* I N S T A L L A T I O N A N D M A I N T E N A N C E *
Combination
Boiler
Water Heater
/
and
or
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
M A N U A L
M A N U A L
NOTICE
WARNING
Date: 12/9/2010
Warranty Registration Card must be filled out by the custo mer and mail ed within thi rty (30 ) days of
installation in order to gain warranty cov erage.
When receiving the CHALLENGER, any clai ms fo r damage or shortage in shipment must be filed immediately against the transportation company by t he co nsignee.
Leave all documentation received with appliance with owner for future reference.
If the information in this manual is not followed exactly, a fire or explosion may
result causing property damage, personal injury or death.
•Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
•WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the
gas supplier.
The following terms are used throughout this manual to bring attention to the presence of
potential hazards or important information concerning the product.
DANGER
Indicates the presence of a hazardous
situation which, if ignored, will result
in death, serious injury or substantial
property damage.
WARNING
Indicates a potentially hazardous situation which, if ignored, can result in
death, serious injury or substantial
property damage.
CAUTION
Indicates a potentially hazardous situation which, if ignored, may result in
minor injury or property damage.
NOTICE
Indicates special instructions on installation, operation or maintenance,
which are important to equipment but
not related to personal injury hazards.
BEST PRACTICE
Indicates recommendations made by
Triangle Tube for the installers which
will help to ensure optimum operation
and longevity of the equipment.
NOTICE
Triangle Tube reserves the right to modify the technical specifications and components of
its products without prior notice.
1
Page 8
Product & Safety Information
DANGER
Do not use this appliance if any part
has been under water. Immediately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system which has been
under water.
WARNING
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do
not use any phone in your building.
- Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
WARNING
Should overheating occur or the gas
supply fails to shut off, turn OFF the
manual gas control valve external to
the appliance.
WARNING
DO NOT add cold make up water when
the appliance is hot. Thermal shock can
cause potential cracks in the heat
exchanger.
CAUTION
When servicing the appliance:
-Avoid electrical shock by disconnecting the electrical supply prior to
performing maintenance.
WARNING
Qualified Installer:
Prior to installing this product read all
instructions included in this manual and all
accompanying manuals/documents with this
appliance. Perform all installation steps
required in these manuals in the proper
order given. Failure to adhere to the guidelines within these manuals can result in
severe personal injury, death or substantial
property damage.
Homeowner:
- This product should be maintained /
serviced and inspected annually by a
qualified service technician.
-This manual is intended for use by a
qualified Installer/Service Technician.
NOTICE
Please reference the appliance model number and the serial number from the rating
label, on the right panel when inquiring
about service or troubleshooting.
NOTICE
Triangle Tube accepts no liability for any
damage resulting from incorrect installation or from the use of components or
fittings not specified by Triangle Tube.
2
Page 9
Product & Safety Information
BURN
DANGER
Bacteria can develop in the domestic
water system if certain minimum water
temperatures are not maintained.
DANGER
HOT WATER CAN SCALD!
Water temperature over 125ºF [52ºC] can
cause severe burns instantly or death from
scalds.
•Children, disabled and elderly are at
highest risk of being scalded.
-Never leave them unattended in or
near shower, bathtub or sink.
-Never allow small children to use a
hot water faucet or draw their own
bath.
DANGER
Protection must be taken against
excessive pressure!
TO PROTECT AGAINST EXCESSIVE TEMPERATURE AND PRESSURE
•Check if a 150 psi [10 bar] pressure
relief valve (field supplied) is installed
as recommended for standard installations or a temperature/pressure relief
valve for storage tank installations.
(DHW side)
•Check if the 30 psi [2 bar] pressure
relief valve supplied is installed in
the recommended location. (CH side)
•To avoid injury, install the relief
devices to comply with local code
requirements.
• To avoid any potential scald hazard or if
codes require specific water temperatures
at the hot water faucet, the installer must:
-Install the factory supplied thermo-
static mixing valve at this appliance
and ensure it is working properly
and
-Set the thermostatic mixing valve to
the lowest temperature which satisfies your hot water needs.
-Feed and adjust water temperature
before bathing or showering.
-Water drained from the system drain
valves may be extremely hot.
TO AVOID INJURY:
-Make sure all connections are tight.
-Direct water flow away from any per-
son.
3
Page 10
Pre-Installation Items
SECTION I - Pre-Installation Items
Code Compliance
The CHALLENGER is certified to both the
Boiler (ANSI Z21.13/CSA 4.9) and Water
Heater (ANSI Z21.10.3/CSA4.3) standards.
Due to the CHALLENGER’s unique heat
exchanger design which incorporates two independent copper water tube coils; one for space
heating and the other for domestic hot water,
the CHALLENGER can be installed as a
Boiler or Water Heater or both. The unused
system does not have to be connected or filled.
Parameter 1 (Installation Type) will need to be
set accordingly (0= Heat and DHW, 2 = DHW
Only and 3 = Heat Only), see page 52 for
Setting Parameters.
This appliance must be installed in accordance
to the following:
-All applicable local, state, national and
provincial codes, ordinances, regulations and laws.
-For installations in Massachusetts, code
requires the appliance to be installed by
a licensed plumber or gas fitter, and if
antifreeze is utilized, the installation of
a reduced pressure backflow preventer
device is required in the boiler’s cold
water fill or make up water supply line.
-For installation in Massachusetts all direct
vented appliances must comply with the
guidelines as outlined on page 10.
- The National Fuel Gas Code NFPA54/
ANSI Z223.1 - Latest edition.
-National Electric Code ANSI/NFPA 70.
- For installations in Canada -“Installation
Code for Gas Burning Equipment”
CAN/CSA B149.1 Canadian Electrical
Code Part 1 CSA C22.1.
-Standards for Controls and Safety
Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1, when required.
NOTICE
The CHALLENGER gas manifold and
gas controls meet the safe lighting and
other performance requirements as specified in ANSI Z21.13 standard.
Determining Product Location
Before locating the CHALLENGER check for
convenient locations to:
-Heating system piping
-Domestic water supply piping
-Venting
-Gas supply piping
-Electrical service
Ensure the appliance location allows the combustion air and vent piping to be routed directly
through the building and terminate properly outside with a minimum amount of length and
bends.
Ensure the area chosen for the installation of the
CHALLENGER is free of any combustible
materials, gasoline and other flammable liquids.
WARNING
Failure to remove or maintain the area
free of combustible materials, gasoline
and other flammable liquids or vapors
can result in severe personal injury,
death or substantial property damage.
Ensure the CHALLENGER and its controls
are protected from dripping or spraying water
during normal operation or service.
The CHALLENGER should be installed in a
location so that any water leaking from the
appliance or piping connections or relief valve
will not cause damage to the surrounding area
or any lower floors in the structure. When such
location cannot be avoided, it is recommended
that a suitable drain pan, adequately drained, be
installed under the appliance. The pan must not
restrict combustion air flow.
4
Page 11
Pre-Installation Items
Boiler or Water Heater Replacement
If the CHALLENGER is replacing an existing
boiler or hot water heater system, the following
items should be checked and corrected prior to
installation:
-Boiler and domestic piping leaks and
corrosion.
- Improper location and sizing of the
expansion tank on the boiler heating
loop. Improper location and sizing of
the thermal expansion tank (if used) on
the domestic supply line.
-If applicable, level and quality of freeze
protection within the boiler system.
- Vent condition
WARNING
If the recommended service clearances
listed above cannot be maintained or the
enclosure in which the appliance is
installed is less than 45 cubic feet [1.3
m3], the space must be ventilated. See
page 8 for ventilation requirements.
NOTICE
When maintaining the approved clearance or less than recommended service
clearances, some product labeling may
become hidden and unreadable.
Clearances
The CHALLENGER is approved for following clearance to combustibles:
-Top panel - 12 inches [30.5 cm]
-Front - 0 inches
-Bottom panel - 12 inches [30.5 cm]
-Rear - 0 inches
-Right side - 4 inches [10.2 cm]
-Left side - 1.5 inches [3.8 cm]
-Boiler and Domestic Piping - 0.25 inches [0.6 cm]
- Reference the appropriate vent supplement for clearance requirements.
BEST PRACTICE
To provide serviceability to the appliance it is recommended that the following clearances be maintained:
WARNING
When installing the CHALLENGER in a
confined space, sufficient air must be provided to allow, under normal operating conditions, proper air flow around the product
to maintain ambient temperatures within
safe limits to comply with the National Fuel
Gas Code NFPA 54 - Standard.
Residential Garage Installations
When installing the CHALLENGER in a residential garage, the following special precautions
per NFPA 54/ANSI Z223.1 must be taken:
-Mount the appliance a minimum 18
inches [458 mm] above the floor level
of the garage. Ensure the burner and
ignition devices / controls are no less
than 18 inches [458 mm] above the
floor level.
-Locate or protect the appliance in a
manner so it cannot be damaged by a
moving vehicle.
Top panel - 24 inches [61 cm].
Front - 24 inches [61 cm].
Bottom panel - 24 inches [61 cm].
Rear - 0 inches
Sides - 6 inches [15.2 cm]
5
Page 12
Pre-Installation Items
Boiler Freeze Protection Feature
The boiler control has a freeze protection feature
built in. This feature monitors the boiler supply
temperature and responds as follows when no
call for heat is present:
-42ºF
[6ºC] Boiler circulator and burner are
ON.
-50ºF
[10ºC] Boiler circulator and burner are
OFF.
CAUTION
The boiler freeze protection feature is
disabled during a hard lockout, (burner
does not operate) however the CH circulator will operate.
CAUTION
The boiler freeze protection feature is
designed to protect the boiler. The boiler must be installed in a primary/secondary piping arrangement. See Section
IV for primary/secondary piping examples. See Section X for antifreeze guidelines.
6
Page 13
Combustion Air and Venting
SECTION II- Combustion Air and
Venting
Combustion Air Contamination
WARNING
If the CHALLENGER combustion air
inlet is located in any area likely to cause
or contain contamination, or if products,
which would contaminate the air cannot
be removed, the combustion air must be
repiped and terminated to another location. Contaminated combustion air will
damage the appliance and its burner system, resulting in possible severe personal
injury, death or substantial property
damage.
WARNING
Do not operate a CHALLENGER if its
combustion air inlet is located near a
laundry room or pool facility. These
areas will always contain hazardous contaminants.
Potential contaminating products
-Spray cans containing chloro/fluorocarbons
-Permanent Wave Solutions
-Chlorinated wax
-Chlorine - based swimming pool chemicals / cleaners
-Calcium Chloride used for thawing ice
-Sodium Chloride used for water softening
-Refrigerant leaks
-Paint or varnish removers
-Hydrochloric acid / muriatic acid
-Cements and glues
-Antistatic fabric softeners used in
clothes dryers
-Chlorine-type bleaches, detergents, and
cleaning solvents found in household
laundry rooms
-Adhesives used to fasten building products and other similar products
Pool and laundry products and common
household and hobby products often
contain fluorine or chlorine compounds.
When these chemicals pass through the
burner and vent system, they can form
strong acids. These acids can create corrosion of the heat exchanger, burner
components and vent system, causing
serious damage and presenting a possible threat of flue gas spillage or water
leakage into the surrounding area.
Please read the information listed below.
If contaminating chemicals are located
near the area of the combustion air inlet,
the installer should pipe the combustion
air inlet to an area free of these chemicals per SECTION VI of this installation
manual.
Areas likely to contain these products
-Dry cleaning / laundry areas and establishments
-Beauty salons
-Metal fabrication shops
-Swimming pools and health spas
-Refrigeration Repair shops
-Photo processing plants
-Auto body shops
-Plastic manufacturing plants
-Furniture refinishing areas and establishments
-New building construction
-Remodeling areas
-Garages with workshops
7
Page 14
Combustion Air and Venting
Ventilation Air Requirements
For installations, involving only the CHALLENGER, in which the minimum service
clearances are maintained as listed on page 5,
no ventilation openings are required.
Combustion Air and Vent Piping
The CHALLENGER requires a Category IV
venting system, which is designed for pressurized venting and condensate.
For installations with less than the minimum
service clearances involving only the CHALLENGER, the space / enclosure must provide
two openings for ventilation. The openings
must be sized to provide 1 square inch [6
square centimeters] of free area per 1,000
BTUH [0.3 Kw] of appliance input. The openings shall be placed 12 inches [30.5 cm] from
the top of the space and 12 inches [30.5 cm]
from the floor of the space.
For installations in which the CHALLENGER
shares the space with air movers (exhaust fan,
clothes dryers, fireplaces, etc.) and other combustion equipment (gas or oil) the space must
be provided with adequate air openings to provide ventilation and combustion air to the
equipment. To properly size the ventilation /
combustion air openings, the installer must
comply with the National Fuel Gas Code
NFPA 54, ANSI Z223.1 for installations in the
U.S or CAN/CSA B149.1 for installations in
Canada/
The CHALLENGER is certified as Direct Vent
(sealed combustion) appliance. A Direct Vent
appliance utilizes uncontaminated outdoor air
(piped directly to the appliance) for combustion.
NOTICE
Install combustion air and vent pipe as
detailed in the CHALLENGER
Concentric Vent/Air System
Supplement 2010-23 included in the
appliance installation envelope. Refer to
instructions for parts list and method of
installation.
DANGER
Verify installed combustion air and vent
piping are sealed gas tight and meet all
provided instructions and applicable
codes, failure to comply will result in
severe personal injury of death.
WARNING
The space must be provided with ventilation / combustion air openings properly sized for all make-up air requirements
(exhaust fans, clothes dryers, fireplaces,
etc.) and the total input of all appliances
located in the same space as the CHALLENGER. The input of a CHALLENGER which uses combustion air
directly from the outside, is excluded
thus additional free area for the openings is not required. Failure to provide
or properly size the openings could
result in severe personal injury, death or
substantial property damage.
8
Page 15
Combustion Air and Venting
Removal of an Existing Boiler and or Water
Heater from a Common Vent System
BEST PRACTICE
When an existing boiler and/or water
heater is removed from a common venting system, the common venting system is
likely to be too large for proper venting of
the remaining appliances. At the time of
removal of an existing boiler and/or water
heater , the following steps shall be followed with each appliance remaining
connected to the common venting system
placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for
proper size and horizontal pitch and determine there is no blockage or restriction,
leakage, corrosion and other deficiencies
which could cause an unsafe condition.
5. Test for spillage at the draft hood relief
opening after 5 minutes of main burner
operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each
appliance remaining connected to the common venting system properly vents when
tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and
any other gas-burning appliance to their
previous condition of use.
7. Any improper operation of the common
venting system should be corrected so the
installation conforms with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CAN/CSA B149.1, Installation
codes. When resizing any portion of the
common venting system, the common
venting system should be resized to
approach the minimum size as determined
using the appropriate tables in Part II of the
National Fuel Gas Code ANSI
Z223.1/NFPA 54 and/or CAN/CSA
B149.1, Installation codes.
3. Insofar as is practical, close all building
doors and windows and all doors between
the space in which the appliances remaining connected to the common venting system are located and other spaces of the
building. Turn on clothes dryers and any
appliance not connected to the common
venting system. Turn on any exhaust fans,
such as range hoods and bathroom
exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust
fan. Close fireplace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
DANGER
Do not install the CHALLENGER into a
common vent with other gas or oil appliances. This may cause flue gas spillage or
appliance malfunction, resulting in possible severe personal injury, death or substantial property damage.
9
Page 16
Combustion Air and Venting
Commonwealth of Massachusetts Installations Only
For direct-vent appliances, mechanicalvent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake is installed
below four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are bedroom(s), a carbon monoxide detector
and alarm shall be placed in the living
area outside the bedroom(s). The carbon monoxide detector shall comply
with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall also
be located in the room that houses the
appliance or equipment and shall:
a. Be powered by the same electrical
circuit as the appliance or equipment such that only one service
switch services both the appliance
and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005
Edition); and
d. Have been approved and listed by
the Nationally Recognized Testing
Laboratory as recognized under 527
CMR.
3. A Product-approved vent terminal must
be used, and if applicable, a Productapproved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions
shall remain with the appliance or
equipment at the completion of the
installation.
4. A metal or plastic identification plate
shall be mounted at the exterior of the
building, four feet directly above the
location of vent terminal. The plate
shall be of sufficient size to be easily
read from a distance of eight feet away,
and read “Gas Vent Directly Below”.
NOTICE
Installer must provide tag identification
plate and ensure the lettering meets code
requirements.
For direct-vent appliances, mechanicalvent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake are installed
above four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are bedroom(s), a carbon monoxide detector
and alarm shall be placed in the living
area outside the bedroom(s). The carbon monoxide detector shall comply
with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses
the appliances or equipment;
b. Be either hard wired or battery
powered or both; and
c. Shall comply with NFPA 720 (2005
Edition)
3. A Product-approved vent terminal must
be used, and if applicable, a Productapproved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions
shall remain with the appliance or
equipment at the completion of the
installation.
10
Page 17
Appliance Preparations
SECTION III - Appliance Preparations
Handling Instructions
The CHALLENGER is generally easier to
handle and maneuver once removed from the
shipping carton.
To remove the shipping carton:
CAUTION
Use care not to lift the appliance from
piping or damage can occur. Use care
not to drop or bump the appliance as
damage to the appliance will result.
1. Remove any shipping straps and the top
shipping carton.
Fig. 1: Optional Floor Stand Assembly,
Part Number: PSSTND04
2. Carefully lift the appliance out of the carton.
3. Discard all packing materials.
Wall Mounting Installation
The CHALLENGER should be wall mounted
using the bracket provided with the appliance.
The CHALLENGER is not designed for floor
installation. If floor installation is required an
optional floor stand part number PSSTND04 is
available through Triangle Tube. Appliance is
not to be installed on carpeting.
NOTICE
The wall used for mounting the CHALLENGER must be vertically plumb and
capable of supporting a minimum 110
pounds [50 kg]. Failure to comply with
these requirements could result in personal injury, death or substantial property damage.
Wall Mounting Guidelines
1. The wall-mounting bracket is designed for
stud spacing of 12 inch [30.5 cm] or 16
inch [40.6 cm] on centers. For unconventional stud spacing, a solid / secure mounting surface must be provided for installation of the bracket.
2. For applications using wood studs, install
the bracket using the lag screws provided
with the appliance. Ensure both lag screws
are installed securely in the studs.
3. For applications using metal studs, install the
bracket to the studs using 3/16” [5 mm] toggle bolts and washers (provided by others)
4. DO NOT mount or attempt to mount the
wall bracket to hollow sheet rock or lath
walls using anchors. Only install appliance
to studs or equivalent wood structure.
5. For applications using solid walls (rock,
concrete, brick, cinder block, etc.), install
the wall bracket using anchors (double
expansion shields) bolts and washers provided with the appliance.
6. The appliance is too heavy and bulky for a
single person to lift and attempt to mount; a
minimum of 2 people is required for
mounting the appliance.
11
Page 18
Appliance Preparations
Lag Screw
(Stud Wall)
Bolts with
Washer
(Solid Wall)
Wall Anchors
(Solid Wall Only)
NOTICE
Use extreme care not to drop the appliance or cause bodily injury while lifting
or mounting the appliance onto the
bracket. Once mounted verify that the
appliance is securely attached to the
bracket and wall. Failure to comply
with the above guidelines could result in
property damage, personal injury or
death.
Stud Walls -Installation
1. Locate the studs in the general area of the
appliance placement.
2. Place the wall-mounting bracket on the
wall centering the mounting slots with the
stud centers and ensuring the upper edge of
the bracket is away from the wall.
3. Level the bracket, while maintaining it’s centering with the studs and use a pencil to mark
the location of the mounting slots/holes.
4. Remove the bracket from the wall and drill
1/4” [6 mm] diameter hole by 3” [76 mm]
deep positioned in the center of each mark.
For applications using metal studs and
3/16” [5 mm] toggle bolts, drill the
required clearance hole.
3. Level the bracket and use a pencil to mark
the location of the mounting slots/holes on
the wall.
4. Remove the bracket from the wall and drill
a 5/8” [16 mm] diameter hole by 1-3/8” [35
mm] deep positioned in the center of each
mark.
5. Install the anchors (provided) flush or
slightly recessed in the drilled holes with
threaded side facing down.
6. Reposition the bracket on the wall and
align mounting slots/holes. Insert the two
bolts with washers (provided) through the
mounting slots/holes and loosely tighten.
7. Level bracket and tighten bolts securely.
Appliance Mounting
1. Obtain assistance in lifting the appliance
onto the wall bracket.
2. Install the appliance making sure the appliance mounting lip located along the upper
edge of the rear jacket panel engages the
wall-mounting bracket. Ensure the appliance is seated properly and is secure.
5. Reposition the bracket onto the wall and
align mounting slots/holes. Insert the two
lag screws provided (or toggle bolts for
metal studs) through the mounting
slots/holes and loosely tighten.
6. Level bracket and tighten screws (bolts for
metal studs) securely making sure not to overtighten to avoid damaging drywall or plaster.
Wall Bracket Installation - Solid Walls
1. Locate the general area of the appliance
placement.
2. Place the wall-mounting bracket on the
wall ensuring the upper edge of the bracket
is away from the wall.
Fig. 2: Wall Mounting The CHALLENGER
12
Page 19
Appliance Preparations
Piping Support Bracket
1. Pre-install the 4 brass compression fittings
into the piping support bracket as shown in
Fig. 4, page 15. Use retaining clips to hold
fittings in place.
BEST PRACTICE
Apply pipe joint compound suitable for
potable water systems to the compression ferrule and compression nut threads
of all brass fittings before installation.
Install appliance pipes into the fittings
until bottom of hex on gas pipe fitting
rests against the top of the piping support bracket before tightening any compression nuts. Do not over tighten compression nuts. If fitting leaks loosen compression nut first and then retighten.
2. Once the appliance is mounted onto the
wall, slip the appliance piping into the fittings until bottom of hex on gas pipe fitting
rests against the top of the piping support
bracket before tightening any compression
nuts.
3. Secure piping support bracket to wall with
hardware supplied.
4. Tighten all fittings to appliance piping
connections with two wrenches.
WARNING
Use a two wrench method when tightening piping near the appliance and its piping connections. Use one wrench to prevent the appliance connections from
turning and the second to tighten adjacent piping. Failure to support the appliance piping connections could damage
piping.
13
Page 20
Boiler Piping
SECTION IV - Boiler Piping
General Piping Requirements
- All plumbing must meet or exceed all local,
state and national plumbing codes.
-Support all piping using hangers. DO NOT
support piping by the appliance or its components.
-Use isolation valves to isolate system components.
-Install unions for easy removal of the
CHALLENGER from the system piping.
WARNING
Use a two wrench method when tightening piping onto the appliance connections. Use one wrench to prevent the
appliance piping from turning / twisting.
Failure to support the appliance piping
and connections in this manner could
cause damage to the appliance and its
components.
above any drain connection to allow
clear visibility of the discharge.
- Should terminate with a plain end, not
with a threaded end. The material of the
piping should have a serviceable temperature rating of 250ºF [121ºC] or greater.
- Should not be subject to conditions
where freezing could occur.
- Should not contain any shut-off valves
or obstructions. No shut-off valve
should be piped between the appliance
and relief valve.
WARNING
Failure to comply with the guidelines on
installing the pressure relief valve and discharge piping can result in personal injury,
death or substantial property damage.
Low Water Cutoff Device
NOTICE
Pressure Relief Valve
1. The CHALLENGER has a ASME
Maximum Allowable Working Pressure of
43.5 PSI [3 bar]. The appliance is supplied
with a 30 psi [2 bar] pressure relief valve
and must be piped using the PRV connection as shown in Fig. 3 page 15.
2. To avoid potential water damage to the surrounding area or potential scalding hazard
due to the operation of the relief valve, the
discharge piping:
- Must be connected to the discharge out-
let of the relief valve and directed to a
safe place of disposal.
- Length should be as short and direct as
possible. The size of the discharge line
should not be reduced, maintain the
same size as the outlet of the relief valve.
- Should be directed downward towards
the floor at all times. The piping should
terminate at least 6 inches [153 mm]
The Low Water Cutoff Device only
applies for space heating. Operation of
the Low Water Cutoff Device does not
prevent a domestic hot water call for heat.
-The CHALLENGER is equipped with a factory installed pressure switch type Low Water
Cut Off device.
-The minimum operating space heating (CH)
system pressure allowable with this device is
7 psig [0.5 bar].
-If CH System pressure is below 7 psig [0.5
bar] the main display will show an error of
“LOP”. If the appliance is installed as domestic hot water heater only, set parameter 2
(installation type) to 2 (domestic only) to
eliminate the “LOP” error in the main display,
see page 52 for setting parameters.
-Check local codes if a Low Water Cutoff
Device is required. If so, determine if this
device meets the requirements of the local
codes.
14
Page 21
Boiler Piping
Boiler Return Connection
with Tee Fitting and
Boiler Drain Valve
Boiler Supply
Connection
with Tee
Fitting and
Temperature/
Pressure Gauge
Pressure Relief Valve
(
Supplied with Boiler)
3/4" Street Elbow
Air Vent
(Supplied with Boiler)
Drain Piping Directed
to a Suitable
Place of Drainage
Drain Valve
(by Others)
1 inch
Compression
Assembly
(supplied)
1 inch
Compression
Assembly
(supplied)
1 inch Tee (by Others)
1 inch
Tee
(supplied)
Temperature Pressure
Gauge (supplied)
Piping Bracket
(supplied)
Retaining Clip
(supplied)
Compression
Ferrule
Compression
Nut
Compression/NPT Adapater
Air Vent
(supplied)
3/4” Tee
(supplied)
3/4” Nipple
(supplied)
3/4” Street
Elbow (supplied)
Installer must provide
relief valve drain piping
directed to a suitable
place of drainage
Pressure Relief Valve
(supplied)
Note:
Fig. 3: Boiler Pressure Relief Valve and Drain Valve Installation
Fig. 4: Near Appliance Piping Assembly
15
Page 22
Boiler Piping
Additional Limit Control
If a LWCO device is required by certain local
jurisdictions or when the boiler is installed
above the system piping, the following guidelines must be followed:
- The LWCO device must be designed
for water installations, electrode probetype is recommended.
- The LWCO device must be installed in
a tee connection on the boiler supply
piping above the appliance.
- Wiring of the LWCO device to the
CHALLENGER should be done in
series with the 120 V line voltage into
the appliance .
If the installation is to comply with ASME or
Canadian requirements, an additional high
temperature limit may be needed. Consult
local code requirements to determine compliance. The limit should be installed as follows:
- Install the limit in the boiler supply piping between the boiler and any isolation
valve.
- Maximum set point for the limit is
200ºF.
- Wiring of the limit device to the CHALLENGER should be done in series with
the 120V line voltage into the appliance.
Backflow Preventer
-Use a backflow preventer valve in the
make-up water supply to the appliance
as required by local codes.
Boiler System Piping Applications
BEST PRACTICE
It is required on all piping applications to
utilize a primary/secondary piping
arrangement. Maintain the minimum
boiler flow rate, see Graphs 5-10 on pages
80-82.
Expansion Tank and Makeup Water
Ensure the expansion tank is properly sized for
the boiler volume (approximately 1 gallon [4
L]) and the system volume and temperature.
CAUTION
Undersized expansion tanks will cause
system water to be lost through the pressure relief valve and cause additional
makeup water to be added to the system.
Eventual boiler heat exchanger failure
can result due to this excessive makeup
water addition.
The expansion tank must be located as shown
in Fig. 5 and Fig. 6 on page 18 when using a
primary/secondary piping arrangement or as
per recognized design methods. Refer to the
expansion tank manufacturer instructions for
additional installation details.
Connect the expansion tank to an air separator
only if the air separator is located on the suction side (inlet) of the system circulator.
Always locate and install the system fill connection at the same location as the expansion
tank connection to the system.
Diaphragm Expansion Tank
Always install an automatic air vent on the top
of the air separator to remove residual air from
the system.
16
Page 23
Boiler Piping
Closed-Type Expansion Tank
It is recommended to pitch any horizontal piping upwards toward the expansion tank 1 inch
per 5 feet [2.5cm / 1.5 M] of piping. Use 3/4”
piping for the expansion tank to allow air within the system to rise.
CAUTION
DO NOT install automatic air vents on a
closed-type expansion tank system. Air
must remain in the system and be
returned to the expansion tank to provide an air cushion. An automatic air
vent would cause air to be vented from
the system resulting in a water-logged
expansion tank.
Circulator
The CHALLENGER must be supplied with a
Central Heating (CH) circulator. The circulator
when wired directly to the CHALLENGER
will allow for domestic hot water priority and
to provide circulation for the freeze protection
feature of the boiler control. See Graph 5-10 on
page 80-82 for pressure drop and minimum
flow rate through the boiler.
Sizing Primary Piping
System Piping - Zone Circulators
Connect the CHALLENGER to the system
piping as shown in Fig. 7 page 20 when zoning
with zone circulators.
The installer must provide a separate circulator
for each zone of space heating.
NOTICE
To ensure an adequate flow rate through
the CHALLENGER, the boiler supply
and return piping size must be a minimum of 1 inch.
System Piping - Zone Valves
Connect the CHALLENGER to the system piping as shown in Fig. 8 page 20 when zoning with
zone valves. The primary / secondary piping
ensures that the boiler loop has sufficient flow.
NOTICE
To ensure an adequate flow rate through
the CHALLENGER, the boiler supply
and return piping size must be a minimum of 1 inch.
See Fig. 7 and 8, page 20, for recommended
piping arrangements based on various applications. Size the piping and system components
required in the space heating system, using recognized design methods.
17
Page 24
Boiler Piping
Max.
12"
Boiler
Supply
S
ystem
Return
System
[30.5 cm]
Cold
Water Fill
Boiler
Supply
Return
7
10
1
2
3
5
4
6
6
6
11
12
7
1
10
9
8
4
3
6
6
6
Cold
Water Fill
Boiler
Supply
Minimum
3/4" Piping
Boiler
Return
Return
System
Supply
System
11
12
Max.
12"
[30.5 cm]
Fig. 5: Near Boiler Piping - Diaphragm Expansion Tank
Fig. 6 : Near Boiler Piping - Closed Type Expansion Tank
1. System circulator
2. Automatic air vent
3. Air separator
4. Automatic fill valve
5. Diaphragm expansion tank
6. Isolation valve
7. Drain/purge valve
8. Tank fitting
9. Closed type expansion tank
10. Primary/secondary connection
11. CH circulator
12. Flow/check valve
18
Page 25
Boiler Piping
System Piping - Radiant Heating
The heat exchanger design of the CHALLENGER allows operation in a condensing
mode. This feature requires no regulation of
the return water temperature back to the boiler
in radiant heating applications.
The highest boiler water supply temperature
can be maintained by the CHALLENGER,
potentially eliminating the need for a mix system to achieve the desired temperature if all
zones of heat are at the same temperature set
point.
Size the system piping and circulator to provide
the flow needed for the radiant system.
NOTICE
To ensure an adequate flow rate through
the CHALLENGER, the boiler supply
and return piping size must be a minimum of 1 inch.
System Piping - Special Application
If the boiler is used in conjunction with a
chilled water/medium system, the boiler and
chiller must be piped in parallel. Install
flow/check valves to prevent the chilled medium from entering into the boiler.
If the boiler is used to supply hot water to the
heating coils of an air handler where they may
be exposed to chilled air circulation, install
flow/check valves or other automatic means
to prevent gravity circulation of the boiler
water during cooling cycles.
19
Page 26
Boiler Piping
2
6
5
5
4
6
3
12
9
8
10
11
4
4
4
4
4
4
Zone Load
7
Additional
Max.
[30.5 cm]
12"
Zone Load
1
5
5
4
6
2
3
3
3
3
3
[
30.5 cm]
9
8
10
11
4
4
4
4
4
4
Zone Load
A
dditional
7
6
Max.
12"
Z
one Load
1
Fig. 7: CH System Piping - Zoning with Zone Circulators
1. CHALLENGER boiler
2. CH circulator
3. Flow/check valve
4 Isolation valve
5. Zone circulator
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
6. Drain/purge valve
Fig. 8: CH System Piping - Zoning with Zone Valves
1. CHALLENGER boiler
2. CH circulator
3. Flow/check valve
4 Isolation valve
5. Zone valve
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
12. System circulator
20
Page 27
Domestic Piping
SECTION V - Domestic Piping
WARNING
HOT WATER CAN SCALD!
•Water temperatures over 125ºF [52ºC]
can cause severe burns instantly, or
death from scalds.
•Feel water before bathing or showering.
•Consumer Product Safety Commission
and some states recommend temperatures settings of 130ºF [54ºC] or less.
Setting thermostat higher than 130ºF
[54ºC] will increase risk of scald injury
and cause severe personal injury or
death.
•Water heated to a temperature suitable
for clothes washing, dish washing and
other sanitizing needs will scald and
cause permanent injury.
•Children and elderly, infirm, or physically handicapped persons are more
likely to be injured by hot water. Never
leave them unattended in or near a bathtub. If anyone using hot water in the
building fits this description, or if state
laws or local codes require certain
water temperatures at hot water faucets,
take special precautions.
General Notes
•Household water usage patterns will affect
water temperature at any faucet or shower.
Occasionally check temperature at each
point of use, then adjust thermostatic mixing valve accordingly. Always recheck
temperature after adjusting.
•Lowering the thermostatic mixing valves as
indicated in these instructions will reduce water
temperature levels. Consult your installer or
service technician.
Operating Restrictions
- Install the factory supplied thermostatic mixing valve at the water
heater. Installation must comply with
valve manufacturer’s recommendation and instructions.
- Use the lowest practical temperature
setting.
- Check water temperature after any
adjustment. You must follow “Setting
the Thermostatic Mixing Valve” procedures.
• Minimum DHW flow rate is 0.5 gpm [2
lpm] to initiate a domestic call for heat.
•Maximum DHW outlet temperature is
149ºF [65ºC].
•Maximum domestic working pressure is
150 psig [10 bar].
•Water quality limitations:
-Chloride, less than 150 ppm or mg/l
-pH value min. 6.5, max. 8.5
-Total hardness 3 - 7 grains/gallon or 50-
120 ppm or mg/l.
-Total Dissolved Solids (TDS), less than
500 ppm or mg/l.
21
Page 28
Domestic Piping
-Iron less than 0.3 ppm or mg/l.
-Aluminum, less than 0.2 ppm or mg/l.
-Copper, less than 1 ppm or mg/l.
-Manganese, less than 0.05 ppm or mg/l.
-Zinc, less than 5 ppm or mg/l.
BEST PRACTICE
In hard water area (more than 7 grains
of harness) soften the cold domestic supply water to the appliance to prevent
lime build-up).
NOTICE
Any water conditioning system must be
installed and maintained in accordance
with manufacturer’s specifications.
Pressure Relief Valve - Standard
Installations
2. To avoid potential water damage to the surrounding area or potential scalding hazard
due to the operation of the relief valve, the
discharge piping:
- Must be connected to the discharge out-
let of the relief valve and directed to a
safe place of disposal.
- Length should be as short and direct as
possible. The size of the discharge line
should not be reduced, maintain the
same size as the outlet of the relief valve.
- Should be directed downward towards
the floor at all times. The piping should
terminate at least 6 inches [152 mm]
above any drain connection to allow
clear visibility of the discharge.
- Should terminate with a plain end, not
with a threaded end. The material of the
piping should have a serviceable temperature rating of 250ºF [121ºC] or greater.
- Should not be subject to conditions
where freezing could occur.
The water heater (if utilized) shall have a field
pressure relief valve installed within 6” [152
mm] of the DHW HOT outlet connection with
the relief valve spindle installed in the vertical
position.
The water heater (if utilized) requires a field
supplied pressure relief valve identified with
the ASME V or HV symbol and set to relieve
at or below 150 psi [ 10 bar] of domestic water
pressure and a minimum relieving capacity of
124,000 Btu/hr with 3/4” NPT threads. For safe
operation of the water heater, the relief valve
must not be removed from its designated point
of installation or plugged.
1. The CHALLENGER is not supplied with a
150 psi [10 bar] pressure relief valve and
must be piped using a PRV connected as
shown in Fig. 11 page 26.
- Should not contain any shut-off valves
or obstructions. No shut-off valve
should be piped between the appliance
and relief valve.
WARNING
Failure to comply with the guidelines on
installing the pressure relief valve and discharge piping can result in personal injury,
death or substantial property damage.
22
Page 29
Domestic Piping
Temperature & Pressure (T&P) Relief
Valve- Storage Tank Installations
CAUTION
To reduce risk of excessive pressures and
temperatures in a storage tank, install
temperature and pressure protective
equipment required by local codes, but
no less than a combination temperature
and pressure relief valve certified by a
nationally recognized testing laboratory
that maintains periodic inspection of
production of listed equipment or materials, as meeting the requirements for
Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems,
ANSI Z21.22. This valve must be
marked with a maximum working pressure of the water heater.
•A storage tank must be protected with a
field supplied T&P relief valve.
•Size the T&P relief valve by the following specifications, unless they conflict
with local codes: 3/4” NPT with an AGA
Rating of 124,000 BTU/hr.
T&P Relief Valve Discharge Piping
- plugged, reduced or restricted.
- subject to freezing.
WARNING
Do not install any valve between T&P
relief valve and storage tank connection
or on T&P relief valve discharge piping.
Do not plug T&P relief valve or discharge piping. Improper placement and
piping of T&P relief valve can cause
severe personal injury, death or substantial property damage.
Drain Valves
Drain valves and fittings are field supplied.
Thermal Expansion
If a backflow preventer, check valve or pressure
reducing valve is piped on cold water supply
piping of water heater, install an expansion tank
on cold water supply line to prevent normal
thermal expansion from repeatedly forcing open
the relief valve.
T&P relief valve discharge piping must be:
- made of material serviceable for temperatures of 250ºF [121ºC] or greater.
- directed so that hot water flows away
from all persons.
- directed to a suitable place for disposal.
- installed so as to allow complete draining of the T&P relief valve and discharge line.
T&P relief valve discharge piping must not
- excessively long. Using more than 2
elbows or 15 feet [4.5 m] of piping can
reduce discharge capacity.
- directly connected to a drain.
- terminate discharge piping within 6”
[152 mm] from drain. Refer to local
codes.
be:
CAUTION
Relief valve is not intended for constant
duty, such as relief of pressure due to
repeated normal system expansion.
Correct this condition by installing a
properly sized expansion tank in domestic water system. Refer to expansion
tank manufacturer’s installation
instructions for proper sizing.
The domestic water volume of the
CHALLENGER is approximately 0.26
gallons [ 1 l]. Remember to include this
volume in sizing of the expansion tank.
23
Page 30
Domestic Piping
Water Hammer
Dishwashers, clothes washers and fast-closing
positive shut-off valves incorporated in the system all contribute to creating water shock. Install
a water hammer arrester to prevent damage to
pipes and appliances. See device manufacturer’s
instructions for application and installation.
Vacuum Breaker - Storage Tank Installations
Installing a vacuum breaker on the inlet of the storage tank will prevent damage to the tank if a negative pressure is developed in the domestic supply
line. See manufacturer’s instructions for application and installation of the vacuum breaker.
General Piping Requirements
•For domestic water piping diagrams, see
Figs 11 and 12, pages 26 and 27.
BEST PRACTICE
It is recommended to install flush valves
as outlined in Fig. 11 and 12, pages 26
and 27 for servicing the domestic coil.
•Use isolation valves to isolate the DHW
connections and system components.
•Use dielectric unions or couplings to protect hot and cold water fittings from corrosion when connecting dissimilar materials
such as copper and galvanized iron pipe.
•If copper pipe is used for domestic water
connections, first solder pipe to a threaded
adapter and then screw adapter onto the
domestic cold water inlet of the appliance.
The domestic cold water inlet contains an
internal plastic flow switch which can be
damaged by heat from soldering.
NOTICE
Do not apply heat to the domestic cold
water inlet when making sweat connections to water heater. Sweat tubing to
adapter before fitting adapter to cold
water inlet of heater. It is imperative that
no heat be applied to the cold water inlet,
as it contains a non metallic flow switch.
•When the water supply pressure is higher
than 70 psig [4.8 bar], it is recommended to
install a pressure reducing valve on cold
water supply line to prevent water loss
through pressure relief valve.
BEST PRACTICE
It is recommended to install a strainer on
the domestic cold water inlet to prevent
any nuisance issues with domestic flow
switch. An optional lead free, 60 mesh ystrainer is available through Triangle Tube
part number CCSTRA01, see Graph 4,
page 79 for strainer pressure loss curve.
•All plumbing must meet or exceed all local,
state and national plumbing codes.
•Use pipe joint compound or tape suitable
for potable water systems.
•Size all piping no smaller than the appliance’s DHW connections.
Thermostatic Mixing Valve
The CHALLENGER is factory supplied with a
thermostatic mixing valve with built-in check
valve. The mixing valve must be installed as
shown in Figs. 9, 11 and 12.
The operating range of the thermostatic mixing
is 90ºF [32ºC] to 120ºF [49ºC].
BEST PRACTICE
Additional thermostatic/anti-scald valves
should be installed at each hot water
faucet, bath and shower outlet.
For applications with a domestic recirculation
loop, the recirculation pump should be controlled
24
Page 31
Domestic Piping
C
o
l
d
H
o
t
A
dapter
C
heck Valve
Mixed
by an aquastat. The maximum recommended setting of the aquastat is 10ºF [5ºC] lower than the
thermostatic mixing valve setting.
DANGER
For proper operation of the thermostatic mixing valve and to prevent potential
scalding hazards, the recirculation loop
should be controlled by an aquastat. DO
NOT use continuous recirculation.
2. Provide recirculation from the storage
tank back to the CHALLENGER using a
bronze type circulator. Maximum recommended recirculation flow rate is 1 gpm.
Setting the Thermostatic Mixing Valve
NOTICE
The thermostatic mixing valve controls
the outlet hot water temperature delivered to the faucets.
WARNING
POTENTIAL SCALD HAZARD. The
mixing valve must be installed on the
CHALLENGER. Removal of the mixing
valve will create a potential scald hazard
resulting in severe personal injury or death.
If any adjustment needs to be made on the
valve:
Fig. 9: Mixing Valve Assembly
Recirculation Piping
•Recirculation piping if applicable must be
installed in the cold water inlet as shown
Figs 11 and 12, page 26 and 27.
•A stainless steel or bronze circulator is recommended and must be controlled by a
aquastat. See Graph 3 page 79 for domestic
pressure loss.
Storage Tank Installations
For applications requiring large volumes of
domestic hot water in a relative short period, the
installer may include a storage type tank (see
Fig. 12 page 27) in the domestic piping.
The installer must:
1. Relocate the thermostatic mixing valve from
the CHALLENGER to the outlet of the storage tank.
-Use a L-Key to remove the set screw securing the knob to the valve.
-Remove the knob and lock ring from the
valve.
-Replace the knob and adjust the set temperature of the valve to the desired temperature.
NOTICE
To calibrate the outlet temperature,
allow the water to run for approximately 2 minutes and measure the water with
a thermometer. To adjust the valve setting, rotate the knob clockwise to
decrease the water temperature or
counter-clockwise to increase the water
temperature.
-Once the desired temperature is achieved,
remove the knob and refit the lock ring
onto the valve’s “Mix” marking.
-Locate the tab on the inner face of the knob
into the retainer in the locking ring. Secure
the knob with set screw.
25
Page 32
Domestic Piping
6
To Dish Washer
or High Temperature
Application
6
M
c
H
1
5
Cold
DHW
Water Inlet
4
10
9
3
2
2
2
7
8
Recirculating
Loop
1/2” compression x 3/4” NPT Adapter
Fittings for DHW
Fig. 10 : Installation of Domestic Compression Adapter Assemblies
Fig. 11 : Domestic Piping - Standard Installations
1. CHALLENGER
2. Isolation valve
3. Backflow preventer or pressure reducing valve (*)
4. Thermal expansion tank (potable)
5. Domestic pressure relief valve - 150 lbs
6. Drain/flush valve
7. Mixing valve with check valve
8. Strainer (*)
9. Flow check valve
10. Circulator (potable , must be controlled by a aquastat )
(*) Optional device may be required by local codes
26
Page 33
Domestic Piping
Storage
Tank
5
Recirculating
Loop
11
1
9
9
8
DHW
Cold
Water
Inlet
8
9
7
3
10
4
2
M
H
C
6
6
2
2
Fig. 12 : Domestic Piping - Storage Tank Installations
1. CHALLENGER
2. Isolation valve
3. Backflow preventer or pressure reducing valve (*)
4. Thermal expansion tank (potable)
5. Temperature/Pressure relief valve
6. Drain/flush valve
7. Mixing valve with check valve
8. Circulator (potable, must be controlled by a aquastat)
9. Flow check valve
10. Strainer (*)
11. Vacuum breaker (*)
(*) Optional device maybe required by local codes
27
Page 34
Installation Vent/Combustion Air & Condensate Drain
SECTION VI - Installing Vent /
Combustion Air & Condensate Drain
Installing Vent and Combustion Air
DANGER
The CHALLENGER must be vented
and supplied with combustion air as
shown in the CHALLENGER Concentric Vent/Air System Supplement 201023, included in the installation envelope.
Refer to instructions for parts list and
method of installation. Once installation
is completed, inspect the vent and combustion air system thoroughly to ensure
systems are airtight and comply with the
instructions given in the venting supplement and are within all requirements of
applicable codes. Failure to comply with
the installation requirements on the
venting and combustion air piping will
cause severe personal injury or death.
Installing Condensate Drain Assembly
NOTICE
The drain line materials must be an
approved material by the authority having jurisdiction. In absence of such
authority, PVC and CPVC piping must
comply with ASTM D1785 or D2845.
The cement and primer used on the piping must comply with ASME D2564 or
F493. For installations in Canada, use
ULC certified PVC or CPVC pipe, fittings and cement/primer.
4. Continue the tubing from the trap assembly
to a floor drain or condensate pump.
NOTICE
When selecting and installing a condensate pump, ensure the pump is approved
for use with condensing appliances. The
pump should be equipped with an overflow switch to prevent property damage
from potential condensate spillage.
1. Locate the condensate trap assembly and
cut top with hacksaw or knife and install as
shown in Fig. 13 page 29.
NOTICE
The installer must fill the condensate
trap with water prior to assembling on
the appliance.
2. Remove front door and install trap. Ensure
the trap is completely seated and secure on
the appliance.
3. Connect 13/16” OD tubing to the drain
barb of the trap assembly.
5. The CHALLENGER will typically produce
a condensate that is considered slightly
acidic with a pH content below 4.0. Install
a neutralizing filter if required by authority
having jurisdiction.
CAUTION
The condensate drain must remain filled
and unobstructed and allow unrestricted
flow of condensate. The condensate
should not be subject to conditions
where freezing could occur. If the condensate is subjected to freezing or
becomes obstructed , it can leak, resulting in potential water damage to the
appliance and surrounding area.
28
Page 35
Installation Vent/Combustion Air & Condensate Drain
Condensate Drain Assembly
* Carefully cut top of condensate drain
assembly with hack saw or knife at
location shown.
*
Fig. 13: Condensate Drain Assembly
29
Page 36
Gas Piping
Position Bracket so
Gas Pipe Hex Rests on Bracket
Tee Fitting (by Others)
Union Fitting (by Others)
Manual Gas
Valve
(Supplied)
Cap Fitting
(by Others)
Sediment Trap
Min. Length of 3” [7.6 cm]
SECTION VII - Gas Piping
Gas Supply Piping Connection
NOTICE
The gas supply piping must be installed
in accordance to all applicable local,
state and national codes and utility
requirements.
1. Install a 1/2” NPT pipe union at the factory
supplied gas nipple, for ease of service.
2. Install the factory supplied manual shutoff
valve in the gas supply piping as shown in
Fig. 14. For installations in Canada the
installer must tag and identify the main
shutoff valve.
3. Install a sediment trap (drip leg) on the gas
supply line prior to connecting to the CHALLENGER gas train as shown in Fig. 14.
-Disconnect the CHALLENGER and its
gas valve from the gas supply piping
during any pressure test greater than
13”w.c. [32 mbar].
WARNING
Do not check for gas leaks with an open
flame. Use a gas detection device or bubble test. Failure to check for gas leaks
can cause severe personal injury, death
or substantial property damage.
7. Use pipe dope compatible with natural and
propane gases. Apply sparingly only to the
male threads of pipe joints so that pipe
dope does not block gas flow.
WARNING
Failure to apply pipe dope as detailed
above can result in severe personal
injury, death or substantial property
damage.
4. Support the gas piping using hangers. Do
not support the piping by the appliance or
its components.
5. Purge all air from the gas supply piping.
6. Before placing the CHALLENGER into
operation, check and test all connections
for leaks.
-Close the manual shutoff valve during
any pressure test with less than 13”w.c.
[32 mbar].
NOTICE
Support gas piping
WARNING
Use a two-wrench method of tightening
gas piping near the appliance and its gas
piping connection. Use one wrench to
prevent the appliance gas line connection from turning and the second to
tighten adjacent piping. Failure to support the appliance gas piping connection
could damage the gas line components.
30
Fig. 14: Recommended Gas Supply Piping
Page 37
Gas Piping
NATURAL GAS
Pipe Sizing - Natural Gas
Refer to Table 1 for schedule 40 metallic pipe
length and diameter requirements for natural
gas, based on rated CHALLENGER input
(divide by 1,000 to obtain cubic feet per hour).
-Table 1 is based on Natural Gas with a specific gravity of 0.60 and a pressure drop
through the gas piping of 0.30”w.c. [0.75
mbar].
- For additional gas piping sizing information, refer to ANSI Z223.1. For Canadian
installations refer to B149.1.
Natural Gas Supply Pressure Requirements
1. Pressure required at the gas valve inlet
supply pressure port:
-Maximum 13”w.c. [32 mbar] at flow or
no flow conditions to the burner.
-Minimum 5”w.c. [13 mbar] during flow
conditions to the burner. Must be verified during start up and with all other
gas appliances operating within the
building.
-Maximum gas inlet pressure must not
be exceeded and minimum gas inlet
pressure is for the purpose of input
adjustment.
2. Install 100% lockup gas pressure regulator
in the gas supply line if inlet pressure can
exceed 13”w.c. [32 mbar] at any time.
Adjust the lockup pressure regulator for
13”w.c. [32 mbar] maximum.
WARNING
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve
is factory-set for the correct outlet pressure. This setting is suitable for natural
gas and propane and requires no field
adjustment. Attempts by the installer to
adjust or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
injury, death or substantial property
damage.
Table 2: Natural Gas Orifice Requirements
CHALLENGER
MODEL
CC850.256” [6.50 mm]650
CC1050.256” [6.50 mm]650
CC1250.285” [7.25 mm]725
Natural
Orifice Size
Orifice
Marking
Length of Pipe in
Feet
SCH 401/2"3/4"1"1-1/4"1-1/2"
1013227852010501600
20921903507301100
3073152285590890
4063130245500760
5056115215440670
754593175360545
1003879150305460
1503164120250380
Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas Per
Table 1: Gas Piping Sizing - Natural Gas
Hour (based on 0.60 specific gravity, 0.30" w.c. pressure drop)
31
Page 38
Gas Piping
Offset Pressure
Cover Screw
T
hrottle Screw
Offset Pressure Port
Gas Supply Inlet
Pressure Port
Flow direction
Gas Orifice
O-Ring Gasket
PROPANE GAS
Pipe Sizing - Propane Gas
Contact the local propane gas supplier for recommended sizing of piping, tanks and 100%
lockup gas regulator.
Propane Gas Supply Pressure Requirements
1. Adjust the propane supply regulator provided by the gas supplier for 13”w.c. [32
mbar] maximum pressure
2. Pressure required at the gas valve inlet supply pressure port:
-Maximum 13”w.c. [32 mbar] at flow or
no flow conditions to the burner
-Minimum 5”w.c. [13 mbar] during flow
conditions to the burner. Must be verified
during start up and with all other gas
appliances operating within the building.
-Maximum gas inlet pressure must not be
excceded and minimum gas inlet pressure
is for the purpose of input adjustment.
Table 3: Propane Gas, Orifice Requirements:
HALLENGER
C
MODEL
CC850.199” [5.05 mm]505
CC1050.199” [5.05 mm]505
CC1250.228” [5.80 mm]580
Propane
Orifice Size
Orifice
Marking
WARNING
DO NOT adjust or attempt to measure gas
valve outlet pressure. The gas valve is factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane and requires no field adjustment.
Attempts by the installer to adjust or measure the gas valve outlet pressure could
result in damage to the valve, causing
potential severe personal injury, death or
substantial property damage.
WARNING
Prior to start up, ensure the appliance is
set to fire propane. Check the rating label
for the type of fuel. Check the gas valve
for propane conversion label. If there is a
conflict or doubt on the burner set up,
remove the gas valve and check for the
propane orifice, see Fig. 15. Failure to
ensure proper burner setup could result in
severe personal injury, death or substantial property damage.
Fig. 15 : Gas Orifice Assembly
32
Page 39
Internal Wiring
SECTION VIII - Internal Wiring
WARNING
ELECTRICAL SHOCK HAZARD. For
your safety, disconnect electrical power
supply to the appliance before servicing
or making any electrical connections to
avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or death.
CAUTION
Prior to servicing, label all wires before
disconnecting. Wiring errors can cause
improper and dangerous operation.
Verify proper wiring and operation after
servicing.
General Requirements
-Wiring must be N.E.C Class 1.
-If original wiring as supplied with the
appliance must be replaced, use only Type
T 194F [90ºC] wire or equivalent as a minimum.
-The CHALLENGER must be electrically
grounded as required by National
Electrical Code ANSI/NFPA 70 - latest edition and / or the Canadian Electrical Code
Part 1, CSA C22.1, Electrical Code.
33
Page 40
Internal Wiring
Ladder Diagram
Schematic Diagram
Fig. 16: CHALLENGER Factory Wiring Diagrams
34
Page 41
External Wiring
SECTION IX- External Wiring
Installation Compliance
All field wiring made during installation must
comply with:
-National Electrical Code NFPA 70 and
any other national, state, provincial or
local codes or requirements.
-In Canada, CSA C22.1 Canadian
Electrical Code Part 1, and any other
local codes.
WARNING
ELECTRICAL SHOCK HAZARD.
Before making any electrical connections to the CHALLENGER, disconnect
electrical power supply at the service
panel. Failure to comply can cause
severe personal injury or death.
Control Module Circulator AMP Ratings
- AMP draw of the CH circulator must not
exceed 2.3 amps.
WARNING
The ON/OFF switch of the CHALLENGER only disables the function of
the appliance. Electrical power remains
at the control module. To avoid a shock
hazard, disconnect power at the external
service switch when servicing the appliance.
Line Voltage Connections
1. Connect a 120 VAC/15A service to the
120V terminals L, N and G inside the
CHALLENGER as shown in Fig. 16,
page 34.
2. Route the incoming 120 VAC power wire
through the provided openings in the bottom right side jacket panel.
3. The appliance must be provided with an
external service switch, check local code
requirements for compliance.
NOTICE
The installer must provide and install a
fused disconnect or 15 amp (minimum)
service switch. Check local electrical
code requirements for compliance.
35
Page 42
External Wiring
Fuse
Control/Display
Temperature control Connector X4 Notes
Room thermostat 7 – 8 Voltage free
Outside temperature sensor 9 – 10 -
Low Voltage Connections
1. Open the display cover and unscrew both
screw to remove the front cover
2. Pull the control/display forward until it tips
downward to provide access.
3. Ensure field installed low voltage wiring is
not run parallel or next to telephone or
power cable.
4. Consult Table 4 for making low voltage
connections.
Table 4: Low Voltage Electrical
Thermostat Wiring
NOTICE
Isolate 120V wiring from 24V wiring to
prevent any potential electrical “noise”.
1. Connect room thermostat or the end switch
(isolated contact only) to the 24V terminal
strip on the swing out control panel, as
shown in Fig. 16, page 34 and Fig. 17.
2. For proper operation install the room thermostat on an inside wall away from influences of heat and cold, i.e. water pipes,
areas of draft, lighting fixtures and fireplaces.
3. Set the thermostat anticipator (if applicable) as follows:
-Set for 0.1 amps when wired directly to
the CHALLENGER.
-Set to match the total electrical power
requirements of the connected devices
when wired to zone relays or other
devices. Refer to the relay manufacturers’ specifications and the thermostat
instructions for additional information
on the anticipator setting.
Fig. 17: Accessing Low Voltage X4 Connections
When making low voltage connections to
the CHALLENGER, ensure no external
voltage is present in the thermostat circuits. If external voltage is present, provide an isolated contact to prevent damage to the appliance control.
36
Page 43
External Wiring
24 V
Transformer
by Others
Honeywell V8043
Zone Valves
or Equivalent
Honeywell R8285B1038
Transformer / Relay
or Equivalent
24V Terminal Strip
System Circulator
24V Low Voltage Wiring
120V High Voltage Wiring
Room Thermostats
H
N
120V
R
C
G
1
3
4
6
7
8
To Challenger
CH Circulator
1. Connect the CH primary circulator to the
CHALLENGER 120 V terminals 1,2 and 3
located inside the appliance as shown in
Fig. 16, page 34.
2. Maximum CH circulator continuous current draw is 2.3 A.
System Circulator - Zone Valve Application
To energize the system circulator shown as
item 12 in Fig. 8 page 20 reference Fig. 18.
Installer to provide a Transformer / Relay such
as Honeywell R8285 or equivalent and Zone
Valves with isolated end switch such as
Honeywell V8043 or equivalent.
Outdoor Reset Control
The CHALLENGER may operate with a variable appliance operating temperature using the
Triangle Tube outdoor sensor, see pages 55
through 57 for installation and set-up.
NOTICE
If the installer opts for a fixed operating
temperature for the boiler system, the
outdoor sensor is not required and
should not be installed.
Fig. 18: Secondary System Circulator Wiring
37
Page 44
External Wiring
H
N
High Voltage
120
V.A.C.
2
4
V
.A.C.
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
To Challenger
24V Terminal Strip
Transformer
(Power)
Zone
Valve
Zone Valve
7
8
To Challenger
24V Terminal Strip
H
N
High Voltage
120
V.A.C.
24
V.A.C.
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
Transformer
(Power)
Zone
Valve
Zone Valve
* Isolation relay
7
8
*Use isolation relay on
3-wire zone valve with
non-isolated end switch.
Control can burn out if
isolation relay is not used.
NOTICE:
4 Wire Zone Valve
3 Wire Zone Valve
Fig. 19: Multiple Zone Field Wiring Using Zone Valves
38
Page 45
External Wiring
T
T
To Challenger
24V Terminal Strip
C
irculator
Z
one 1
Thermostat
zone 1
H
oneywell
R
845A
R
elay
1
20
H
VAC
N
Circulator
Zone 2
Thermostat
zone 2
Additional zones may be
added as shown above
7
8
6
2
1
4
3
5
6
2
1
4
3
5
T
T
TT
Thermostat
Zone 1
Zone 1
Circulator
120 VAC
N
To Challenger
24V Terminal Strip
Zone 2
Circulator
Zone 3
Circulator
Thermostat
Zone 2
Thermostat
Zone 3
R
C
T1 T1 T2 T2 T3 T3
C3
C3
C2 C2 C1 C1 PR PR
X2 X1 L1 L2 ZC
H
7
8
Fig. 20: Field Wiring with Zone Circulators
Fig. 21: Typical Zone Relay Panel Wiring
39
Page 46
Start-Up Preparation
SECTION X - Start-Up Preparation
Check Boiler System Water Chemistry
WARNING
Do not use petroleum-base cleaning or
sealing compounds in the boiler system.
Damage to seals and gaskets in the system components could occur, resulting
in substantial property damage.
NOTICE
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
Water pH Level 6.5 to 8.5
Flush Boiler and Domestic System to
Remove Sediment
The installer must flush the boiler system to
remove any sediment to allow proper operation
of the CHALLENGER .
Flush the systems until the water runs clean
and is free of sediment.
For zoned systems, each zone should be flushed
through a purge valve. Purge valves and isolation valves should be installed on each zone to
allow proper flushing of the system.
Check and Test Antifreeze
For boiler systems containing antifreeze solutions, follow the antifreeze manufacturer’s
instructions in verifying the inhibitor level and
to ensure the fluid characteristics are within
specification requirements.
Maintain the boiler water pH between 6.5 and
8.5. Check using litmus paper or contact a
water treatment company for a chemical analysis.
If the pH does not meet this requirement, do
not operate the CHALLENGER or leave the
appliance filled until the condition is corrected.
Water Total Hardness Less Than 7
Grains/Gallon
For areas with unusually hard water (total
hardness above 7 grains/gallon or 120ppm or
mg/l) consult a water treatment company.
Chlorinated Water
Do not use the CHALLENGER to heat a
swimming pool or spa directly.
Maintain the chlorine level of the water at levels considered safe for drinking.
Due to the degradation of inhibitors over time,
antifreeze fluids must be periodically replaced.
Refer to the manufacturer of the antifreeze for
additional instructions.
NOTICE
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
40
Page 47
Start-Up Preparation
Use of Antifreeze in the Boiler System
WARNING
NEVER use automotive or ethylene glycol antifreeze or undiluted antifreeze in
the boiler system as freeze protection.
This can cause severe personal injury,
death or substantial property damage if
ignored.
Determine the antifreeze fluid quantity using
the system water content volume and following
the antifreeze manufacturer instructions.
The boiler water volume of the CHALLENGER
CC 85 is 0.37 gallons [1.4 l], CC 105 is 0.42 gallons [1.6 l] and CC 125 is 0.50 gallons [1.9 l].
Remember to include this volume in sizing of the
expansion tank.
Check with local codes requirements for the
installation of backflow preventers or actual
disconnection from the boiler’s cold water fill
or make up water supply line.
Filling the Boiler System
1. Close the boiler drain valve located on the
bottom of the appliance and any manual or
automatic air vent in the system.
2. Open all system isolation valves.
3. Fill the boiler system to correct system
pressure. Correct pressure will vary with
each application.
NOTICE
Typical residential system fill pressure is
12 psi [0.8 bar]. System pressure will
increase when system temperature
increases. Operating pressure of the system should never exceed 25 psi [1.7 bar].
4. Purge air and sediment in each zone of the
appliance system through the purge valve.
Open air vents to allow air to be purged in
the zones.
5. Once the system is completely filled and
purged of all air and sediment, check the
system pressure and check/repair any leaks.
NOTICE
Massachusetts Code requires the installation of a backflow preventer if antifreeze
is used.
Ensure the concentration of antifreeze to water
does not exceed a 50/50 ratio.
NOTICE
System water, including additives, must
be practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
WARNING
Unrepaired system leaks will cause continual makeup water to be added to the
appliance. Continual makeup water
could cause mineral buildup within the
heat exchanger, reducing the heat transfer, causing possible heat buildup and
eventual heat exchanger failure.
Check Low Water-Cut-Off Device
-The CHALLENGER is provided with a
factory installed LWCO device that measures boiler CH system pressure of more
than 7 psig [0.5 bar].
-Compare CH system pressure gauge reading to Challenger’s control pressure reading, which can only be viewed when no CH
or DHW call is present, adjust pressure
accordingly.
41
Page 48
Start-Up Preparation
Check For Gas Leaks
WARNING
Prior to start-up and during initial operation, smell near the floor and around the
appliance for gas odorant or any unusual
odor. Do not proceed with the start-up if
there is any indication of a gas leak. Any
leaks found must be repaired immediately.
WARNING
Propane installations only - The propane
supplier mixes an odorant with the
propane to make its presence detectable.
In some cases the odorant can fade and
the gas may no longer have an odor.
Prior to start-up of the appliance and
periodically after start-up have the
propane supplier check and verify the
odorant level.
NOTICE
In systems using 3-wire zone valves,
backfeed of voltage to the appliance is a
common problem. Use an isolation relay
to prevent voltage from the external circuit entering the CHALLENGER control panel.
-Reconnect the external thermostat
wires to the control terminal strip.
Inspection of Condensate Drain Assembly
1. Inspect and ensure the Condensate Drain
Assembly is properly installed as described
on page 28 and shown in Fig. 13 on page
29.
2. Remove the Condensate Drain Assembly
and fill with fresh water.
NOTICE
Check Thermostat Circuit
-Disconnect the external thermostat wires
from the control terminal strip, located on
the swing out panel.
-Connect a voltmeter across the wire ends
of the external thermostat wiring.
-Close each thermostat, zone valve and
relay in the external circuit one zone at a
time and check the voltage reading across
the wire ends.
-There should NEVER be voltage measured at the wire ends.
-If voltage is measured at the panel under any
condition, check and correct the external
wiring.
The condensate drain assembly must be
installed on the appliance and filled with
water when the CHALLENGER is in
operation. The condensate drain assembly prevents flue gas emissions from
entering the condensate line. Failure to
ensure trap is filled with water could
result in severe personal injury or death.
3. Re-Install the condensate drain assembly.
42
Page 49
Start-Up Procedures
SECTION XI - Start-Up Procedures
Final Checks Before Start-Up
c Read page 46 through 57 regarding the
operation of the CHALLENGER control.
c Verify the CHALLENGER and the boiler
system are full of water and all system
components are correctly set for operation,
including the minimum flow rate through
the boiler, see pages 80-82.
c Verify Start-up Preparation items outlined on
pages 40 thru 42 have been completed.
c Verify all electrical connections are correct
and securely fastened.
c Inspect vent and combustion air piping for
signs of deterioration from corrosion, physical
damage or sagging. Verify combustion air
and vent piping are intact and correctly
installed and supported. Reference the
CHALLENGER vent supplement.
c Verify burner configuration - gas orifice
size.
- Check for proper labeling on the gas
valve (propane only) and the rating label
for proper gas configuration.
- If there is doubt on the burner configuration, remove the gas valve and check for
proper gas orifice size. See pages 31 and
32 for orifice sizes.
c Ensure the vent Condensate Drain
Assembly is filled with water.
CHALLENGER Start-Up
1. Press the ON-OFF button “” located on
the front control panel to the OFF position.
Turn ON the electrical supply/service to the
appliance.
2. Read and follow the Operating Instructions
outlined on page 45.
If CHALLENGER Does Not Start Correctly
1. Verify DHW and CH systems are turned
ON (parameter 1) is set to “0”. Read setting the appliance parameters Section of
the manual starting on page 52 for more
information.
2. Check for loose electrical connections,
blown fuse (external or internal at the
appliance control) or open service switch.
3. Is the external limit control (if applicable)
open? Ensure the external limit is reset to
the closed position.
4. Is the gas supply valve(s) open at the appliance and meter?
5. Is incoming gas supply pressure at the
appliance more than 5”w.c. [13 mbar] and
less than 13” w.c. [32 mbar] for natural or
propane with all gas appliances ON or
OFF.
6. Are the heating thermostats set above room
temperature?
If none of these conditions correct the problem,
contact Triangle Tube Tech Service.
Check the CHALLENGER and System
c Check Piping.
Check piping and components for
leaks. If found, shut down the appliance and repair immediately.
Purge any remaining air from the system
piping. Air in the system piping will
interfere with circulation creating heat
distribution problems and system noise.
c Check Vent Piping and Combustion Air
Piping.
Check for gas-tight seal at every connection and seam of the venting and
combustion air piping.
WARNING
Venting system must be sealed gas-tight
to prevent flue gas spillage and potential
carbon monoxide emissions, which will
result in severe personal injury or death.
43
Page 50
Start-Up Procedures
cCheck Gas Piping
Check around the appliance for gas
odor following the procedure outlined
in this manual on Page 42.
WARNING
If any gas leaks are found or suspected,
shut the appliance down immediately.
Use a gas detection device or bubble test
to locate the source of the gas leak and
repair at once. Do not operate the appliance until the leak is corrected. Failure
to comply with this procedure could
result in severe personal injury, death or
substantial property damage.
c Verify Flame Pattern and Combustion
Check the flame pattern through the
inspection port on the left side of the
heat exchanger. The flame should be
blue and stable and should be the length
of the burner.
the combustion levels are not within the
range given in Table 5 for the firing rate,
shut the appliance down and contact
Triangle Tube Engineering Department.
Failure to comply with this requirement
could result in severe personal injury,
death or substantial property damage.
Table 5: Recommended Combustion Levels
Natural GasPropane Gas
CO2 at High
Fire (H)
(and + 2x)
Door Off
CO2 at Low
Fire (L)
(and -)
Door Off
CO Max.100 ppm100 ppm
9% to 9.8%10.5% to 11%
0 to 0.3 lower
than high fire
9.0 % minimum
0 to 0.3 lower
than high fire
10.5 % minimum
WARNING
The combustion testing and adjustments
must be performed by a qualified
installer, service agency or the gas supplier. All combustion measurements must be
performed with calibrated equipment to
ensure proper reading and accuracy.
Test for CO2 and for CO during high and
low firing rate. To manually place the
appliance into high or low fire mode, reference page 50. The combustion reading
should be within the range listed in Table
5. The CO level should not exceed 100
ppm when combustion is correct.
WARNING
The combustion levels should be measured at high and low firing rate, refer to
page 50 of the CHALLENGER control
section on how to set the firing rate. If
Offset Pressure
Low Fire (L)
( and -)
Door Off
cMeasure Input - Natural Gas Only
-0.023” WC
[-5.7 PA]
-0.023” WC
[-5.7 PA]
1. Ensure the appliance is firing at maximum
firing rate. To manually place the appliance
into high fire mode, reference page 50.
2. Operate the appliance for approximately
10 minutes.
3. Turn off all gas appliances within the building, except the CHALLENGER.
4. At the gas meter, record the time required
to use one cubic foot of gas.
5. Calculate Natural gas input using the following equation:
3600 x 1000 / number of second recorded
for one cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate
the input rating listed on the appliance.
44
Page 51
Start-Up Procedures
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which automatically lights the burner. DO NOT try to light the
burner by hand.
B.BEFORE OPERATING, smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air and
will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use
any phone in your building
•Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
OPERATING INSTRUCTIONS
1.STOP! Read the safety information above. This
appliance is equipped with an ignition device
which automatically lights the burner. DO NOT
try to light the burner by hand.
2.Set room thermostat(s) to lowest setting. Turn
the external manual gas valve handle clockwise
“CLOSE” (valve handle shall be per-
pendicular to gas piping).
3.Turn “OFF” all electrical power to the appliance.
4.Remove the front jacket panel on the appliance.
5.Turn the external manual gas valve handle
counter clockwise to “OPEN” gas supply (valve handle shall be parallel to gas piping).
6.Wait five (5) minutes to clear out any gas. If you
then smell gas in the jacket enclosure or around
the appliance, STOP! Follow “B” in the safety
information above. If you don’t smell gas, go to
the next step.
• If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to turn the external manual gas
valve. Never use tools. If the valve will not turn
by hand, don’t try to repair it; call a qualified service technician. Force or attempted repair may
result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under water.
7.Turn “ON” all electric power to the appliance. Push
ON/OFF button on the CHALLENGER control
panel display until LED above button is lit.
8.Set room thermostat(s) to desired setting(s).
9.The CHALLENGER control panel display will
show a sequence of numbers (1,2,3,4) as the right
digit. Sequence digit 3 or 4 indicates the appliance
is firing. A blank display means there is no call for
heat (all external thermostats are satisfied).
10. If the appliance will not operate with a call for heat
and the system piping is not hot, follow the instructions “To Turn Off Gas to Appliance”, below and
call your service technician or gas supplier.
11. Replace the front jacket panel. Make sure the panel is
seated firmly in place and all mounting screws are
tightened.
TO TURN OFF GAS TO APPLIANCE
1.Set the room thermostat to lowest setting.
2.Turn“OFF” all electric power to the appliance if
service is to be performed.
3. Turn the external manual gas valve handle clockwise to “CLOSE”, (valve handle shall be
perpendicular to gas piping).
45
Page 52
Start-Up Procedures
Appliance ON/OFF
1. The appliance operation is started using the
ON/OFF button.
2. When appliance is in operation, the green
LED above theON/OFF will be lit.
3. When the appliance is not in operation, the
green LED above the ON/OFF will not
be lit. The main display will show “OFF”
and the operating display will show .
Set Boiler CH Set Point Temperature
1. Press the CH/DHW/Parameter button “ ”
at the display panel for approximately 2 to
3 seconds until the radiator “” (CH)
LED, lights up and the main display begins
to flash.
2. Press the or buttons to set the desired
temperature setting on the main display.
3. Press the reset button to close the set-
ting menu and store the changes.
NOTICE
If the reset button is not pressed within 30 seconds, the settings menu is automatically closed and the changes are
stored.
If the ON/OFF button is pressed prior
to the resest button, the settings menu
is closed and the changes are NOT
stored.
3. The following displays should occur:
A] Self check on power up
[
[ ] No call for heat
4. Initiate a call for heat by raising the set
point of the room thermostat to the highest
setting. The following operating display
should occur
1] This is the prepurge cycle. The burner
[
blower and the CH (Central Heating) circulator become energized. The blower has a
10 seconds prepurge cycle.
2] This is the ignition cycle. The control
[
module will energize and open the gas
valve and begin the spark for ignition.
-If the burner flame proves, the burner
will begin to modulate.
-If the burner flame is not proven the
control module will repeat the ignition
sequence after approximately 15 seconds . If the flame is not proven after
four attempts the control will lockout
and the main display will show [
the fault LED above the reset button will flash and [E] will flash in the
operating display.
-To verify flame failure lockout, close
the manual shut off valve on the gas
supply piping to the appliance and
repeat ignition sequence. When verification is completed, ensure the manual
shut off valve is returned to the open
position.
4]and
Operation Verification - Space Heating
NOTICE
Digit and characters shown as [0], in the
following outline, represent the control
module operating display.
1. Set the room thermostat to the lowest setting.
2. Turn off power to the appliance, wait a few
seconds and turn on power to the appliance.
3] This is the normal CH operation cycle.
[
The control module will begin to modulate the burner firing rate based on actual
appliance outlet temperature and the set
point temperature. The CH water temperature is displayed on the operating panel.
5. Allow the appliance to operate and allow
the boiler outlet temperature to reach the
set point temperature.
1] The setpoint temperature has been
[
reached. The burner shutdown and post
purge cycle of the burner begins. The con-
46
Page 53
Start-Up Procedures
trol module will close the gas valve and the
blower will continue for 30 seconds for a
post purge cycle before shutting down. The
CH circulator will continue to run until the
room thermostat is satisfied.
6. Lower the room thermostat set point below
the room temperature to end the call for
heat.
1] This begins a post purge cycle. When
[
the room thermostat is satisfied, the appliance will shutdown.
7] The CH circulator will continue to run
[
for a 1 minute post pump cycle.
NOTICE
The CH circulator automatically runs
for 10 seconds once every 24 hours to
prevent seizing. Timing for this automatic switching starts after the last call for
heat.
[] The appliance is in Standby MODE wait-
ing for a call for heat.
7. Verify the operation of the appliance by
repeating the operational sequence several
times.
NOTICE
If the reset button is not pressed within 30 seconds, the settings menu is automatically closed and the changes are
stored.
If the ON/OFF button is pressed prior
to the resest button, the settings menu
is closed and the changes are NOT
Operation Verification - Domestic Hot
Water (if applicable)
NOTICE
Digit and characters shown as [
following outline, represent the control
module operating display.
1. Set the room thermostat to the lowest setting.
2. Turn off power to the appliance, wait a few
seconds and turn on power to the appliance.
3. The following displays should occur:
A] Self check on power up
[
stored.
0], in the
8. Return the room thermostat to a desired setting.
Set DHW Set Point Temperature
1. Press the CH/DHW/parameter button “ ”
at the display panel for approximately 2 to
3 seconds until the faucet “ ” (DHW)
LED lights up and the main display begins
to flash.
2. Press the or buttons to set the desired
temperature on the main display. Minimum
setting is 104ºF [40ºC], Maximum setting
is 149ºF [65ºC], factory default is 120ºF
[49ºC].
3. Press the reset button to close the setting menu and store the changes.
[ ] No call for heat
4. Turn on a domestic hot water faucet to initiate a domestic call. The display should show
1] This is the prepurge cycle. The burner
[
blower become energized. The blower has
a 10 seconds prepurge cycle. The CH (central heating) circulator will remain off, to
provide DHW priority.
2] This is the ignition cycle. The control
[
module will energize and open the gas
valve and begin the spark for ignition.
-If the burner flame proves, the burner
will begin to modulate.
47
Page 54
Start-Up Procedures
-If the burner flame is not proven the
control module will repeat the ignition
sequence after approximately 15 seconds . If the flame is not proven after
four attempts the control will lockout
and the main display will show [
the fault LED above the reset button will flash and [E] will flash in the
operating display.
-To verify flame failure lockout, close
the manual shut off valve on the gas
supply piping to the appliance and
repeat ignition sequence. When verification is completed, ensure the manual
shut off valve is returned to the open
position.
4]and
4] This is the normal DHW operation
[
cycle. The control module will begin to
modulate the burner firing rate based on
actual DHW set point temperature. The
DHW water temperature is displayed in
the main display.
5. Turn off the domestic hot water faucet to
end the call for heat.
1] This begins a post purge cycle. The
[
control module closes the gas valve and the
blower continues for approximately 10 seconds post purge.
6. Verify the DHW operation by repeating the
outlined operation sequence several times.
48
Page 55
Start-Up Procedures
1. On/Off (Lit when on)
2. CH operation or setting maximum CH temperature
3. DHW operation or setting DHW temperature
4. Main display with temperature of CH or DHW or
CH water pressure or fault code
5. Temperature ºF or pressure psi
6. Temperature ºC or pressure bar
7. DHW function eco (learned)
8. DHW function on (minimum block temp)
9. Operating display
10. Flashes to indicate fault
A. On/Off button
B. CH /DHW/parameter button
C. - button
D. + button
E. Units U.S. customary or metric
F. DHW function off/eco/on
G. Service button
H. Reset/store button
Read-Out
Operation
Control Dispaly
Appliance ON/OFF
1. The appliance operation is started using the
ON/OFF button.
2. When appliance is in operation, the green
LED above theON/OFF will be lit.
3. When the appliance is not in operation, the
green LED above the ON/OFF will not
be lit. The main display will show “OFF”
and the operating display will show .
Units
Press Up or Down arrow button to change the
displayed units from U.S. Customary (ºF or psi)
to metric (ºC or bar). The ºF/psi LED will be lit
for U.S. Customary units or ºC/bar LED will be
lit for metric units.
NOTICE
Units cannot be changed if the main display (Parameter Mode) or operating display (Error Mode) is flashing.
Additional DHW Functions
Additonal DHW setting can be activated by
pressing the DHW button.
-ON (LED lit above the DHW
-ECO (LED lit above the DHW
-OFF (no LED lit) - The appliance will not
BEST PRACTICE
In application in which the DHW is not
utilized or the DHW demand is minimal,
set the DHW function to OFF.
49
button) - The appliance DHW function
is activated continuously. The appliance
will maintain a minimum heat exchanger temperature to assure instant delivery
of hot water.
button) - The DHW function is selflearning. The appliance will not maintain a minimum heat exchanger temperature during the night or extended
absences without DHW demands.
maintain a minimum heat exchanger temperature. This will affect the delivery and performance of the initial DHW temperature.
Page 56
Start-Up Procedures
TO TEMPORARILY PLACE THE BURNER INTO HIGH FIRE TEST MODE: press
and hold both the “
” and “+” button simul-
taneously once until operating display shows
“h” for CH high fire or twice until the operating display shows “H” for DHW high fire.
While in the test mode:
-high limit will function
-appliance CH circulator will function
-the test mode will time out in approximately 10 minutes
TO TEMPORARILY PLACE THE BURNER INTO LOW FIRE TEST MODE: press
and hold both the “
” and “” button simul-
taneously until operating display shows “L”.
TO DEACTIVATE THE HIGH OR LOW
FIRE TEST MODE: press and hold both the
“+” and “-” button simultaneously.
50
Page 57
Start-Up Procedures
Function
Main Display
Operating Display
OFF
XXP
XXP
XXX
7
Press
No demand for heat
Control self-test
Fan pre purge or post purge cycle
Space Heating (CH) post pump cycle
XXX
XXX
6
A
1
Ignition sequence
XXX
2
Burner ON for space heating (CH)
XXX
3
Burner ON for domestic hot water (DHW)
4
Burner ON for DHW pre-heating or freeze
protection
The
LED will be lit for CH (central heating call)
8
Burner OFF due to reaching temperature
setpoint
button to turn appliance ON
LED lite abovebutton will be lit
The
LED will be lit for DHW (domestic call)
“X” represents temperature or pressure readings when temperature is displayed
it will be followed by “ºF” or “ºC” in the main display. When pressure is displayed
it will be followed by a “P” in the main display. Pressure can only be read when the
operating display is blank or shows a “A”.
NOTICE
when appliance is ON
51
Page 58
Start-Up Procedures
Adjustments
Description
Parameters
Factory Settings
(Flashing)
LED
(Flashing)
Installation type
0
186ºF [86Cº]
120ºF [49Cº]
0=Combi (Heat and DHW)
2=DHW only (no heating system required)
3=Heating only
CH pump continuous
0
0=Intermittent pump on for heat and post purge
1=pump continuously active except during DHW call
Min. supply temperature of the heat curve
86ºF [30Cº]
Adjustment range 59°F to 140°F [16ºC to 60ºC]
Min. outside temperature of the heat curve
0ºF [-18Cº]
Adjustment range -22°F to 50°F [-30ºC to 10ºC]
Max. outside temperature of the heat curve
64 ºF [18Cº]
Adjustment range 59°F to 77°F [16ºC to 26ºC]
CH pump post purge period
1
Adjustment range 0 to 15 minutes
Waiting time after a DHW demand before a
CH demand is answered *
0
Adjustment range 0 to 15 minutes
Anti-cycling period during CH operation**
** The anti-cycling time starts when burner shuts down during a CH call due to boiler water reaching the boiler set point temperature. The CH circulator
will continue to operate while the burner is blocked.
* The wainting time starts at the end of the DHW call (no DHW flow - DHW flow switch contacts are open) and blocks the burner and CH circulator. if
DHW function is turned ON ( LED is lit above the DHW button) or ECO is ON ( LED is lit above DHW button) than the burner will continue to
fire for DHW until a minimum heat exchanger temperature is achieved. Burner and CH circulator will continue to be blocked until the remaining waiting
time ends.
0
Minimal switch-off time in CH operation
Adjustable from 0 to 15 minutes
1
2
5
6
7
8
o
P
Main Display
Operating
Display
Boiler set point temperature
DHW (domestic) setpoint temperature
Adjustment range 86ºF to 194ºF [30ºC to 90ºC]
Adjustment range 104ºF to 149ºF [40ºC to 65ºC]
Setting the Appliance Parameters
1. Press the “”button at the display panel
for approximately 2 to 3 seconds until main
display begins to flash.
2. Press the “”button repeatedly to scroll
through the list of parameters. The operating
display will show the parameter number
and main display will show the parameter
setting.
3. To modifiy a parameter press the or
buttons.
4. Press the button to close the setting
menu and store the changes.
NOTICE
If the reset button is not pressed within 30 seconds, the settings menu is automatically closed and the changes are
stored.
If the ON/OFF button is pressed prior
to the resest button, the settings menu
is closed and the changes are NOT
stored.
52
Page 59
Start-Up Procedures
Error (Hard Lockout) Mode
If a system fault occurs, the system enters a
hard lockout condition which requires a manual reset by pressing the RESET button . A
hard lock is indicated by a flashing [E] on the
operating display as well as a flashing LED
light above the reset button. The error code
is located on the main display. The error must
be corrected before the control will reset.
CAUTION
The appliance freeze protection feature
is disabled during a Hard Lockout, however the CH circulator will operate.
CAUTION
Table 6: 12 K Ohm NTC Sensor Resistance
During a hard lockout or low water condition the appliance will not re-start
without service. If the heating system is
left unattended in cold weather appropriate safeguards or alarms should be
installed to prevent property damage.
53
Page 60
Start-Up Procedures
1
0, 11, 12,
1, 28
4
0
2
29,30
5
6
8
1
3, 14
Sensor fault S1
-
CH Supply
• Check wiring for break
•
Check for proper flow direction
• Replace S1
• E10 open sensor
• E 11 Short sensor
•
Replace S2
•
E 20 open sensor
•
E 21 short sensor
2
0, 21, 22,
2
3, 24
-
CH Return
Sensor fault S2
• Check wiring for break
•
Check for proper flow direction
- Sensor fault after self check
• Replace S1 and/or S2
- Temperature too high
•
Air in installation
• Pump not running
• Insufficient flow in installation, shut off valves closed, pump setting too low
• Flow switch sticking or miss-installed
- S1 and S2 interchanged
• Check water flow
• Check wiring
• Replace S1 or S2
- No flame signal
• Manual Gas shut off valve closed
• No or incorrect ignition gap
• Gas supply pressure too low of failling
• Gas valve or ignition unit not powered
- Poor flame signal
• Condensate drain blocked
• Check adjustment of gas valve
- Flame detection fault
• Replace ignition cable + spark plug cap
• Replace ignition unit at gas valve
• Replace boiler controller
- Incorrect fan speed
• Fan catching on casing
• Wiring between fan and casing
• Check wiring for poor wire contact
• Replace fan
- Gas valve relay faulty
• Replace boiler controller
LOP
- Low CH system pressure
• Raise CH pressure above 7 psi [ 0.5 bar]
LED above
button will flash, correct condition, and press button.
O
perating
D
isplay
(
Flashing)
Main Display
Possible Solution
E
rror Description
E
3, 18, 19
Fault
- Flue sensor
• E18 open sensor
• E19 Short sensor
• Check/Replace sensor
• E19 Excessive Temperature
• Clean heat exchanger
E
7, 17
Fault
- DHW sensor
• E17 open sensor
• Check/replace sensor
• E7 Excessive temperature
• Check gas orifice
• Check combustion settings
E
50F
- Improper frequency
• Verify ground
• Frequency should be between 45 and 65 Hz
E
E
E
E
E
E
E
E
E
Error (Hard Lockout) Codes
54
Page 61
Outdoor Resest Control
S
ensor Enclosure
P
lastic Anchors (2)
Seal Gasket
Front Cover
Mounting
S
crews
(2)
SECTION XII - Outdoor Reset Control
The appliance setpoint for a heating call can be
fixed or vary with the outdoor temperature. If
the application requires a constant supply temperature from the boiler, the outdoor temperature
sensor should not be connected to the appliance.
If an outdoor temperature sensor is connected to
the appliance, the outdoor reset function is automatically enabled and will vary the CH setpoint
with the change in outdoor temperature. The
outdoor reset function has no affect on the DHW
setpoint during a domestic call.
4. Mount the sensor enclosure at an elevation
on the exterior wall to prevent accidental
damage or tampering.
5. Avoid mounting the enclosure in areas subjected to excessive moisture.
6. Once an area on the exterior wall has been
determined, to affix the enclosure use the
enclosure as a template to mark the location
of the mounting screws.
7. Using a 3/16” [5 mm] drill bit, drill 2 pilot
holes on the marked locations.
8. Tap the enclosed plastic anchors into the
pilot holes. Use care not to damage the
anchors.
9. Mount the sensor enclosure using the
screws provided.
Wiring the Sensor
1. Remove the sealing nut and sealing gasket
from the sensor enclosure.
Fig. 22: Sensor Enclosure and Components
Mounting the Outdoor Sensor
1. Remove the front cover and mounting
screws / anchors from the sensor enclosure.
2. When mounting the enclosure the exterior
wall selected should represent the heat load
of the building. Typically a northern or
northeastern wall will suit most buildings.
A southern facing wall may suit buildings
that have large glass walls or windows on
the southern face.
3. Ensure the sensor enclosure is shielded
from direct sunlight or the effects of heat or
cold from other sources (exhaust fans,
appliance vents...) to prevent false temperature sensing.
2. Route two 18 gauge wires through the sealing nut and gasket. Connect the wires to
the sensor terminals 1 and 2.
3. Re-insert the sealing gasket and tighten the
sealing nut to the sensor enclosure.
4. Route the sensor wire back to the CHALLENGER, ensuring the wires are not run
parallel to telephone or power cables.
NOTICE
If the sensor wires are located in an area
with sources of potential electromagnetic
interference (close to 120 V wiring) the
sensor wires should be shielded or the
wires should be routed in a grounded
metal conduit. If using shielded cable,
the shielding should be connected to the
common ground of the appliance.
5. Connect the sensor wires to the outdoor sensor terminals 9 and 10 on the low voltage X4
connector terminal strip located at the control on the swing out panel (see appliance
wiring diagram, Fig. 16 page 34).
55
Page 62
Outdoor Resest Control
Adjusting Outdoor Reset Curve
The appliance CH set point along with
Parameters 5, 6 & 7 define the settings of the
outdoor reset curve. See Graph 1 and Table 7,
page 57 for an example of modifying the outdoor reset curve.
Boiler CH (Maximum Boiler Operating
Temeprature)
Factory Setting
186ºF
[86ºC]
Minimum
Setting
86ºF
[30ºC]
Maximum
Setting
194ºF
[90ºC]
If an outdoor temperature sensor is not connected to the appliance, the appliance setpoint
for a heating call will be set to the CH Setpoint.
If an outdoor temperature sensor is connected,
the CH Maximum Boiler Operating Setpoint
becomes the appliance setpoint on the CH
Reset Curve Coldest Day.
This parameter is not applicable if an outdoor
sensor is not connected to the appliance. When
an outdoor temperature sensor is connected,
the CH Minimum Boiler Operating Setpoint
becomes the appliance setpoint on the CH
Reset Curve Warmest Day.
the CH Reset Curve Coldest Day is the coldest
design temperature of the heating system.
CH Reset Curve Warmest Day
(Parameter 7)
Factory Setting
64ºF
[18ºC]
Minimum
Setting
59ºF
[16ºC]
Maximum
Setting
77ºF
[26ºC]
Thisparameterisnotapplicableifanoutdoor
sensor is not connected to the appliance. When
an outdoor temperature sensor is connected,
the CH Reset Curve Warmest Day is the
warmest design temperature of the heating system.
Changing Outdoor Reset Parameters
1. Press the “”button at the display panel
for approximately 2 to 3 seconds until main
display begins to flash.
2. Press the “”button repeatedly to scroll
through the list of parameters. The operating
display will show the parameter number
and main display will show the parameter
setting.
3.Tomodifiyaparameterpresstheor
buttons.
4. Press the button to close the setting
menu and store the changes.
The appliance control module has now been
reprogrammed with the desired parameter values.
CH Reset Curve Coldest Day
(Parameter 6)
Factory Setting
00ºF
[- 18ºC]
Minimum
Setting
-22ºF
[-30ºC]
This parameter is not applicable if an outdoor
sensor is not connected to the appliance. When
an outdoor temperature sensor is connected,
Maximum
Setting
50ºF
[10ºC]
NOTICE
Pressing the ON/OFF button will exit
the parameter setting mode without
storingtheparameterchanges.
56
Page 63
Outdoor Resest Control
90
20
60
80
100
140
70
64
50
30
10 0
-10
77
Boiler Temperature ( F)
Outdoor Air Temperature ( F)
Boiler CH Set Point
Parameter 5
Set Point
Parameter 7 Setting
Parameter 6 Setting
Graph 1: Outdoor Air Temperature Reset Curve (Example)
Table 7: Outdoor Air Temperature Reset (Example)
Outdoor
Temperature
Appliance target Temp.
Based on Outdoor Temp.
10ºF or Lower140ºF
30ºF117ºF
50ºF93ºF
64ºF or Higher77ºF
Graph 1 illustrates Appliance CH Setpoint adjusted to 140ºF target temperature at
10ºF outdoor air temperature
Note: Factory setting of CH set point is 186ºF
57
Page 64
Check-Out Procedures
SECTION XIII- Check-Out Procedures
NOTICE
Perform the following check-out procedures as outlined and check off items as
completed. When procedures are completed, the installer should complete the
installation record on page 59.
Check-Out Procedures
c Boiler system water chemistry checked and
verified as outlined on page 40.
c The appliance air vent and any automatic
air vents caps placed within the system are
open one full turn.
c Air is purged from the heating zones and
appliance system piping.
c Confirm the appliance has proper gas ori-
fice as noted on pages 31 and 32.
c Checked and verified room thermostat(s)
function properly and the thermostat(s)
heat anticipator (if used) was properly set.
c Observed several operating cycles for
proper operation of the CHALLENGER
and the system.
c Set the room thermostat(s) to the desired
room temperature.
c Reviewed all instructions shipped with the
CHALLENGER with the homeowner or
maintenance personnel.
c Completed the Installation Record on page
59.
c Ensure all manuals and other documents
are returned to the Installation envelope
and given to the owner for safekeeping.
c Thermostat circuit wiring checked and ver-
ified that no voltage is present to the low
voltage terminals as outlined on page 42.
c Operating Instructions on page 45 were fol-
lowed during start-up.
c Combustion levels and flame pattern veri-
fied as outlined on page 44.
c Measured the rate of input on Natural Gas
as outlined on page 44.
c Checked the incoming gas pressure to the
CHALLENGER to ensure a minimum
pressure of 5”w.c [13 mbar] during flow
conditions to all gas appliances and a maximum pressure of 13”w.c [32 mbar] during
non-flow conditions for Natural and
Propane.
c Adjusted balancing valves and system limit
controls to provide design temperatures to
the primary space heating system.
c In multiple zone applications, adjusted for
correct flow of appliance water to each
zone.
58
Page 65
CHALLENGER Model Number:
Serial Number:
Date of Installation:
Fuel: Natural Gas Propane
Measured Rate of Input:
Combustion Readings:
CO
2
O2
CO
The following items were completed during installation:
Installation instructions have been followed and completed
Check-out procedures have been followed and completed
Information regarding the unit and installation received and left with owner /
maintenance personnel.
At least on an annual basis the following maintenance should be performed by a qualified service technician:
General
-Attend to any reported problems.
-Inspect the interior of the appliance jacket
area; clean and vacuum if necessary.
-Clean the condensate drain assembly and
fill with fresh water.
-Check for leaks: water, gas, flue and condensate.
-Verify flue vent piping and air inlet piping
are in good condition, sealed tight and
properly supported.
-Check appliance water pressure, piping and
expansion tank.
-Check control settings.
Owner Maintenance
Periodically:
-Check the area around the appliance.
-Check and remove any blockage from the
combustion air inlet and ventilation openings.
-Check the temperature and pressure
gauges.
Monthly:
-Check vent piping.
-Check combustion air inlet piping.
-Check the pressure relief valve.
-Check the condensate drain assembly.
Every 6 months:
-Check appliance piping and gas supply piping
for corrosion or potential signs of leakage.
-Operate the pressure relief valve.
-Check ignition electrode (sand off any
white oxide; clean and reposition).
-Check ignition wiring and ground wiring.
-Check all control wiring and connections.
-Check burner flame pattern (stable and uniform).
Additional items if combustion or performance
is poor:
-Clean heat exchanger and flue ways.
-Remove burner assembly and clean inside
of burner head using compressed air only.
Once the maintenance items are completed,
review the service with the owner.
WARNING
Follow the maintenance procedures
given throughout this manual. Failure
to perform the service and maintenance
or follow the directions in this manual
could result in damage to the CHALLENGER or in system components,
resulting in severe personal injury, death
or substantial property damage.
60
Page 67
Maintenance Procedures
SECTION XVI - Maintenance
Procedures
Maintenance Procedures
WARNING
The CHALLENGER should be inspected and serviced annually, preferably at
the start of the heating season, by a qualified service technician. In addition, the
maintenance and care of the appliance
as outlined on page 60 and further
explained on pages 61 through 67 should
be performed to assure maximum efficiency and reliability of the appliance.
Failure to service and maintain the
CHALLENGER and the system components could result in equipment failure,
causing possible severe personal injury,
death or substantial property damage.
NOTICE
Verify that combustion air inlet area is free of
any contaminates. Refer to the materials listed
on page 7 of this manual. If any of these products are in the area from which the appliance
takes its combustion air, they must be removed
immediately or the combustion air intake must
be relocated to another area.
Inspect Burner Area
Remove the appliance front jacket panel.
Vacuum any dirt or debris from the blower
component.
Re-install front jacket panel when completed.
WARNING
Do not use solvents to clean any of the
components. The components could be
damaged, resulting in unreliable or
unsafe operation.
The following information provides
detailed instruction for completing the
maintenance items outline in the maintenance schedule on page 60. In addition
to this maintenance, the CHALLENGER should be serviced at the
beginning of the heating season by a
qualified service technician.
Reported Problems
Any problems reported by the owner should be
checked, verified and corrected before proceeding with any maintenance procedures.
Check Surrounding Area
Verify that the area surrounding the CHALLENGER is free of combustible / flammable
materials or flammable vapors or liquids.
Remove immediately if found.
Check System Piping
Inspect all piping (water and gas) for leaks and
verify that the piping is leak free and properly
supported.
Inspect the fittings and components on the
appliance and verify they are leak free.
WARNING
Eliminate all boiler leaks. Continual fresh
make-up water will reduce the heat
exchanger life causing appliance failure.
Leaking water may also cause severe
property damage to the surrounding area.
Inspect the gas supply piping using the
procedure outlined on Page 42.
61
Page 68
Maintenance Procedures
Clean Condensate Drain Assembly
1. Remove the condensate assembly from the
appliance.
2. Empty any water from the trap and drain
assembly. Flush with fresh water as necessary to clean.
3. Check the drain piping from the condensate
drain assembly to the drain. Flush to clean
as necessary.
4. Fill the condensate drain assembly with water.
5. Reassemble the condensate drain assembly
onto the appliance.
WARNING
When re-assembling the condensate drain
assembly ensure all gaskets are in place and
correctly installed. Ensure all associated
internal joints are complete, tight and secure.
Failure to comply can result in flue gas leakage resulting in severe personal injury, death
or substantial property damage.
Check Ventilation Air Openings
Verify that all ventilation openings to the
mechanical room or building are open and
unobstructed. Check the operation and wiring
of any automatic ventilation dampers.
Check and verify the vent discharge and the
combustion air intake are free of debris and
obstructions.
Inspect Vent and Combustion Air Piping
Visually inspect the venting system and combustion air piping for blockage, deterioration
or leakage. Repair any deficiencies.
Verify that the combustion air inlet piping is
connected, sealed and properly supported.
WARNING
Failure to inspect the vent system and
combustion air inlet piping and to have
any conditions repaired, can result in
severe personal injury or death.
Check Boiler System
Verify all system components are correctly
installed and operating properly.
Check the cold fill pressure for the system, typical cold water fill pressure is 12 psig [0.8 bar].
Verify the system pressure, as the appliance
operates at high temperature, to ensure the pressure does not exceed 25 psig [1.7 bar].
Excessive pressure reading indicates expansion
tank sizing is incorrect or system performance
problems.
Inspect air vent and air separators in the system. Remove the caps on automatic air vents
and briefly depress the valve stem if present to
flush vent. Replace the cap when completed.
Ensure vents do not leak, replace any leaking
vents.
Removing Internal Flue and Condensate
Pan For Inspection
1. Loosen the flue pipe retaining ring as
shown in Fig. 23, page 63.
2. Pull up on the flue pipe to disengage from
the condensate pan as show in Fig. 24.
3. Pull the flue pipe down and out to disengage
from the vent adapter as shown in Fig. 24,
page 63.
4. Lift up the condensate pan to disengage
from trap.
5. Once the condensate pan is clear of the bottom jacket, rotate it towards the front of the
appliance and push down on the rear to disengage from the heat exchanger as shown
in Fig. 25, page 63.
-Inspect the flue pipe and condensate
pan for cracks, damage or distortion.
Check all gaskets for tears, discoloration or other damage, replace as necessary.
-Once inspection is completed re-assem-
ble the condensate pan and flue pipe in
reverse order.
62
Page 69
Maintenance Procedures
1
2
3
1
2
3
Fig. 23: Loosening of Flue Pipe
Retaining Ring
Fig. 24: Removal of Flue Pipe
Fig. 25: Removal of Condensate Pan
63
Page 70
Maintenance Procedures
WARNING
When re-assembling the condensate pan
and flue pipe ensure all gaskets are in
place and correctly installed. Ensure all
associated joints are complete, tight and
secure. Failure to comply can result in
flue gas leakage resulting in severe personal injury, death or substantial property damage.
Check Expansion Tank
Refer to Section IV - Boiler Piping for recommended location of the expansion tank
and air eliminators.
Closed -Type Tank:
-Ensure tank is partially filled with
water leaving an air gap as a cushion.
Refer to the manufacturer’s instruction
for proper fill level.
-Ensure the tank is fitted with a device
that reduces gravity circulation of airsaturated tank water back into the system. This device prevents air from
bubbling up through the water as it
returns from the system.
-Ensure no automatic air vents are used
in the system. This will allow air to
escape from the system instead of
returning to the tank.
Diaphragm Tank:
-Ensure the system contains a minimum of
one automatic air vent. Recommended
location of the air vent should be atop an
air eliminator.
-Remove the tank from the system and
check the charge pressure. For residential applications the charge pressure is
typically 12 psig [0.8 bar]. If tank does
not hold a charge pressure, then the
membrane is damaged and the tank
should be replaced.
Check Relief Valve(s)
Inspect the relief valve(s) and lift the lever to
verify flow at least annually or as recommended on the warning tag of the valve.
WARNING
Before manually operating the relief
valve(s), ensure the discharge piping is
directed to a suitable place of disposal to
avoid a potential scald hazard. The discharge piping must be full size without
restriction and installed to permit complete drainage of both the valve and line.
If after closing the valve, the valve fails to seat
properly or continually weeps, replace the
relief valve. Ensure the cause of the relief
valve to weep is the valve itself, not due to system over-pressurization caused by an expansion tank that is waterlogged or undersized.
Inspection of Ignition Electrode
Remove the ignition electrode.
Remove any white oxides accumulated on the
electrode using fine grit sandpaper or steel wool.
If the electrode does not clean to a satisfactory
condition, replace the ignitor .
When replacing the ignition electrode, ensure
the gasket is in good condition and correctly
positioned, replace gasket if necessary.
Check igniter to Fig. 26, page 65.
Check Ignition Wiring and Ground Wiring
Inspect the burner wiring from the burner control module to the ground at heat exchanger.
Ensure wiring is in good condition and securely connected.
Check ground continuity of the wiring to the
appliance heat exchanger or piping using a
continuity meter.
Replace and correct ground wire if ground continuity is not completed and satisfactory.
64
Page 71
Maintenance Procedures
0
.12 [ 3 mm]
0.12 [3 mm]
0.43 [11 mm]
Spark gap app. 0.18”
1.06” -1.12”
[27 mm - 29 mm]
[5 mm]
1.75 [44 mm]
1.18 [30 mm]
(
4
5
.
0
0
)
Fig. 26: Igniter Dimensions
65
Page 72
Maintenance Procedures
Check Control Wiring
Inspect all control wiring. Ensure wiring is in
good condition and properly connected.
Check Control Settings
1. Check the control CH/DHW/parameter settings by pressing the thermometer button
“” on control when the LED is lit for “
” this is the CH setting when the LED is lit
for “” this is the DHW setting. Adjust
settings with “” or “” buttons as necessary.
2. Press the button to close the setting
menu and store the changes.
3. Check any external limit control settings (if
used). Adjust settings as necessary.
Perform Start-up and Checkout Procedures
Start the appliance and perform the start-up
procedure as listed in this manual.
Close the external manual gas valve on the gas
supply line and disconnect the gas piping and
plug inside the appliance.
Disconnect the wiring harness connectors from
the blower.
Remove the mounting bolts and washers securing the front of the heat exchanger and set bolts
and washers aside.
Carefully remove the front of the heat exchanger. Ensure combustion chamber insulation is
not damaged during removal. See WARNING
on page 68.
Remove the burner head mounting screws and
remove the burner head. Inspect the burner
head for deterioration. Use compressed air or
a vacuum to clean the burner head. Replace
burner head if necessary. Replace burner head
gasket.
Re-assemble the burner head and burner head
gasket. Ensure mounting screws are tight.
Verify the cold water fill pressure is correct and
the operating pressure of the boiler is within
normal operating range.
Complete the checkout procedures as referenced in this manual.
Check Burner Flame
Inspect the burner flame through the observation port on left side off the heat exchanger.
If flame pattern is not fully blue and covers the
entire burner surface during high fire. Ensure
combustion at both high and lowfire meet the
requirements listed in Table 5, page 44. If combustion is OK and flame pattern is not fully blue
& covers the entire burner surface during highfire, shut the appliance down and allow it to cool
thoroughly before disassembly.
Remove the blower.
Use a vacuum cleaner or compressed air to
clean the interior of the blower and venturi
assembly. Inspect the blower blades to ensure
they are clean and not damaged.
Re-assemble the blower and venturi onto front
of the heat exchanger . Ensure all gaskets are
in good condition, and positioned correctly.
Replace gaskets if necessary.
Re-assemble the front of the heat exchanger
with bolts and washers onto the heat exchanger. Ensure the gasket and combustion chamber
insulation is in place and not damaged, replace
gasket and insulation if necessary. See WARNING on page 68. Ensure all screws and bolts
are tight.
Reconnect the wiring harness connectors to the
blower.
66
Page 73
Maintenance Procedures
Re-assemble the gas supply connections and
plug to gas valve inside the appliance. Open
the external manual gas valve. Check gas piping for any leaks as outlined on page 42 and
repair if necessary. Place the appliance back
into service.
Check Combustion Levels
Refer to page 44 of this manual for measuring
combustion levels and burner adjustments.
Clean Heat Exchanger
1. Shut down the appliance:
- Follow the instructions on Page 45 "To
Turn Off Gas to Appliance"
- Do not drain the appliance unless it will
be subject to freezing conditions.
- Do not drain the appliance if freeze
protection fluid is used in the system.
2. Allow the appliance to cool down to room
temperature before servicing.
3. Disconnect the gas piping and plug to the
gas valve.
4. Disconnect the wiring harness connectors
from the blower.
9. Re-assemble the blower the wiring harness.
10. Reconnect the gas piping and plug to gas
valve. Check for leaks, repair if necessary.
11. Close isolation valves at the appliance boiler piping to isolate the appliance from the
heating system.
12. Attach a hose to the boiler drain valve and
flush the boiler thoroughly with fresh
water by using the purge valves to allow
water to enter through the make-up water
line to the boiler.
13. Once the boiler has been completely
flushed, return the boiler and system piping back to operation.
14. Perform the required startup and checkout
procedures as outlined on pages 40 to 58.
Review With Owner
Ensure the owner understands the importance to perform the maintenance schedule
specified in this manual.
Remind the owner of the importance to call
a licensed contractor should the appliance
or system exhibit any unusual behavior.
5. Remove the mounting bolts and washers
securing the front of the heat exchanger
and set aside.
6. Carefully remove the front of the heat
exchanger. Ensure combustion chamber
insulation is not damaged during removal.
See WARNING on page 68.
7. Use a vacuum cleaner, compressed air or
water to remove any accumulation from
the heat exchanger flue ways. Do not use
any solvent.
8. Re-assemble the front of the heat exchanger onto the heat exchanger. Ensure the gasket and combustion chamber insulation is
in place and not damaged, replace gasket
and insulation if necessary. See WARNING on page 68.
The combustion chamber insulation
contains ceramic fibers, which are classified as a possible human carcinogen.
When exposed to extremely high temperatures, the ceramic fibers, which
contain crystalline silica, can be converted into cristobalite.
Avoid Breathing and Contact with Skin
and Eyes
When removing or repairing the combustion
chamber insulation follow these precaution
measures:
1. Use a NIOSH approved respirator which
meets OSHA requirements for cristobalite
dust, similar to N95. Contact NIOSH at
1-800-356-4676 or on the web at
www.cdc.gov/niosh for latest recommendations.
2. Wear long sleeved, loose fitting clothing,
gloves and eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes
separately from other laundry and rinse
washing machine thoroughly.
6. Discard used insulation in an air tight
plastic bag.
NIOSH Stated First Aid:
Eye/Skin: Immediately irrigate
Breathing: Clean fresh air
68
Page 75
Replacement Parts
Pressure relief and automatic air vent assembly
T
S
Vent/air adapter
Low voltage/terminal strip X4
DHW sensor S3
Blower
DHW flow switch
Ignition electrode
High voltage terminal strip
Condensate pan
Control/Display
CH Return sensor S2
CH supply sensor S1
Fig. 27: CHALLENGER Internal Components
WARNING
Replacement parts must be purchased
through a local Triangle Tube distributor. When ordering part please provide
the model number and description
and/or part number of replacement part.
69
Use only genuine Triangle Tube replacement parts to ensure warranty coverage
and to avoid damage to appliance and
improper operation of appliance.
Contact Triangle Tube at 856-228-8881
or www.triangletube.com for list of distributors nearest you.
Page 76
Replacement Parts
3
Fig. 28 : CHALLENGER Front Door
Part Number
Item
CC85
1CCRKIT04Wall Bracket Assembly (Not Shown)
2CCRKIT05
2ACCFTG01Connector Pipe CH (Not Shown)
2BCCFTG02Connector Pipe DHW (Not Shown)
3CCRKIT06CCRKIT07CCRKIT08Front Door Assembly
Part Number
CC105
Part Number
CC125
Description
Pipe Connectors & Brackets Assembly
(Not Shown)
70
Page 77
Replacement Parts
2
2
3
1
2
3
3
4
3
Fig. 29: CHALLENGER Vent Components
Part Number
Item
CC85
1CCRKIT0980/125 Vent /Air Adapter Assembly
2CCRKIT10CCRKIT11CCRKIT12Vent Assembly
3CCRKIT13Condensate Collector Assembly
4CCRKIT14Condensate Drain Assembly
Part Number
CC105
Part Number
CC125
Description
71
Page 78
Replacement Parts
9
1
3
2
8
11
6
4
10
5
7
4
Fig. 30 : CHALLENGER Internal Components
Item
Part Number
CC85
Part Number
CC105
Part Number
CC125
Description
1CCRKIT15Igniter Assembly
2CCCLB01Ignition Cable
3CCRKIT16Sight Glass Assembly
4CCRKIT17CH Sensor Assembly
5CCSENS02DHW Sensor
6CCRKIT18DHW Flow Switch Assembly
7CCRKIT19CH Pressure Sensor Assembly
8CCRKIT20CCRKIT21CCRKIT22CH Supply pipe Assembly
9CCRKIT23CCRKIT24CCRKIT25CH Return Pipe Assembly
10CCRKIT26DHW Supply Pipe Assembly
11CCRKIT27DHW Return Pipe Assembly
72
Page 79
Replacement Parts
4
1
2
3
Fig. 31 : CHALLENGER Blower & Gas Valve Components
Item
Part Number
CC85
Part Number
1CCRKIT28Ignition Transformer Assembly
2CCRKIT29Gas Valve Assembly
3CCRKIT30CCRKIT31Gas Pipe Assembly
4CCRKIT32Blower Assembly
CC105
Part Number
CC125
73
Description
Page 80
Replacement Parts
1
Fig. 32 : CHALLENGER Burner Components
Part Number
Item
CC85
1CCRKIT33Burner Assembly
Part Number
CC105
Part Number
CC125
Description
74
Page 81
Replacement Parts
3
4
2
1
Fig. 33 : CHALLENGER Control Components
Part Number
Item
CC85
1CCCON01Control/Display
2CCCS01Housing Plastic Control
3CCRKIT34Flip Panel
4CCFUSE01Fuse
Part Number
CC105
Part Number
CC125
Description
75
Page 82
Specifications
A
F
1.97”
[5 cm]
[6.5 cm]
[6.5 cm]
[6.5 cm]
[6.5 cm]
[8 cm]
2.56”
2.56”
2.56”
2.56”
3.15”
H
9.45”
[24 cm]
6.10”
[15.5 cm]
E
Z
Z
33.07 [84 cm]
30.71 [85.6 cm]
CH Supply
DHW Cold
DHW Hot
Vent/Air
CH Return
28.35 [72 cm]
flexible
1” NPT
1” NPT
1/2” NPT
C
D
80/125 (concentric)
Challenger CC 85
Challenger CC 105
Challenger CC 125
3/4” NPT
3/4” NPT
B
13.58”
[34.5 cm]
17.72”
[45 cm]
Z
Front View& Side CHALLENGER
76
Page 83
Specifications
Fuel
DOE
Heating Capacity
BTUH [KW]
N
ote 1 & 4
Modulation
Input
BTUH [KW]
N
ote 4
DOE Seasonal
Efficiency AFUE
Note 3
Net Boiler
IBR Rating
BTUH [KW]
Note 2
23,000 [6.7]
to
84,000 [24.6]
96%
Shipping
Weight
Lbs [Kg]
66 [30]
Natural
o
r
Propane
Natural
or
Propane
N
atural
or
Propane
Model
CHALLENGER
CC 85
CHALLENGER
CC 105
CHALLENGER
CC 125
65,000
[19.3]
110,000
94,000
[27.8]
75,000
[22.3]
29,000 [8.5]
to
106,000 [31]
96%
73 [33]
82,000
[24.3]
96,000
[28.4]
110,000
[
32.8]
33,000 [9.7]
to
124,000 [36.3]
96%
8
0 [36]
Water
Heater
Energy
Factor
Continious
Domestic
Flow
77ºF Rise
2.3 gpm
[8.7 lpm]
1.8 gpm
[6.8 lpm]
2.7 gpm
[10.41 lpm]
Model
CHALLENGER
CC 85
CHALLENGER
CC 105
CHALLENGER
CC 125
87%
87%
87%
Note 1:The heating capacity of the CHALLENGER
CC 85/105/125 is based on the test requirements of the U.S. Department of Energy.
Note 2:The IBR rating is based on a piping and pick
Note 3:Based on the given AFUE the CHAL-
LENGER CC 85/105/125 meets the energy
efficiency guidelines established by Energy
Star.
up allowance of 1.15. This allowance should
be sufficient for the standard radiation requirements for a building load.
77
Page 84
Specifications
Challenger Domestic Performance
NOTICE
If actual flow rate exceeds the value listed in Graph 2 the domestic outlet temperature will be reduced.
Graph 2 : Domestic Flow Rate at 120ºF Domestic Outlet and Varing Domestic Inlet Temperature
78
Page 85
Specifications
Domestic Pressure Drop
Graph 3 : Pressure Loss Through Domestic
CCSTRA01 Optional Strainer
Pressure Drop Curve
Graph 4 : Pressure Loss Through Optional Domestic Strainer
79
Page 86
Specifications
Pressure Drop Comparison - Grundfos
Graph 5 : Pressure Loss Through Boiler - Grundfos Circulators
Pressure Drop Comparison - Taco
Graph 6 : Pressure Loss Through Boiler - Taco Circulators
NOTICE
Minimum allowable boiler flow rate at full input: - 4 gpm CHALLENGER CC85
80
Page 87
Specifications
Pressure Drop Comparison - Grundfos
Graph 7 : Pressure Loss Through Boiler - Grundfos Circulators
Pressure Drop Comparison - Taco
Graph 8 : Pressure Loss Through Boiler - Taco Circulators
NOTICE
Minimum allowable boiler flow rate at full input: - 5 gpm CHALLENGER CC105
81
Page 88
Specifications
Pressure Drop Comparison - Grundfos
Graph 9 : Pressure Loss Through Boiler - Grundfos Circulators
Pressure Drop Comparison - Taco
Graph 10 : Pressure Loss Through Boiler - Taco Circulators
NOTICE
Minimum allowable boiler flow rate at full input: - 6 gpm CHALLENGER CC125
82
Page 89
Notes
Page 90
Notes
Page 91
Notes
Page 92
Additional quality water heating equipment available
from Triangle Tube
Maxi-Flo and Spa Heat Exchangers
SMART Indirect Fired Water Heaters
-Construction of high quality corrosion resistant
stainless steel (AISI 316) or titanium
-Specially designed built-in flow restrictor to assure
maximum heat exchange
-Compact and light weight
-Available in 5 sizes that can accommodate any size
pool or spa