TriangleTube Phase III HM Series, HM G-30, HM G-25 Installation And Maintenance Manual

Page 1
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa­tion in order to gain warranty coverage.
When receiving Phase III®units, any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
WARNING
* I N S
* I N S T T
A L L
A L L A A
T I O N
T I O N
A N D M
A N D M
A I N
A I N
T E N
T E N
A N C E *
A N C E *
M
M
A N U
A N U
A L
A L
- Input from 100,000 to 120,000 Btu/hr -
NOTICE
TECH-HMG-25/30-11/99
Phase III HM Series
G-25 & G-30
Gas Fired Forced Draft
with Optional
Sealed Combustion
Combination Heate
rs
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
For Your Safety
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppli­er’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
CONFORMS TO
ANSI Z 21-10-3 CERTIFIED TO
90870
CGA CAN 1-4-3 M85
Page 2
i
SAFETY INFORMATION
Product and safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
PRE-INSTALLATION
Code compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Verifying venting system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation located in confined spaces . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Combustion and ventilation air requirements . . . . . . . . . . . . . . . . . . . . . . 4
Recommended clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Locating combination heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operating restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION
Venting the combination heater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chimney draft venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Direct venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Venting through cold area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Direct venting procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Piping the combination heater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Thermal expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Air vent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Temperature and pressure relief valve . . . . . . . . . . . . . . . . . . . . . . 9
Pressure relief valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Water hammer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
General piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Inner tank (domestic) piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Outer tank (system) piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Domestic piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Primary piping - near appliance piping . . . . . . . . . . . . . . . . . . . . . 12
Space heating piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Combination heater wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-17
Gas supply piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-19
COMBINATION HEATER START-UP
Filling the inner tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Filling the outer tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Burner operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
System piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TABLE OF CONTENTS
Page 3
ii
Venting system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
SETTING THE WATER TEMPERATURE
Setting the combination water heater limits. . . . . . . . . . . . . . . . . . . . . . . . 23
Setting domestic water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
COMBINATION HEATER MAINTENANCE
Annual maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Flueway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Pressure relief valve and T&P relief valve. . . . . . . . . . . . . . . . . . . 24
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Air vent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Periodical maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Combustion chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Draining the combination heater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Drain outer tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Drain inner tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-26
Space heating system contains sufficient anti-freeze . . . . . . . . . . . 28
SPECIFICATION DATA
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
PARTS LIST
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
SAMPLE SPECIFICATION
Sample specification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
TABLE OF CONTENTS
Page 4
1
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas suppli­er, call the fire department.
Installation and service must be per­formed by a qualified installer, service agency or the gas supplier.
Should overheating occur or the gas supply fails to shut off, turn OFF the manual gas control valve external to the appliance.
To prevent damage to inner tank, installer must:
• Fill inner tank prior to outer tank during start-up.
• Relieve primary system pressure below 15 psig prior to draining inner tank.
CAUTION
WARNING
DANGER
DANGER
PRODUCT & SAFETY INFORMATION
Indicates the presence of a hazardous situation which, if ignored, will result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situa­tion which, if ignored, can result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situa­tion which, if ignored, may result in minor injury or property damage.
Indicates special instructions on installa­tion, operation or maintenance, which are important to equipment but not related to personal injury hazards.
NOTICE
CAUTION
WARNING
DANGER
The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product.
Page 5
2
Bacteria can develop in the domestic water system if certain minimum water temperatures are not maintained.
Water temperature over 125ºF can cause severe burns instantly or death from scalds.
Children, disabled and elderly are at highest risk of being scalded.
-Never leave them unattended in or near shower, bathtub or sink.
-Never allow small children to use a hot water faucet or draw their own bath.
If any one using hot water in the building fits this description or codes require spe­cific water temperatures at hot water faucet, we recommend:
a)ensure the factory installed thermosta-
tic mixing valve is working properly.
b)to set the thermostatic mixing valve
for the lowest temperature which sat­isfies your hot water need.
This will also provide the lowest operating cost.
Adjusting the water temperature
Setting the knob to a lower temperature will not have an immediate effect. The stored hot water will first have to be used.
Further adjustments may be necessary as you use your Phase III Combination Heater System.
Protection must be taken against excessive temperature and pressure!
TO PROTECT AGAINST EXCES­SIVE TEMPERATURE AND PRES­SURE
Check if the Temperature and Pressure (T&P) relief valve is in the location provided. (Domestic Water)
Check if the 30 psi relief valve sup­plied is in the location provided. (Primary water)
•To avoid injury, install the relief devices to comply with local code requirements.
CAUTION
WARNING
DANGER
WARNING
PRODUCT & SAFETY INFORMATION
!
DANGER
HOT
BURN
Page 6
3
A. Combustion air inlet B. Flueway fitted with stainless steel turbulators C. Primary water D. Primary Circuit thermostat (up to 180ºF) sensing bulb E. Burner F. Water cooled immersed combustion chamber G. Primary circuit drain connection H. Corrugated stainless steel heat exchanger J. 1 1/2” of rigid (CFC-Free) polyurethane insulation K. Steel body containing primary water L Primary Connections M.Baffles (turbulators) N. Primary connection O. Baked enamel steel jacket T. Domestic water U. Safety limit thermostat (200ºF) (manual reset) (not shown) L.W.C.O.: Low water cut-off device (not shown)
Anatomy of your Combination Heater
PRE-INSTALLATION
Fig. 1: Cross section of Combination Heater
Legend
1- CODE COMPLIANCE
Combination Heater installation must con­form to the requirements of local codes and the authority having jurisdiction. In the absence of these requirements:
Gas fired heaters should be installed in accordance with National Fuel Gas Code, ANSI Z223.1.
For installations in Canada - CGA/B149 Installation Code for Gas Burning Equipment.
All electrical wiring, including grounding of the heater must be in accordance with local codes; or in the absence of local codes with the National Electrical Code, ANSI/NFPA 70.
The HM G-Series combination heaters are exempted from ASME Section VIII-1-86-136. Check with local codes for applicability.
2- VERIFYING VENTING SYSTEM
• Confirm that the venting system is of sufficient size to handle the flue gases of all connected equipment.
Check that it is clear and free of obstruc­tions. Particular attention should be given to replacement of oil systems.
Soot may have degraded the chimney liner and/or accumulated in the chimney liner requiring a liner replacement or cleaning.
•Visually inspect the venting system for proper size and horizontal pitch.
If inspection reveals that the existing chimney is unsafe or inadequate for the application, it should be rebuilt to con­form to local or national codes, lined or relined, or provided with a new chimney or vent sized for the application.
DANGER
L
Hot water outlet
U
A B
C
T
D
E
Cold
water
inlet
O M
K
J
H N
F
G
Page 7
3- INSTALLATION LOCATED IN CON-
FINED SPACES
Sufficient air must be pro vided for satisf ac­tory combustion, proper venting and venti­lation to maintain ambient temperatures at safe limits under normal operating condi­tions in accordance with National Fuel Gas Code latest editions.
For installations located in unconfined spaces in buildings, infiltration may be adequate for combustion and ventilation. However, in a building of tight construction (i.e. weather stripping, vapor barriers, caulked, etc.), addi­tional air may be provided using the methods described in Combustion and Ventilation Air Requirements.
4- COMBUSTION AND VENTILATION AIR
REQUIREMENTS
1.When all air is to be taken from INSIDE a building with adequate infiltration, the confined space shall be provided with two permanent openings to the room. Each opening, one located within 12” above the floor the other within 12” of the ceiling, shall have a free area of one square inch per 1,000 BTU/H for the total input of all the equipment located in the space, but not less than 100 square inches.
2.When all air is taken from OUTDOORS the confined space shall be provided with two openings, one 12” above the floor the other 12” below the ceiling. Each opening shall be sized for total input of all the equipment in the space as follows:
a. If opening is directly connected to the
outdoors, or if connected to the out­doors through vertical ducts: 1 square inch free area per 4,000 BTU/H total input.
b. If opening is connected to the outdoors
through horizontal ducts: 1 square inch free area per 2,000 BTU/H total input.
3. Ducts, when used, shall have the same cross sectional area as the free area of the openings to which they are connected.
The minimum dimension of a rectangu­lar air duct is 3 inches.
4. Sealed combustion applications:
•A 3” diameter vent can be connected directly to the blower inlet to draw outside air directly to the heater.
• See Table 1, pg. 7 for Air Inlet System Limitation.
• Galvanized steel, stainless steel or equivalent vent material.
When the combination heater is to be installed in beauty shops, dry cleaning establishments or other places with airborne chlorides, fluorides, hydrocarbons or clean­ing fluids, it is essential the combustion air is taken from outside these areas.
5- RECOMMENDED CLEARANCES
Clearance to combustibles: Sides 6”, Top 6”, Venting 8”, Rear 6”,
Front 6” .
HM combination heaters are certified for combustible floors. This combination heater should not be installed directly on carpet. It must be installed directly on the floor or on metal or wood panel covering the entire combination heater base. The panel must be strong enough to carry the weight of the heater when full of water.
Clearance for servicing:
- 12” for piping & servicing rear.
- 24” for access to control and compo­nents, front.
- 36” for flueways, top.
- 6” on remaining side
NOTICE
NOTICE
4
PRE- INSTALLATION
Page 8
5
PRE- INSTALLATION
6- LOCATING COMBINATION HEATER
Direct, sidewall venting
Give special attention to location of combi­nation heater vent to avoid possibility of severe personal injury, death, or substantial property damage.
- Flue gases will form a white plume in winter.
- Plume could obstruct favorite window view.
- Prevailing winds could cause freezing of condensate and water/ice build-up on building, plants or roof.
- Excessive winds may cause nuisance Combination Heater shutdowns when unit is sidewall vented.
- Locate or guard the vent to prevent accidential contact by people or pets.
-Vent must terminate at least 4 feet below, 4 feet horizontally from any door, window or gravity air inlet to the building. This vent must not be less than 7 feet above grade when located adjacent to public walkways.
- DO NOT terminate vent into window well, stairwell, alcove, courtyard or other recessed area.
- DO NOT terminate vent above any door, window or gravity air inlet. Condensate can freeze causing ice formations.
-Terminate vent at least 6 feet from adja­cent walls.
-Terminate vent at least 1 foot above grade, including normal snowline.
This combination heater is not approved for outdoors installation. It should be located indoors in an area with above freezing temperatures.
The combination heater should be located so that any leakage from the tank or water connections will not cause damage to the area adjoining the combination heater or to lower floors in the structure.
- When such a location is una voidable a suitable drain pan with adequate drainage, should be placed under the combination heater. The pan must not restrict combustion air flow.
7- OPERATING RESTRICTIONS
Maximum working pressure for inner (domestic water) tank is 150 psig.
Maximum working pressure for outer (primary water) tank is 45 psig.
Maximum domestic hot water tempera­ture is 180ºF (use only for special high­temperature operational requirements).
Inner tank has factory installed Temperature & Pressure Relief Valve with an AGA rating of 100,000 Btu/hr for G-25 and 200,000 Btu/hr. for G-30.
Outer tank has a factory installed 30 psig relief valve rated at 535,000 Btu/hr
Electrical rating:120 V, 60 Hz, less than 12 amperes
Single wall heat exchanger in combina­tion heater complies with National Standard Plumbing Code, provided that:
- Outer tank water (including addi­tives) is practically non-toxic, hav­ing toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products,
- Outer tank pressure is limited to maximum 30 psig by approved relief valve.
pH & chloride limits for combination heater are:
- Chloride, less than 80 mg/l.
- pH, 6-8.
NOTICE
WARNING
Page 9
6
1- VENTING THE COMBINATION HEATER
Determine venting method to use. Refer to appropriate sections for instal­lation details.
• Use vent materials approved by local codes for gas-fired appliances. In their absence refer to:
- National Fuel Gas Code, ANSI Z223.1.
- In Canada, refer to CAN/CGA B149 Installation Code for Gas Fired Equipment.
- NFPA 211, Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances.
1A. Chimney Draft Venting
Use galvanized steel vent or equivalent
•To prevent downdrafts, chimney should extend at least 2 feet above highest part of roof or other structures within 30 feet.
•To vent with another appliance, see National Fuel Gas Code, ANSI Z223.1, latest edition.
•For inside chimney (no walls exposed to outside).
- Inside of chimney must be lined with vitreous tile or metal liner.
- Maintain two-inch clearance from combustible material to vent pipe.
- DO NO T use chimney with open f ire­place.
- Inspect chimney and clean if needed.
- Make horizontal runs as short as possi­ble. Long runs can cause condensation.
- When longer runs are used, support with appropriate hangers.
-To prevent blockage, do not vent into bottom of chimney.
-Vent pipe must not go beyond inside wall of chimney.
-Vent passing through floors or ceil­ings must be firestopped.
Outside chimney (one or more walls exposed to outside)
- Can be used for chimney draft vent­ing only when lined with corrosion resistant metal liner. Provide con­densation drain.
- Size liner per ANSI Z223.1. Increase breeching at the appliance.
- Can be used a raceway for direct venting.
1B. Direct Venting
When replacing an existing appliance on common venting system, the vent system may be too large for remaining appli­ances. Refer to ANSI Z223.1 for proper sizing.
Give special attention to location of Combination Heater vent to avoid possi­bility of severe personal injury, death, or substantial property damage.
•Review “Locating Combination Heater” to determine location of venting.
Use AL29-4C or equivalent vent material.
1C. Venting Through Cold Areas
Extended runs through cold areas could cause condensation which must be drained away.
Provide a means to trap and drain con­densation from the vent system. Do not place drain where freezing could occur.
Crimped ends of vent pipe must face toward appliance.
WARNING
CAUTION
INSTALLATION
Page 10
Use AL29-4C or equivalent vent material and follow “Direct Venting” Procedure.
1D. Direct Venting Procedur e
1.Determine entire vent length and num­ber of elbows required. Actual venting system must not exceed limitations in Table 1 below or as stated in ANSI Z
223.1.
2.Use 3-inch diameter vent pipe pitched up from Combination Heater. Do not connect other appliances to this vent.
3.Seal all AL29-4C vent joints with approved silicone sealant (400ºF ­Dow 732 RTV or equivalent)
4.MAINTAIN TWO-INCH CLEAR­ANCE from combustible materials to vent pipe.
5.Long horizontal vent runs should be supported with appropriate hangers. Ensure vent pipe is pitched up from the unit at 1/4” per foot minimum.
6.Direct sidewall vent termination:
• Masonary walls - make a 3 1/2 to 4 -
inch diameter hole.
• Combustible material - requires 7-
inch hole. Make sheet metal plate with 3-inch hole to cover opening.
• Must be in the same pressure zone
(i.e. same outside wall) as the com­bustion air inlet.
7
INSTALLATION
Total length for 3" AL29-4C Venting System and 3"
Combustion Air Inlet vs number of elbows
Maximum length - feet 50 45 40 35
Maximum number of elbows
1234
Direct Venting thru Non-Combustible Wall
Direct Venting through
Outside Chimney
Fig. 2
Fig. 3
Table 1
Caulk opening
Anchored fastners
Cement
mortar
seal
Metal Plate
Vent Termination
Flashing
recommended to direct exhaust away from wall
12" Min.
Grade level
Sealed chimney
opening
3" Stainless steel vent pipe
vertical run through
entire chimney
Seal all joints inside and outside of chimney
Air Intake
Triangle
Tube
Pitch up
1/4"/Ft
Page 11
8
Metal Plate
Direct Venting thru Combustible Wall
INSTALLATION
Draft Venting Through the Roof
Draft Venting through Inside Chimney
Fig. 4
Fig. 5
Fig. 6
2" Min.
clearance
Caulk opening
Anchored fastners
Vent Termination
Flashing
Anchored
fastners
recommended
to direct exhaust
away from wall
12" Min.
Grade level
Flashing with Collar
Per ANSI Z-223.1
Air Intake
Triangle
Tube
Size Vent
Vent Cap
Inside
Chimney
Seal
Tight
Pitch up
1/4"/Ft
Increaser connection
(size per ANSI Z-223.1)
Air Intake
Triangle
Tube
Page 12
9
2- PIPING THE COMBINATION HEATER
A-Thermal Expansion
If a backflow preventer, check valve or pressure reducing v alve is piped on cold water inlet, install an expansion tank on cold water supply line to prevent nor­mal thermal expansion from repeatedly forcing open T&P relief valve.
T&P relief valve is not intended for constant duty, such as relief of pressure due to repeated normal system expan­sion. Correct this condition by installing a properly sized expansion tank in domestic water system. Refer to expansion tank manufacturer’s instructions for proper sizing.
B- Air Vent
Automatic air vent is factory installed on the heater.
Unscrew vent cap on air vent one full turn. Leave cap unscrewed one turn for normal venting.
C- Temperature and Pressure Relief
Valve
T&P relief valve is factory installed on inner tank of the heater.
T&P relief valve per AGA of 100,000 Btu/hr for G-25.
T&P relief valve rated per AGA of 200,000 Btu/hr for G-30.
T&P relief valve dischar ge piping must be:
- made of material serviceable for temperatures of 250ºF or greater
- directed so that hot water flows away from all persons.
- directed to a suitable place for disposal.
- installed so as to allow complete draining of the T&P relief valv e and discharge line.
T&P relief valve dischar ge piping must not be:
-excessively long. Using more than 2 elbows or 15 feet of piping can reduce discharge capacity.
- directly connected to a drain. Terminate discharge piping within 6” from floor. Refer to local codes.
- plugged, reduced or restricted.
- subjected to freezing.
Do not install any valve between T&P r elief valve and tank connection, or on T&P relief valve discharge piping. Do not plug T&P relief valve or discharge piping. Improper placement and piping of T&P relief valve can cause severe personal injury, death or substantial property dam­age.
D- Pressure Relief Valve
Pressure relief valve is factory installed on outer tank of the heater.
30 psig pressure relief valve rated per AGA of 535,000 Btu/hr.
Provide safe discharge through piping near floor or close to floor drain. Relief valv e must be installed so that the spindle is vertical.
To avoid scalding or water damage, relief valve discharge must be piped near floor or close to floor drain. Do not plug, valve or place any obstruction in dis­charge piping.
3. WATER HAMMER
Dishwashers, clothes washers and fast-clos­ing positive shut-off valves incorporated in the system all contribute to creating water shock. Install a water hammer arrester to pre­vent damage to pipes and appliances. See manufacturer’s instructions for application and installation.
WARNING
WARNING
CAUTION
INSTALLATION
Page 13
10
4. GENERAL PIPING
All plumbing must meet or exceed all local, state and national plumbing codes.
Use pipe dope or tape suitable for potable water on the domestic piping.
Use isolation valves to isolate sys­tem components.
Install unions for easy removal of com­bination heater. Use dielectric unions or couplings to protect hot and cold water fittings from corrosion when connect­ing dissimilar materials such as copper and galvanized iron pipe.
If plastic is used for primary water con­nections, it must not exceed a maximum oxygen diffusion rate of 0.1 mg/liter­day for combination heater protection.
When water supply pressure is higher than T&P relief valve rating, install a pressure reducing valve on cold water supply line to prevent water loss through T&P relief valve.
5. INNER TANK (DOMESTIC) PIPING
•A thermostatic mixing valve and check valve are factory installed on the domestic hot water outlet.
Install U tube assembly, (factory assem­bled & provided with the combination heater), to the mixing valve/check valve outlet and to the factory assembly tee at the cold water inlet.
- If there is a need to alter the piping such as adding a tee upstream of the mixing valve to deliver 140º water to the dish washer, (if local codes per­mit) the installer must re-install this mixing valve prior to operation of the combination heater.
The mixing valve must remain mounted on the domestic hot water outlet at all times. Removal of automatic mixing
valve from combination heater will result in severe personal injury or death.
•For recommended domestic water pip­ing arrangement see Fig. 7 page 11.
•For recommended domestic water pip­ing with recirculation see Fig. 8 page 11.
To prevent potential scalding hazard, recircu­lation must be controlled by an additional aquastat. Do not use continuous recirculation.
6. OUTER TANK SYSTEM PIPING
• Recommended piping shown page 12 and 13.
• Install expansion tank:
Diaphragm-type expansion tank. Ensure tank pressure and size will handle system fill pressure and water volume.
- Fill pressure may be adjusted at tank for design conditions. Follow manufacturer’s instructions.
- Locate expansion tank near the unit, before the inlet of the circulator.
Closed-type expansion tank. Size tank to system requirements. Refer to man­ufacturer’s instructions.
Undersized expansion tanks can cause sys­tem water to be lost from relief valve and makeup water added through fill valve Eventual outer tank failure can result.
If antifreeze is used in system water, local codes may require a backflow pre­venter on cold water supply line.
Use antifreeze specifically intended f or hydronic heating systems. Inhibited propylene glycol is recommended.
System water (including additives) must be practically non-toxic, having toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial products.
CAUTION
DANGER
DANGER
INSTALLATION
Page 14
Fig. 8: G Model with mixing valve and recirculation
Fig. 7: G Model with mixing valve without recirculation
1. Mixing valve
2. Flow check valve
3. Shut off valve
4. Backflow preventer or pressure reducing valve
6. Thermal expansion tank
7. Circulator (controlled by aquastat)
8. Domestic drain valve
9. Vacuum breaker (if code permitting)
Note: All shut off valves shown in this figure must be shut when siphon draining the combination heater
Note: All shut off valves shown in this figure must be closed when siphon draining the combination heater
* Re-attach valve handle when draining inner tank.
* Re-attach valve handle when draining inner tank.
11
Do not use automotive, ethylene glycol or any undiluted or petroleum-based antifreeze.
This can cause severe personal injury, death or substantial property damage.
•Any water conditioning system must be installed and maintained in accordance with manufacturer’s specifications.
WARNING
INSTALLATION
To dishwasher if permitted by codes
U-Tube assembly
3*
2 1
3
6
6" Heat trap
9
4
3
Cold water
inlet
7
To dishwasher if permitted by codes
8
3
2
3*
2
1
U-Tube assembly
3
8
6
6" Heat trap
9
4
3
Cold water
inlet
Page 15
To
system
2
1
From
system
2
3
4
2
Cold
water
fill
12
3
To
system
2
1
From
system
2
42
Cold
water
fill
INSTALLATION
To
system
2
1
From
system
2
3
4
2
Cold
water
fill
Primary Piping -Near Appliance Piping
Piping with diaphragm -
type expansion tank
Piping with closed -
type expansion tank
1. Circulator
2. Manual shut-off valve
3. Expansion tank
4. Auto fill valve
Piping with diaphragm - type expansion tank
(alternate circulator location)
Fig. 9
Fig. 9A
Fig. 9B
Page 16
13
1
12" max.
2
2
3
1
2
3
1
2
3
2
3
2
L O A D
L O A D
INSTALLATION
Fig. 10: Primary piping - Zoning with Circulators
Fig. 11: Primary Piping - Zoning with Zone Valve
1. Ciruclator
2. Manual shut-off valves
3. Flow check valve
4. Zone valve
Note: See page 12 for near appliance piping.
• Install balancing valves to adjust flow to distribute heat to all zones
• Size primary manifold for total flow of all ciculators
• Size each circulator to individual circuit requirements
• Install balancing valves to adjust flow to distribute heat to all zones
44
2
1
2
L O A D
2
2
2
L O A D
2
Page 17
14
INSTALLATION
7- COMBINATION HEATER WIRING
Electrical shock hazard. Can cause severe personal injury, death or substan­tial property damage. Disconnect power before installing and/ or servicing.
Wiring Diagram Requirements
All wiring must be a minimum of 14 gauge and installed in accordance with:
- U.S.A. - National Electrical Code and any other national, state or local code requirements having jurisdiction.
- Canada - C.S.A. C22.1 Canadian Electrical Code Part 1 and any other national, provincial and local code requirements having jurisdiction.
If original wire, supplied with appli­ance must be replaced, Type 90ºC or its equivalent must be used.
All electrical contacts shown do not hav e power applied - off shelf condition.
Zone Valves
•Transformer should be sized for maxi­mum load of all zone valves.
Space Heating
•For single zone space heating wiring, connect 24 V thermostat wiring to com­bination heater snap-set labeled “Room Thermostat”.
Outdoor Control Limit
Provided and installed by others
Remove factory jumper and use terminal 9 &10
WARNING
Fig. 12: Wiring Diagram
R2A
Auto Reset Limit
120 VAC
B
3
R
4
R1A
5
R
120V
24V
B
R
7
LWCO
H
On-Off Switch
1
B
B
Y
8
Manual
Reset Limit
Circulator
Blower
Secondary
T-stat
Primary
T-stat
N
G
2
W
Y
3 Port Valve Snap-set
Room T -stat Snap-set
11
BL
9
10
R2B
Factory Jumper
Equipment
Ground
17
16
19
18
V
R3B
Air Switch
15
Note
Note
1.
All wiring must comply with the National Electrical
All wiring must comply with the National Electrical
1.
Code and additional national, state or local code
Code and additional national, state or local code
requirements. For Canadian installations, all
requirements. For Canadian installations, all wiring must comply with the Canadian Electrical Code
wiring must comply with the Canadian Electrical Code
All wiring must be N.E.C. Class 1.
2.
2.
All wiring must be N.E.C. Class 1.
Use 90ºC. thermoplatic wire or equivalent, if only
3.
Use 90ºC. thermoplatic wire or equivalent, if only
3.
4.
R2
OR
OR
R3A
the original wire must be replaced.
the original wire must be replaced.
- Denotes Terminal Block
4.
- Denotes Terminal Block
6
Y
TT
P
V
14
13
Ignition Control
(see Fig. 18)
P
Y
R3
V
R1
12
Page 18
15
INSTALLATION
W
•Factory wired
Domestic priority - will not provide heat to the sytem
Maximum domestic performance
Fig. 13: Circulator wiring - domestic priority
Fig. 14: Power supply wiring - high voltage
W
BK
R
Circulator
Harness
W
G
120 V Supply
Field Wire
GN
H
BK G W
Factory Wire
Harness
Page 19
16
INSTALLATION
Fig. 15: Field wiring with zone circulators.
120
H
VAC
N
Honeywell
R845A
Relay
Circulator
Zone 1
T
2
T
Thermostat
zone 1
T
4
1
Thermostat
zone 2
T
3
6
5
Circulator
Zone 2
3
4
1
2
5
Additonal zones may be
added as shown above
6
1
C
To HM
" Room Thermostat"
Snap Set
Page 20
17
H
H
High Voltage
120
V.A.C.
24
V.A.C.
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
To HM
"Room Thermostat"
Snap Set
Transformer
(Power)
Zone
Valve
Zone Valve
C
1
INSTALLATION
4 W ire Zone Valve
3 W ire Zone Valve
Fig. 16: Multiple zone field wiring using zone valves
* Use isolation relay on 3-wire
zone valve with non-isolated end switch. Transformer and combination heater control can burn out if isolation relay is not used.
Additional zones
Zone 1
Zone 2
H
120
Transformer
(Power)
Room
Thermostat
Room
Thermostat
V.A.C.
24
V.A.C.
Zone
Valve
Additional zones may
be added as shown above
H
High Voltage
Zone Valve
* Isolation relay
To HM
1
"Room Thermostat"
C
Snap Set
Page 21
18
INSTALLATION
1. GAS SUPPLY PIPING
Check that the gas supply meter has suffi­cient capacity for the full input of the unit and any other appliances on the meter.
Refer to Table 2 & 2A page 20 for rec­ommended gas piping.
Support gas piping with hangers, not by the heater or its accessories.
Purge all air from gas supply piping.
Before placing the combination heater into operation check the unit and its gas connections for leaks.
- Close manual main shut-off valve during any pressure testing at less than 13”W.C.
- Disconnect heater and gas valv e from gas supply piping during any pres­sure testing greater than 13”W.C.
Do not check for gas leaks with an open flame - use bubble test. Failure to use bubble test or check for gas leaks can cause severe personal injury, death or substantial property damage.
Use pipe dope compatible with natural and/or propane gas. Apply sparingly
only to male threads of pipe joints so that pipe dope does not block gas flow.
Failure to apply pipe dope as detailed above can result in severe personal injury, death or substantial property damage.
Natural Gas:
1.Refer to Table 2 page 20 for pipe length and diameter. Based on rated combina­tion heater input (divide input by 1,000 to obtain cubic feet per hour).
2. Inlet pressure at gas valve inlet: maxi­mum 14”W.C, minimum 5”W.C.
3.Install 100% lock-up gas pressure regu­lator in supply line if inlet pressure exceeds 14”W.C. Adjust for 13”W.C. maximum.
WARNING
WARNING
Fig. 17
1" x 1" 3/4" Tee
3" Minimum
Direction of flow
Manual Shut off valve
Pressure gauge port (1/8" NPT plugged)
Male union 3/4" NPT
Burner gas train
Pipe Cap
Page 22
19
INSTALLATION
Length of Pipe Capacity of Pipe in Cubic Feet of Gas Per Hour
in Feet (based on 0.60 specific. gravity, 0.30" w.c. pressure drop )
SCH 40 1/2" 3/4" 1" 1-1/4" 1-1/2"
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 860 40 63 130 245 500 760 50 56 115 215 440 670
75 45 93 175 360 545 100 38 79 150 305 460 150 31 64 120 250 380
Table 2: Gas piping sizing - natural gas
•For additional piping schedules, see ANSI Z223.1
Canadian installations must comply with CAN/CGA B149.1 or B149.2 Installation Code.
Page 23
1- FILLING THE INNER TANK
(Domestic W ater)
Never operate combination heater unless it is completely filled with water.
Always fill the inner tank before filling the outer tank to prevent any damage to the inner tank.
1.Close domestic water drain valve
2. Open domestic water isolation valves for combination heater.
3. Vent air from inner (domestic water) tank by opening nearest hot water faucet. Fill domestic water tank com­pletely by allowing water to run until there is a constant flow of water.
4.Close hot water faucet
2- FILLING THE OUTER TANK
(Primary W ater)
1. Close drain valve at system water out­let of combination heater.
2. Open combination heater’s system iso­lation valves.
3.Allow air to escape from outer (system water) tank by opening cap on auto­matic air vent, located on top of com­bination heater.
4.Fill to correct system pressure. Correct pressure will vary with each applica­tion. Normal cold water fill pressure is 12 psig.
For proper combination heater opera­tion, always leave vent cap unscrewed one full turn.
5.When tank is full, air will stop escaping and vent will close. If air vent does not seat proper­ly (i.e., water leaks out), remove cap A. Briefly push in valve B and release it to clean valve seat. Screw cap A on completely, then unscrew one turn.
6. If antifreeze is used in primary water, ensure concentration never exceeds a 50/50 ratio. Primary water (including additives) must be practically non­toxic, having a toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products. Inhibited propylene glycol is recommended. Follow antifreeze manufacturer’s instructions.
Do not use automotive or ethylene glycol antifreeze, or any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage if ignored.
3- BURNER OPERATION
1. Check to see if the HM Combination Heater is filled with water (10-12 psi on Pressure & Temperature gauge on con­sole).
2.Follow operating instructions on page for start-up of the Combination Heater.
3. If appliance fails to start, check for the following conditions:
• Loose connection or blown fuse at power supply
• Secondary thermostat set below water temperature
• Thermostat set below room temper­ature
• Gas not turn on at meter or appliance
WARNING
NOTICE
CAUTION
CAUTION
20
COMBINATION HEATER START UP
A
B
Page 24
21
• Incoming natural gas pressure less than 4” W.C, or propane less than 11” W.C.
4. Check burner flames for proper flame pattern:
•Typical -transparent blue
•Overfired - Flames are large
• Underfired - flame are small
• Lack of combustion air - Yellow tip­ping on flames
4- SYSTEM PIPING
• Check sytem piping for leaks, if found, repair immediately
5- VENTING SYSTEM
• Check the gas tight seal at all vent connection.
COMBINATION HEATER START UP
Honeywell VR 8304M
Honeywell S8610
Fig. 18:Intermittent pilot combination Gas Valve & Electronic Ignition Control
(See Fig. 12)
Inlet
Gas Control Knob
Outlet
Pilot Outlet
12
13
Page 25
22
COMBINATION HEATER START UP
OPERATING INSTRUCTIONS - Honeywell VR8300A
TO TURN OFF GAS TO APPLIANCE
1. STOP! Read the safety information above.
2. Set the heating system thermostat to the low­est setting.
3. Turn off all electric power supply to the appliance.
4. Open front jacket panel and ensure the “ON
- OFF” switch is the “OFF” position
5. This appliance is equipped with an elec-
tronic ignition system. Do not attempt to light the burner by hand.
6. Push in gas control knob slightly and turn clockwise to “OFF” position.
NOTE: Knob cannot be turn to “OFF” unless knob is pushed in slightly. Do not force.
Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you then smell gas, STOP! Follow step “2” in the safety information above. If you don’t smell gas, proceed to the next step.
7. Turn the gas control knob counterclockwise to”ON” position.
8. Reconnect the power supply to the appli-
ance.
9. Reset the unit’s “ON-OFF” switch to ON
and close the front jacket panel.
10. Set the heating system thermostat to the desired
setting.
11. If the appliance will not operate, follow the
instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
The following instructions must be f ollowed exactly, a fire or explo­sion may result causing property damage, personal injury or loss of life.
1. Set the system thermostat to lowest setting.
2. Open front jacket panel and turn “ON-OFF” switch to OFF
3. To turn unit “OFF” follow step 6 in “Operating Instructions” above.
4. Close front jacket panel.
1. This appliance is equipped with an electron­ic ignition system. Do not attempt to light the burner by hand.
2. BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building
•Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppli­er’s instructions.
• If you cannot reach your gas supplier, call the fire department.
3. Use only your hand to push in or turn the gas control knob or move the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explo-
Page 26
The water temperature control knobs are located on the control console. The set point is indicated by a temperature indica­tor on the top of the back plate behind the knob. When shipped from the factory the knobs are rotated completely counter­clockwise to the lowest temperature setting. The temperature settings can be increased by rotating the knobs clockwise,
see Fig. 19 and 20 below.
•Turn thermostat knob clockwise to increase water temperature.
•Turn thermostat knob counter-clock­wise to reduce water temperature.
The recommended temperature settings are 180ºF for the primary thermostat and 140ºF for the secondary thermostat.
Studies have indicated that dangerous bac­teria can form in the potable water distri­bution system if certain minimum water temperatures are not maintained. F or pre­vention of this, it is recommended the sec­ondary thermostat be set at 140ºF.
By storing the water temperature at 140ºF or higher, the quantity of domes­tic water delivered is higher and the customer has additional protection from any bacteria growth.
The secondary thermostat maintains the minimum domestic water storage tem­perature.
1. SETTING THE COMBINATION WATER HEATER TEMPERATURE LIMITS
a. See Figs. 19 and 20 for recommended
setting.
2. SETTING DOMESTIC WATER TEMPER­ATURE
HOT WATER REPRESENTS A SERI­OUS SAFETY HAZARD DUE TO THE POTENTIAL OF SCALDING
A thermostatic mixing valve is REQUIRED in the domestic hot water outlet that would allow the domestic water to be supplied at a lower temperature than the storage temperature.
The factory installed thermostatic mixing valve can be adjusted to control domestic supply water at 95ºF to 120ºF.
Refer to the mixing valve’s manufacturer’s instructions for setting the desired domestic supply temperature.
For proper operation of the thermostatic mixing valve, the shut-off valve located on the U-tube assembly MUST remain open to avoid a potential scald hazard.
DANGER
DANGER
DANGER
23
SETTING THE WATER TEMPERATURE
Fig. 19 : Secondary Thermostat Setting
Fig. 20 : Primary Thermostat Setting
Temperature Indicator
Temperature UpTemperature Down
e
m
s
t
o
i
c
D
g
e
a
s
h
e
P
n
c
i
a
t
a
p
e
S
Back Plate
h
I
I
-
I
I
-
I
I
e
s
a
P
h
a
s
h
e
P
I
I
-
I
I
-
P
I
I
h
a
e
s
Knob
Temperature Indicator
Temperature UpTemperature Down
a
c
p
e
S
t
a
i
n
e
g
h
D
e
I
I
o
s
I
a
-
h
P
-
I
I
I
e
Back Plate
s
a
h
P
-
I
I
I
m
P
h
e
a
s
s
t
e
i
c
I
I
I
-
P
h
a
s
e
Knob
Page 27
24
1- ANNUAL MAINTENANCE
A- Flueway
Must be examined annually.
Examine flueway by removing the vent pipe, jacket and flue collector from the top of the combination heater.
- If cleaning is necessary, remove the flue baffles and burner,
- Sweep with a flue brush or any wire scratch brushes.
- Remove any particulate that may have fallen into the combustion chamber before replacing the burner.
Reinstall the flue baffles and flue collector.
Examine the vent system for any obstruction to the flow of combustion or ventilation air and for deterioration or damage which could cause leakage of flue gases or improper venting.
Clean, repair or replace as required.
B. Pressure relief valve and T&P relief
valves
Manually operate the pressure & T&P relief valves at least once a year. This will release some hot water.
Before manually operating either pr essure or T&P relief valve check that the dis­charge is directed to a suitable place for disposal. The discharge line must be full size, without restriction and installed to permit complete drainage of both the valve and line.
T&P relief valve
Located on the center rear top of the heater. (see Fig. 22 page 29).
Lift the lever handle and permit water to discharge for several seconds.
•If after closing the valve, the valve fails to completely reset and water continues to flow, shut OFF power to the heater and follow the draining procedure. Partially drain the inner tank and replace the T&P relief valve.
If T&P weeps periodically, it may be due to thermal expansion (see Thermal Expansion page 9.)
Pressure relief valve
Located on the left rear top of the outer
primary tank. (see fig: 22 page 29)
Shut OFF the power to the heater.
Lift the lever handle to permit water to discharge for several seconds.
After closing the valve, if some water continues to flow , shut OFF the tw o iso­lation valves separating the combina­tion heater from heating system. Partially drain the outer tank and replace the pressure relief valve.
Water from opened drain valves, unions and other connections may be extremely hot. To avoid personal injury, death or substantial property damage;
-Tighten all drain hose connections
- Direct hot water away from all persons
C. Antifreeze
The outer (primary) tank is compatible with inhibited propylene glycol solu­tion with a maximum a 50/50 mix.
Primary water (including additives) must be practically non-toxic, having toxicity rating or class of 1, as listed in the Clinical Toxicology of Commercial Products.
WARNING
WARNING
COMBINATION HEATER MAINTENANCE
Page 28
25
COMBINATION HEATER MAINTENANCE
Do not use automotive or ethylene glycol antifreeze, or any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage;
Introduction of antifreeze can be done
through the drain valve located on the rear bottom of the heater.
Check the pH value of the concentration.
If different than pH 7, the antifreeze must be replaced immediately.
.
Failing to replace the antifreeze periodi­cally voids the warranty on the combi­nation heater.
Other undiluted solutions are prohibit-
ed and could cause severe personal injury or substantial property damage.
D. Air Vent
Check air operation
- Remove vent cap. Briefly push in valve and release it to clean valve seat. Screw vent cap on completely, then unscrew one turn.
When shutting down a unit for an extend­ed period of time, it is recommended to follow the maintenance pr ocedures shown under annual maintenance before r estart­ing the unit.
2- PERIODICAL MAINTENANCE
• Follow instructions on circulator for oiling, if it is oil lubricated.
Check valves, pipes and fittings for leaks.
Check functions of field installed controls (see control manufacturer’s installations).
Check thermostatic mixing valve per enclosed manufacturer’s installation and maintenance instructions.
3- COMBUSTION CHAMBER
No maintenance is required for com­bustion chamber. The combustion chamber is an integral part of the com­bination heater which can not be removed or replaced.
4- DRAINING THE COMBINATION HEATER
A. Drain Outer Tank
Always drain outer tank before you drain inner (potable water) tank to prevent any damage to inner tank.
1. Disconnect power supply to the HM Combination Heater
2.Close isolation valv es to heating system
3. Connect a garden hose to drain valve located bottom/rear of combination heater. Direct the discharge to a safe place of disposal and drain the primary tank.
Water from opened drain valves, unions and other connections may be extremely hot. To avoid personal injury, death or substantial property damage;
-Tighten all drain hose connections
- Direct hot water away from all
persons.
B. Drain Inner Tank (see Figs. 7 & 8
page 11)
1. Close the shut off valve on the cold water line supply.
2.Connect a hose from the domestic tank drain valve to a floor drain
WARNING
CAUTION
CAUTION
CAUTION
WARNING
Page 29
26
COMBINATION HEATER MAINTENANCE
3. Re-attach valve handle and close the water shut off valve on the U-tube assembly .
4.Open drain valve.
5. Open and separate the hot water line union or a hot water faucet above the combination heater. This will initiate the siphoning procedure.
6.To refill and put the HM Combination Heater back in operation, follow the instruction under “Filling the Inner Tank” page 20 .
7. Open the water shut-off valve on the U-Tube assembly and remove handle
C. When Space Heating System Contains
Sufficient Anti-Freeze
1.Disconnect power supply to combina­tion heater
2. If system pressure is greater than 15 psig, relieve system pressure before proceeding.
System pressure must not exceed 15 psig to prevent damage to inner tank.
3.Follow the procedures for draining the inner tank. The outer tank does not require draining.
4.When draining is complete
- close drain valve
- remove hose
CAUTION
Page 30
27
Fig. 21B: Rear view
SPECIFICATIONS DATA
Fig. 21A: Side view
1. Primary circuit, ø 1” NPT
2. Primary circuit drain valve connection, ø 1/2” NPT
3. Domestic temperature/pressure relief valve (150 psi), ø 3/4” NPT
4. Primary circuit & pressure relief valve (30 psi), ø 1” NPT
5. Domestic cold water inlet, ø 3/4” NPT
6. Domestic Hot water outlet & secondary thermostat sensor, ø 3/4” NPT
7. Automatic reset safety sensor & LWCO pressure sensor, ø 3/4” NPT
8. Primary pressure & manual reset safety sensor, ø 1/2” NPT
9. Primary thermostat sensor, & primary temperature indicator, ø 1/2” NPT
10. Primary circuit & air vent, ø 1” NPT
LEGEND
Fig. 22: Top view of Combination Heater
Front
C
Primary Connection
& Pressure Relief Valve
10
E
3
4
Domestic
cold
5
Domestic
hot
6
G
A
D
F
1
2
H
J
B
T&P Relief Valve
Primary Connection & Air Vent
4
6
Domestic Hot Water
7
9
3
10
8
Domestic Cold Water Supply with Dip Tube
5
Page 31
28
SPECIFICATIONS DATA
Model 10 min. Peak Flow 1st Hour Continuous Flow
Storage Temp. Storage Temp. Rise in Temp.
140ºF 180ºF 140ºF 180ºF 80ºF
G-25 46 56 153 163 128 G-30 51 61 178 188 153
Chart 4: Performance
Type HM G-25 HM G-30
Input Btu/hr 100,000 120,000 Inner Tank Capacity Gal 20 20 Outer Tank Capacity Gal 22 22 Dimensions Inches A5959 B2121 C2828 D 54.5 54.5 E1414 F5454 G88 H1616 Vent size ø 3" 3" Connections: TP Valve (domestic) ø 3/4" 3/4" Domestic water ø 3/4" 3/4" Primary connection ø 1" 1" Drain ø 1/2" 1/2" Empty weight lb 363 363 Heat exchanger surface Sq. Ft. 17 17
Chart 3: Dimensional Data
Page 32
29
PARTS LIST
Chart 5
All technical data are subject to change without notice
Item Part No. Description Quantity required
by Model
HM G 25, 30
1 Jacket, Front 1
2 Jacket, Door 1
3 Jacket, Left side 1
4 Jacket, Right side 1
5 Jacket , Back 1
6 Jacket, Top cover 1
7 Control panel console 1
8 HMSWI02 ON/OFF switch 1
9 HMGAU01 Temp./Pres. gauge 1 10 P3THT01 Operating T'Stat. 2 11 P3KWB01 Knob 2 12 P3BZL01 Bezel 2 13 HMC0N01 Manual Reset T'Stat 1
14 Flue Collector - 3" 1
15 Turbulators 4
16 HMTPVO1-35 T & P Relief Valve 150 psi 1 17 HMRLV01 Pressure Relief Valve 30 psi 1 18 P3AVT01 Auto. Air Vent 1 19 P3BSH01 Bushing 1/8"x1/2" 1 20 HMLWC01 Pres. SW. (L.W.C.O.) 1 21 P3DT04 Dip Tube 1 22 HMDRA01 Drain Valve 1 23 HMTH01 Auto reset safety thermostat 1 24 P3VLV01 Mixing valve 1 25 HMCKV01 Check valve - in line 1 26 HNSNP01 Snap sets 2
Page 33
For your own convenience and information, please fill out the following: CONTRACTOR/INSTALLER:
Name: Address:
Phone Number: Date Installed:
30
SAMPLE SPECIFICATION - GAS FIRED
Phase III®HM Series Gas Fired Combination Heater HM G Model ______or equal.
1. The Combination Heater(s) shall be Phase III
®
Model ______ having gas input of______ BTU/hr and a recovery rate of ________ GPH at 100º tempera­ture rise.
2. The construction consists of an annular stainless steel heat exchanger with center flueway, immersed in a primary fluid for indirect firing.
The primary fluid - also cooling off the base of the combustion chamber - pre­vents a direct contact of the flame and combustion gases with the corrugated hot water tank. This unique design insures a possible 180º F continuous hot water pro­duction .
3. The heat exchanger made with high grade stainless steel shall have a mini­mum of 17 Square Feet of heat transfer surface and will be corrugated. The working pressure rating shall be 150 Psi.
4. The combination heater shall be factory ­equipped with two adjustable thermostat at 125-180 ºF, and a safety limit aquas­tat set at 200ºF with manual reset.
The outer tank containing the primary fluid shall be protected by a Low Water Cut-Off device, and a pressure relief valve set at 30 Psi.
The inner tank shall be protected by a 150 Psi Temperature and Pressure Relief Valve.
6. The complete unit(s) shall be insulated with rigid polyurethane foam insulation and installed in a steel cabinet which has been finished with a baked enamel paint.
7. The combination heater shall be covered by a limited Five-year warranty against leaks and corrosion.
8. The combination heater shall be equipped with a sealed gas burner with force draft vent system.
Page 34
Additional quality water heating equipment available
from
Triangle Tube/Phase III
- Exclusive Tank-in-Tank design
-Stainless steel construction
-Available in 8 sizes and 2 models
- Limited LIFETIME residential warranty
- 15 year limited commercial warranty
- Self cleaning/self descaling design
- Construction of high quality corrosion resistant stain­less steel (AISI 316)
- Specially designed built-in flow restrictor to assure maximum heat exchange
- Compact and light weight
-Available in 5 sizes that can accommodate any size pool or spa
TTP Brazed Plate Heat Exchangers
-For domestic water, snow melting, radiant floor, refrigeration
- Plates made of stainless steel, with a 99.9 % copper and brazed, ensuring a high resistance to corrosion
- Self cleaning and self descaling
- Computerized sizing available from Triangle Tube/Phase III
-Available in capacities from 25,000 BTU/hr to 5,000,000 BTU/hr
Phase III Indirect Fired Water Heaters
Maxi-flo Pool and Spa Heat Exchangers
Freeway Center - 1 Triangle Lane - Blackwood, NJ 08012 Tel: (856) 228 8881 - Fax: (856) 228 3584 http://www.triangletube.com E-mail: Sales@triangletube.com
Member of
Group
Loading...