indirect Water Heater Sensor PSRKIT22 is installed.
Displays the current external modulation signal being received from an external
controller.
CHAPTER 9
PressureDisplays the current system water pressure.
CH Ignitions
CH Runtime
DHW Ignitions
DHW Runtime
Mix Zone TemperatureDisplays the current low temperature mix zone temperature.
Displays the number of central heating ignitions since the unit was installed. This
counter increases in increments of twenty.
Displays the number of hours the INSTINCT has run for a central heating call since
the unit was installed.
Displays the number of domestic hot water ignitions since the unit was installed.
This counter increases in increments of twenty.
Displays the number of hours the INSTINCT has run for a domestic hot water call
since the unit was installed.
62
Page 75
CHAPTER 9 - CTRLMAX OPERATION
Boiler Information
Lockout History
a
b
b
c
b
d
b
e
b
f
f
b
e
b
d
b
a
b
c
c
b
b
b
d
b
e
a
f
f
e
b
d
b
a
b
b
c
b
c
b
d
b
b
e
a
f
f
b
e
b
d
b
c
b
b
a
Lockout History
1. Blower speed 5h ago
2. DHW Sensor Open 2h ago
3. Sensor Drift 25 h ago
4. No error 27 h ago
5. No error 27 h ago
6. No error 27 h ago
Lockout Details
Blower speed
Boiler Status --
Heating Call --
DHW Call --
Boiler Firing Rate 44%
Ionization current 44μA
9.14.2 Lockout Screen
If a problem occurs, the Lockout Screen replaces the
Home Screen. The backlight will remain on until the
lockout is reset.
Touching any arrow soft key will return to the Home
Screen so that additional troubleshooting can be performed. See Sections 9.14.3 on page 64 and 9.14.4 on page 65 for a list of lockouts and descriptions.
Select the Home Screen icon at the bottom of any
screen to return to the lockout screen.
Lockout History records the last eight lockouts. Six lines are displayed on the Lockout History screen at one time. Each line contains a
lockout description followed by how long ago the lockout occurred.
Touch the
or soft keys to scroll through the items then touch
to select and get more details through the Lockout Details screen.
The following information items are recorded at the time of a lockout:
• Boiler Status
• Heating Call
• Domestic Call
• Boiler Firing Rate
• Flame Ionization Current
• Boiler Setpoint
• Boiler Supply Temperature
• Boiler Return Temperature
• Boiler Flue Temperature
• Outdoor Temperature
• System Temperature
Low Water
Water pressure has fallen below
7.2 psi. Increase pressure
to normal range.
If problem persists,
call for service
E37
Lockout message.
Lockout text. The rst sentence describes the lockout,
the second sentence gives a possible cure, and the third
tells how to reset the lockout.
Lockout reference code. Refer to Sections 9.14.3
on page 64 and 9.14.4 on page 65for more
information.
CHAPTER 9
63
Page 76
CHAPTER 9 - CTRLMAX OPERATION
9.14.3 Manual Reset Lockouts
CodeLockout MessageDescription
E1Failed IgnitionThe burner failed to light after 5 ignition attempts.
E2False FlameFlame detected prior to ignition.
E3High Boiler TemperatureBoiler temperature has reached 210°F [99ºC] or 102°F [39°C].
E5Blower SpeedBlower is not at correct speed or speed signal is not being received by control module.
E8Flame Circuit ErrorFlame circuit test failed.
E9Gas Valve Circuit ErrorGas valve circuit test failed.
E13Reset Limit ReachedResets are limited to 5 every 15 minutes.
E15Sensor DriftSupply or return sensor reading has drifted.
E16Supply Sensor StuckSupply sensor reading is not changing.
E17Return Sensor StuckReturn sensor reading is not changing.
E18Sensor FailureSupply or return sensor reading changed very rapidly.
E19Flame Failure During Startup Phase Flame lost after startup
E21Internal Control FaultA / D conversion error.
E30Supply Sensor ShortedA short circuit has been detected in the boiler supply temperature sensor circuit.
E31Supply Sensor OpenAn open circuit has been detected in the boiler supply temperature sensor circuit.
E43Return Sensor ShortedA short circuit has been detected in the boiler return temperature sensor circuit.
E44Return Sensor OpenAn open circuit has been detected in the boiler return temperature sensor circuit.
E47Water Pressure Sensor ErrorWater pressure sensor is disconnected or broken.
E80Return > SupplyReturn temperature is higher than supply temperature.
E83Delta T ProtectionExcessive difference between boiler supply and return temperatures has occured 5 times
CHAPTER 9
E84High Flue TemperatureFlue temperature has exceeded high limit 5 times
E87External Limit OpenAn external manual reset limit has opened
64
Page 77
CHAPTER 9 - CTRLMAX OPERATION
9.14.4 Automatic Reset Blocking Lockouts
CodeLockout MessageDescription
E7High Flue TemperatureFlue temperature exceeds high limit.
E12Internal Control FaultEEPROM misconguration.
E25Internal Control FaultCRC check error.
E32DHW Sensor ShortedA short circuit has been detected in the DHW temperature sensor circuit.
E33DHW Sensor OpenAn open circuit has been detected in the DHW temperature sensor circuit.
E34Low VoltageLine voltage has fallen below an acceptable operating level.
E37Low WaterWater pressure has fallen below 7.2 psi.
E45Flue Sensor ShortedA short circuit has been detected in the boiler ue temperature sensor circuit.
E46Flue Sensor OpenAn open circuit has been detected in the boiler ue temperature sensor circuit.
E76External Limit OpenAn external automatic reset boiler limit has opened.
E77High Mix Circuit TemperatureMix circuit temperature exceeds Mix zone high limit setting.
E78Mix Circuit Sensor ShortedA short circuit has been detected in the mix circuit temperature sensor circuit.
E79Mix Circuit Sensor OpenAn open circuit has been detected in the mix circuit temperature sensor circuit.
E81Sensor DriftSupply and return temperatures are not equal.
E82Delta T Protection Excessive dierence between the boiler supply and return temperatures.
E89Incorrect SettingA parameter setting is in conict with another setting.
E90Firmware MismatchControl module and display rmware versions are incompatible.
E91System Sensor ShortedA short circuit has been detected in the system temperature sensor circuit.
E92System Sensor OpenAn open circuit has been detected in the system temperature sensor circuit.
E93Outdoor Sensor ShortedAn open circuit has been detected in the outdoor temperature sensor circuit.
E94Internal Display FaultDisplay memory error.
E95Supply Sensor ErrorSupply sensor reading is invalid.
E96Outdoor Sensor OpenAn open circuit has been detected in the outdoor temperature sensor circuit.
E97Cascade MismatchCascade conguration has changed.
E98Cascade Bus ErrorCommunication with other boilers has been lost.
E99Controller Bus ErrorCommunication between boiler display and control module has been lost.
CHAPTER 9
65
Page 78
INTENTIONALLY LEFT BLANK
Page 79
CHAPTER 10 - START-UP PREPARATION
10.1. Boiler System Fluid Requirements
NOTICE
Chapter 10
10.1.3 Chlorinated Water
Do not use the INSTINCT to heat a swimming pool or
spa directly.
Requirements below must be met for warranty
coverage of INSTINCT heat exchangers. A thorough cleaning of any existing system, using
approved heating system cleaning agents is required prior to installation of the INSTINCT boiler. System should be treated with an approved
inhibitor after filling for long term protection.
WARNING
Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to seals and gaskets in the system components can occur, resulting in substantial
property damage, serious injury, or death.
NOTICE
System fluid including additives, must be practically non-toxic, having a toxicity rating or
Class of 1, as listed in Clinical Toxicology of
Commercial Products.
10.1.1 Boiler Fluid pH Level 6.0 to 8.0
Maintain the boiler uid pH between 6.0 and 8.0. Check
using litmus paper or contact a water treatment company for a chemical analysis.
Maintain the chlorine level of the water at levels considered safe for drinking.
10.1.4 Flush Boiler to Remove Sediment
The installer must ush the boiler system to remove any
sediment to allow proper operation of the INSTINCT .
Flush the system until the water runs clean and is free
of sediment.
For zoned systems, each zone should be ushed
through a purge valve. Purge valves and isolation
valves should be installed on each zone to allow proper
ushing of the system.
10.1.5 Cleaning of Old Boiler/System:
• Drain the existing system.
• Fill system with fresh water and cleaner, place existing boiler in operation and run all zones.
• Follow manufacturer’s instructions for proper cleaner concentration and proper cleaning time.
• Thoroughly drain and ush system with fresh water
after cleaning.
• Install new boiler and ll system with fresh water
and proper amount of inhibitor.
• Verify pH and inhibitor level per inhibitor manufacturer’s specs; add inhibitor if necessary.
If the pH does not meet this requirement, do not operate the INSTINCT or leave the unit lled until the condition is corrected.
10.1.2 Boiler Fluid Hardness Less Than 7 Grains
For areas with unusually hard water (hardness above 7
grains) consult a water treatment company.
10.1.6 Cleaning of New Boiler/System:
• Install new boiler and ush system with clean water
to remove any debris.
• Fill system with fresh water and proper amount of
inhibitor.
• Verify pH and inhibitor level per inhibitor manufacturer’s specs; add inhibitor if necessary.
67
Page 80
Chapter 10
CHAPTER 10 - START-UP PREPARATION
10.1.7 Check and Test Antifreeze
For boiler systems containing antifreeze solutions, follow the antifreeze manufacturer’s instructions in verifying the inhibitor level and to ensure the uid characteristics are within specication requirements.
Due to the degradation of inhibitors over time, antifreeze
uids must be periodically replaced. Refer to the manufacturer of the antifreeze for additional instructions.
10.1.8 Use of Antifreeze in the Boiler System
WARNING
NEVER use automotive or ethylene glycol antifreeze or undiluted antifreeze in the system
as freeze protection. This can result in substantial property damage, serious injury, or
death.
Determine the antifreeze uid quantity using the system water volume and following the antifreeze manufacturer instructions.
The water volume of the INSTINCT is approximately:
-2 gallons [8 L] for INSTINCT Solo 110
-3 gallons [12 L] for INSTINCT Solo/Combi 155 and
INSTINCT Solo 199
-4 gallons [15 L] for INSTINCT Combi 199.
Remember to include the volume of the expansion tank.
Check with local code requirements for the installation
of backow preventers or actual disconnection of the
boiler’s cold water ll or make up water supply line.
DANGER
HOT WATER CAN SCALD!
• Water temperatures over 125ºF can cause
severe burns instantly, or death from scalds.
• Feel water before bathing or showering.
• Consumer Product Safety Commission
and some states recommend temperatures settings of 130ºF or less. Setting
thermostat higher than 130ºF will increase risk of scald injury and cause se-
vere personal injury or death.
• Water heated to a temperature suitable
for clothes washing, dish washing and
other sanitizing needs will scald and
cause permanent injury.
• Children and elderly, infirm, or physically handicapped persons are more likely
to be injured by hot water. Never leave
them unattended in or near a bathtub. If
anyone using hot water in the building
fits this description, or if state laws or local codes require certain water temperatures at hot water faucets, take special
precautions.
Ū Install the factory supplied automat-
ic mixing valve at water heater and/
or install a point of use mixing valve
at each hot water faucet, bath and
shower outlet. Selection and installation of point of use mixing valves
must comply with valve manufacturer’s recommendation and instruc-
tions.
NOTICE
Massachusetts Code requires the installation of
a backflow preventer if antifreeze is used.
Ensure the concentration of antifreeze to water does
not exceed a 50/50 ratio.
NOTICE
System fluid including additives, must be practically non-toxic, having a toxicity rating or
Class of 1, as listed in Clinical Toxicology of
Commercial Products.
68
Ū Use the lowest practical temperature
setting.
Ū Check water temperature after any
adjustment of the mixing valve.
• Failure to comply with these instructions
will result in serious injury, or death.
Page 81
CHAPTER 10 - START-UP PREPARATION
10.2. Filling the Boiler System
1. Close the boiler drain valve located on the bottom
of the unit and any manual or automatic air vents
in the system.
2. Open all system isolation valves.
3. Fill the boiler system to correct system pressure.
Correct pressure will vary with each application.
NOTICE
Typical residential system fill pressure is 12 psi.
System pressure will increase as system temperature increases. Operating pressure of the
system should never exceed 30 psi.
4. Purge air and sediment in each zone of the boiler
system through the purge valve. Open air vents to
allow air to be purged from the zones.
5. Once the system is completely lled and purged of
all air and sediment, check the system pressure and
check/repair any leaks.
Chapter 10
General Notes
• Household water usage patterns will aect water
temperature at any faucet or shower. Occasionally
check temperature at each point of use, then adjust
the mixing valve setting accordingly. Always recheck temperature after adjusting the mixing valve.
• Lowering the automatic mixing valve as indicated
in these instructions will reduce water temperature
levels. Consult your installer or service technician.
10.3.1 Filling the Domestic Circuit
CAUTION
• Never use the INSTINCT Combi unless the
circuits of the water heater are completely
filled with water.
• Failure to comply with these instructions can
result in minor property damage, or injury.
1. Close domestic water drain valve.
2. Open domestic water isolation valves slowly on the
water heater piping.
WARNING
Unrepaired system leaks will cause continual makeup water to be added to the boiler.
Continual makeup water will cause mineral
buildup within the heat exchanger, reducing
the heat transfer, causing heat buildup and
eventual heat exchanger failure. This can result in substantial property damage, serious
injury, or death.
10.3. INSTINCT Combi Water Heater - Water
Requirements
NOTICE
The thermostatic mixing valve controls the
hot water temperature delivered to the faucets.
WARNING
POTENTIAL SCALD HAZARD. A mixing
valve must be installed on the INSTINCT
Combi. Removal or adjustment of the mixing valve will create a potential scald hazard,
which can result in serious injury, or death.
CAUTION
Make sure to open the domestic isolation valve
slowly to prevent any damage to the domestic
circuit flow sensor.
3. Vent air from domestic circuit by opening nearest
hot water faucet, until there is a constant ow of
water.
4. Close hot water faucet.
10.4. Check Low Water Cut-Off Device
• The INSTINCT is provided with a factory installed
LWCO device that monitors system pressure.
• Access the Boiler Information Menu by following
instructions in Section 9.14 on page 61. Scroll
down to see the current system pressure and verify
it is within the range given in Section 10.2 above.
If any adjustment needs to be made to the valve’s temperature setpoint refer to the manufacturer’s instructions included with the valve.
69
Page 82
Chapter 10
CHAPTER 10 - START-UP PREPARATION
10.5. Check For Gas Leaks
WARNING
• Prior to start-up and during initial operation, check for a gas leak using a combustable gas detector. Do not proceed
with the start-up if there is any indication
of a gas leak. Any leaks found must be re-
paired immediately.
• Propane installations only - The propane
supplier mixes an odorant with the propane to make its presence detectable. In
some cases the odorant can fade and the
gas may no longer have an odor.
• Prior to start-up of the unit and periodically after start-up have the propane sup-
plier check and verify the odorant level.
• Failure to comply with these instructions
can result in substantial property dam-
age, serious injury, or death.
• There should NEVER be voltage measured at the
wire ends.
• If voltage is measured under any condition, check
and correct the external wiring.
NOTICE
In systems using 3-wire zone valves, voltage
backfeed to the unit is a common problem. Use
an isolation relay to prevent voltage from the ex-
ternal circuit from entering the INSTINCT.
• Reconnect the external thermostat wires to the low
voltage terminal strip.
10.7. Inspect Condensate Drain Assembly
1. Inspect and ensure the Condensate Drain Assembly
is properly installed as described in Section 6.2 on
page 38.
2. Remove the plug from the Condensate Drain As-
sembly and ll with fresh water.
10.6. Check Thermostat Circuit
• Disconnect the external thermostat wires from the
low voltage terminals.
• Connect a voltmeter across the wire ends of the external thermostat wiring.
• Close each thermostat, zone valve and relay in the
external circuit one zone at a time and check the
voltage reading across the wire ends.
WARNING
The condensate drain assembly must be filled
with water when the INSTINCT is in operation.
The condensate drain assembly prevents flue
gas emissions from entering the condensate
line. Failure to ensure trap is filled with water
can result in serious injury, or death.
3. Re-Install plug in condensate drain assembly.
70
Page 83
CHAPTER 11 - START-UP PROCEDURES
11.1. Final Checks Before Start-Up
Ø Read Chapter 9 on page 51 regarding the oper-
ation of the CTRLMax Boiler Management System.
Ø Verify the INSTINCT and the boiler system are full
of water and all system components are correctly
set for operation, including the minimum ow rate
through the boiler, see specications in Chapter
19 on page 101..
Ø Verify Start-up Preparation items outlined in Chap-
ter 10 on page 67 have been completed.
Ø Verify all electrical connections are correct and se-
curely fastened.
Ø Inspect vent and combustion air piping for signs
of deterioration from corrosion, physical damage or
sagging. Verify combustion air and vent piping are
intact and correctly installed and supported. Reference the INSTINCT Vent Supplement.
Ø Verify burner conguration - Propane only.
• Check for proper labeling on the venturi and
the rating label for propane conguration.
• If there is doubt on the burner conguration,
remove the venturi and check for proper propane gas orice sizing on venturi labeling. Refer
to Section 7.3.2 on page 42 for orice sizes.
Refer to Fig 16, Fig 17 or Fig. 28 on page 44 for
location of the propane gas orice.
Ø Ensure the Condensate Drain Assembly is lled
with water.
4. Is an external limit (if applicable) open? Ensure the
external limit is reset to the closed position.
5. Are the gas supply valves open at the unit and meter?
6. Is incoming gas supply pressure at the unit more
than 5”w.c. and less than 13” w.c. with all gas appliances ON and OFF.
7. Are the heating thermostats set above room temperature?
If none of these conditions correct the problem, contact Triangle Tube Technical Support.
11.3. Check the INSTINCT and System
11.3.1 Check Boiler Piping.
• Check Boiler system piping and components for
leaks. If found, shut down the unit and repair immediately.
• Purge any remaining air from the system. Air in the
system will interfere with circulation, creating heat
distribution problems and noise.
11.3.2 Check Vent and Combustion Air Piping.
• Check for a gas-tight seal at every connection and
seam of the vent and combustion air piping.
DANGER
CHAPTER 11
11.2. INSTINCT Start-Up
1. Turn ON the electrical supply/service to the unit.
Touch the ON-OFF button located on the front control panel to the OFF position.
2. Read and follow the Operating Instructions outlined on following page.
If INSTINCT Does Not Start Correctly
1. Check for loose electrical connections, blown fuses
on control module, or an open service switch.
2. Verify CH and DHW operation is enabled. A radiator
or faucet icon with an X through it indicates that
function is disabled.
3. Check the system pressure in the Boiler Information
Menu by following the instructions in Section 9.14
on page 61.
Venting system must be sealed gas-tight to
prevent flue gas spillage and carbon monoxide emissions, which will result in serious
injury, or death.
11.3.3 Verify Carbon Monoxide Detector
Verify that at least two (2) carbon monoxide detectors
are installed and operating properly. One must be installed in the mechanical room where the INSTINCT is
located and another installed in the living area outside
the bedroom(s).
71
Page 84
FOR YOUR SAFETY, READ BEFORE OPERATING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result,
causing substantial property damage, serious injury, or death.
A. This appliance does not have a pilot. It is equipped
with an ignition device which automatically lights
the burner. DO NOT try to light the burner by hand.
B. BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use
any phone in your building
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the re department.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above. This appliance is equipped with an ignition device which
automatically lights the burner. DO NOT try to light
the burner by hand.
2. Set room thermostat(s) to lowest setting. Turn the
external manual gas valve handle clockwise
to “CLOSE” (valve handle must be perpendicular to
gas piping).
3. Turn the service switch on the appliance control
panel OFF.
4. Remove the front jacket panel on the unit.
5. Wait ve (5) minutes to clear out any gas. If you then
smell gas in the jacket enclosure or around the unit,
STOP! Follow “B” in the safety information above. If
you don’t smell gas, go to the next step.
6. Turn the external manual gas valve handle counter
clockwise
shall be parallel to gas piping).
to “OPEN” gas supply (valve handle
C. Use only your hand to turn the external manual gas
valve. Never use tools. If the valve will not turn by
hand, don’t try to repair it; call a qualied service
technician. Force or attempted repair may result in
a re or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualied service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
7. Turn the service switch on the appliance control
panel “ON”.
8. Set room thermostat(s) to desired setting(s).
9. The appliance control panel display will show the
current operating status on the Status Line at the
bottom of the screen. “Standby” means there is no
call for heat (all thermostats are satised). “CH Demand” indicates a space heating call has been received. “DHW Demand” indicates a domestic hot
water call has been received. A ame icon will be
displayed when the unit is red.
10. If the unit will not operate, follow the instructions
“To Turn O Gas to Appliance” and call your service
technician or gas supplier.
11. Replace the front jacket panel. Make sure the panel
is seated rmly in place and all mounting screws are
tightened.
TO TURN OFF GAS TO APPLIANCE
1. Set the room thermostat to lowest setting.
2. Turn the service switch on the appliance control
panel to “OFF”
72
3. Turn the external manual gas valve handle clockwise
to “CLOSE”.
Page 85
CHAPTER 11 - START-UP PROCEDURES
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
f
b
g
a
b
c
d
11.3.4 Check Gas Piping
Check around the unit for gas odor following the procedure outlined in this manual on page 64.
DANGER
If any gas leaks are found or suspected, shut
the unit down immediately. Use a gas detection device or bubble test to locate the
source of the gas leak and repair at once. Do
not operate the unit until the leak is corrected. Failure to comply with this procedure will
result in substantial property damage, seri-
ous injury, or death.
11.3.5 Verify Flame Pattern and Combustion
1. Check the ame pattern through the observation
port of the heat exchanger. The ame should be
blue and stable. The ame should be over the
length of the burner head. It is not possible to determine correct combustion by inpecting eh colour
and pattern of the ame. It is important to measure
combustion with a calibrated ue gas analyser.
d. Touch the soft key while the FAN icon is
highlighted to manually re the burner and
power the CH circulator(s).
Manual Operation
FAN
CH1
DHW
Released
O
O
O
CH2
NOTICE
An adequate CH load must be present to dissipate the heat generated during the combustion
test. If an adequate CH load is not available, an
indirect water heater can be used to dissipate
the heat by creating a DHW call which will en-
able the DHW circulator.
CHAPTER 11
NOTICE
Combustion testing and adjustments must be
performed by a qualified installer, service agency or the gas supplier. All combustion measurements must be performed with recently
calibrated equipment (1 year max.) to ensure
proper reading and accuracy.
2. Test for CO2 or O2 and for CO during high ring
rate. The combustion readings must be within the
range listed in Table 6 on page 74. The CO level
must not exceed 150 ppm for natural gas and
200 ppm for propane gas when combustion is
correct. Perform the following procedure to manu-
ally place the burner into high re.
a. Touch simultaneously on the and soft
keys for 3 seconds to access the functions for the
installer. Reference Section 9.1 on page 51.
b. Enter the installer access code “054” by using
and soft keys to select a digit location
the
and the
Touch the
c. Touch the
Operation icon
and soft keys to change the digit.
soft key to enter the access code.
soft key to highlight the Manual
then touch the soft key.
e. Touch the
from 1% to 100%. Hold down the
soft key to adjust the ring rate
soft key to
rapidly increase the ring rate.
f. Touch the
soft key while the FAN icon is
highlighted to shutdown the burner.
3. If the combustion levels during high re (100%) are
outside the acceptable levels, adjust the THROTTLE
SCREW (see Fig. 13 on page 25 and Fig. 27 on
page 43, and Fig. 28 on page 44) according to
Table 5 on page 74.
4. Once the combustion level is set at high re (100%),
manually place the boiler into low re (1%) mode by
touching the
soft key to adjust ring rate down.
5. Verify the combustion levels during low re (1%) are
within the acceptable combustion levels in Table 6
on page 74.
WARNING
If the combustion levels at low fire (1%) are
not within the range given in Table 6 on page 74, shut the boiler down and contact Trian-
gle Tube Technical Support. Failure to comply with this requirement can result in substantial property damage, serious injury, or
death.
73
Page 86
CHAPTER 11 - START-UP PROCEDURES
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
f
b
g
a
b
c
d
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
a
b
c
d
e
f
b
b
b
b
a
b
c
d
e
f
b
b
f
b
g
a
b
c
d
CHAPTER 11
Table 5 - Throttle Screw Adjustment
DirectionINSTINCT Solo/Combi
Clockwise
Counter-Clockwise
Decrease CO2
Increase O
2
Increase CO2
Decrease O
2
11.3.6 Measure Input - Natural Gas Only
1. Ensure the boiler is ring at maximum ring rate. To
manually place the boiler into high re, reference
Section 11.3.5 on page 73.
2. Operate the unit for approximately 10 minutes.
3. Turn o all gas appliances within the building, except the INSTINCT.
4. At the gas meter, record the time required to use
one cubic foot of gas.
5. Calculate Natural gas input using the following
equation:
3600 x 1000 / number of seconds recorded for one
cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate the in-
3. Touch the
icon
4. Touch the
tings icon
5. Touch the
perature then touch the
6. Touch the
touch the
7. Touch the
icon
soft key while CH & DHW Settings
is highlighted.
soft key to highlight the Boiler Set-
then touch the soft key.
soft key to highlight Lockout Tem-
soft key.
soft key to highlight 102ºF [39ºC] then
soft key.
soft key to highlight the Home Screen
then touch the soft key.
8. Initiate a CH or DHW call and conrm that a High
Boiler Temperature lockout occurs once the supply
temperature reaches 102ºF [39ºC].
9. Touch any ARROW soft key to return to the Home Screen.
10. Touch simultaneously on the
and soft keys for
3 seconds to access the functions for the installer.
11. Touch the
icon
soft key while the CH & DHW Settings
is highlighted.
put rating listed on the unit.
12. Touch the
soft key to highlight the Boiler Set-
11.3.7 Test High Temperature Limit
The high temperature limit can be temporarily lowered
from 210ºF [99ºC] to 102º F [39ºC] for testing.
1. Touch simultaneously on the
for 3 seconds to access the functions for the install-
er. Reference Fig. 34 on page 51.
2. Enter the installer access code “054”, using the
and
soft keys to select a digit and the and
soft keys to change the digit. Touch the
to enter the access code.
CO2 Range9.0 to 10.5%10.4 to 11.0%
CO2 Target9.50%10.80%
O2 Range4.85 to 2.15 %5.1 to 4.2 %
High Fire
O2 Target3.95%4.50%
CO Max150 ppm200 ppm
CO2 RangeLow Fire CO2 range 9.0 to 10.0 %
Target values are equivalent to High Fire values, ensure
CO2 values measured are less than or equal to High Fire
O2 RangeLow Fire O2 range 4.85 to 3.0 %
Low Fire
Target values are equivalent to High Fire values, ensure
O2 values measured are higher than or equal to High
CO Max10 ppm10 ppm
and soft keys
soft key
Table 6 - Acceptable Combustion Levels
Natural Gas (All Models)Propane (All Models)
CO2 measurements
Fire O2 measurements
tings icon
13. Touch the
perature, then touch the
14. Touch the
touch the
15. Touch the
icon
16. Touch the
turn the unit to service.
then touch the soft key.
soft key to highlight Lockout Tem-
soft key.
soft key to highlight 210ºF [99ºC] then
soft key.
soft key to highlight the Home Screen
then touch the soft key.
soft key to reset the lockout and re-
Low Fire CO2 range 10.4 to 11.0 %
Target values are equivalent to High Fire values, ensure
CO2 values measured are less than or equal to High Fire
CO2 measurements
Low Fire O2 range 5.1 to 4.2 %
Target values are equivalent to High Fire values, ensure
O2 values measured are higher than or equal to High
Fire O2 measurements
74
Page 87
CHAPTER 12 - OUTDOOR RESET CONTROL
The use of the outdoor reset function is required to optimize boiler eciency, see notice below. If the outdoor
sensor is not installed before turning on the INSTINCT,
an Outdoor Sensor Open error (E96) will be displayed.
The error will not prevent the boiler from operating. The
error will automatically reset once the outdoor sensor
is installed or if the outdoor reset function is disabled.
ReferenceSection 9.7 on page 56 for information on
disabling the outdoor reset function. The outdoor reset
function can only be disabled if the installation meets
one of the exceptions listed in the IMPORTANT notice
below.
12.1. Mounting the Outdoor Sensor
1. The exterior wall selected for mounting the outdoor sensor should represent the heat load of the
building. Typically a northern wall will suit most
buildings.
2. Ensure the outdoor sensor is shielded from direct
sunlight or the eects of heat or cold from other
sources (exhaust fans, appliance vents...) to prevent
false temperature readings.
3. Mount the outdoor sensor at an elevation on the
exterior wall to prevent accidental damage or tampering.
4. Avoid mounting the outdoor sensor in areas subjected to excessive moisture.
5. Once an area on the exterior wall has been determined, follow the mounting instructions included
with the outdoor sensor.
12.2. Wiring the Sensor
1. Connect 18 AWG 2-wire cable or similar to the outdoor sensor.
2. Route the cable back to the INSTINCT boiler, ensuring the wires are not run parallel to telephone or
power wiring.
NOTICE
If the sensor wires are located in an area
with sources of electromagnetic interference
(EMI), the sensor wires should be shielded or
the wires should be run in a grounded metal
conduit. If using shielded cable, the shielding
should be connected to the common ground of
the unit.
3. Connect the outdoor sensor wires to low voltage terminals X6-1&2 located at the bottom of the CTRLMax
control module as shown in Fig. 33 on page 49.
CHAPTER 12
IMPORTANT
In accordance with Chapter 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a
feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature
is equipped with an override which is provided primarily to permit the use of an external energy management
system that serves the same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS
IS TRUE.
• An external energy management system is installed that reduces the boiler water temperature
as the heating load decreases.
• This boiler is not used for any space heating
• This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/
hr or greater.
• This boiler is equipped with a tankless coil.
75
Page 88
INTENTIONALLY LEFT BLANK
Page 89
CHAPTER 13 - EXTERNAL MODULATING CONTROL
The INSTINCT can directly accept an analog
0-10 VDC signal from an external modulating boiler
controller to control the ring rate.
13.1. Wiring the Modulating Controller
Run two 18 gauge wires from the external modulating
boiler controller’s 0-10 VDC boiler output to low voltage
terminals X5-1&2 located at the bottom of the CTRLMax
control module, as shown in Fig. 33 on page 49.. This
signal will both enable and modulate the boiler. No wiring is required at the thermostat terminals.
External modulating control will only function if the
external modulating controller is properly wired to the
INSTINCT as follows:
• X5-1 = +
• X5-2 = -
NOTICE
13.2. CTRLMax Programming
The CTRLMax control module must be programmed to
accept the 0-10 VDC signal from the external modulating boiler control.
1. Use the Heating EZ Setup function to set CH De-
mand to 0-10V Modulation Signal. Reference Sec-
tion 9.7 on page 56.
13.3. Programming of External Modulating
Control
The external modulating control must be programmed
to send 2 VDC to enable the boiler and run it at low re,
and 10 VDC to run the boiler at high re. Once the control enables the boiler, it must wait 30 seconds to allow
the burner to stabilize before modulating the boiler.
CHAPTER 13
Ensure that the polarity of the connections
from the external modulating boiler controller
to the boiler are correct. Reversed polarity will
lead to no response from the boiler.
CTRLMax Factory Settings
FACTORY DEFAULT
HEATING SETTING
Heating OperationEnabledEnabled
Demand Type
Absolute Max CH Setpoint185°F [85°C]185°F [85°C]68°F [20°C]188°F [87°C]
CH1 Maximum Setpoint180°F [82°C]180°F [82°C]68°F [20°C]188°F [87°C]
DHW to CH Call Blocking1 Minute1 Minute0 Minute30 Minutes
Antilegionella FunctionDisabled
Enabled
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP RESETINSTALLER RESET
✓
✓✓
✓✓
✓✓
✓✓
✓
✓✓
✓
✓
✓
Enabled
✓
BOILER SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
INSTINCT Solo
INSTINCT Combi
Lockout Temp.210°F [99°C]
Modbus Address0=BCST0=BCST247
Flex. Relay 1(CH)CH1
Flex. Relay 2(DHW)DHW
Flex. Relay 3(P3)CH1/CH2/DHW
Flex. Relay 4(ERR)ERROR
Flex. Relay 5(Flame)FLAME
Flex. Relay 6(P4)CH2
Error Relay
On Lockout, Blocking
and Warning
Pump PWM Minimum30%1%100%
Ignition LevelVaries by model
Mix Zone High Limit114°F [45°C]68°F [20°C]176°F [80°C]
Appliance SettingVaries by model
Altitude Setting0 ft0 ft20,000 ft
EZ SETUP RESETINSTALLER RESET
✓
✓
✓
78
Page 91
CHAPTER 14 - CHECK-OUT PROCEDURES
NOTICE
Perform the following check-out procedures
as outlined and check off items as completed. When procedures are completed, the installer should complete the installation record
in Chapter 15 on page 81.
q Boiler system uid chemistry checked and veried
as outlined in Section 10.1 on page 67..
q Boiler system was completely ushed to remove
any debris/sediment.
q Any automatic air vents placed within the system
are open one full turn.
q Air is purged from the heating zones and boiler sys-
tem piping.
q If applicable, conrm that the burner has been
properly congured for Propane as outlined in Sec-
tion 7.3 on page 42.
q Thermostat circuit wiring checked and veried that
no voltage is present as outlined in Section 10.6 on
page 70.
q Operating Instructions were followed during start-
up.
q Combustion levels and ame pattern veried as
outlined in Section 11.3.5 on page 73.
q Measured the rate of input on Natural Gas as out-
lined in Section 11.3.6 on page 74.
q Test high temperature limit as outlined in Section
11.3.7 on page 74.
q Checked the incoming gas pressure to the IN-
STINCT to ensure a minimum pressure of 5”w.c
during ow conditions to all gas appliances and a
maximum pressure of 13”w.c during non-ow conditions for Natural and Propane.
q Adjusted balancing valves and system limit con-
trols to provide design temperatures to the primary
space heating system.
q In multiple zone applications, adjusted for correct
ow of boiler water to each zone.
q Checked and veried room thermostat(s) function
properly and the thermostat(s) heat anticipator (if
used) was properly set.
q Observed several operating cycles for proper oper-
ation of the INSTINCT and the system.
q Set the room thermostat(s) to the desired room
temperature.
q Reviewed all instructions shipped with the IN-
STINCT with the homeowner or maintenance personnel.
q Completed the Installation Record of Chapter 15
on page 81.
q Ensure all manuals and other documents are re-
turned to the Installation envelope and given to
the owner for safekeeping.
CHAPTER 14
79
Page 92
INTENTIONALLY LEFT BLANK
Page 93
CHAPTER 15 - INSTALLATION RECORD
Ensure all manuals and other documents are returned to the Installation envelope and given to the owner for
safekeeping.
INSTINCT Model Number:
Serial Number:
Date of Installation:
Fuel: Natural Gas Propane
Measured Rate of Input:
Combustion Readings:
As Operating:
CO
2
%
Btu/hr =
As Installation Manual Table 6:
CO
2
3600
seconds per 1ft
%
3
gas
x 1000
OK
NOT OK
O
2
CO
%
ppm
O
2
CO
%
ppm
The following items were completed during installation:
Installation instructions have been followed and completed
Check-out procedures have been followed and completed
Information regarding the unit and installation received and left with owner /
maintenance personnel.
If air for combustion is taken from inside the property the customer has been made
aware of their obligation to ensure air grilles remain free from obstruction at all times.
CHAPTER 15
Installer Information
(Company)
(Address)
(Address)
(Phone Number)
(Contractor / Installer Name)
(Customer Name)
SignatureDate
SignatureDate
81
Page 94
INTENTIONALLY LEFT BLANK
Page 95
CHAPTER 16 - MAINTENANCE SCHEDULES
16.1. Service Technician
At least on an annual basis the following maintenance
should be performed by a qualied service technician:
General
• Attend to any reported problems.
• Inspect the interior of the boiler jacket area; clean
and vacuum if necessary.
• Clean the condensate drain assembly and ll with
fresh water.
• Check boiler uid pH on systems.
• Check for leaks, both inside and outside the unit:
water, gas, ue and condensate.
• Verify vent piping and air inlet piping are in good
condition, sealed tight and properly supported.
• Check boiler water pressure, piping and expansion
tank.
• Check control settings.
• Check ignition electrode (sand o any white oxide;
clean and reposition).
• Check ignition wiring and ground wiring.
• Check all control wiring and connections.
• Check burner ame pattern (stable and uniform).
• Check carbon monoxide detectors.
Additional items if combustion or performance is poor:
• Clean heat exchanger and ue ways.
• Remove burner assembly and clean burner head
using compressed air only.
16.2. Owner Maintenance
Periodically:
• Check the area around the unit.
• Check and remove any blockage from the combustion air inlet and ventilation openings.
• Check the temperature and pressure gauges.
Monthly:
• Check vent piping.
• Check combustion air inlet piping.
• Check the pressure relief valve.
• Check that the condensate drain system goes to
the loor drain.
Every 6 months:
• Check boiler piping and gas supply piping for corrosion or potential signs of leakage.
• Operate the pressure relief valve.
WARNING
Follow the maintenance procedures given
throughout this manual. Failure to perform
the service and maintenance or follow the
directions in this manual can result in damage to the INSTINCT or system components,
resulting in substantial property damage, se-
rious injury, or death.
Once the maintenance items are completed, review
the service with the owner.
DANGER
• Where air for combustion is taken directly from inside the property. It is essential
this air supply is free from obstruciton.
Failure to supply adequate air for combus-
tion may result in serious injury or death.
CHAPTER 16
83
Page 96
INTENTIONALLY LEFT BLANK
Page 97
CHAPTER 17 - MAINTENANCE PROCEDURES
17.1. Service Technician Maintenance Procedures
WARNING
The INSTINCT must be inspected and serviced
annually, preferably at the start of the heating
season, by a qualified service technician. In addition, the owner maintenance and care of the
unit as outlined in Chapter 16 on page 83 and
further explained in the INSTINCT User’s Information manual should be performed to assure
maximum efficiency and reliability of the unit.
Failure to service and maintain the INSTINCT
and the system components can result in equipment failure, resulting in substantial property
damage, serious injury, or death.
NOTICE
The following information provides detailed
instructions for completing the service technician maintenance items outlined in the main-
tenance schedule of Chapter 16 on page 83.
17.2. Reported Problems
Any problems reported by the owner should be
checked, veried and corrected before proceeding
with any maintenance procedures.
17.3. Check Surrounding Area
• Re-install venturi inlet elbow and front jacket panel
when completed.
WARNING
Do not use solvents to clean any of the burner components. The components could be
damaged, resulting in unreliable or unsafe
operation. Failure to comply with this instruction can result in substantial property
damage, serious injury, or death.
17.5. Check System Piping
• Inspect all water and gas piping for leaks and verify
that the piping is properly supported.
• Inspect the ttings and components on the unit
and verify they are leak free.
WARNING
Eliminate all system water leaks. Continual
fresh make-up water will reduce the heat exchanger life causing boiler failure. Leaking
water may also cause severe property damage to the surrounding area. Inspect the gas
supply piping using the procedure outlined in
Section 11.3.4 on page 73. Failure to comply
with this instruction can result in substantial
property damage, serious injury, or death.
• Verify that the area surrounding the INSTINCT is free
of combustible / ammable materials or ammable
vapors or liquids. Remove immediately if found.
• Verify that combustion air inlet area is free of any
contaminates. Refer to the materials listed in Sec-tion 2.1 on page 5 of this manual. If any of
these products are in the area from which the unit
takes its combustion air, they must be removed
immediately or the combustion air intake must be
relocated to another area.
17.4. Inspect Burner Area
• Remove the boiler front jacket panel and venturi
inlet elbow.
• Vacuum any dirt or debris from the burner/blower
components.
• Check the burner plate mounting nuts for tightness, see Section 17.24 on page 88 for torque
specication.
• Check burner plate gasket for discoloration or damage.
• Check for ue gas leakage where the condensate
pan connects to the heat exchanger and at the top
and bottom of the internal vent pipe.
17.6. Clean Condensate Drain Assembly
NOTICE
For the INSTINCT Combi unit, the front panel
needs to be removed to gain access to the con-
densate drain assembly.
• Loosen the retaining nut from the condensate drain
assembly and disconnect the assembly from the boiler.
• Empty any water from the trap and ush with fresh
water as necessary to clean.
• Remove plastic ball and clean with fresh water.
• Check the drain piping from the condensate drain
assembly to the drain. Refer to Section 6.2 on page
38. Flush to clean as necessary.
• Install the plastic ball into the condensate drain
assembly and reassemble onto the boiler by tightening the retaining nut with rubber seal onto the
boiler. Hand tight only.
• Remove the ll plug on the condensate drain assembly and ll with water. See Fig. 24 on page 39.
• Replace the ll plug on drain assembly.
CHAPTER 17
85
Page 98
CHAPTER 17 - MAINTENANCE PROCEDURES
17.7. Check Ventilation Air Openings
• Verify that all ventilation openings to the mechanical room or building are open and unobstructed.
Check the operation and wiring of any automatic
ventilation dampers.
• Check and verify the vent termination and the combustion air intake are free of debris and obstructions.
17.8. Inspect Vent and Combustion Air Piping
• Visually inspect the venting system and combustion air piping for blockage, deterioration of gaskets or leakage. Repair any deciencies.
• Verify that the combustion air inlet and vent piping
is connected, sealed and properly supported.
DANGER
Failure to inspect the vent system and combustion air inlet piping and to have any conditions
repaired, will result in serious injury, or death.
17.9. Check Boiler System
• Verify all system components are correctly installed
and operating properly.
• Check the cold ll pressure for the system. Typical
cold water ll pressure is 12 psig.
• Verify the system pressure, as the unit operates at
high temperature, does not exceed 30 psig. Excessive pressure indicates expansion tank sizing is incorrect or system performance problems.
• Inspect air vent and air separators in the system.
Ensure vents do not leak, replace any leaking vents.
CHAPTER 17
• Verify boiler uid pH level is between 6.0 and 8.0.
• Check and verify inhibitor /antifreeze concentration
within the boiler water meets inhibitor/antifreeze
manufacturer’s specications.
• If necessary contact a boiler water treatment company for a chemical analysis.
17.10. Check Expansion Tank
Refer to Chapter 4 on page 15 for recommended location of the expansion tank and air eliminators.
Closed -Type Tank:
• Ensure tank is partially lled with water leaving an
air gap as a cushion. Refer to the manufacturer’s
instruction for proper ll level.
• Ensure the tank is tted with a device that reduces
gravity circulation of air-saturated tank water back
into the system. This device prevents air from bubbling up through the water as it returns from the
system.
• Ensure no automatic air vents are used in the system. This will allow air to escape from the system
instead of returning to the tank.
Diaphragm Tank:
• Ensure the system contains a minimum of one automatic air vent. Recommended location of the air
vent should be atop an air eliminator.
• Remove the tank from the system and check the
charge pressure. For residential applications, the
charge pressure is typically 12 psig. If tank does not
hold pressure, then the membrane is damaged and
the tank should be replaced.
17.11. Check Boiler Relief Valve
Inspect the relief valve and lift the lever to verify ow at
least annually or as recommended on the warning tag
of the valve.
WARNING
Before manually operating the pressure relief
valve, ensure the discharge piping is directed to a suitable place of disposal to avoid a
potential scald hazard. The discharge piping
must be full size without restriction and installed to permit complete drainage of both
the valve and line. Failure to comply with this
instruction can result in substantial property
damage, serious injury, or death.
If after closing the valve, the valve fails to seat properly
or continually weeps, replace the relief valve. Ensure
the cause of the relief valve to weep is the valve itself,
not due to system over-pressurization caused by an expansion tank that is waterlogged or undersized.
17.12. Inspection of Ignitor
• Remove the ignitor from the burner mounting plate.
• Remove any white oxides accumulated on the ignitor using ne grit sandpaper or steel wool. If the
ignitor does not clean to a satisfactory condition,
replace the ignitor .
• When installing the ignitor, ensure the gasket is in
good condition and correctly positioned. Replace
the gasket if necessary. Tighten ignitor screws in
multiple steps, alternating between the screws to
ensure proper alignment. See Section 17.24 on page 88 for torque specications.
86
Page 99
CHAPTER 17 - MAINTENANCE PROCEDURES
17.13. Check Ignition Cable and Ground Wiring
• Inspect the ignition cable from the spark generator
to the ignitor.
• Inspect the ground wire from the spark generator
to the ignitor.
• Ensure wiring is in good condition and securely
connected.
• Check ground continuity using a continuity meter.
• Replace ground wire if ground continuity is not
satisfactory.
17.14. Check Control Wiring
Inspect all control wiring. Ensure wiring is in good condition and properly connected.
17.15. Check Control Settings
• Review all boiler settings in the Heating & DHW
EZ Setup menus. Adjust settings as necessary, see
Section 9.7 on page 56 and Section 9.8 on page 58
• Check any external limit control settings (if used).
Adjust settings as necessary.
17.16. Perform Start-up and Checkout Proce-
dures
• Start the unit and perform the start-up procedures
as listed in Chapter 11 on page 71.
• Verify the cold water ll pressure is correct and the
operating pressure of the boiler is within normal
operating range.
• Complete the checkout procedures as outlined in
Chapter 14 on page 79.
17.17. Check Burner Flame
• Inspect the ame pattern through the observation
port of the heat exchanger.
• If ame pattern is not fully blue and covers the entire burner surface during high re, shut the unit
down and allow it to cool thoroughly before disassembly.
• Close the external manual gas valve on the gas
supply line and disconnect the gas piping and gas
valve wire harness connector.
• Disconnect the wiring harness connectors from the
blower and remove the blower clamp. Remove the
blower from the unit.
• Remove the mounting nuts securing the burner
plate to the heat exchanger and set aside.
• Carefully remove the burner plate assembly from
the heat exchanger. Ensure that the combustion
chamber 2-in-1 insulation is not damaged during
removal of burner mounting plate assembly.
• Remove the burner head mounting screws and remove the burner head. Inspect the burner head for
deterioration. Use compressed air or a vacuum to
clean the burner head.
• Remove the venturi and gas valve assembly from
the blower.
• Use a vacuum cleaner or compressed air to clean
the interior of the blower assembly. Inspect the
blower blades to ensure they are clean and not
damaged.
• Re-assemble the venturi and gas valve onto the
blower. Ensure the venturi gasket or o-ring is in
good condition and positioned correctly. Replace
gasket or o-ring if necessary.
• Re-assemble the burner head onto the burner
mounting plate. Ensure the burner head gasket
is in good condition and positioned correctly. Replace gasket if necessary.
• Re-assemble the burner plate assembly onto the
heat exchanger. Ensure the combustion chamber
2-in-1 insulation is in place and positioned correctly. Replace if necessary.
• Remove the blower gasket from the burner plate
assembly and clean with fresh water. Reinstall
blower gasket onto burner plate assembly with the
check valve hinge at the top.
• Re-assemble the blower onto the burner plate and
reconnect the wiring harness connectors.
• Re-assemble the gas supply connection and wire
harness to the gas valve. Open the external manual
gas valve. Check gas piping for any leaks as outlined
in Section 10.5 on page 70 and repair if necessary.
• Torque all screws, bolts, and nuts in accordance
with specications in Section 17.24 on page 88.
• Place the unit back into service.
17.18. Check Flame Signal
• The ame signal can be read from the Boiler Information screen. It should be a min. 2-3 Α at low re.
• Check the ignitor condition if ame signal is low.
• Check ground wire for continuity if ame signal is
low. Replace ignitor if conditions are satisfactory.
CHAPTER 17
87
Page 100
CHAPTER 17 - MAINTENANCE PROCEDURES
17.19. Check Combustion Levels
• Re-assemble the blower onto the burner plate and
reconnect the wiring harness connectors.
Refer to Section 11.3.5 on page 73 for measuring
combustion levels and burner adjustments.
17.20. Check Flue Gas Temperature
• Manually place the boiler into high re. See Section
11.3.5 on page 73 for procedure.
• Navigate to the Boiler Information Menu to observe the
ue gas temperature. See Section 9.14 on page 61 .
• If the ue gas temperature is more than 54°F [30°C]
above the supply water temperature, shut the boiler down and follow the heat exchanger cleaning
procedure below.
• Reconnect the gas piping and wire harness to the
gas valve. Open the external manual gas valve.
Check gas piping for any leaks as outlined in Sec-tion 10.5 on page 70 and repair if necessary.
• Torque all screws, bolts, and nuts in accordance
with specications in Section 17.24 on page 88.
• Close isolation valves on the boiler water piping to
isolate the boiler from the heating system.
• Attach a hose to the boiler drain valve and ush
the boiler thoroughly with fresh water by using the
purge valves to allow water to enter through the
make-up water line to the boiler.
• Once the boiler has been completely ushed, re-
17.21. Clean Heat Exchanger
Shut down the boiler:
• Follow the instructions on page 72 “To Turn
O Gas to Appliance”
• Do not drain the boiler unless the boiler will be
subject to freezing conditions.
• Do not drain the boiler if antifreeze is used in
the system.
• Allow the boiler to cool down to room temperature
before servicing.
turn the boiler back into operation.
• Perform the required startup and checkout proce-
dures as outlined in Chapter 10 on page 67 and Chapter 14 on page 79.
17.22. Check Carbon Monoxide Detectors
Verify that at least two (2) carbon monoxide detectors
are installed and operating properly. One must be installed in the mechanical room where the INSTINCT is
located and another installed in the living area outside
the bedroom(s).
• Close the external manual gas valve on the gas
supply line and disconnect the gas piping and gas
valve wire harness connector.
• Disconnect the wiring harness connectors from the
blower and remove the blower clamp. Remove the
blower from the unit.
CHAPTER 17
• Remove the mounting nuts securing the burner
17.23. Review With Owner
Ensure the owner understands the importance of performing the maintenance schedule specied in this
manual.
plate to the heat exchanger and set aside.
• Carefully remove the burner plate assembly from
17.24. Torque Specifications Table
the heat exchanger. Ensure that the combustion
chamber 2-in-1 insulation is not damaged during
removal of burner mounting plate assembly.
• Use compressed air or water to remove any accumulation from the heat exchanger ue ways.
• Re-assemble the burner plate assembly onto the
heat exchanger. Ensure the combustion chamber
2-in-1 insulation is in place and positioned correctly. Replace if necessary.
ItemMin.Max.
Burner Plate Nuts4453
Burner Head Bolts26.531
Fan Clamp Screw6271
Gas Valve Screws3135
Venturi Screws3135
Ignitor Screws26.531
Torque Req’d (in-lbs)
• Remove the blower gasket from the burner plate
assembly and clean with fresh water. Reinstall
blower gasket onto burner plate assembly with the
check valve hinge at the top.
88
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.