TriangleTube SOLO 110, SOLO 155, SOLO 199, COMBI 155, COMBI 199 User's Information Manual

Page 1
User’s Information Manual
SOLO 110155199 & COMBI 155199
NOTICE
- Customer must register unit within thirty (30) days of installation in order to gain warranty coverage. See Warranty Card for details.
WARNING
• To maintain the safety & longevity of
your appliance, read and follow the maintenance schedule information throughout this manual.
• If the information in this manual
is not followed exactly, a fire or explosion may result causing substantial property damage, serious injury, or death.
FOR YOUR SAFETY
• Do not store or use gasoline or
other flammable vapors and liquids in the vicinity of this or any other appliance.
- Leave all documentation received with appliance with the owner for future reference.
• WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch;
do not use any phone in your building.
- Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas
supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
222168 A01 - July 2019 2019-17
ORIGINAL
THE
INNOVATORS
Page 2
INTENTIONALLY LEFT BLANK
Page 3
TABLE OF CONTENTS
SAFETY INFORMATION .......................................................................................................V
PRODUCT AND SAFETY INFORMATION ...........................................................................VI
PRODUCT AND SAFETY INFORMATION ......................................................................... VII
CHAPTER 1 - COMBUSTION AIR CONTAMINATION ......................................................... 1
CHAPTER 2 - MAINTENANCE SCHEDULES ...................................................................... 3
2.1. Service Technician ..........................................................................................................................3
2.2. Owner Maintenance ........................................................................................................................3
CHAPTER 3 - MAINTENANCE PROCEDURES ................................................................... 5
3.1. Owner Maintenance Procedures ...................................................................................................5
3.2. Daily Maintenance ...........................................................................................................................5
3.2.1 Check Surrounding Area .....................................................................................................5
3.2.2 Check Ventilation Air Openings ............................................................................................ 5
3.2.3 Check Temperature Display and Pressure Gauge ..............................................................6
3.3. Monthly Maintenance .....................................................................................................................6
3.3.1 Check Vent and Combustion Air Piping ..............................................................................6
3.3.2 Check Pressure Relief Valve .................................................................................................6
3.3.3 Check Condensate Drain System ........................................................................................7
3.4. 6-Month Maintenance ....................................................................................................................8
3.4.1 Check Water and Gas Piping ................................................................................................8
3.4.2 Operate Pressure Relief Valve ..............................................................................................8
3.4.3 Check Carbon Monoxide Detectors ..................................................................................... 8
CHAPTER 4 - OPERATING INSTRUCTIONS ...................................................................... 9
CHAPTER 5 - CTRLMAX OPERATION ............................................................................... 11
5.1. CTRLMax Navigation .....................................................................................................................11
5.2. CTRLMax Menu Structure ............................................................................................................ 12
5.3. Home Screen ................................................................................................................................. 13
5.4. Status Line Messages ................................................................................................................... 14
5.5. Main Menu ..................................................................................................................................... 15
5.6. EZ Setup ........................................................................................................................................15
5.7. CH / DHW Operation ................................................................................................................... 16
5.8. Language Selection ...................................................................................................................... 17
5.9. Boiler Information ........................................................................................................................18
5.9.1 Information Items ................................................................................................................ 19
5.10. Lockout History ............................................................................................................................ 20
5.10.1 Lockout Screen .................................................................................................................... 21
5.10.2 Manual Reset Lockouts .......................................................................................................22
5.10.3 Automatic Reset Blocking Lockouts ..................................................................................23
iii
Page 4
INDEX OF ILLUSTRATIONS
Fig. 1 - Condensate Drain Assembly ..........................................................................................................7
Fig. 2 - Condensate Retention Clip - (Solo Models only) .........................................................................7
Fig. 3 - CTRLMax User Interface ...............................................................................................................11
iv
Page 5
SAFETY INFORMATION
TITLE
SAFETY
IMPORTANT EXTRACTS FROM THE CONSUMER PRODUCT SAFETY COMMISSION WEBSITE
WWW.CPSC.GOV
Carbon monoxide is produced by burning fuel. There­fore, any fuel-burning appliance in your home is a po­tential CO source.
When cooking or heating appliances are kept in good working order, they produce little CO. Improperly oper­ating appliances can produce fatal CO concentrations in your home.
What should you do?
Proper installation, operation, and maintenance of fu­el-burning appliances in the home is the most import­ant factor in reducing the risk of CO poisoning.
Make sure appliances are installed according to the manufacturer’s instructions and the local codes. Most appliances should be installed by professionals.
Always follow the appliance manufacturer’s directions for safe operation.
Have the heating system (including chimneys and vents) inspected and serviced annually by a trained ser­vice technician.
Examine vents and chimneys regularly for improper connections, visible cracks, rust or stains.
Look for problems that could indicate improper appli­ance operations:
• Decreased hot water supply
• Furnace unable to heat house or runs continuously
• Sooting, especially on appliances and vents
• Unfamiliar, or burning odor
• Increased moisture inside of windows Operate portable generators outdoors and away from
open doors, windows, and vents that could allow CO to come indoors.
In addition, install battery-operated CO alarms or plug­in CO alarms with battery back-up in your home. Ev­ery home should have a CO alarm in the hallway near the bedrooms in each separate sleeping area. The CO alarms should be certied to the requirements of the most recent UL, IAS, or CSA standard for CO alarms. Test your CO alarms frequently and replace dead batteries. A CO alarm can provide added protection, but is no sub­stitute for proper installation, use and upkeep of appli­ances that are potential CO sources.
Symptoms of CO poisoning
The initial symptoms of CO poisoning are similar to the u (but without the fever) They include:
• Headache
• Fatigue
• Shortness of breath
• Nausea
• Dizziness If you suspect that you are experiencing CO poisoning,
get fresh air immediately. Leave the home and call for assistance from a neighbor’s home. You could lose con­sciousness and die from CO poisoning if you stay in the home.
Get medical attention immediately and inform medical sta that CO poisoning is suspected. Call the Fire De­partment to determine when it is safe to reenter the home.
v
Page 6
SAFETY
PRODUCT AND SAFETY INFORMATION
IMPORTANT SAFETY INFORMATION FOR THE HOMEOWNER AND THE TECHNICIAN
This manual contains important information with respect to the operation and maintenance of the appliance.
This manual must be provided to the Homeowner, who will keep it in a safe place for future reference.
Triangle Tube accepts no liability for any damage, injury, or loss of life resulting from incorrect installation, alteration of any factory supplied parts, or the use of parts or ttings not specied by Triangle Tube. If there is a conict or doubt about the proper installation of the unit or any factory supplied
replacement parts please contact Triangle Tube Technical Support.
DEFINITIONS
The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product.
DANGER
Indicates the presence of a hazardous situa­tion which, if ignored, will result in substantial
property damage, serious injury, or death.
WARNING
Indicates a potentially hazardous situation which, if ignored, can result in substantial
property damage, serious injury, or death.
CAUTION
Indicates a potentially hazardous situation which, if ignored, can result in minor property
damage, or injury.
NOTICE
Indicates special instructions on installation, operation or maintenance, which are import­ant to the equipment but not related to person-
al injury hazards.
BEST PRACTICE
Indicates recommendations made by Triangle Tube for the installers, which will help to ensure optimum operation and longevity of the equip-
ment.
STOP !
READ BEFORE SERVICING
Failure to adhere to the guidelines within this manual
can result in substantial property damage, serious
injury, or death.
TECHNICIAN: When calling or writing about the INSTINCT, please have the boiler model and serial number available.
DANGER
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water.
• Avoid electrical shock when servicing the appliance, by disconnecting the electrical supply prior to performing service or maintenance.
• Failure to comply with these instructions will result in substantial property damage, serious
injury, or death.
WARNING
• The INSTINCT Installation manual is for use only by a qualified heating installer/service technician. The homeowner will use this User's Information Manual for reference.
• What to do if you smell gas:
- Do not try to light any appliance
- Do not touch any electrical switch; do not use
any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the
fire department.
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
• Prior to installing this product, the qualified installer must read all instructions included in this manual and all accompanying manuals/ documents with this appliance.
• All installation steps required in these manuals must be performed in the proper order given.
• This product must be maintained / serviced and inspected annually by a qualified service technician.
• Failure to comply with these instructions can result in substantial property damage, serious injury, or death.
vi
Page 7
PRODUCT AND SAFETY INFORMATION
WARNING
• A byproduct of any gas fired appliance is carbon monoxide. Triangle Tube requires the installation of a minimum of two (2) hard-wired carbon monoxide detectors with an alarm and battery back-up; one in the mechanical room where the boiler is located and another installed in the living area outside the bedroom(s) for all installations. Consult the local authority having jurisdiction for any additional carbon monoxide
detector requirements in your area. See Chapter
2 of the INSTINCT Installation & Maintenance Manual for additional carbon monoxide detector
requirements in Massachusetts.
• Failure to comply with these instructions can result in substantial property damage, serious injury, or death.
Service and Maintenance:
• Allow the unit to cool down prior to servicing to avoid severe burns.
• The INSTINCT must be maintained as outlined in this manual and have at least annual service performed by a qualified service technician to ensure unit / system reliability.
INSTINCT Operation
• Do not block flow of combustion air to the INSTINCT. If the combustion air blockage is easily accessible and removable, then remove it. If blockage is not obvious or cannot be removed, have the unit and system checked by a qualified service technician. If in doubt turn off your INSTINCT Boiler.
• Do not allow contaminated air to enter the unit’s combustion air inlet. See page 3 for details.
SAFETY
Boiler and System Water
• Have the boiler and system water chemistry checked at least annually by a qualified service technician.
• Do not use petroleum-based cleaning or sealing compounds in the boiler or system. Gaskets and seals in the system may be damaged, which can result in substantial property damage.
• Do not use any product not specifically designed for boiler / hydronic heating systems. Serious damage to the unit, piping system, personnel and / or property may result.
• Continual fresh makeup water will reduce the life of the INSTINCT. Addition of oxygen can cause internal corrosion in the system components. All leaks in the system must be repaired at once to prevent excessive makeup water.
• Do not add cold makeup water when the appliance is hot. Thermal shock can potentially cause cracks in the heat exchanger.
• Failure to comply with these instructions can result in substantial property damage, serious injury, or death.
CAUTION
• It is prohibited to carry out any modifications to the appliance without prior written consent from Triangle Tube.
• Faulty parts must only be replaced by genuine Triangle Tube factory parts.
• Failure to comply with these instructions can result in minor property damage, or injury.
• The INSTINCT is equipped with a low water cutoff device. The boiler and system piping must be filled and pressurized to 12 psig prior to startup. The unit will shut down if the pressure falls below 7.2 psig.
• Should overheating occur or if the gas supply fails to shut off, DO NOT turn OFF or disconnect the electrical supply to the pump. Instead, turn OFF the manual gas control valve external to the appliance.
• Combustion Readings - For your safety and to benefit from best warranty terms, ask your installer to provide combustion readings that are to be registered with Triangle Tube. See Warranty Card. Combustion readings should be checked at least annually for safe and reliable operation.
NOTICE
The homeowner is only permitted to carry out the basic set-up operations (EZ Setup) after he has received all relevant instructions from the installer. Any other set­up must be carried out by a qualified installer.
• In case of any anomaly, please call your qualified service technician.
• Make sure to reference the unit’s model number and serial number from the rating label when inquiring about service or troubleshooting.
• Triangle Tube reserves the right to change the technical characteristics, components and features of its products without prior notice. Check for an updated version of this manual at www.triangletube.com.
vii
Page 8
INTENTIONALLY LEFT BLANK
Page 9
CHAPTER 1 - COMBUSTION AIR CONTAMINATION
WARNING
If the INSTINCT combustion air inlet is located in an area likely to cause or contain contamina­tion, or if products which could contaminate the air cannot be removed, the combustion air must be repiped and terminated at another lo­cation. Contaminated combustion air will dam­age the unit and its burner system, and can result in substantial property damage, serious
injury, or death.
DANGER
Do not operate the INSTINCT if the com­bustion air inlet is located near a laundry room or pool facility. These areas will al-
ways contain hazardous contaminants.
Pool, laundry, common household, and hobby products often contain fluorine or chlorine compounds. When these chem­icals pass through the burner and vent system, they can form strong acids. These acids will corrode the heat exchanger, burner components, and vent system, causing serious damage and possible flue gas spillage or water leakage into
the surrounding area.
Please read the information listed below. If contaminating chemicals are located near the area of the combustion air inlet, the installer must pipe the combustion air inlet to an area free of these chemicals.
Failure to comply with these instructions will result in substantial property dam-
age, serious injury, or death.
The INSTINCT boiler is classified as a Category IV appliance. This utilizes un­contaminated indoor or outdoor air for applicance combustion. A direct vent installation uses the outdoor air. Air sup­ply, combusiton chamber, heat exchang­er and evacuation of POC (products of combustion) for this type of appliance is sealed with respect to the room in which
the appliance is installed.
An in-direct installation uses uncontam­inated indoor air for appliance combus-
tion.
When the air for combustion is taken from the room an air grille must be in-
stalled by the contractor.
DANGER
Ensure the vent grilles are free from ob­struction at all times. Do not be tempt­ed to restrict or cover the air grilles as it
could cause serious injury, or death.
Potential contaminating products
Spray cans containing chloro/uorocarbons
Permanent Wave Solutions
Chlorinated wax
Chlorine based swimming pool chemicals / cleaners
Calcium Chloride used for thawing ice
Sodium Chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid / muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and clean­ing solvents found in household laundry rooms
Adhesives used to fasten building products and other similar products
Areas likely to contain these products
Dry cleaning / laundry areas and establishments
Beauty salons
Metal fabrication shops
Swimming pools and health spas
Refrigeration Repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture renishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
CHAPTER 1
1
Page 10
INTENTIONALLY LEFT BLANK
Page 11
CHAPTER 2 - MAINTENANCE SCHEDULES
2.1. Service Technician
At least on an annual basis the following maintenance should be performed by a qualied service technician:
General
Attend to any reported problems.
Inspect the interior of the boiler jacket area; clean and vacuum if necessary.
Clean the condensate drain assembly and ll with fresh water.
Check boiler uid pH on systems.
Check for leaks, both inside and outside the unit: water, gas, ue and condensate.
Verify vent piping and air inlet piping are in good condition, sealed tight and properly supported.
Check boiler water pressure, piping and expansion tank.
Check control settings.
Check ignition electrode (sand o any white oxide; clean and reposition).
Check ignition wiring and ground wiring.
Check all control wiring and connections.
Check burner ame pattern (stable and uniform).
Check carbon monoxide detectors.
Additional items if combustion or performance is poor:
Clean heat exchanger and ue ways.
Remove burner assembly and clean burner head using compressed air only.
2.2. Owner Maintenance
Periodically:
Check the area around the unit.
Check and remove any blockage from the combus­tion air inlet and ventilation openings.
Check the temperature and pressure gauges.
Monthly:
Check vent piping.
Check combustion air inlet piping or air grilles.
Check the pressure relief valve.
Check the condensate drain system.
Every 6 months:
Check boiler piping and gas supply piping for cor­rosion or potential signs of leakage.
Operate the pressure relief valve.
Check carbon monoxide detectors.
WARNING
Follow the maintenance procedures given in Chapter 3 on page 5 of this manual. Failure
to perform the service and maintenance or follow the directions in this manual can result in damage to the INSTINCT or system com­ponents, resulting in substantial property
damage, serious injury, or death.
CHAPTER 2
Service Technician maintenance procedures can be found in Chapter 17 of the INSTINCT Installation and Maintenance manual.
Once the maintenance items are completed, review the service with the owner.
3
Page 12
INTENTIONALLY LEFT BLANK
Page 13
CHAPTER 3 - MAINTENANCE PROCEDURES
3.1. Owner Maintenance Procedures
WARNING
The INSTINCT must be inspected and ser­viced annually, preferably at the start of the heating season, by a qualified service tech­nician. In addition, the owner maintenance
and care of the unit as outlined in Chapter 2 on page 3 and further explained in this
chapter should be performed to assure max­imum safety, efficiency and reliability of the unit. Failure to service and maintain the INSTINCT and the system components can result in equipment failure, resulting in sub­stantial property damage, serious injury, or
death.
WARNING
In the case of In-direct vent installation the air openings provided by the installer to supply ventilation and combustion air are essential for safe operation of the appliance. The user must respect the importance of these air openings and ensure that they are not partial ly or fully blocked under any condition. Fail­ure to ensure free uncontaminated air flow through the openings can result in substantial
property damage, serious injury, or death.
NOTICE
The following information provides detailed instructions for completing the owner main­tenance items outlined in the maintenance
schedule in Chapter 2 on page 3.
3.2. Daily Maintenance
3.2.1 Check Surrounding Area
WARNING
If contaminates are found:
Remove products immediately from the area. If they have been there for an ex­tended period, call a qualified service technician to inspect the unit for possible
damage from corrosion.
If products cannot be removed, immedi­ately call a qualified service technician to re-pipe the combustion air inlet pip­ing and locate the combustion air intake
away from the contaminated areas.
Failure to comply with these instructions can result in substantial property damage, seri-
ous injury, or death
Verify that the area surrounding the INSTINCT is free of combustible / ammable materials or am­mable vapors or liquids. Remove immediately if found.
Verify that combustion air inlet area is free of any contaminates. Refer to the materials listed in Chapter 1 on page 1 of this manual. If any of these products are in the area from which the unit
-
takes its combustion air, they must be removed immediately or the combustion air intake must be relocated to another area.
WARNING
CHAPTER 3
3.2.2 Check Ventilation Air Openings
Verify that all ventilation openings to the mechan­ical room or building are open and unobstructed.
Check and verify that the vent termination and the combustion air intake are free of de­bris and obstructions. Remove any debris on the air intake or flue exhaust openings. If re­moving the debris does not allow the unit to operate correctly, contact a qualified service technician to inspect the unit and the vent /
combustion air system.
Eliminate all the materials listed in Chapter 1 on page 1 from the area surrounding the
unit and from the vicinity of the combustion
air inlet.
5
Page 14
CHAPTER 3 - MAINTENANCE PROCEDURES
CHAPTER 3
3.2.3 Check Temperature Display and Pressure Gauge
Ensure the pressure reading on the pressure gauge does not exceed 25 psig. Higher pressure readings may indicate a problem with the expansion tank.
Ensure the temperature on the display panel does not exceed 194ºF. Higher temperature readings may indicate a water ow problem.
Contact a qualied service technician if problem persists.
WARNING
The annual servie and inspection must ensure
the venting and air supply are maitained in a correct and safe working condition. Damaged vent and air supply can result in serious injury,
or death.
3.3. Monthly Maintenance
3.3.2 Check Pressure Relief Valve
1. Visually inspect the pressure relief valve and the relief valve discharge pipe for signs of weeping or leakage.
2. If the pressure relief valve weeps often, the expan­sion tank may not be operating properly. Immedi­ately contact a qualied service technician to in­spect the unit and system.
3.3.1 Check Vent and Combustion Air Piping
Visually inspect the venting system and combus­tion air piping for blockage, deterioration of gas­kets or leakage. Contact a qualied service techni­cian immediately if any problems are found.
WARNING
In the case of In-direct vent installation the air openings provided by the installer to supply ventilation and combustion air are essential for safe operation of the appliance. The user must respect the importance of these air openings and ensure that they are not partial ly or fully blocked under any condition. Fail­ure to ensure free uncontaminated air flow through the openings can result in substantial
property damage, serious injury, or death.
DANGER
Failure to inspect the vent system and com­bustion air inlet piping and to have any con­ditions repaired, will result in serious injury,
or death.
-
6
Page 15
CHAPTER 3 - MAINTENANCE PROCEDURES
3.3.3 Check Condensate Drain System
1. Ensure condensate drain assembly is rmly secured to bottom of the unit. See Fig. 1 on the right. Ensure the Retention clip is secure. See Fig. 2 (Solo Models only).
WARNING
Do not operate the boiler without the fac­tory-supplied condensate drain assembly installed. Operation of the boiler without the condensate drain assembly installed can result in property damage, serious injury, or
death.
2. While the unit is running, check the discharge end of the condensate drain tubing. Ensure no ue gas is leaking from the condensate drain tubing by holding your ngers near the opening.
3. If you notice ue gas leaking, turn o the unit and contact a qualied service technician to inspect the unit and condensate drain assembly.
4. Ensure the condensate drain tubing is not blocked by pouring water through the ll plug port on the condensate drain assembly. The water should ow out of the end of the drain tubing. If water does not appear at the end of the drain tubing, contact a qualied service technician to inspect and clean the condensate drain assembly.
5. To ll the condensate drain assembly, remove the ll plug from the condensate assembly. Slowly pour wa­ter into the assembly until water appears at the end of the drain tubing. Stop lling and replace plug.
RETAINING NUT
RETENTION
CLIP
FOR SOLO
MODELS ONLY
REFER TO FIG. 2
PLASTIC BALL
NOT SHOWN
CONDENSATE
DRAIN ASSEMBLY
RETENTION
FOR SOLO
MODELS ONLY
SEALS
FILL PLUG WITH VACCUM BREAK PORT
Fig. 1 - Condensate Drain Assembly
CLIP
COMPRESSION NUT WITH RUBBER SEAL
Flexible tubing (or 3/4 PVC/ CPVC Piping to Drain)
RETAINING NUT
CHAPTER 3
Fig. 2 - Condensate Retention Clip - (Solo Models only)
7
Page 16
CHAPTER 3 - MAINTENANCE PROCEDURES
TITLE
CHAPTER 3
3.4. 6-Month Maintenance
3.4.1 Check Water and Gas Piping
1. Remove the boiler front jacket panel and perform a gas leak inspection per steps 1 through 6 of the Operating Instructions on page 9. If gas odor or a leak is detected, immediately shut down the unit following procedures on page 9. Call a qualied service technician.
2. Visually inspect for leaks around the internal boiler water connections and around the heat exchanger. Visually inspect the external system piping, circula tors, and system components and ttings. Immedi­ately call a qualied service technician to repair any leaks.
WARNING
Have leaks fixed at once by a qualified service technician. Failure to comply can result in substantial property damage, serious injury,
or death.
3.4.2 Operate Pressure Relief Valve
1. Before proceeding, verify that the relief valve outlet has been piped to a safe place, avoiding any possi­bility of scalding from hot water.
3. If water ows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the lever again to clean the valve seat. If the valve does not properly seat and con­tinues to weep afterwards, contact a qualied ser­vice technician to inspect the valve.
f water does not ow from the valve when you lift
4. I the lever completely, the valve or discharge line may be blocked. Immediately shut the unit down per the instructions on page 9. Call a qualied
-
service technician to inspect the valve and dis charge line.
3.4.3 Check Carbon Monoxide Detectors
Verify that at least two (2) carbon monoxide detectors are installed and operating properly. One must be in­stalled in the mechanical room where the INSTINCT is located and another installed in the living area outside the bedroom(s).
Contact a qualied service technician if carbon mon­oxide detectors are not installed or operating properly.
-
WARNING
To avoid water damage or scalding, a dis­charge line must be connected to the relief valve outlet and directed to a safe place of disposal. This discharge line must be installed by a qualified service technician in accor dance with the INSTINCT installation manu­al. The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge. Failure to comply can result in substantial
property damage, serious injury, or death.
2. Read the pressure gauge to ensure the system is pressurized. Lift the relief valve top lever slightly, allowing water to relieve through the valve and dis­charge piping.
-
8
Page 17
CHAPTER 4 - OPERATING INSTRUCTIONS
FOR YOUR SAFETY, READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result,
causing substantial property damage, serious injury, or death.
A. This appliance does not have a pilot. It is equipped
with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
B. BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell next to the oor be­cause some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building
Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppli­er’s instructions.
If you cannot reach your gas supplier, call the re department.
OPERATING INSTRUCTIONS
C. Use only your hand to turn the external manual
gas valve. Never use tools. If the valve will not turn by hand, don’t try to repair it; call a qualied service technician. Force or attempted repair may result in a re or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CHAPTER 4
1. STOP! Read the safety information above. This ap­pliance is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.
2. Set room thermostat(s) to lowest setting. Turn the external manual gas valve handle clockwise to “CLOSE” (valve handle must be perpendicular to gas piping).
3. Turn the service switch on the appliance control panel OFF.
4. Remove the front jacket panel on the unit.
5. Wait ve (5) minutes to clear out any gas. If you then smell gas in the jacket enclosure or around the unit, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the next step.
6. Turn the external manual gas valve handle count­er clockwise handle shall be parallel to gas piping).
to “OPEN” gas supply (valve
TO TURN OFF GAS TO APPLIANCE
1. Set the room thermostat to lowest setting.
2. Turn the service switch on the appliance control panel to “OFF”
7. Turn the service switch on the appliance control panel “ON”.
8. Set room thermostat(s) to desired setting(s).
9. The appliance control panel display will show the current operating status on the Status Line at the bottom of the screen. “Standby” means there is no call for heat (all thermostats are satised). “CH Demand” indicates a space heating call has been received. “DHW Demand” indicates a domestic hot water call has been received. A ame icon will be displayed when the unit is red.
10. If the unit will not operate, follow the instructions “To Turn O Gas to Appliance” and call your service technician or gas supplier.
11. Replace the front jacket panel. Make sure the panel is seated rmly in place and all mounting screws are tightened.
3. Turn the external manual gas valve handle clock­wise
to “CLOSE”.
9
Page 18
INTENTIONALLY LEFT BLANK
Page 19
CHAPTER 5 - CTRLMAX OPERATION
The CTRLMax Boiler Management System is designed to be exible yet easy to use. CTRLMax monitors and controls the INSTINCT to provide heat as eciently as possible.
All CTRLMax features are easy to use through a graphi­cal display where information is presented either graph­ically or in plain English, so code charts are not required. Fig. 3 below shows an CTRLMax display example of the INSTINCT Solo red for a domestic hot water demand.
5.1. CTRLMax Navigation
The CTRLMax navigation is performed through soft keys that react to the touch and emit a short beep when tapped.
NOTICE
Exert a light and short touch (tap) on the soft keys to activate their function. Holding the touch too long will not generate any reaction from the CTRLMax, unless it is a combination of soft keys meant to be touched simultaneously for a determined duration, as instructed in this manual. The arrow keys can also be held longer
to increase or decrease values faster.
Navigation is performed through four arrow soft keys
by touching the center soft key .
To shut down the unit, touch the
DANGER
When touching the
shuts down but is not isolated from power supply. Therefore, live current is still present in the unit. For your safety, disconnect elec­trical power supply to the unit before servic­ing or making any electrical connections to avoid possible electric shock hazard. Failure
to do so can cause serious injury, or death.
NOTICE
When shutting down using the the appliance will not react to any heat de­mand. However, the basic appliance protec­tion functions (such as frost protection, etc.)
remain active.
In addition, the arrow soft keys are no longer
illuminated, and the
,
dimmed.
soft key.
soft key, the unit
soft key,
soft key lighting is
, , with a center soft key (OK /Reset func-
tions) for making selections and entering information. The Main Menu can be entered from the Home Screen
Instinct
DHW
DHW Demand
The menu system utilizes icons to represent each se­lection. The current selected menu is displayed as a re­versed image with a text description shown at the top of the display. Menus can be entered by selecting the the desired icon (highlights) using the arrow soft keys.
CHAPTER 5
Fig. 3 - CTRLMax User Interface
11
Page 20
CHAPTER 5 - CTRLMAX OPERATION
5.2. CTRLMax Menu Structure
INSTINCT
186°F
DHW
156°F
Target = 186°F
DHW Demand
CHAPTER 5
EZ Setup
CH / DHW Operation
Heating Enabled
Select Language
Select Language
English
Français Nederlands Español Italiano Deutsch
Boiler Information
a
b
c
d
e
f
b
b
b
a
b
c
d
e
f
b
b
a
b
c
d
e
f
b
b
b
b
Boiler Information
b
b
b
b
f
e
d
c
b
b
b
b
a
f
e
d
b
c
b
b
b
b
a
f
e
d
c
b
a
Lockout History
a
b
c
d
e
a
b c
d
e
a
b
c
d
e
f
b
b
b
b
f
f
b
e
b
d
b
c
b
b
b
b
a
f
f
e
b
d
b
b
c
b
b
b
b
a
f
b
e
b
d
b
c
b
b
a
Heating EZ Setup DHW EZ Setup
12
EZ Setup Reset Display EZ Setup
Page 21
CHAPTER 5 - CTRLMAX OPERATION
5.3. Home Screen
The Home Screen presents status information in a very user friendly way so that the current state of the boiler can be quickly accessed.
Screen backlight - it will illuminate when any soft key is touched, and remain illuminated for ve min­utes.
Screen brightness - it can be adjusted at the Home screen by touching and holding simulta-
neously the Touch the
crease the contrast. Touch
and soft keys for 2 seconds.
and soft key to increase or de-
to end the process.
Main Icons of CTRLMax display
Central Heating - indicates information related to central/space heating.
DHW - indicates information related to Domes-
tic Hot Water.
Home - to go back to the home screen.
Back - to go back to the previous screen.
Warm Weather Shutdown - displays on the home screen when the outdoor temperature reaches the Warm Weather Shutdown tempera­ture.
Reset - to reset the system to the factory set­tings.
Settings - to access controller settings (lan-
guage, units, etc.).
Easy Setup - to quickly adjust the most com-
mon settings.
CH/DHW operation - to enable/disable the central/space heating or Domestic Hot Water func­tions
The model is indicated at the top of the screen.
The INSTINCT is represented in the center of the Home Screen. Basic operating infor-
mation such as supply and return temperatures are displayed as well as current burner
Radiator icon: indicates that a central heating call has been received. A small number 1 or 2 indicates which CH calls are active
A ame symbol is displayed when the unit is red. The ame size changes to indicate the current ring rate.
Basic information: The user can toggle
through items using the keys to view Target, Supply, Return, Domestic, Outdoor, System and Mix Zone temperatures, DHW ow.
and soft
status.
INSTINCT Combi
186°F
156°F
Target = 186°F
DHW Demand
Information - to get information on the boiler.
Faucet icon: indicates that a DHW call has been received.
Circulator icons: indicate which circulators are currently
DHW
powered.
Status line: displays the current operating state of the boiler.
CHAPTER 5
13
Page 22
CHAPTER 5 - CTRLMAX OPERATION
5.4. Status Line Messages
Standby - Indicates that the INSTINCT is ready to re-
spond when a demand is received.
CH Demand - A central heating call has been received.
DHW Demand - A domestic hot water call has been
received.
CH/DHW Demand - Central heating and domestic hot water calls are being received simultaneously. Both calls are being satised simultaneously because domestic hot water priority has been disabled.
DHW Priority - Central heating and domestic hot wa­ter calls are being received simultaneously. Domestic hot water call is being satised rst because it has prior­ity over central heating calls.
Priority Timeout - Central heating and domestic hot wa­ter calls are being received simultaneously. The domestic hot water priority time limit has been exceeded. Priority will now switch back and forth between central heating and domestic hot water calls until one call is satised.
External Demand - An external modulation call has been received.
DHW Post Pump - The domestic hot water circulator(s) is/are running to remove heat from the INSTINCT at the completion of a call.
Freeze Protection - The burner is red because the freeze protection feature has been activated. Freeze protection will end once the supply/system water tem­perature is raised to 60°F [16°C].
Boiler Protection - The burner ring rate is being re­duced because of an excessive dierence between the boiler supply and return temperatures. The ring rate will begin increasing once the temperature dierence is less than 45°F [25°C].
Low Water Pressure - The system pressure has dropped to 10.1 psi. The INSTINCT will still respond to calls until the pressure drops below 7.2 psi. Increase system pres­sure to 14.5 psi to clear Low Water Pressure warning
Lockout Description - The lockout which currently has the INSTINCT shut down is displayed.
CHAPTER 5
Slave Operation - The INSTINCT is a slave in a cascade system.
Manual Operation - The burner or circulators have manually been enabled in the Installer Menu.
CH Burner Delay - The burner will not re until the call blocking time has elapsed.
DHW Burner Delay - The burner will not re until the call blocking time has elapsed.
CH Setpoint Reached - The burner is not red because the supply/system water temperature exceeds the set­point. The central heating circulator(s) continue(s) to operate and the burner will re again once the supply/ system water temperature drops below the setpoint.
DHW Setpoint Reached - The burner is not red be­cause the supply/system water temperature exceeds the setpoint. The domestic circulator(s) continue(s) to oper­ate and the burner will re again once the supply/system water temperature drops below the setpoint.
CH Post Pump - The central heating circulator(s) is/are running to remove heat from the INSTINCT at the com­pletion of a call.
14
Page 23
CHAPTER 5 - CTRLMAX OPERATION
5.5. Main Menu
The Main Menu can be entered from the Home Screen
by touching the The menu system utilizes icons to represent each se-
lection. The currently selected menu is displayed as an inversed im-
age with a text description shown at the top of the display. Menus can be entered by scrolling through the icons
using the arrow soft keys, highlighting the desired icon
and touching the
soft key.
soft key.
INSTINCT Combi
186°F
Target = 186°F
5.6. EZ Setup
The EZ Setup menus provide a simple way to quick­ly customize CTRLMax for each installation. EZ Setup prompts the user to make selections which allows the INSTINCT to be setup very quickly without searching through long lists of settings and manually making ad­justments.
DHW
156°F
The EZ Setup menu can be accessed by selecting this icon.
The Boiler Information Menu can be accessed by selecting this icon.
DHW Demand
Touch center soft key
EZ Setup
CHAPTER 5
Currently selected menu
The CH / DHW Operation Menu can be accessed by selecting this icon.
The Home Screen icon at the bottom of each screen returns to the Home Screen when selected.
The Previous Screen icon at the bottom of each screen returns to the previous screen when selected.
15
Page 24
CHAPTER 5 - CTRLMAX OPERATION
5.7. CH / DHW Operation
The CH / DHW Operation Menu can be entered from the Main Menu by selecting the CH / DHW Operation icon
CHAPTER 5
and touching the heating or domestic hot water functions of the INSTINCT.
soft key. The CH / DHW Operation Menu provides a simple way to disable either the central
CH / DHW Operation
Heating Operation can be enabled and disabled by se­lecting the radiator icon and
touching the toggle operation between enabled and disabled.
A radiator icon with an X through it indicates that the heating function is disabled.
This icon is also displayed on the Home Screen when dis­abled.
soft key to
Heating Enabled
Domestic Hot Water Opera­tion can be enabled and dis­abled by selecting the faucet
icon and touching the soft key to toggle operation between enabled and dis­abled.
A faucet icon with an X through it indicates that the domestic hot water function is disabled.
This icon is also displayed on the Home Screen when dis­abled.
16
Page 25
CHAPTER 5 - CTRLMAX OPERATION
5.8. Language Selection
The Select Language Menu can be entered from the Main Menu by selecting the Select Language icon and touch-
ing the (nine dierent languages: English, French, Dutch, Spanish, Italian, German, Czech, Polish and Russian).
soft key. The Select Language Menu provides a simple way to select the language used on the display
Select Language
Touch the to select the required lan-
guage then touch the soft key to store the setting
and soft keys
Select Language
English
CHAPTER 5
Français Nederlands Español Italiano Deutsch
17
Page 26
CHAPTER 5 - CTRLMAX OPERATION
5.9. Boiler Information
Boiler Information can be viewed by selecting the Boiler Information icon and pressing the OK button. Boiler Information provides real time operating information of the INSTINCT.
Boiler Information
Boiler Information
a
b
b
c
b
d
b
e
b
f
f
b
e
b
d
b
a
b
c
c
b
b
d
b
b
e
a
f
f
e
b
d
b
a
b
b
c
b
c
b
d
b
b
e
a
f
f
b
e
b
d
b
c
b
b
a
CHAPTER 5
Boiler Information displays six boil­er readings at a time. Each line con­tains an information item followed by its current value. Touch the and
soft key to scroll through
additional information items.
Some information items include a logging function.
Select the information item then
touch the
soft key to view its
graph. One sample is recorded every 12
minutes to produce a graph of the last 24 hours.
Boiler Information
Boiler Status Standby
Heating Call No
DHW Call No
Boiler Firing Rate --
Ionization current 0μA
Boiler Setpoint --
The following items have a logging function:
Boiler Firing Rate
Ionization Current
Boiler Setpoint
Boiler Setpoint
194
Boiler Supply Temperature
Boiler Return Temperature
Boiler Flue Temperature
Outdoor Temperature
68
-16.00
-24.00
-8.00
0.00
DHW Storage Temperature
External Modulation Signal
• Pressure
18
Page 27
CHAPTER 5 - CTRLMAX OPERATION
5.9.1 Information Items
Information Item Description
Boiler Status
Heating Call Displays if a central heating call is present.
DHW Call Displays if a domestic hot water call is present.
Boiler Firing Rate Displays the current ring rate of the INSTINCT.
Ionization Current Displays the current ame ionization current from the ignitor.
Boiler Setpoint Displays the current setpoint of the INSTINCT.
Supply Temp. Displays the current supply temperature of the INSTINCT.
Return Temp. Displays the current return temperature to the INSTINCT.
Boiler Flue Temp. Displays the current ue temperature of the INSTINCT.
Outdoor Temp. Displays the current outdoor temperature.
DHW Storage Temp.
External Modulation Signal
Displays the current operating state of the INSTINCT. This is the same as the sta­tus line on the home screen.
Displays the current DHW storage temperature when Indirect Water Heater Sen­sor PSRKIT22 is installed.
Displays the current external modulation signal being received from an external controller.
CHAPTER 5
Pressure Displays the current system water pressure.
CH Ignitions
CH Runtime
DHW Ignitions
DHW Runtime
Mix Zone Temperature Displays the current low temperature mix zone temperature.
Displays the number of central heating ignitions since the unit was installed. This counter increases in increments of twenty.
Displays the number of hours the INSTINCT has run for a central heating call since the unit was installed.
Displays the number of domestic hot water ignitions since the unit was installed. This counter increases in increments of twenty.
Displays the number of hours the INSTINCT has run for a domestic hot water call since the unit was installed.
19
Page 28
CHAPTER 5 - CTRLMAX OPERATION
5.10. Lockout History
Lockout History can be viewed by selecting the Lockout History icon and pressing the OK button. The Lockout History Screen lists the last eight lockouts along with how long ago they occurred.
Boiler Information
Lockout History
a
b
b
c
b
d
b
e
b
f
f
b
e
b
d
b
a
b
c
c
b
b
b
d
b
e
a
f
f
e
b
d
b
a
b
b
c
b
c
b
d
b
b
e
a
f
f
b
e
b
d
b
c
b
b
a
CHAPTER 5
Lockout History displays the last eight lockouts. The newest lock­out is displayed at the top of the screen.
The lockout message is followed by how long ago the error oc­curred.
Touch the
and soft keys to
scroll through additional lockouts.
Lockout Details displays the lock­out at the top of the screen fol­lowed by a snapshot of the boiler information recorded at the time of the lockout.
Touch the
and soft keys to scroll through additional informa­tion items.
Lockout History
1. Blower speed 5h ago
2. DHW Sensor Open 2h ago
3. Sensor Drift 25 h ago
4. No error 27 h ago
5. No error 27 h ago
6. No error 27 h ago
Lockout Details
Blower speed
Boiler Status --
Heating Call --
DHW Call --
Boiler Firing Rate 44%
Ionization current 44μA
20
Page 29
CHAPTER 5 - CTRLMAX OPERATION
5.10.1 Lockout Screen
If a problem occurs, the Lockout Screen replaces the Home Screen. The backlight will remain on until the lockout is reset.
Pressing any arrow button will return to the Home Screen so that additional troubleshooting can be performed. See Sections 5.10.2 on page 22 and 5.10.3 on page 23 for a list of lockouts and descriptions.
The lockout message is displayed at the top of the screen
Low Water
The rst sentence gives a description of the lockout.
The third sentence tells how to reset the lockout
Water pressure has fallen below
an acceptable operating level.
Increase pressure to normal
range. Boiler will automatically
reset once water level returns to
normal.
The second sentence gives a possible cure for the lockout.
Press any ARROW button to return to the Home Screen while locked out.
The Main Menu can then be entered from the Home Screen to help diagnose the problem.
Select the Home Screen icon at the bottom of any menu screen to return to the Lockout Screen.
If problem persists,
call for service
Press any ARROW Button
INSTINCT Solo
186°F
156°F
Target = --
E37
The lower right corner displays the lockout reference code
CHAPTER 5
Low Water
The status line now displays the lockout
21
Page 30
CHAPTER 5 - CTRLMAX OPERATION
5.10.2 Manual Reset Lockouts
Code Lockout Message Description
E1 Failed Ignition The burner failed to light after 5 ignition attempts.
E2 False Flame Flame detected prior to ignition.
E3 High Boiler Temperature Boiler temperature has reached 210°F [99ºC] or 102°F [39°C].
E5 Blower Speed Blower is not at correct speed or speed signal is not being received by control module.
E8 Flame Circuit Error Flame circuit test failed.
E9 Gas Valve Circuit Error Gas valve circuit test failed.
E13 Reset Limit Reached Resets are limited to 5 every 15 minutes.
E15 Sensor Drift Supply or return sensor reading has drifted.
CHAPTER 5
E16 Supply Sensor Stuck Supply sensor reading is not changing.
E17 Return Sensor Stuck Return sensor reading is not changing.
E18 Sensor Failure Supply or return sensor reading changed very rapidly.
E19 Flame Failure During Startup Phase Flame lost after startup
E21 Internal Control Fault A / D conversion error.
E30 Supply Sensor Shorted A short circuit has been detected in the boiler supply temperature sensor circuit.
E31 Supply Sensor Open An open circuit has been detected in the boiler supply temperature sensor circuit.
E43 Return Sensor Shorted A short circuit has been detected in the boiler return temperature sensor circuit.
E44 Return Sensor Open An open circuit has been detected in the boiler return temperature sensor circuit.
E47 Water Pressure Sensor Error Water pressure sensor is disconnected or broken.
E80 Return > Supply Return temperature is higher than supply temperature.
E83 Delta T Protection Excessive difference between boiler supply and return temperatures has occured 5 times
E87 External Limit Open An external manual reset limit has opened
22
Page 31
CHAPTER 5 - CTRLMAX OPERATION
5.10.3 Automatic Reset Blocking Lockouts
Code Lockout Message Description
E7 High Flue Temperature Flue temperature exceeds high limit.
E12 Internal Control Fault EEPROM misconguration.
E25 Internal Control Fault CRC check error.
E32 DHW Sensor Shorted A short circuit has been detected in the DHW temperature sensor circuit.
E33 DHW Sensor Open An open circuit has been detected in the DHW temperature sensor circuit.
E34 Low Voltage Line voltage has fallen below an acceptable operating level.
E37 Low Water Water pressure has fallen below 7.2 psi.
E45 Flue Sensor Shorted A short circuit has been detected in the boiler ue temperature sensor circuit.
E46 Flue Sensor Open An open circuit has been detected in the boiler ue temperature sensor circuit.
E76 External Limit Open An external automatic reset boiler limit has opened.
E77 High Mix Circuit Temperature Mix circuit temperature exceeds Mix zone high limit setting.
E78 Mix Circuit Sensor Shorted A short circuit has been detected in the mix circuit temperature sensor circuit.
E79 Mix Circuit Sensor Open An open circuit has been detected in the mix circuit temperature sensor circuit.
E81 Sensor Drift Supply and return temperatures are not equal.
E82 Delta T Protection Excessive dierence between the boiler supply and return temperatures.
E89 Incorrect Setting A parameter setting is in conict with another setting.
E90 Firmware Mismatch Control module and display rmware versions are incompatible.
E91 System Sensor Shorted A short circuit has been detected in the system temperature sensor circuit.
E92 System Sensor Open An open circuit has been detected in the system temperature sensor circuit.
E93 Outdoor Sensor Shorted A short circuit has been detected in the outdoor temperature sensor circuit.
E94 Internal Display Fault Display memory error.
E95 Supply Sensor Error Supply sensor reading is invalid.
E96 Outdoor Sensor Open An open circuit has been detected in the outdoor temperature sensor circuit.
CHAPTER 5
E97 Cascade Mismatch Cascade conguration has changed.
E98 Cascade Bus Error Communication with other boilers has been lost.
E99 Controller Bus Error Communication between boiler display and control module has been lost.
23
Page 32
Additional quality water heating equipment available
from Triangle Tube
Maxi-Flo Pool and Spa Heat Exchangers
SMART Indirect Fired Water Heaters
Constructed of high quality corrosion resistant stainless steel (AISI 316) or titanium
Specially designed built-in ow restrictor to assure maximum heat exchange
Compact and light weight
Available in 8 sizes to accommodate any size pool or spa
TTP Brazed Plate Heat Exchangers
Exclusive Tank-in-Tank design
Stainless steel construction
Available in 7 sizes
Limited LIFETIME residential warranty
6 Year limited commercial warranty
Self cleaning/self descaling design
For domestic water, snow melting, radiant oor
Plates made of stainless steel, with 99.9 % copper
brazing, ensuring a high resistance to corrosion
Self cleaning and self descaling
Computerized sizing available from Triangle Tube
Available in capacities from 25,000 BTU/hr to
5,000,000 BTU/hr
24
Triangle Tube - 1240 Forest Parkway, Suite 100, West Deptford NJ 08066
Tel: (856) 228 8881 - Fax: (856) 228 3584 - E-mail: info@triangletube.com
Loading...