* I N S T A L L A T I O N A N D M A I N T E N A N C E *
prestige
Solo 60
Solo 175
Solo 250
Solo 399
Water Boiler
L
I
S
T
E
D
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
M A N U A L
M A N U A L
NOTICE
WARNING
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installation in order to gain warranty coverage.
When receiving the PRESTIGE Solo unit, any claims for damage or shortage in shipment must be filed
immediately against the transportation company by the consignee.
Leave all documentation received with appliance with owner for future reference.
If the information in this manual is not followed exactly, a fire or explosion may
result causing property damage, personal injury or death.
•Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
Series III
•WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier ’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the
gas supplier.
FOR YOUR SAFETY
2010-7 Manual Prestige Solo 60/175/250/399 - Revised 02/17/10
The following terms are used throughout this manual to bring attention to the presence of
potential hazards or important information concerning the product.
DANGER
Indicates the presence of a hazardous
situation which, if ignored, will result in
death, serious injury or substantial
property damage.
WARNING
Indicates a potentially hazardous situation which, if ignored, can result in
death, serious injury or substantial
property damage.
CAUTION
Indicates a potentially hazardous situation which, if ignored, may result in
minor injury or property damage.
NOTICE
Indicates special instructions on installation, operation or maintenance, which
are important to equipment but not
related to personal injury hazards.
BEST PRACTICE
Indicates recommendations made by
Triangle Tube for the installers which
will help to ensure optimum operation
and longevity of the equipment
NOTICE
Triangle Tube reserves the right to modify the technical specifications and components of
its products without prior notice.
1
Page 8
Product & Safety Information
DANGER
Do not use this appliance if any part
has been under water. Immediately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system which has been
under water.
WARNING
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do
not use any phone in your building.
- Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
WARNING
Should overheating occur or the gas
supply fails to shut off, turn OFF the
manual gas control valve external to
the appliance.
WARNING
DO NOT add cold make up water when
the boiler is hot. Thermal shock can
cause potential cracks in the heat
exchanger.
CAUTION
When servicing the boiler:
-Avoid electrical shock by disconnecting the electrical supply prior to
performing maintenance.
WARNING
Qualified Installer:
Prior to installing this product read all
instructions included in this manual and all
accompanying manuals/documents with this
appliance. Perform all installation steps
required in these manuals in the proper
order given. Failure to adhere to the guidelines within these manuals can result in
severe personal injury, death or substantial
property damage.
Homeowner:
- This product should be maintained /
serviced and inspected annually by a
qualified service technician.
-This manual is intended for use by a
qualified Installer/Service Technician.
NOTICE
Please reference the unit’s model number and the serial number from the rating label, on the backside of the control
panel when inquiring about service or
troubleshooting.
NOTICE
Triangle Tube accepts no liability for any
damage resulting from incorrect installation or from the use of components or
fittings not specified by Triangle Tube.
2
Page 9
Pre-Installation Items
SECTION I - Pre-Installation Items
Code Compliance
This product must be installed in accordance to
the following:
-All applicable local, state, national and
provincial codes, ordinances, regulations and laws.
-For installations in Massachusetts, code
requires the boiler to be installed by a
licensed plumber or gas fitter, and if
antifreeze is utilized, the installation of
a reduced pressure backflow preventer
device is required in the boiler’s cold
water fill or make up water supply line.
-For installation in Massachusetts all direct
vented appliances must comply with the
guidelines as outlined on page 11.
- The National Fuel Gas Code NFPA54/
ANSI Z 223.1 - Latest edition.
-National Electric Code ANSI/NFPA 70.
- For installations in Canada -“Installation
Code for Gas Burning Equipment”
CGA/B149.1 or B149.2 Canadian
Electrical Code Part 1 CSA C22.1.
-Standards for Controls and Safety
Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1, when required.
Ensure the boiler location allows the combustion air/vent piping to be routed directly through
the building and terminate properly outside with
a minimum amount of length and bends.
Ensure the area chosen for the installation of the
PRESTIGE Solo is free of any combustible
materials, gasoline and other flammable liquids.
WARNING
Failure to remove or maintain the area
free of combustible materials, gasoline
and other flammable liquids or vapors
can result in severe personal injury,
death or substantial property damage.
Ensure the PRESTIGE Solo and its controls
are protected from dripping or spraying water
during normal operation or service.
The PRESTIGE Solo should be installed in a
location so that any water leaking from the
boiler or piping connections or relief valve will
not cause damage to the area surrounding the
unit or any lower floors in the structure.
Boiler Replacement
If the PRESTIGE Solo is replacing an existing
boiler, the following items should be checked
and corrected prior to installation:
NOTICE
The PRESTIGE Solo boiler gas manifold
and gas controls meet the safe lighting and
other performance requirements as specified in ANSI Z21.13 latest edition.
Determining Product Location
Before locating the PRESTIGE SOLO check
for convenient locations to:
-Heating system piping
-Venting
-Gas supply piping
-Electrical service
-Boiler piping leaks and corrosion.
- Improper location and sizing of the
expansion tank on the boiler heating
loop.
-If applicable, level and quality of freeze
protection within the boiler system.
Recommended Clearances
The PRESTIGE Solo is approved for zero
clearance to combustibles, excluding vent and
boiler piping.
-Boiler Piping - 1/4 inch from combustible materials.
3
Page 10
Pre-Installation Items
- Reference the appropriate vent supplement for clearance requirements.
BEST PRACTICE
To provide serviceability to the unit it is
recommended that the following clearances be maintained:
Top boiler jacket - 24 inches [610 mm].
Front - 24 inches [610 mm].
Bottom boiler piping - 24 inches [610
mm].
Rear - 0 inches
Sides - 6 inches [153 mm]
WARNING
If the clearances listed above cannot be
maintained or the enclosure in which the
boiler is installed is less than 85 cubic feet,
the space must be ventilated. See page 6
for ventilation requirements.
Residential Garage Installations
When installing the PRESTIGE Solo in a residential garage, the following special precautions
per NFPA 54/ANSI Z223.1 must be taken:
-Mount the unit a minimum 18 inches
[458 mm] above the floor level of the
garage. Ensure the burner and ignition
devices / controls are no less than 18
inches [458 mm] above the floor level.
-Locate or protect the unit in a manner
so it cannot be damaged by a moving
vehicle.
Boiler Freeze Protection Feature
The boiler control has a freeze protection feature
built in. This feature monitors the boiler temperature and responds as follows when no call for
heat is present:
-46ºF Boiler circulator is ON
-38ºF Boiler circulator is ON and burner
operates at low fire
-50ºF Burner OFF and boiler circulator
operates for approximately 10 minutes
NOTICE
When maintaining zero clearance or less
than recommended clearances, some
product labeling may become hidden
and unreadable.
WARNING
When installing the PRESTIGE Solo in
a confined space, sufficient air must be
provided for proper combustion and
venting and to allow, under normal operating conditions, proper air flow around
the product to maintain ambient temperatures within safe limits to comply with
the National Fuel Gas Code NFPA 54 latest edition.
CAUTION
The boiler freeze protection feature is
disabled during a hard lockout, however
the CH circulator will operate.
CAUTION
The boiler freeze protection feature is
designed to protect the boiler. The boiler
should be installed in a primary/secondary piping arrangement if it is
installed in an unheated space or
exposed to water temperatures of 46ºF or
less. See Section IV for primary/secondary piping examples. See Section IX
for antifreeze guides.
4
Page 11
Combustion Air Venting
SECTION II - Combustion Air and
Venting
Combustion Air Contamination
WARNING
If the PRESTIGE Solo combustion air
inlet is located in any area likely to cause
or contain contamination, or if products,
which would contaminate the air cannot
be removed, the combustion air must be
repiped and terminated to another location. Contaminated combustion air will
damage the unit and its burner system,
resulting in possible severe personal
injury, death or substantial property
damage.
WARNING
Do not operate a PRESTIGE Solo if its
combustion air inlet is located near a
laundry room or pool facility. These
areas will always contain hazardous contaminants.
Potential contaminating products
-Spray cans containing chloro/fluorocarbons
-Permanent Wave Solutions
-Chlorinated wax
-Chlorine - based swimming pool chemicals / cleaners
-Calcium Chloride used for thawing ice
-Sodium Chloride used for water softening
-Refrigerant leaks
-Paint or varnish removers
-Hydrochloric acid / muriatic acid
-Cements and glues
-Antistatic fabric softeners used in
clothes dryers
-Chlorine-type bleaches, detergents, and
cleaning solvents found in household
laundry rooms
-Adhesives used to fasten building products and other similar products
Pool and laundry products and common
household and hobby products often
contain fluorine or chlorine compounds.
When these chemicals pass through the
burner and vent system, they can form
strong acids. These acids can create corrosion of the heat exchanger, burner
components and vent system, causing
serious damage and presenting a possible threat of flue gas spillage or water
leakage into the surrounding area.
Please read the information listed below.
If contaminating chemicals are located
near the area of the combustion air inlet,
the installer should pipe the combustion
air inlet to an outside area free of these
chemicals per SECTION V of this
installation manual.
Areas likely to contain these products
-Dry cleaning / laundry areas and establishments
-Beauty salons
-Metal fabrication shops
-Swimming pools and health spas
-Refrigeration Repair shops
-Photo processing plants
-Auto body shops
-Plastic manufacturing plants
-Furniture refinishing areas and establishments
-New building construction
-Remodeling areas
-Garages with workshops
5
Page 12
Combustion Air Venting
Ventilation and Combustion Air
Requirements - Direct Vent
A Direct Vent appliance utilizes uncontamined
outdoor air (piped directly to the appliance) for
combustion.
For Direct Vent installations, involving only
the PRESTIGE Solo, in which the minimum
service clearances are maintained as listed on
page 4, no ventilation openings are required.
For Direct Vent, zero clearance installations
involving only the PRESTIGE Solo, the space
/ enclosure must provide two openings for ventilation. The openings must be sized to provide
1 square inch of free area per 1,000 BTUH of
boiler input. The openings shall be placed 12
inches from the top of the space and 12 inches
from the floor of the space.
For installations in which the PRESTIGE Solo
shares the space with air movers (exhaust fan,
clothes dryers, fireplaces, etc.) and other combustion equipment (gas or oil) the space must
be provided with adequate air openings to provide ventilation and combustion air to the
equipment. To properly size the ventilation /
combustion air openings, the installer must
comply with the National Fuel Gas Code
NFPA 54, ANSI Z223.1 for installations in the
U.S or CSA B149.1 and B149.2 for installations in Canada.
WARNING
The space must be provided with ventilation / combustion air openings properly sized for all make-up air requirements
(exhaust fans, clothes dryers, fireplaces,
etc.) and the total input of all appliances
located in the same space as the PRESTIGE Solo, excluding the input of a
Direct Vent PRESTIGE Solo which uses
combustion air directly from the outside,
thus additional free area for the openings is not required. Failure to provide
or properly size the openings could
result in severe personal injury, death or
substantial property damage.
Ventilation and Combustion Air
Requirements - Category IV
A Category IV appliance utilizes uncontaminated indoor or outdoor air (surrounding the
appliance) for combustion.
BEST PRACTICE
In order to reduce the potential risks
associated with indoor contaminates
(listed on page 5), flammable vapors and
tight housing construction (little or no
infiltration air), it is recommended to
pipe uncontaminated combustion air
directly from the outdoors to the appliance. This practice also promotes higher
system efficiency by reducing heated
indoor air from being exhausted from
the house and replaced by cold infiltration air into the house.
For installations in which the PRESTIGE Solo
shares the space with air movers (exhaust fan,
clothes dryers, fireplaces, etc.) and other combustion equipment (gas or oil) the space must be
provided with adequate air openings to provide
ventilation and combustion air to the equipment.
To properly size the ventilation / combustion air
openings, the installer must comply with the
National Fuel Gas Code NFPA 54, ANSI Z223.1
for installations in the U.S or CSA B149.1 and
B149.2 for installations in Canada, as referenced
in this section of the manual and titled Methods
of Accessing Combustion Air into a Space.
WARNING
The space must be provided with ventilation / combustion air openings properly sized for all make-up air requirements
(exhaust fans, clothes dryers, fireplaces,
etc.) and the total input of all appliances,
including the PRESTIGE Solo when
located in the same space. Failure to provide or properly size the openings could
result in severe personal injury, death or
substantial property damage.
6
Page 13
Combustion Air Venting
Methods of Accessing Combustion Air Into A
Space - Category IV
Indoor Combustion Air
NOTICE
The methods listed in this section for
accessing Indoor Combustion Air
assume that the infiltration rate is adequate and not less than .40 ACH. For
infiltration rates less than .40 ACH, reference the NFPA 54 National Fuel Gas
Code for additional guidance.
Opening Size and Location
Openings used to connect indoor spaces shall
be sized and located in accordance with the
following see Fig. 1:
The minimum dimension of air openings shall be not less than 3 inches.
- Combining spaces in different stories.
The volumes of spaces in different stories shall be considered as communicating spaces where such spaces are connected by one or more openings in
doors or floors having a total minimum
free area of 2 sq. in./1000 Btu/hr of
total input rating of all gas utilization
equipment.
Outdoor Combustion Air
BEST PRACTICE
Isolating the combustion appliance room
from the rest of the building and bringing in uncontaminated outside air for
combustion and ventilation is always
preferred.
Fig. 1:
All Combustion Air from Adjacent
Indoor Spaces Through Indoor
Combustion Openings
- Combining spaces on the same story.
Each opening shall have a minimum
free area of 1 sq. in./1000 Btu/hr of the
total input rating of all gas utilization
equipment in the space, but not less than
100 sq. inches. One opening shall commence within 12 inches of the top, and
one opening shall commence within 12
inches of the bottom of the enclosure.
Opening Size and Location
The minimum dimension of air openings shall
be not less than 3 inches
Openings used to supply combustion and ventilation air shall be sized and located in accordance with the following:
One Permanent Opening Method. See Fig. 2
One permanent opening, commencing within 12
in. of the top of the enclosure, shall be provided.
The equipment shall have clearances of at least 1
inch from the sides and 6 in. from the front of the
appliance. The opening shall directly communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the
outdoors and shall have a minimum free area of
the following:
-1sq. in./3000 Btu/hr of the total input
rating of all equipment located in the
enclosures, and
7
Page 14
Combustion Air Venting
Fig. 2:
All Combustion Air from Outdoors
Through One Permanent Air
Opening
-Not less than the sum of the areas of all
vent connectors in the space.
Two Permanent Openings Method.
Two permanent openings, one commencing
within 12 in. of the top and one commencing
within 12 in. of the bottom of the enclosure,
shall be provided. The openings shall communicate directly, or by ducts, with the outdoors
or spaces that freely communicate with the outdoors, as follows:
-Where directly communicating with the
outdoors or where communication to the
outdoors is through vertical ducts, each
opening shall have a minimum free area
of 1 sq. in./4000 Btu/hr of total input rating of all equipment in the enclosure.
See Fig.3.
Fig. 3:
Fig. 4:
All Combustion Air from Outdoors
Through Ventilated Attic
All Combustion Air from Outdoors
Through Horizontal Ducts
-Where communicating with the outdoors is through horizontal ducts, each
opening shall have a minimum free
area of not less than 1 sq.in./2000
Btu/hr of total input rating of all equipment in the enclosure. See Fig. 4.
Combination of Indoor and Outdoor
Combustion Air
Indoor Openings: Where used, openings connecting the interior spaces shall comply with
the Indoor Combustion Air section on page 7.
8
Page 15
Combustion Air Venting
Outdoor Opening(s) Location. Outdoor opening(s) shall be located in accordance with the
Outdoor Combustion Air section.
Outdoor Opening(s) Size. Outdoor opening(s) shall
be calculated in accordance with the following:
- The ratio of the interior spaces shall be
the available volume of all communicating spaces divided by the required
volume.
- The outdoor size reduction factor shall
be 1 minus the ratio of interior spaces.
- The minimum size of outdoor opening(s) calculated in accordance with the
above outdoor air section multiplied by
the reduction factor. The minimum
dimension of air openings shall not be
less than 3 in.
DANGER
Do not install the PRESTIGE Solo into a
common vent with other gas or oil appliances. This may cause flue gas spillage or
appliance malfunction, resulting in possible severe personal injury, death or substantial property damage.
Combustion Air and Vent Piping
The PRESTIGE Solo requires a Category IV
venting system, which is designed for pressurized venting and condensate.
BEST PRACTICE
In order to reduce the potential risks
associated with indoor contaminates
(listed on page 5), flammable vapors
and tight housing construction (little or
no infiltration air), it is recommended
to pipe uncontaminated combustion air
directly from the outdoors to the appliance. This practice also promotes higher
system efficiency by reducing heated
indoor air from being exhausted from
the house and replaced by cold infiltration air into the house.
NOTICE
Install combustion air and vent pipe as
detailed in the PRESTIGE Solo Vent
Supplement included in the boiler
installation envelope. Refer to optional
vent kit instructions for addition vent
installation instructions.
DANGER
Verify installed combustion air and vent
piping are sealed gas tight and meet all
provided instructions and applicable
codes, failure to comply will result in
severe personal injury of death.
The PRESTIGE Solo is certified per ANSI
Z21.13 as a Category IV or Direct Vent (sealed
combustion) appliance. A Category IV appliance utilizes uncontamined indoor or outdoor
air (surrounding the appliance) for combustion.
A Direct Vent appliance utilizes uncontaminated outdoor air (piped directly to the appliance)
for combustion.
9
Page 16
Combustion Air Venting
Removal of an Existing Boiler from a
Common Vent System
BEST PRACTICE
When an existing boiler is removed from a
common venting system, the common venting
system is likely to be too large for proper
venting of the remaining appliances. At the
time of removal of an existing boiler, the following steps shall be followed with each
appliance remaining connected to the common venting system placed in operation,
while the other appliances remaining connected to the common venting system are not
in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for
proper size and horizontal pitch and determine there is no blockage or restriction,
leakage, corrosion and other deficiencies
which could cause an unsafe condition.
5. Test for spillage at the draft hood relief
opening after 5 minutes of main burner
operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each
appliance remaining connected to the common venting system properly vents when
tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and
any other gas-burning appliance to their
previous condition of use.
7. Any improper operation of the common
venting system should be corrected so the
installation conforms with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CAN/CGA B149, Installation codes.
When resizing any portion of the common
venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II of the National Fuel
Gas Code ANSI Z223.1/NFPA 54 and/or
CAN/CGA B149, Installation codes.
3. Insofar as is practical, close all building
doors and windows and all doors between
the space in which the appliances remaining connected to the common venting system are located and other spaces of the
building. Turn on clothes dryers and any
appliance not connected to the common
venting system. Turn on any exhaust fans,
such as range hoods and bathroom
exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust
fan. Close fireplace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
DANGER
Do not install the PRESTIGE Solo into a
common vent with other gas or oil appliances. This may cause flue gas spillage or
appliance malfunction, resulting in possible severe personal injury, death or substantial property damage.
10
Page 17
Combustion Air Venting
Commonwealth of Massachusetts Installations Only
For direct-vent appliances, mechanicalvent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake is installed
below four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are bedroom(s), a carbon monoxide detector
and alarm shall be placed in the living
area outside the bedroom(s). The carbon monoxide detector shall comply
with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall also
be located in the room that houses the
appliance or equipment and shall:
a. Be powered by the same electrical
circuit as the appliance or equipment such that only one service
switch services both the appliance
and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005
Edition); and
d. Have been approved and listed by
the Nationally Recognized Testing
Laboratory as recognized under 527
CMR.
3. A Product-approved vent terminal must
be used, and if applicable, a Productapproved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions
shall remain with the appliance or
equipment at the completion of the
installation.
4. A metal or plastic identification plate
shall be mounted at the exterior of the
building, four feet directly above the
location of vent terminal. The plate
shall be of sufficient size to be easily
read from a distance of eight feet away,
and read “Gas Vent Directly Below”.
NOTICE
Installer must provide tag identification
plate and ensure the lettering meets code
requirements.
For direct-vent appliances, mechanicalvent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake are installed
above four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are bedroom(s), a carbon monoxide detector
and alarm shall be placed in the living
area outside the bedroom(s). The carbon monoxide detector shall comply
with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses
the appliances or equipment;
b. Be either hard wired or battery
powered or both; and
c. Shall comply with NFPA 720 (2005
Edition)
3. A Product-approved vent terminal must
be used, and if applicable, a Productapproved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions
shall remain with the appliance or
equipment at the completion of the
installation.
11
Page 18
Unit Preparations
SECTION III - Unit Preparations
Handling Instructions
The PRESTIGE Solo is generally easier to
handle and maneuver once removed from the
shipping carton.
To remove the shipping carton:
CAUTION
Use care not to lift the unit from, or place
the unit on the front plastic control
panel, damage can occur. Use care not to
drop, bump or rotate the boiler upside
down, as damage to the boiler will result.
1. Remove any shipping straps and open the
side of the shipping carton.
2. Slide the unit with the foam inserts out of
the carton.
3. Discard all packing materials.
Wall Mounting Guidelines
1. The wall-mounting bracket is designed for
stud spacing of 12 inch or 16 inch on centers. For unconventional stud spacing, a
solid / secure mounting surface must be
provided for installation of the bracket.
2. For applications using wood studs, install
the bracket using the lag screws provided
with the boiler. Ensure both lag screws are
installed securely in the studs.
3. For applications using metal studs, install
the bracket to the studs using 3/16” toggle
bolts and washers.
4. DO NOT mount or attempt to mount the
wall bracket to hollow sheet rock or lath
walls using anchors. Only install boiler to
studs or equivalent wood structure.
5. For applications using solid walls (rock,
concrete, brick, cinder block, etc.), install
the wall bracket using anchors (double
expansion shields) and bolts with washers
provided with the boiler.
Wall Mounting Installation
The PRESTIGE Solo should be wall mounted
using the bracket provided with the boiler. The
PRESTIGE Solo is not designed for floor
installation. If floor installation is required an
optional floor stand is available through
Triangle Tube.
NOTICE
The wall used for mounting the PRESTIGE Solo must be vertically plumbed
and capable of supporting a minimum
130 pounds [59 kg] for the PRESTIGE
Solo 60, 175 pounds [80 kg] for PRESTIGE Solo 175/250 and 250 pounds [115
Kg] for PRESTIGE Solo 399. Failure to
comply with these requirements could
result in personal injury, death or substantial property damage.
6. The boiler is too heavy and bulky for a single person to lift and attempt to mount; a
minimum of 2 people is required for
mounting the boiler.
NOTICE
Use extreme care not to drop the boiler
or cause bodily injury while lifting or
mounting the boiler onto the bracket.
Once mounted verify that the boiler is
securely attached to the bracket and
wall. Failure to comply with the above
guidelines could result in property damage, personal injury or death.
12
Page 19
Unit Preparations
PRESTIGE Solo 60/175/250 Stud Walls Installation
1. Locate the studs in the general area of the
boiler placement.
2. Place the wall-mounting bracket on the
wall centering the mounting slots with the
stud centers and ensuring the upper edge of
the bracket is away from the wall.
3. Level the bracket, while maintaining it’s
centering with the studs and use a pencil to
mark the location of the mounting slots.
4. Remove the bracket from the wall and drill
1/4” diameter hole by 3” deep positioned in
the center of each mark. For applications
using metal studs and 3/16” toggle bolts,
drill the required clearance hole.
5. Reposition the bracket onto the wall and
align mounting slots/holes. Insert the two
lag screws provided (or toggle bolts for
metal studs) through the mounting
slots/holes and loosely tighten.
Wall Bracket Installation - Solid Walls
1. Locate the general area of the boiler placement.
2. Place the wall-mounting bracket on the
wall ensuring the upper edge of the bracket
is away from the wall.
3. Level the bracket and use a pencil to mark
the location of the mounting slots on the
wall.
4. Remove the bracket from the wall and drill
a 5/8” diameter hole by 1-3/8” deep positioned in the center of each mark.
5. Install the anchors (provided) flush or
slightly recessed in the drilled holes with
threaded side facing down.
6. Reposition the bracket on the wall and
align mounting slots/holes. Insert the two
bolts (provided) through the mounting
slots/holes and loosely tighten.
7. Level bracket and tighten bolts securely.
6. Level bracket and tighten screws (bolts for
metal studs) securely making sure not to
over-tighten to avoid damaging drywall or
plaster.
PRESTIGE Solo 399 Stud Walls Installation
1. To distribute the weight of the boiler evenly when mounting onto a stud wall it is recommended to use the PRESTIGE Solo
Wall Frame kit.
2. When using the wall frame to mount the
boiler reference the kit installation instructions and ensure the frame is securely fastened to the wall.
3. If the structure of wall is questionable, in
supporting a minimum weight of 250
pounds [115 kg.], it is recommended to use
the optional floor stand.
Boiler Mounting
1. Obtain assistance in lifting the boiler onto
the wall bracket.
2. Install the boiler making sure the boiler
mounting lip located along the upper edge
of the rear jacket panel engages the wallmounting bracket. Ensure the boiler is
seated properly and is secure.
13
Page 20
Boiler Piping
SECTION IV - Boiler Piping
General Piping Requirements
- All plumbing must meet or exceed all local,
state and national plumbing codes.
-Support all piping using hangers. DO NOT
support piping by the unit or its components.
-Use isolation valves to isolate system components.
-Install unions for easy removal of the
PRESTIGE Solo from the system piping.
WARNING
Use a two wrench method when tightening piping onto the boiler connections.
Use one wrench to prevent the boiler
piping from turning / twisting. Failure
to support the boiler piping and connections in this manner could cause damage
to the boiler and its components.
Pressure Relief Valve
1. The PRESTIGE Solo is supplied with a 30
psi pressure relief valve and must be piped
using the PRV connection as shown in Fig.
5 page 15.
2. To avoid potential water damage to the surrounding area or potential scalding hazard
due to the operation of the relief valve, the
discharge piping:
- Must be connected to the discharge out-
let of the relief valve and directed to a
safe place of disposal.
- Length should be as short and direct as
possible. The size of the discharge line
should not be reduced, maintain the
same size as the outlet of the relief valve.
- Should be directed downward towards
the floor at all times. The piping should
terminate at least 6 inches [153 mm]
above any drain connection to allow
clear visibility of the discharge.
- Should terminate with a plain end, not
with a threaded end. The material of
the piping should have a serviceable
temperature rating of 250ºF or greater.
- Should not be subject to conditions
where freezing could occur.
- Should not contain any shut-off valves
or obstructions. No shut-off valve
should be piped between the boiler and
relief valve.
WARNING
Failure to comply with the guidelines on
installing the pressure relief valve and
discharge piping can result in personal
injury, death or substantial property
damage.
Low Water Cutoff Device
-The PRESTIGE Solo is equipped with a factory installed pressure switch type Low Water
Cut Off device.
-The minimum operating system pressure
allowable with this device is 10 psig.
-Check local codes if a Low Water Cutoff
Device is required. If so, determine if this
device meets the requirements of the local
codes.
NOTICE
The PRESTIGE Solo control system also
senses the system water temperatures
entering and exiting the heat exchanger
to provide protection against low water
conditions Where local codes and jurisdiction do not accept a pressure device
for low water protection, the jurisdictions may accept these PRESTIGE Solo
integral control functions as a means of
providing low water protection.
14
Page 21
Boiler Piping
Boiler Return Connection
with Tee Fitting and
Boiler Drain Valve
Boiler Supply
Connection
Pressure Relief Valve
(
Supplied with Boiler)
3/4" Street Elbow
Air Vent
Drain Piping Directed
to a Suitable
Place of Drainage
Fig. 5: Pressure Relief Valve and Boiler Drain Valve Installation
15
Page 22
Boiler Piping
Additional Limit Control
If a separate LWCO device is required by certain local jurisdictions or when the boiler is
installed above the system piping, the following guidelines must be followed:
- The LWCO device must be designed
for water installations, electrode probetype is recommended.
- The LWCO device must be installed in
a tee connection on the boiler supply
piping above the boiler.
- Wiring of the LWCO device to the
PRESTIGE Solo is done directly onto
the 24V terminal strip, reference Fig.
20 page 32 for available terminals for
an external limit (manual or auto reset).
If the installation is to comply with ASME or
Canadian requirements, an additional high
temperature limit may be needed. Consult
local code requirements to determine compliance. The limit should be installed as follows:
- Install the limit in the boiler supply piping between the boiler and any isolation
valve.
- Maximum set point for the limit is
194ºF.
- For wiring of the limit reference Fig. 20,
page 32, using the external limit/manual
reset terminals on the 24V terminal strip.
This will provide a "hard" lockout
requiring a manual reset of the control.
Boiler System Piping Applications
BEST PRACTICE
It is recommended on all piping applications to utilize a primary/secondary piping arrangement as a means to provide
freeze protection of the boiler, which is an
integral function of the boiler control.
Maintain the minimum boiler flow rate,
see Graphs 2 through 5 on pages 72 & 73.
For other piping arrangements, consult
the Engineering Department at Triangle
Tube or consult other approved/recognized design arrangements.
BEST PRACTICE
On piping applications utilizing a single
zone or other recognized piping design
arrangements, it is recommended that the
installer uses flow/check valves with
weighted seats at or near the appliance to
prevent gravity circulation.
Expansion Tank and Makeup Water
Ensure the expansion tank is properly sized for
the boiler volume (3 gallons [12 L] for the
PRESTIGE Solo 60, 5 gallons [19 L] for the
PRESTIGE Solo 175/250, 7 gallons [26 L] for
PRESTIGE Solo 399) and the system volume
and temperature.
CAUTION
Backflow Preventer
-Use a backflow preventer valve in the
make-up water supply to the unit as
required by local codes.
Undersized expansion tanks will cause
system water to be lost through the pressure relief valve and cause additional
makeup water to be added to the system.
Eventual boiler heat exchanger failure
can result due to this excessive makeup
water addition.
16
Page 23
Boiler Piping
The expansion tank must be located as shown
in Fig. 6 and Fig. 7 on page 18 when using a
primary/secondary piping arrangement or as
per recognized design methods. Refer to the
expansion tank manufacturer instructions for
additional installation details.
Connect the expansion tank to an air separator
only if the air separator is located on the suction side (inlet) of the system circulator.
Always locate and install the system fill connection at the same location as the expansion
tank connection to the system.
Diaphragm Expansion Tank
Always install an automatic air vent on the top
of the air separator to remove residual air from
the system.
Closed-Type Expansion Tank
It is recommended to pitch any horizontal piping upwards toward the expansion tank 1 inch
per 5 feet of piping. Use 3/4” piping for the
expansion tank to allow air within the system
to rise.
Sizing Primary Piping
See Fig. 8 through 14, pages 20 - 24, for recommended piping arrangements based on various applications. Size the piping and system
components required in the space heating system, using recognized design methods.
Domestic Hot Water System Piping
See Fig. 8 , page 20 for recommended piping to
a DHW system. This recommended piping
configuration ensures priority is given to the
production and recovery of the DHW.
The piping for the DHW is separate from the
boiler system piping and does not require a primary / secondary piping configuration.
To wire the DHW circulator to the boiler control module, reference Section VIII - External
Wiring.
System Piping - Zone Circulators
Connect the PRESTIGE Solo to the system
piping as shown in Fig. 9 page 21 when zoning
with zone circulators.
CAUTION
DO NOT install automatic air vents on a
closed-type expansion tank system. Air
must remain in the system and be
returned to the expansion tank to provide an air cushion. An automatic air
vent would cause air to be vented from
the system resulting in a water-logged
expansion tank.
Circulator
The PRESTIGE Solo must be supplied with a
Central Heating (CH) circulator. The circulator
when wired directly to the PRESTIGE Solo
will allow for domestic hot water priority and
to provide circulation for the freeze protection
feature of the boiler control. See Graphs 2
through 5 on pages 72 & 73 for pressure drop
and minimum flow rate through the boiler.
The installer must provide a separate circulator
for each zone of space heating as well as the
boiler circulator.
NOTICE
To ensure an adequate flow rate through
the PRESTIGE Solo, the boiler supply
and return piping size must be a minimum of 1 inch for the PRESTIGE Solo
60, 1-1/4 inch for the PRESTIGE Solo
175/250 and 1-1/2 inch for the PRESTIGE Solo 399.
17
Page 24
Boiler Piping
Max.
12"
Boiler
Supply
System
Return
System
Cold
Water Fill
Boiler
Supply
Return
7
10
1
2
3
5
4
6
6
6
11
12
7
1
10
9
8
4
3
6
6
6
Cold
Water Fill
Boiler
Supply
Minimum
3/4" Piping
Boiler
Return
Return
System
Supply
System
Max.
12"
11
12
Fig. 6: Near Boiler Piping - Diaphragm Expansion Tank
Fig. 7 : Near Boiler Piping - Closed Type Expansion Tank
1. System circulator
2. Automatic air vent
3. Air separator
4. Automatic fill valve
5. Diaphragm expansion tank
6. Isolation valve
Note: Pitch horizontal piping upwards (1” of pitch
per 5 ft of piping) towards
expansion tank.
7. Drain/purge valve
8. Tank fitting
9. Closed type expansion tank
10. Primary/secondary connection
11. Boiler circulator
12. Flow/check valve
18
Page 25
Boiler Piping
System Piping - Zone Valves
Connect the PRESTIGE Solo to the system piping as shown in Fig. 10 page 21 when zoning
with zone valves. The primary / secondary piping
ensures that the boiler loop has sufficient flow.
NOTICE
To ensure an adequate flow rate through
the PRESTIGE Solo, the boiler supply
and return piping size must be a minimum of 1 inch for the PRESTIGE Solo 60,
1-1/4 inch for the PRESTIGE Solo
175/250 and 1-1/2 inch for the PRESTIGE
Solo 399.
System Piping - Through Boiler
In new or retrofit applications in which
primary/secondary arrangement is not utilized, the
PRESTIGE Solo allows this flexibility due to a
lower boiler pressure drop, see Graphs 2 through
7 on pages 75 through 77.
Figure 11, page 22 illustrates a multiple zone
valve system with a single system/boiler circulator. A by-pass loop with a pressure differential
valve must be installed on the system piping.
Figure 12, page 22 illustrates a single zone utilizing the boiler circulator as the system circulator.
System Piping - Radiant Heating
The heat exchanger design of the PRESTIGE
Solo allows operation in a condensing mode.
This feature requires no regulation of the return
water temperature back to the boiler in radiant
heating applications.
The boiler water supply temperature can be
maintained by the PRESTIGE Solo, eliminating the need for a mix system to achieve the
desired temperature.
It is recommended for the installer to add a
high temperature limit as shown in Fig.13 page
23. This will ensure that the primary supply
temperature does not exceed the maximum
allowable temperature for the radiant tubing.
EST PRACTICE
B
The addition of the high temperature
limit is important if the PRESTIGE Solo
is connected to a domestic hot water system, which requires a high primary supply water temperature.
Size the system piping and circulator to provide
the flow needed for the radiant system.
NOTICE
To ensure an adequate flow rate through
the PRESTIGE Solo, the boiler supply
and return piping size must be a minimum of 1 inch for the PRESTIGE Solo
60, 1-1/4 inch for the PRESTIGE Solo
175/250 and 1-1/2 inch for the PRESTIGE Solo 399.
System Piping - Special Application
If the boiler is used in conjunction with a
chilled water/medium system, the boiler and
chiller must be piped in parallel. Install
flow/check valves to prevent the chilled medium from entering into the boiler.
If the boiler is used to supply hot water to the
heating coils of an air handler where they may
be exposed to chilled air circulation, install
flow/check valves or other automatic means
to prevent gravity circulation of the boiler
water during cooling cycles.
System Piping - Multiple Units Installation
Use a balanced manifold system as the primary / secondary connection to the space heating
piping as shown in Fig. 14 page 24.
Maintain a minimum of 6 inches [153 mm] of
clearance between units to allow for servicing.
Refer to Figs. 6 and 7 page 18 to install air separator and expansion tank.
For the space heating piping refer to the applications mentioned in this manual or use recognized design methods.
19
Page 26
Boiler Piping
2
1
7
5
6
6
3
3
4
Supply
System
System
Hot
Cold
Domestic
Domestic
Return
8
Fig. 8: DHW Boiler Piping with a PRESTIGE Solo and SMART
1. PRESTIGE Solo boiler
2. SMART water heater
3. Isolation valve
4. DHW circulator
5. CH circulator
6. Flow/check valve
7. Pressure relief valve
8. Drain/purge valve
NOTICE
The boiler system piping shown in Fig. 8
must be a “closed” system to avoid any
oxygen contamination and potential failure of the outer tank of the Smart.
20
Page 27
Boiler Piping
5
5
4
6
1
2
3
3
3
3
3
9
8
10
1
1
4
4
4
4
4
4
Z
one Load
Additional
7
6
Max.
12"
Z
one Load
2
6
5
5
4
6
1
3
12
9
8
10
11
4
4
4
4
4
4
Zone Load
7
Additional
Max.
12"
Zone Load
Fig. 9: CH System Piping - Zoning with Zone Circulators
1. PRESTIGE Solo boiler
2. CH circulator
3. Flow/check valve
4 Isolation valve
5. Zone circulator
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
6. Drain/purge valve
Fig. 10: CH System Piping - Zoning with Zone Valves
1. PRESTIGE Solo boiler
2. CH circulator
3. Flow/check valve
4 Isolation valve
5. Zone valve
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
12. System circulator
21
Page 28
Boiler Piping
1
2
7
6
4
Additional
Zone Load
4
5
4
4
4
2
Zone Load
9
8
10
11
4
5
12
P
1
2
7
6
4
2
Single
Zone load
9
8
10
11
4
3
Note: Verify CH circulator is properly sized to
overcome the system pressure drop and provide adequate flow through the
boiler system.
Fig. 11: CH System Piping - Multiple Zone Valve with Single System/Boiler Circulator
1. PRESTIGE Solo boiler
2. CH circulator
4 Isolation valve
5. Zone valve
6. Drain/purge valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
12. Pressure Differential Valve
7. Pressure relief valve
Note: Verify CH circulator is properly sized to
overcome the system pressure drop and provide adequate flow through the
boiler system.
Fig. 12: CH System Piping - Single Zone System with Single System/Boiler Circulator
1. PRESTIGE Solo boiler
2. CH circulator
3. Flow/check valve
4 Isolation valve
5. Zone valve
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
22
Page 29
Boiler Piping
2
5
5
4
6
1
3
13
12
9
8
10
11
4
4
4
Radiant Zone
Additional
4
4
4
6
7
Radiant Zone
Max.
12"
Note: Manifold mounted valve
actuators may be used in lieu of
zone valves.
Fig. 13: CH System Piping - Radiant/Low Temp. Heating
1. PRESTIGE Solo boiler
2. CH circulator
3. Flow check valve
4 Isolation valve
5. Zone valve
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
12. System circulator
13. High temperature limit control
23
Page 30
Boiler Piping
3
2
2
2
2
To the
System
5
5
5
1
1
1
From the System
4
6
7
8
9
2
12"
Max.
3
2
3
2
5
5 5
1. Boiler circulator
2. Isolation valve
3. Flow/check valve
4. System circulator
5. Drain/purge valve
6. Automatic air vent
7. Air separator
8. Diaphragm expansion tank
9. Automatic fill valve
Fig. 14: Multiple PRESTIGE Solo Boiler Piping - Primary / Secondary / Piping using Balanced Manifold System
24
Page 31
Installating Vent/Combustion Air & Condensate Drain
SECTION V - Installing Vent /
Combustion Air & Condensate Drain
Installing Vent and Combustion Air
DANGER
The PRESTIGE Solo must be vented
and supplied with combustion air as
shown in the PRESTIGE Solo Vent
Supplement, included in the boiler
installation envelope. Refer to optional
vent kit instructions for additional vent
installation instructions. Once installation is completed, inspect the vent and
combustion air system thoroughly to
ensure systems are airtight and comply
with the instructions given in the venting
supplement and are within all requirements of applicable codes. Failure to
comply with the installation requirements on the venting and combustion air
piping will cause severe personal injury
or death.
WARNING
Ensure the condensate drain assembly
contains the plastic seated ball. Do not
install the condensate drain assembly if
the ball is lost or missing, replace the
entire assembly.
3. Remove the compression nut and rubber
seal from the drain outlet.
4. Using 3/4” x 2’ flexible PVC tube provided, slide the compression nut and rubber
seal over the pipe
NOTICE
The use of 3/4” PVC or CPVC pipe is
also acceptable. If 3/4” pipe is used
deburr and chamfer pipe to allow mating onto the drain assembly.
5. Thread the rubber seal into the compression nut to ease installation of the pipe to
the drain assembly.
Installing Condensate Drain Assembly
1. Locate the condensate drain assembly and
install as shown in Fig. 15 page 26.
NOTICE
The installer may want to fill the condensate trap with water prior to assembling on the unit.
2. Remove the retaining nut and rubber seal
from the condensate drain assembly and
slide over the heat exchanger condensate
drain nipple. Connect the condensate drain
assembly to the retaining nut and tighten.
Hand tight only!
6. Seat the pipe onto the drain assembly and
tighten the compression nut. Hand tight
only!
NOTICE
The installer may opt to using 13/16" ID
tubing in lieu of rigid piping.
NOTICE
The drain line materials must be an
approved material by the authority having jurisdiction. In absence of such
authority, PVC and CPVC piping must
comply with ASTM D1785 or D2845.
The cement and primer used on the piping must comply with ASME D2564 or
F493. For installations in Canada, use
CSA or ULC certified PVC or CPVC
pipe, fittings and cement/primer.
7. Continue the pipe from the drain assembly
to a floor drain or condensate pump.
25
Page 32
Installating Vent/Combustion Air & Condensate Drain
Flexible Tubing
(or 3/4 PVC/
CPVC Piping
to Drain)
Compression
Nut with Rubber Seal
Fill Plug
with Vac cum
Break Port
Condensate
Drain Assembly
Plastic Ball
Retaining Nut
with Rubber Seal
(Hand Tight Only)
Heat Exchanger
Condensate
Drain Nipple
NOTICE
When selecting and installing a condensate pump, ensure the pump is approved
for use with condensing boilers and furnaces. The pump should be equipped
with an overflow switch to prevent property damage from potential condensate
spillage.
8. The PRESTIGE Solo will typically produce
a condensate that is considered slightly
acidic with a pH content below 3.0. Install
a neutralizing filter if required by authority
having jurisdiction.
CAUTION
The condensate drain must remain filled
and unobstructed and allow unrestricted
flow of condensate. The condensate
should not be subject to conditions
where freezing could occur. If the condensate is subjected to freezing or
becomes obstructed , it can leak, resulting in potential water damage to the boiler and surrounding area.
Fig. 15: Condensate Drain Assembly
26
Page 33
Gas Piping
Sediment
Trap Min.
Length of 3"
Union Fitting
Cap
Te e Fitting
External Manual
Gas Shut Off
Valve (Must Be
Within 6' of the
Boiler)
Gas Flow
SECTION VI - Gas Piping
Gas Supply Piping Connection
7. Use pipe dope compatible with natural and
propane gases. Apply sparingly only to the
male threads of pipe joints so that pipe
dope does not block gas flow.
NOTICE
The gas supply piping must be installed
in accordance to all applicable local,
state and national codes and utility
requirements.
1. Install a 1/2” NPT for PRESTIGE Solo 60,
3/4” NPT for PRESTIGE Solo 175/250 or
1” NPT for PRESTIGE Solo 399 pipe
union at the factory supplied gas nipple, for
ease of service.
2. Install a manual shutoff valve in the gas
supply piping as shown in Fig. 16. For
installations in Canada the installer must
tag and identify the main shutoff valve.
3. Install a sediment trap (drip leg) on the gas
supply line prior to connecting to the PRESTIGE Solo gas train as shown in Fig. 16.
4. Support the gas piping using hangers. Do
not support the piping by the unit or its
components.
WARNING
Failure to apply pipe dope as detailed
above can result in severe personal
injury, death or substantial property
damage.
WARNING
Use a two-wrench method of tightening
gas piping near the unit and its gas piping connection. Use one wrench to prevent the boiler gas line connection from
turning and the second to tighten adjacent piping. Failure to support the boiler gas piping connection could damage
the gas line components.
5. Purge all air from the gas supply piping.
6. Before placing the PRESTIGE Solo into
operation, check and test all connections
for leaks.
-Close the manual shutoff valve during
any pressure test with less than 13”w.c..
-Disconnect the PRESTIGE Solo and its
gas valve from the gas supply piping
during any pressure test greater than
13”w.c..
WARNING
Do not check for gas leaks with an open
flame. Use a gas detection device or bubble test. Failure to check for gas leaks
can cause severe personal injury, death
or substantial property damage.
Fig. 16: Recommended Gas Supply Piping
27
Page 34
Gas Piping
NATURAL GAS
Pipe Sizing - Natural Gas
Refer to Table 1 for schedule 40 metallic pipe
length and diameter requirements for natural
gas, based on rated PRESTIGE Solo input
(divide by 1,000 to obtain cubic feet per hour).
-Table 1 is based on Natural Gas with a specific gravity of 0.60 and a pressure drop
through the gas piping of 0.30”w.c..
- For additional gas piping sizing information, refer to ANSI Z223.1. For Canadian
installations refer to B149.1 or B149.2.
Natural Gas Supply Pressure Requirements
1. Pressure required at the gas valve inlet
supply pressure port:
-Maximum 13”w.c. at flow or no flow
conditions to the burner.
-Minimum 5”w.c. during flow conditions
to the burner. Must be verified during
start up and with all other gas appliances
operating within the building.
2. Install 100% lockup gas pressure regulator
in the gas supply line if inlet pressure can
exceed 13”w.c at any time. Adjust the lockup pressure regulator for 13”w.c maximum.
WARNING
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve
is factory-set for the correct outlet pressure. This setting is suitable for natural
gas and propane and requires no field
adjustment. Attempts by the installer to
adjust or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
injury, death or substantial property
damage.
NOTICE
The natural gas orifice requirements are:
PRESTIGE Solo 60: 0.204” (5.2 mm)
PRESTIGE Solo 175: None Required
PRESTIGE Solo 250: None Required
PRESTIGE Solo 399: 0.339” (8.6 mm)
Table 1: Gas Piping Sizing - Natural Gas
Length of Pipe in
Feet
SCH 401/2"3/4"1"1-1/4"1-1/2"
1013227852010501600
20921903507301100
3073152285590890
4063130245500760
5056115215440670
754593175360545
1003879150305460
1503164120250380
Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas Per
Hour (based on 0.60 specific gravity, 0.30" w.c. pressure drop)
28
Page 35
Gas Piping
PROPANE GAS
Pipe Sizing - Propane Gas
Contact the local propane gas supplier for recommended sizing of piping, tanks and 100%
lockup gas regulator.
Propane Gas Supply Pressure Requirements
1. Adjust the propane supply regulator provided by the gas supplier for 13”w.c. maximum pressure
2. Pressure required at the gas valve inlet supply pressure port:
-Maximum 13”w.c. at flow or no flow
conditions to the burner
-Minimum 5”w.c. during flow conditions
to the burner. Must be verified during
start up and with all other gas appliances
operating within the building.
WARNING
Prior to start up, ensure the unit is set to
fire propane. Check the rating label for
the type of fuel. Check the gas valve for
propane conversion label. If there is a
conflict or doubt on the burner set up,
remove the gas valve and check for the
propane orifice, see Fig. 17 or 18, page
30. Failure to ensure proper burner
setup could result in severe personal
injury, death or substantial property
damage.
NOTICE
The propane orifice requirements are:
PRESTIGE Solo 60: 0.120” (3.1 mm)
PRESTIGE Solo 175: 0.221” (5.6 mm)
PRESTIGE Solo 250: 0.250” (6.3 mm)
PRESTIGE Solo 399: 0.264” (6.7 mm)
WARNING
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve
is factory-set for the correct outlet pressure. This setting is suitable for natural
gas and propane and requires no field
adjustment. Attempts by the installer to
adjust or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
injury, death or substantial property
damage.
29
Page 36
Gas Piping
Gas Valve
Orifice
Gaskets
Venturi
V
enturi
I
nlet Supply
Pressure Port
P
ropane
O
rifice
G
as Valve
Gasket
Gas Valve
Pipe Fitting
Gas Valve
Fig. 17: Gas Valve / Venturi Assembly - PRESTIGE Solo 60/175/250
Fig. 18: Gas Valve / Venturi Assembly - PRESTIGE Solo 399
30
Page 37
Internal Wiring
Terminal Block
Wiring Tool
SECTION VII - Internal Wiring
WARNING
ELECTRICAL SHOCK HAZARD. For
your safety, disconnect electrical power
supply to the unit before servicing or
making any electrical connections to
avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or death.
CAUTION
Prior to servicing, label all wires before
disconnecting. Wiring errors can cause
improper and dangerous operation.
Verify proper wiring and operation after
servicing.
General Requirements
-Wiring must be N.E.C Class 1.
-If original wiring as supplied with the unit
must be replaced, use only Type T 90ºC
wire or equivalent as a minimum.
-The PRESTIGE Solo must be electrically
grounded as required by National
Electrical Code ANSI/NFPA 70 - latest edition and / or the Canadian Electrical Code
Part 1, CSA C22.1, Electrical Code.
Control Module Circulator AMP Ratings
- AMP draw of the CH circulator not to
exceed 2 amps.
-AMP draw of the DHW circulator not to
exceed 2 amps.
Wiring Tool Instructions
1. Locate the wiring tools on the PRESTIGE
Solo just below the MCBA control in a
plastic bag and below the extra fuses.
2. Locate the terminal blocks on the PRESTIGE Solo below the MCBA control.
NOTICE
The 120V Terminals are located on the
left set of Terminal Blocks. The 24V
Terminals are located on the right set of
terminal blocks.
3. Carefully pull down on the lower half of
the terminal block to remove.
4. Hook the wiring tool into the desired slot of
the terminal block as shown in Fig.19.
5. Push wiring tool in towards the terminal
block and insert wire in slot at bottom of
terminal block.
6. Repeat steps 4 & 5 until all wiring is complete.
Fig. 19:
7. Re-connect the lower half of the terminal
block to the upper half.
8. Place the wiring tool back into the plastic
bag or leave tool hooked to a slot on the
24V terminal block.
BEST PRACTICE
When wiring the PRESTIGE Solo allow
additional length of wire for the access
panel to swing open during servicing.
Using the Wiring Tool on the
Terminal Blocks
31
Page 38
Internal Wiring
O-10v External Inputs (+)
DHW Sensor or Thermostat
DHW Sensor or Thermostat
O-10v External Inputs (-)
Gas Valve
PRESTIGE
Solo 399 Only
Heating circulator (supplied on the PRESTIGE Solo 110 only)
Fig. 20: Prestige Solo Boiler Factory Wiring
To properly connect wires to terminal block, use wiring tool included with PRESTIGE Solo. See wiring tool instructions, page 31.
32
Page 39
External Wiring
SECTION VIII- External Wiring
Installation Compliance
All field wiring made during installation must
comply with:
-National Electrical Code NFPA 70 and
any other national, state, provincial or
local codes or requirements.
-In Canada, CSA C22.1 Canadian
Electrical Code Part 1, and any other
local codes.
WARNING
ELECTRICAL SHOCK HAZARD.
Before making any electrical connections to the PRESTIGE Solo, disconnect
electrical power supply at the service
panel. Failure to comply can cause
severe personal injury or death.
Line Voltage Connections
1. Connect a 120 VAC/15A service to the
120V terminal strip on the wiring panel
below the PRESTIGE Solo control module, as shown in Fig. 20, page 32.
2. Route the incoming 120 VAC power wire
through the provided openings in the bottom jacket panel.
3. The unit is provided with a service switch
located on the front panel, check local code
requirements for compliance.
Domestic Hot Water Aquastat Wiring
1. Connect the DHW thermostat (aquastat) to
the 24V terminal strip on the wiring panel
located below the PRESTIGE Solo control
module as shown in Fig. 20, page 32.
2. Route all wiring through the provided
openings, in the bottom jacket panel. Allow
enough wire for access panel to swing open
during servicing.
Thermostat Wiring
NOTICE
Isolate 120V wiring from 24V wiring to
prevent any potential electrical “noise”.
1. Connect room thermostat or the end switch
(isolated contact only) of a relay control
panel to the 24V terminal strip on the
wiring panel below the PRESTIGE Solo
control module, as shown in Fig. 20, page
32.
2. For proper operation install the room thermostat on an inside wall away from influences of heat and cold, i.e. water pipes,
areas of draft, lighting fixtures and fireplaces.
3. Set the thermostat anticipator (if applicable) as follows:
-Set for 0.2 amps when wired directly to
the PRESTIGE Solo.
NOTICE
If local electrical codes or conditions
require an additional service switch, the
installer must provide and install a fused
disconnect or 15 amp (minimum) service
switch.
-Set to match the total electrical power
requirements of the connected devices
when wired to zone relays or other
devices. Refer to the relay manufacturers’ specifications and the thermostat
instructions for additional information
on the anticipator setting.
33
Page 40
External Wiring
24 V
Transf ormer
by Others
Honeywell V8043
Zone Valves
or Equivalent
Honeywell R8285D
Transformer / Relay
or Equivalent
24V Terminal Strip
System Circulator
24V Low Voltage Wiring
120V High Voltage Wiring
Room Therm ostats
H
N
120V
R
C
G
1
3
4
6
7
8
To Prestige
NOTICE
When making low voltage connections to
the Prestige, ensure no external voltage
is present in the thermostat circuits. If
external voltage is present, provide an
isolated contact to prevent damage to
the boiler control.
CH and DHW Circulator
1. Connect the CH primary circulator to the
PRESTIGE Solo 120 V terminals 1,2 and 3
as shown in Fig. 20, page 32.
2. Connect the DHW circulator to the PRESTIGE Solo 120 V terminals 4, 5 and 6 as
shown in Fig. 20, page 32.
3. Maximum circulator continuous current
draw is 2A for each circulator.
System Circulator - Zone Valve Application
To energize the system circulator shown as
item 12 in Fig. 10 page 21 reference Fig. 21.
Installer to provide a Transformer / Relay such
as Honeywell R8285 or equivalent and Zone
Valves with isolated end switch such as
Honeywell V8043 or equivalent.
External Modulating Control
The PRESTIGE Solo firing rate can be controlled by an external modulating boiler controller. See page 32 for wiring and Page 54 for
control module setup.
Outdoor Reset Control
The PRESTIGE Solo may operate with a variable boiler operating temperature using the
Triangle Tube outdoor sensor, see pages 50
through 53 for installation and set-up.
NOTICE
If the installer opts for a fixed operating
temperature for the boiler system, the
outdoor sensor is not required and
should not be installed.
Additional 24V Limit Wiring
The PRESTIGE Solo provides 24V terminal
connections for additional limit controls as
shown in Fig. 20 page 32. These limit terminal
connections will provide a "hard" lockout
requiring a manual reset of the PRESTIGE
Solo control, or a “soft” lockout in which the
PRESTIGE Solo will automatically reset.
Fig. 21: Secondary System Circulator Wiring
34
Page 41
External Wiring
H
N
High Voltage
120
V. A . C .
24
V. A . C .
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
To Prestige
24V Terminal Strip
Transformer
(Power)
Zone
Va l ve
Zone Valve
7
8
To Prestige
24V Terminal Strip
H
N
High Voltage
120
V.A.C.
24
V.A.C.
Room
Thermostat
Room
Thermostat
Zone 1
Zone 2
Additional zones
Additional zones may
be added as shown above
Transformer
(Power)
Zone
Valve
Zone Valve
* Isolation relay
7
8
*Use isolation relay on
3-wire zone valve with
non-isolated end switch.
Transformer and the Prestige
MCBA control can burn out
if isolation relay is not used.
NOTICE:
4 Wire Zone Valve
3 Wire Zone Valve
Fig. 22: Multiple Zone Field Wiring Using Zone Valves
35
Page 42
External Wiring
T
T
To Prestige
24V Terminal Strip
C
irculator
Zone 1
Thermostat
zone 1
H
oneywell
R
845A
Relay
120
H
VA C
N
C
irculator
Zone 2
Thermostat
zone 2
Additional zones may be
added as shown above
7
8
6
2
1
4
3
5
6
2
1
4
3
5
T
T
TT
Thermostat
Zone 1
Zone 1
Circulator
120 VAC
N
To Prestige
24V Terminal Strip
Zone 2
Circulator
Zone 3
Circulator
Thermostat
Zone 2
Thermostat
Zone 3
R
C
T1 T1T2T2T3T3
C3
C3
C2C2C1C1PRPR
X2X1L1L2ZC
H
7
8
Fig. 23: Field Wiring with Zone Circulators
Fig. 24: Typical Zone Relay Panel Wiring
36
Page 43
Start-Up Preparation
SECTION IX - Start-Up Preparation
Check Boiler System Water Chemistry
WARNING
Do not use petroleum-base cleaning or
sealing compounds in the boiler system.
Damage to seals and gaskets in the system components could occur, resulting in
substantial property damage.
NOTICE
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
Water pH Level 6.0 to 8.0
Flush Boiler and Domestic System to
Remove Sediment
The installer must flush the boiler system to
remove any sediment to allow proper operation
of the PRESTIGE Solo .
Flush the systems until the water runs clean
and is free of sediment.
For zoned systems, each zone should be
flushed through a purge valve. Purge valves
and isolation valves should be installed on each
zone to allow proper flushing of the system.
Check and Test Antifreeze
For boiler systems containing antifreeze solutions, follow the antifreeze manufacturer’s
instructions in verifying the inhibitor level and
to ensure the fluid characteristics are within
specification requirements.
Maintain the boiler water pH between 6.0 and
8.0. Check using litmus paper or contact a water
treatment company for a chemical analysis.
If the pH does not meet this requirement, do
not operate the PRESTIGE Solo or leave the
unit filled until the condition is corrected.
Water Hardness Less Than 7 Grains
For areas with unusually hard water (hardness
above 7 grains) consult a water treatment
company.
Chlorinated Water
Do not use the PRESTIGE Solo to heat a
swimming pool or spa directly.
Maintain the chlorine level of the water at levels considered safe for drinking.
Due to the degradation of inhibitors over time,
antifreeze fluids must be periodically replaced.
Refer to the manufacturer of the antifreeze for
additional instructions.
NOTICE
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
37
Page 44
Start-Up Preparation
Use of Antifreeze in the Boiler System
WARNING
NEVER use automotive or ethylene glycol antifreeze or undiluted antifreeze in
the primary system as freeze protection.
This can cause severe personal injury,
death or substantial property damage if
ignored.
Determine the antifreeze fluid quantity using
the system water content volume and following
the antifreeze manufacturer instructions.
The water volume of the PRESTIGE Solo is
approximately 3 gallons [12 L] for PRESTIGE
Solo 60 or 5 gallons [19 L] for PRESTIGE Solo
175/250 or 7 gallons [26 L] for PRESTIGE Solo
399 . Remember to include the volume of the
expansion tank.
Check with local codes requirements for the
installation of backflow preventers or actual
disconnection from the boiler’s cold water fill
or make up water supply line.
NOTICE
Massachusetts Code requires the installation of a backflow preventer if antifreeze
is used.
2. Open all system isolation valves.
3. Fill the boiler system to correct system
pressure. Correct pressure will vary with
each application.
NOTICE
Typical residential system fill pressure is
12 psi. System pressure will increase
when system temperature increases.
Operating pressure of the system should
never exceed 25 psi.
4. Purge air and sediment in each zone of the
boiler system through the purge valve.
Open air vents to allow air to be purged in
the zones.
5. Once the system is completely filled and
purged of all air and sediment, check the
system pressure and check/repair any
leaks.
WARNING
Unrepaired system leaks will cause continual makeup water to be added to the
boiler. Continual makeup water could
cause mineral buildup within the heat
exchanger, reducing the heat transfer,
causing possible heat buildup and eventual heat exchanger failure.
Ensure the concentration of antifreeze to water
does not exceed a 50/50 ratio.
NOTICE
System water, including additives, must
be practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
Filling the Boiler System
1. Close the boiler drain valve located on the
bottom of the unit and any manual or automatic air vent in the system.
Check Low Water Cut-Off Device
-The PRESTIGE Solo is provided with a
factory installed LWCO device that measures system pressure of more than 10 psi.
-Remove the front jacket panel and check for
continuity across the low water cut-off
device wire terminals. The contacts should
be closed when system pressure is greater
than 10 psi. See item 6, on Fig. 27 page 66
(PRESTIGE Solo 60) or on Fig. 27A page
67 (PRESTIGE Solo 175/250) or Fig. 27B
page 68 (PRESTIGE Solo 399) for location
of the LWCO.
38
Page 45
Start-Up Preparation
Check For Gas Leaks
WARNING
Prior to start-up and during initial operation, smell near the floor and around the
unit for gas odorant or any unusual odor.
Do not proceed with the start-up if there
is any indication of a gas leak. Any leaks
found must be repaired immediately.
WARNING
Propane installations only - The propane
supplier mixes an odorant with the
propane to make its presence detectable.
In some cases the odorant can fade and
the gas may no longer have an odor.
Prior to start-up of the unit and periodically after start-up have the propane
supplier check and verify the odorant
level.
NOTICE
In systems using 3-wire zone valves,
backfeed of voltage to the unit is a common problem. Use an isolation relay to
prevent voltage from the external circuit
entering the PRESTIGE Solo control
panel.
-Reconnect the external thermostat
wires to the 24V terminal strip on the
wiring panel.
Inspection of Condensate Drain Assembly
1. Inspect and ensure the Condensate Drain
Assembly is properly installed as described
on page 25 and shown in Fig. 15 on page
26.
2. Remove the plug from the Condensate
Drain Assembly and fill with fresh water.
Check Thermostat Circuit
-Disconnect the external thermostat wires
from the 24V terminal strip on the wiring
panel.
-Connect a voltmeter across the wire ends of
the external thermostat wiring.
-Close each thermostat, zone valve and
relay in the external circuit one zone at a
time and check the voltage reading across
the wire ends.
-There should NEVER be voltage measured
at the wire ends.
-If voltage is measured at the panel under any
condition, check and correct the external
wiring.
NOTICE
The condensate drain assembly must be
filled with water when the PRESTIGE
Solo is in operation. The condensate
drain assembly prevents flue gas emissions from entering the condensate line.
Failure to ensure trap is filled with water
could result in severe personal injury or
death.
3. Re-Install plug in condensate drain assembly.
39
Page 46
Start-Up Procedures
SECTION - Start-Up Procedures
Final Checks Before Start-Up
c Read page 45 through 48 regarding the
operation of the PRESTIGE Solo control.
c Verify the PRESTIGE Solo and the boiler
system are full of water and all system
components are correctly set for operation,
including the minimum flow rate through
the boiler, see pages 79 through 81.
c Verify Start-up Preparation items outlined on
pages 37 thru 39 have been completed.
c Verify all electrical connections are correct
and securely fastened.
c Inspect vent and combustion air piping for
signs of deterioration from corrosion, physical
damage or sagging. Verify combustion air
and vent piping are intact and correctly
installed and supported. Reference the PRESTIGE Solo vent supplement.
c Verify burner configuration - Propane only.
- Check for proper labeling on the gas
valve and the rating label for propane
configuration.
- If there is doubt on the burner configuration, remove the gas valve and check for
proper propane gas orifice size: 0.120” or
3.1 mm for PRESTIGE Solo 60, 0.221” or
5.6mm for PRESTIGE Solo 175, 0.250” or
6.3 mm for PRESTIGE Solo 250 or 0.264”
or 6.7 mm for PRESTIGE Solo 399. Refer
to Figs. 17 & 18, page 30 for location of
the propane gas orifice.
NOTICE
PRESTIGE Solo Start-Up
1. Turn the ON-OFF switch located on the front
control panel to the OFF position. Turn ON
the electrical supply/service to the unit.
2. Read and follow the Operating Instructions
outlined on page 42.
If PRESTIGE Solo Does Not Start Correctly
1. Verify DHW (parameter 2) and CH (parameter 3) systems are turned ON or set to
“01”. Read the Boiler Display Standby and
Parameter Section of the manual starting
on page 47 for more information.
2. Check for loose electrical connections,
blown fuse (external or internal to the
MCBA Control) or open service switch.
3. Check continuity across the L.W.C.O
device for a closed circuit. See item 5 on
Fig. 27, page 66 and item 6 Fig. 27A, page
67 and Fig. 27B, page 68.
4. Is the external limit control (if applicable)
open? Ensure the external limit is reset to
the closed position.
5. Is the gas supply valve(s) open at the unit
and meter?
6. Is incoming gas supply pressure at the unit
more than 5”w.c. and less than 13” w.c. for
natural or propane with all gas appliances
ON or OFF.
7. Are the heating thermostats set above room
temperature?
If none of these conditions correct the problem,
refer to the PRESTIGE Solo Trouble-Shooting
Guide or contact Triangle Tube Tech Service.
For natural gas applications the Prestige
60 requires an orifice: 0.204” (52mm), and
the Prestige 399 requires and orifice:
0.330” (8.6 mm)
c Ensure the vent Condensate Drain
Assembly is filled with water.
Check the PRESTIGE Solo and System
c Check Boiler Piping.
Check Boiler system piping and components for leaks. If found, shut down
the unit and repair immediately.
Purge any remaining air from the system
piping. Air in the system piping will
interfere with circulation creating heat
distribution problems and system noise.
40
Page 47
Start-Up Procedures
c Check Vent Piping and Combustion Air
Piping.
Check for gas-tight seal at every connection and seam of the venting and
combustion air piping.
WARNING
Venting system must be sealed gas-tight
to prevent flue gas spillage and potential
carbon monoxide emissions, which will
result in severe personal injury or death.
cCheck Gas Piping
Check around the unit for gas odor following the procedure outlined in this
manual on Page 39.
WARNING
If any gas leaks are found or suspected,
shut the unit down immediately. Use a
gas detection device or bubble test to
locate the source of the gas leak and
repair at once. Do not operate the unit
until the leak is corrected. Failure to
comply with this procedure could result
in severe personal injury, death or substantial property damage.
Test for CO2 or O2 and for CO during
high firing rate. To manually place the
boiler into high fire mode, reference
page 45. The combustion reading
should be within the range listed in
Table 2. The CO level should not
exceed 100 ppm when combustion is
correct.
WARNING
The combustion levels should be measured at high firing rate, refer to page 45
of the PRESTIGE Solo control section
on how to set the firing rate. If the combustion levels are not within the range
given in Table 2 for the firing rate, shut
the boiler down and contact Triangle
Tube Engineering Department. Failure
to comply with this requirement could
result in severe personal injury, death or
substantial property damage.
Table 2: Recommended Combustion Levels
Natural Gas
All Models
O2 Min.2.30%2.70%3.70%
O2 Max.5.30%4.70%5.20%
Propane
Solo 60/175/250
Propane
Solo 399
c Verify Flame Pattern and Combustion
Check the flame pattern through the
inspection port of the heat exchanger.
The flame should be blue and stable.
The flame should be the length of the
burner head openings.
WARNING
The combustion testing and adjustments
must be performed by a qualified
installer, service agency or the gas supplier. All combustion measurements must be
performed with calibrated equipment to
ensure proper reading and accuracy.
CO2 Min.8.80%10.70%10.00%
CO2 Min.10.50%12.00%11.00%
CO Max.100 ppm100 ppm100 ppm
cMeasure Input - Natural Gas Only
1. Ensure the boiler is firing at maximum firing
rate. To manually place the boiler into high
fire mode, reference page 45.
2. Operate the unit for approximately 10
minutes.
3. Turn off all gas appliances within the building, except the PRESTIGE Solo.
4. At the gas meter, record the time required
to use one cubic foot of gas.
41
Page 48
Start-Up Procedures
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which automatically lights the burner. DO NOT try to light the
burner by hand.
B. BEFORE OPERATING, smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air and
will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use
any phone in your building
•Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
OPERATING INSTRUCTIONS
1.STOP! Read the safety information above. This
appliance is equipped with an ignition device
which automatically lights the burner. DO NOT
try to light the burner by hand.
2.Set room thermostat(s) to lowest setting. Turn the
external manual gas valve handle clockwise
“CLOSE” (valve handle shall be per-
pendicular to gas piping).
3.Turn the service switch on the PRESTIGE control panel OFF.
4.Remove the front jacket panel on the unit.
5.Turn the external manual gas valve handle
counter clockwise to “OPEN” gas supply (valve handle shall be parallel to gas piping).
6.Wait five (5) minutes to clear out any gas. If you
then smell gas in the jacket enclosure or around
the unit, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the
next step.
• If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to turn the external manual gas
valve. Never use tools. If the valve will not turn by
hand, don’t try to repair it; call a qualified service
technician. Force or attempted repair may result in
a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
7.Turn the service switch on the PRESTIGE control panel “ON”.
8.Set room thermostat(s) to desired setting(s).
9.The PRESTIGE control panel display will show
a sequence of numbers (0,1,2,3,4,etc.) as the left
digit. Sequence digit 3 or 4 indicates the boiler is
firing. Sequence digit 0 means there is no call for
heat (all external thermostats are satisfied).
10. If the unit will not operate with a call for heat and the
system piping is not hot, follow the instructions “To
Turn Off Gas to Appliance”, below and call your
service technician or gas supplier.
11. Replace the front jacket panel. Make sure the panel is
seated firmly in place and all mounting screws are
tightened.
TO TURN OFF GAS TO APPLIANCE
1.Set the room thermostat to lowest setting.
2.Turn the service switch on the PRESTIGE control panel to “OFF”
3. Turn the external manual gas valve handle clockwise to “CLOSE”.
42
Page 49
Start-Up Procedures
5. Calculate Natural gas input using the following equation:
3600 x 1000 / number of second recorded
for one cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate
the input rating listed on the unit.
Set Boiler CH Set Point
1. Press the MODE button until the display
shows PARA. This is the parameter mode
of the control.
2. Press the STEP button until the first digit
on the display shows "4". The last three
digits on the display shows the CH
Maximum Boiler Operating Setpoint.
3. Press the "+" or "-" button to change the
setting.
NOTICE
When an outdoor sensor is used, the setting of Parameter 4 is the CH setpoint
when the outdoor temperature is at or
below 0ºF. When the outdoor temperature is above 0ºF, the PRESTIGE Solo
control will calculate the boiler setpoint
between the minimum and maximum
temperature settings.
4. Press the "STORE" button to save the setting.
TIGE Solo or turn down DHW tank aquastat (if used) to ensure the boiler does not
receive a DHW call for heat.
2. Set the room thermostat to the lowest setting.
3. Turn off power to the boiler, wait a few
seconds and turn on power to the boiler.
4. The following displays should occur:
U1.22] Software version
[
[
A140] Self check on power up
0140] No call for heat
[
5. Initiate a call for heat by raising the set
point of the room thermostat to the highest
setting. The following display should
occur.
5140] This is a fan / air flow check. The
[
burner blower will be energized momentarily prior to the prepurge cycle.
1140] This is the prepurge cycle. The
[
burner blower and the CH (Central
Heating) circulator become energized. The
blower has a 10 second prepurge cycle.
2140] This is the ignition cycle. The con-
[
trol module will energize and open the gas
valve and begin the spark for ignition.
-If the burner flame proves, the burner
will continue to fire at the ignition fan
speed for approximately 10 seconds to
stabilize the flame.
Operation Verification - Space Heating
NOTICE
Digits and characters shown as [
in the following outline, represent the
control panel display. The last three digits on the display represent the measured
boiler water temperature and may differ
from what is shown in the manual.
1. Disconnect the DHW (Domestic Hot
Water) thermostat wiring from the PRES-
0000
-If the burner flame is not proven the
control module will repeat the ignition
sequence. If the flame is not proven
after five attempts the control will lockout and the display will show [
],
43
-To verify flame failure lockout, close
the manual shut off valve on the gas
supply piping to the boiler and repeat
ignition sequence. When verification is
completed, ensure the manual shut off
valve is returned to the open position.
3140] This is the normal CH operation
[
cycle. After the flame is proven and stabilized the burner will fire at low input for
E-02]
Page 50
Start-Up Procedures
approximately 1 minute. After this time
period, the control module will begin to
modulate the burner firing rate based on
actual boiler outlet temperature and the set
point temperature.
6. Allow the boiler to operate and allow the
boiler outlet temperature to reach the set
point temperature.
6180] This begins the burner shutdown
[
and post purge cycle. The CH circulator
will continue to run until the room thermostat is satisfied.
7. Lower the room thermostat set point below
the room temperature to end the call for
heat.
1180] This begins a post purge cycle.
[
When the room thermostat is satisfied, the
boiler will shutdown. The control module
will close the gas valve and the blower will
continue for 30 seconds for a post purge
cycle before shutting down. If another call
for heat is initiated, the boiler will remain
off for an additional 30 seconds before
starting a new ignition sequence.
7180] The CH circulator will continue to
[
run for a 1 minute post pump cycle.
0180]The boiler is in standby MODE
[
waiting for a call for heat.
8. Verify the operation of the boiler by repeating the operational sequence several times.
9. Return the room thermostat to a desired setting. Reconnect the DHW wiring or return
the DHW aquastat to desired setting, placing the DHW system into operation.
Operation Verification - Domestic Hot
Water (if applicable)
5140] This is a fan / air flow check. The
[
burner blower will be energized momentary prior to the prepurge cycle.
1180] This is prepurge cycle. The burner
[
blower and DHW circulator become energized and the 10 second prepurge cycle
begins.
2180] The boiler will begin the ignition
[
sequence. The same sequence of establishing flame, trail for ignition and attempts for
ignition as described in the space heating
applies for domestic water heater.
4180] This indicates normal operation
[
for DHW. The burner will begin modulating its input to maintain the DHW set point.
The burner will not go into the low input
rate for the 1 minute flame stabilization
period that occurs in CH mode.
3. Lower the DHW aquastat to satisfy the call
for heat.
1180] The post purge cycle begins. The
[
control module closes the gas valve and the
blower continues for a 30 second post
purge.
8180] The DHW circulator will continue
[
for a 30 second post pump cycle. If another DHW call for heat is initiated the boiler
ignition sequence will begin immediately.
0180] Boiler is in standby MODE wait-
[
ing for a CH or DHW call for heat.
4. Verify the DHW operation of the boiler by
repeating the outlined operation sequence
several times.
5. Return the DHW aquastat and room thermostat to the desired setting.
1. As outlined in the verification for space
heating, repeat STEPS 2 through 4.
2. Raise the DHW aquastat setting to initiate a
call for heat. As in the space heating operation the display should show:
44
Page 51
Start-Up Procedures
S
tb
Y
T
est function: Burner on, high fire mode
Test function: Burner on, low fire mode
18
0
18
0
H
L
Display
Boiler function
Boiler Control Display
Standby Mode
This is the standard mode for the PRESTIGE
Solo. The control automatically returns to this
mode after 20 minutes if no keys have been
pressed on the display. Any parameters that
were modified are then stored.
The first character shows (on left side of display) the current status of the boiler depending
on the condition of both the boiler and the
burner. The last 3 characters indicate the boiler
supply temperature.
If the burner is blocked due to a “soft” lockout,
the display alternates between a 9 followed by
the boiler supply temperature and a “b” with a
two digit error code.
TO TEMPORARILY PLACE THE BURNER INTO HIGH FIRE TEST MODE: press
the MODE button until “
Then press and hold both the MODE and “+”
buttons simultaneously until the first digit
flashes “H”.
While in the test mode:
-high limit will function
-boiler CH circulator will function
StbY” is displayed.
TO DEACTIVATE THE HIGH OR LOW
FIRE TEST MODE: press the MODE button
until “
hold both the “+” and “-” buttons simultaneously to deactivate the high or low fire test
mode.
StbY” is displayed. Then press and
NOTICE
If the “+” button is held in, the CH system
(parameter 3) will be turned OFF and the
display will show “
hold the “+” button to turn the CH system back ON, the display will show “c”
followed by CH set point. If the “-” button is held in while in the “
domestic system (parameter 2) will be
turned OFF and the display will show
dOFF”. Press and hold “-” button to
“
turn the domestic system back ON, the
display will show “d” followed by domestic set point temperature.
cOFF”. Press and
StbY” mode,
-domestic circulator will not function
-the test mode will time out in approxi-
mately 10 minutes
TO TEMPORARILY PLACE THE BURNER INTO LOW FIRE TEST MODE: press
the MODE button until “
Then press and hold both MODE and “-” buttons simultaneously until the first digit flashes
“L”.
StbY” is displayed.
45
Page 52
STANDBY, no demand for heat
Fan prepurge or post purge cycle
Ignition sequence
Burner ON for space heating (CH)
Burner ON for domestic hot water (DHW)
Pre-check for air flow prior to prepurge cycle
Burner OFF due to reaching temperature setpoint
Domestic hot water (DHW) post pump cycle
Space Heating (CH) post pump cycle
Burner blocked:
Supply temperature too high (202 F) . Burner
will remain OFF until temperature drops
below 200 F
Return temperature too high (202 F). Burner
will remain OFF until temperature drops
below 200 F
Return temperature is higher than
supply temperature. Burner will remain OFF
until corrected.
Supply temperature increased too quickly.
Burner will remain OFF for a 10 minute period.
Burner will recycle, increasing waiting period 1
minute for a max. 15 minutes
Factory supplied LWCO device or
external limit (terminals 15 & 16) is OPEN.
Burner off for 150 seconds, auto reset.
0
1
18
0
18
0
18
0
18
0
18
0
18
0
18
0
18
0
18
0
18
0
2
3
4
5
6
7
8
9
1
8
b
1
9
b
2
4
b
2
5
b
2
6
b
2
D
isplay
B
oiler function
No blower signal
Blower signal present with no demand, Burner
will remain OFF until condition terminates
Temperature difference between the supply and
return is more than 72 F. Burner will remain OFF
for 150 seconds. Burner will recycle increasing
wating period 1 minute for a max. 20 cycle.
Flue temperature sensor is short-circuited.
Burner OFF until corrected
Flue temperature senor is “open” Burner OFF
until corrected.
Flue temperature greater than 240 F but less
than 250 F. Burner off for 150 seconds
Wait for the blower to start
8
b
2
2
9
b
3
0
b
3
5
b
4
0
b
Indirect water heater temperature sensor is
short-circuited. Burner OFF until corrected.
Indirect water heater temperature sensor is
“open” or disconnected. Burner OFF until
corrected.
3
3
b
3
8
b
5
2
b
6
5
b
Power frequency deviation
1
1
6
b
Flame current signal lost
1
8
b
1
Start-Up Procedures
Standby Mode Display
46
Page 53
Start-Up Procedures
AR
A
P
D
omestic Hot Water Setting (See Note 1)
DHW Application Selection (See Note 2)
CH Application Selection (See Note 3)
CH Maximum Boiler Operating Setpoint
1.
2
14
0
0
1
0
1
8
1
6
3
4
.
.
.
.
STEP
STEP
STEP
STEP
K
ey:
Display
D
escription ofparameters
AR
A
P
MODE
Key:
Display
Pressing MODE once
Setting The Boiler Parameters
Parameter mode
To access PARAMETER mode when the system is in STANDBY mode, press the MODE
button once.
To scroll through the list of parameters, simply
press the “STEP” button. The first digit is the
parameter number followed by the parameter
value. To modify a parameter value, use the +
or - keys. Then press “STORE” to save the
value you just changed. The display flashes
once to confirm the data has been stored.
To activate the parameters you changed, press
“RESET”. However, if you do not press a key,
the system returns to STANDBY mode after 20
minutes and automatically stores the changes.
Note 1: This parameter is factory set to 140ºF.
It is important to note the control adds 46ºF to
this setting, therefore the actual domestic hot
water boiler setpoint is 140ºF + 46ºF = 186ºF.
Note 2: This parameter should not be changed
from the factory setting of 01. The performance of the DHW will be affected and can
become unreliable.
Note 3: This parameter should not be changed
from the factory setting of 01. The performance of the CH (Central/Space Heating) will
be affected and can become unreliable.
47
Page 54
Start-Up Procedures
NF
O
I
AR
A
P
MODE
NF
O
I
MODE
Key:
Display
Pressing MODE once
Pressing MODE twice
J
1
2
.3
4
.5
6
Accessing Boiler Information
Information mode
To switch from STANDBY mode to INFORMATION mode, press MODE twice.
Press STEP until the system displays the information you need. The first digit is the information item number followed by the items value.
The decimal point located behind the first position flashes to indicate that the boiler is in
INFO mode.
NOTICE
The ignition counters and burner hours
are split into three two digit numbers.
For example:
Write the numbers down from left to right
to arrive at 123,456 CH ignitions.
NOTICE
In the INFO Mode a temperature reading of -22 typically indicates an “open”
circuit. A temperature reading of 240
typically indicates a short-circuit.
Display Digit
Segments
48
Page 55
G
as valve harness not properly connected
Failed ignition after 5 attempts
P
ower supply lost after lockout occured
Internal control failure
Internal control failure
E
E
0
2
03
0
4
0
8
0
9
E
E
E
Display
H
ard Lockout
Internal control failure
0
5
E
Internal control failure
0
6
E
Internal control failure
0
7
E
Flame detected prior to burner startup
E
0
0
I
nternal control failure
External limit (terminals 13 & 14) is OPEN
Blower signal does not reset to zero
No blower signal present
Supply Temperature sensor is short circuited
1
1
1
2
1
5
1
6
2
9
2
8
E
E
E
E
E
E
Flue Temperature exceeds 250 F
5
2
E
Internal control error - failure to read parameters
6
1
E
Return Temperature sensor is short circuited
Supply Temperature sensor is OPEN
Return Temperature sensor is OPEN
Internal control failure
Internal control failure
Inadequate power supply to the fan
E
E
3
1
32
3
6
3
7
4
4
60
6
5
E
E
E
E
E
Flue Temperature sensor is short circuit
4
0
E
Return Temperature exceeds 212 F
Supply Temperature increased too rapidly
Internal control failure
I
nternal control failure
Internal control failure
Internal control failure
Internal control failure
1
7
1
9
2
5
1
3
E
E
E
E
Supply Temperature exceeds 212 F
1
8
E
E
1
4
Flue Temperature sensor is OPEN
3
5
E
E
Internal control failure
1
5
E
Supply or Return Temperature sensor drift
2
3
Invalid power frequency
Supply or Return Temperature failure
Supply or Return Temperature not changing
1
31
1
1
1
1
22
2
4
E
E
E
Start-Up Procedures
Error (Hard Lockout) Mode
If a serious fault occurs, the system enters a
hard lockout condition which requires a manual reset by pressing the RESET button. A hard
lock is indicated by displaying an E for the first
digit, followed by the error code.
For a detailed description of the error codes, reference the PRESTIGE Solo Troubleshooting
Guide.
CAUTION
The boiler freeze protection feature is
disabled during a Hard Lockout, however the CH circulator will operate.
CAUTION
During a hard lockout or low water condition the boiler will not re-start without
service. If the heating system is left unattended in cold weather appropriate safeguards or alarms should be installed to
prevent property damage.
49
Page 56
Outdoor Reset Control
SECTION XI - Outdoor Reset Control
The boiler setpoint for a heating call can be
fixed or vary with the outdoor temperature. If
the application requires a constant supply temperature from the boiler, the outdoor temperature sensor should not be connected to the boiler. If an outdoor temperature sensor is connected to the boiler, the outdoor reset function
is automatically enabled and will vary the CH
setpoint with the change in outdoor temperature. The outdoor reset function has no affect
on the DHW setpoint during a domestic call.
4. Mount the sensor enclosure at an elevation
on the exterior wall to prevent accidental
damage or tampering.
5. Avoid mounting the enclosure in areas subjected to excessive moisture.
6. Once an area on the exterior wall has been
determined, to affix the enclosure use the
enclosure as a template to mark the location
of the mounting screws.
7. Using a 3/16” drill bit, drill 2 pilot holes on
the marked locations.
8. Tap the enclosed plastic anchors into the
pilot holes. Use care not to damage the
anchors.
9. Mount the sensor enclosure using the
screws provided.
Wiring the Sensor
1. Remove the sealing nut and sealing gasket
from the sensor enclosure.
Fig. 25: Sensor Enclosure and Components
Mounting the Outdoor Sensor
1. Remove the front cover and mounting
screws / anchors from the sensor enclosure.
2. When mounting the enclosure the exterior
wall selected should represent the heat load
of the building. Typically a northern or
northeastern wall will suit most buildings.
A southern facing wall may suit buildings
that have large glass walls or windows on
the southern face.
3. Ensure the sensor enclosure is shielded
from direct sunlight or the effects of heat or
cold from other sources (exhaust fans,
appliance vents...) to prevent false temperature sensing.
2. Route two 18 gauge wires through the sealing nut and gasket. Connect the wires to
the sensor terminals 1 and 2.
3. Re-insert the sealing gasket and tighten the
sealing nut to the sensor enclosure.
4. Route the sensor wire back to the PRESTIGE Solo boiler, ensuring the wires are
not run parallel to telephone or power
cables.
NOTICE
If the sensor wires are located in an area
with sources of potential electromagnetic
interference (EMI) the sensor wires
should be shielded or the wires should be
routed in a grounded metal conduit. If
using shielded cable, the shielding should
be connected to the common ground of
the unit.
5. Connect the sensor wires to the outdoor sensor terminals on the 24V terminal strip located inside the boiler enclosure (see boiler
wiring diagram, Fig. 20 page 32).
50
Page 57
Outdoor Reset Control
Summer / Winter Switch at Boiler
If required the CH (Central Heating) system can
be turned off at the boiler, similar to a manual
summer / winter switch by pressing and holding
the “+” button while in
the “StbY” mode. The
display will show “cOFF”. Pressing and holding
the “+” button turns the CH system back on.
The display will show “c” followed by the CH
set point temperature.
WARNING
If a parameter setting is changed but the
STORE button is not pressed to save the
setting, the MCBA will automatically
store the setting after 20 minutes. Ensure
all parameters are at their factory settings or appropriately revised for the
application prior to commissioning the
boiler. Failure to comply could result in
erratic or unreliable operation of the
Prestige boiler.
CH Maximum Boiler Operating Setpoint
(Parameter 4)
inimum
Factory Setting
186ºF86ºF194ºF
M
Setting
aximum
M
Setting
If an outdoor temperature sensor is not connected to the boiler, the boiler setpoint for a
heating call will be set to the CH Maximum
Boiler Operating Setpoint. If an outdoor temperature sensor is connected, the CH
Maximum Boiler Operating Setpoint becomes
the boiler setpoint on the CH Reset Curve
Coldest Day. The outdoor temperature can be
monitored on the boiler display via item 4 of
the INFO menu.
Once a parameter setting has been
revised and stored pressing the STEP
button will display the setting of the next
parameter without showing P_XX. To
avoid confusion, it is advisable to continue pressing the STEP button until
Parameter 46 is reached. The next press
of the STEP button will cause the display
torollovertoParameter1.ContinuepressingtheSTEPbuttonuntilthenext
parameter to be adjusted is reached and
revise the setting.
Adjusting Outdoor Reset Curve
Parameters 4, 10, 11, & 12 define the settings
of the outdoor reset curve. See Graph 1 and
Table 3, page 53 for an example of modifying
the outdoor reset curve.
This parameter is not applicable if an outdoor
sensor is not connected to the boiler. When an
outdoor temperature sensor is connected, the
CH Minimum Boiler Operating Setpoint
becomes the boiler setpoint on the CH Reset
Curve Warmest Day.
CH Reset Curve Coldest Day
(Parameter 11)
FactorySetting
00ºF(-)22ºF50ºF
Minimum
Setting
Maximum
Setting
This parameter is not applicable if an outdoor
sensor is not connected to the boiler. When an
outdoor temperature sensor is connected, the
CH Reset Curve Coldest Day is the coldest
design temperature of the heating system.
51
Page 58
Outdoor Reset Control
CH Reset Curve Warmest Day
(Parameter 12)
Factory Setting
64ºF60ºF78ºF
This parameter is not applicable if an outdoor
sensor is not connected to the boiler. When an
outdoor temperature sensor is connected, the
CH Reset Curve Warmest Day is the warmest
design temperature of the heating system.
Entering MCBA Access Code
The installer must enter the MCBA Access
Code to adjust the advanced parameter settings
of the MCBA. The Access Code can be
entered as follows:
1. Press the MODE button until the display
shows
2. Press and hold the MODE and STEP buttons together for 2 to 3 seconds until the
display shows
After Parameter 4, the display will show P followed by the parameter number. Once a particular parameter is reached, the display will
change to show the current setting of that parameter.
NOTICE
The actual parameter values displayed on
the display may vary depending on the
application, but the sequence will always
occur in the order shown.
Changing a Parameter Setting
1. Use the “+” or “–“ button to change the
parameter setting.
3. Press the STEP button once and the display
C_
XX
will show
random number.
4. Press the “+” or “–“ buttons to change the
number displayed to read
hold the “+” or “–“ button to rapidly
change the number.
5. When the display reads
STORE button to save the Access Code.
The display should flash to indicate that the
Access Code was saved.
After the Access Code has been entered, the
advanced parameters can be accessed by pressing the MODE button until the display shows
where
XX
represents a
C_54.. Press and
C_54, press the
PARA. Once the display shows PARA, press
the STEP button to reach the appropriate parameter. The display should follow the following
sequence:
Press STEP once-
1140
2. Press the STORE button to save the
change. The display should flash to indicate that the change was saved.
3. Press the RESET button to leave the Access
Code mode.
52
Page 59
Outdoor Reset Control
90
20
60
100
140
180
70
64
50
30
100
-10
86
Boiler Temperature ( F)
Outdoor Air Temperature ( F)
Parameter 4 Set Point
Parameter 10
Set Point
Parameter 12 Setting
Parameter 11 Setting
Graph 1: Outdoor Air Temperature Reset Curve (Example)
Table 3: Outdoor Air Temperature Reset (Example)
Outdoor
Temperature
0ºF or Lower140ºF
23ºF122ºF
40ºF108ºF
64ºF or Higher86ºF
Boiler target Temp.
Based on Outdoor Temp.
Graph 1 illustrates Parameter 4 adjusted to 140ºF target temperature at 0ºF outdoor
air temperature
Note: Factory setting of Parameter 4 is 186ºF.
53
Page 60
External Modulating Control
SECTION XII - External Modulating
Control
The boiler can directly accept an analog 0-10
VDC signal to control the firing rate from an
external modulating boiler controller.
Wiring the Modulating Controller
Run two 18 gauge wires from the external
modulating boiler controllers 0-10 VDC boiler
output to the external input terminals on the
low voltage terminal strip inside the boiler. (see
boiler wiring diagram, Fig. 20 page 32). This
signal will both enable and modulate the boiler. No wiring is required at the thermostat (TT) terminals 7 and 8 of the boiler.
NOTICE
Ensure that the polarity of the connections from the external modulating boiler controller to the boiler is correct.
Reversed polarity could lead to erratic
and/or no response from the boiler controller.
NOTICE
Ensure that Parameter 4 is set above the
highest setpoint of the external modulating control. Paramater 4 is a boiler high
temperature limit when using an external modulating controller.
Programming of External Modulating
Control
The external modulating control must be programmed to send 1.8 VDC to enable the boiler
and run it at low fire, and 10 VDC to run the
boiler at high fire. Once the control enables the
boiler, it must wait 2 minutes to allow the burner to stabilize before modulating the boiler.
Parameter Adjustment
The Prestige MCBA control module must be
programmed to accept the 0-10 VDC signal
from the external modulating boiler control.
CH Operating Signal Section
(Parameter 45)
Factory Setting
0002
Revised
Setting
Follow the procedure for entering the MCBA
Access Code on page 52, and then change the
setting of Paramater 45 from the factory setting
of 00 to 02.
54
Page 61
External Modulating Control
Factory Setting Parameters
11
201DHW Application Selection
301CH Application Selection
4186ºFCH Maximum Boiler Operating Setpoint
1086ºFCH Minimum Boiler Operating Setpoint
1100ºFCH Reset Curve Coldest Day
1264ºFCH Reset Curve Warmest Day
13-22ºFFrost Protection Setpoint
1832ºFCH Block Temperature Setting
1900 MinutesBoost Feature Setting
2000ºFParallel Shift Value
2146ºFSetpoint Value Addition for DHW
40ºF
HW Setting
D
3201 MinutesCH Circulator Post Pump Time Period
3303 x 10.2 Sec.DHW Circulator Post Pump Time Period
3802ºFDHW On Differential
3906ºFDHW Off Differential
4003 x 10.2 Sec.CH Call Blocking Time
4100 x 10.2 Sec.DHW Call Blocking Time
4200 x 10.2 Sec.DHW to CH Call Blocking Time
4300 MinutesDHW Priority Timeout
4500CH Operating Signal Selection
4602DHW Operating Signal Selection
55
Page 62
Check-Out Procedures
SECTION XIII- Check-Out Procedures
NOTICE
Perform the following check-out procedures as outlined and check off items as
completed. When procedures are completed, the installer should complete the
installation record on page 57.
Check-Out Procedures
c Boiler system water chemistry checked and
verified as outlined on page 37.
c The boiler air vent and any automatic air
vents placed within the system are open
one full turn.
c Air is purged from the heating zones and
boiler system piping.
c If applicable, confirm that the burner has
been properly configured for Propane as
outlined on page 29.
c Checked and verified room thermostat(s)
function properly and the thermostat(s)
heat anticipator (if used) was properly set.
c Observed several operating cycles for
proper operation of the PRESTIGE Solo
and the system.
c Set the room thermostat(s) to the desired
room temperature.
c Reviewed all instructions shipped with the
PRESTIGE Solo with the homeowner or
maintenance personnel.
c Completed the Installation Record on page
57.
c Ensure all manuals and other documents
are returned to the Installation envelope
and given to the owner for safekeeping.
c Thermostat circuit wiring checked and ver-
ified that no voltage is present to the low
voltage terminals as outlined on page 39.
c Operating Instructions on page 42 were fol-
lowed during start-up.
c Combustion levels and flame pattern veri-
fied as outlined on page 41.
c Measured the rate of input on Natural Gas
as outlined on page 41.
c Checked the incoming gas pressure to the
PRESTIGE Solo to ensure a minimum
pressure of 5”w.c during flow conditions to
all gas appliances and a maximum pressure
of 13”w.c during non-flow conditions for
Natural and Propane.
c Adjusted balancing valves and system limit
controls to provide design temperatures to
the primary space heating system.
c In multiple zone applications, adjusted for
correct flow of boiler water to each zone.
56
Page 63
Installation Record
PRESTIGE Model Number:
Serial Number:
Date of Installation:
Fuel: Natural Gas Propane
Measured Rate of Input:
Combustion Readings:
CO
2
O2
CO
The following items were completed during installation:
Installation instructions have been followed and completed
Check-out procedures have been followed and completed
Information regarding the unit and installation received and left with owner / maintenance personnel.
At least on an annual basis the following maintenance should be performed by a qualified service technician:
General
-Attend to any reported problems.
-Inspect the interior of the boiler jacket area;
clean and vacuum if necessary.
-Clean the condensate drain assembly and
fill with fresh water.
-Check for leaks: water, gas, flue and condensate.
-Verify flue vent piping and air inlet piping
are in good condition, sealed tight and
properly supported.
-Check boiler water pressure, piping and
expansion tank.
-Check control settings.
Owner Maintenance
Periodically:
-Check the area around the unit.
-Check and remove any blockage from the
combustion air inlet and ventilation openings.
-Check the temperature and pressure
gauges.
Monthly:
-Check vent piping.
-Check combustion air inlet piping.
-Check the pressure relief valve.
-Check the condensate drain system.
Every 6 months:
-Check boiler piping and gas supply piping
for corrosion or potential signs of leakage.
-Operate the pressure relief valve.
-Check ignition electrode (sand off any
white oxide; clean and reposition).
-Check ignition wiring and ground wiring.
-Check all control wiring and connections.
-Check burner flame pattern (stable and uniform).
Additional items if combustion or performance
is poor:
-Clean heat exchanger and flue ways.
-Remove burner assembly and clean burner
head using compressed air only.
Once the maintenance items are completed,
review the service with the owner.
WARNING
Follow the maintenance procedures
given throughout this manual. Failure
to perform the service and maintenance
or follow the directions in this manual
could result in damage to the PRESTIGE Solo or in system components,
resulting in severe personal injury, death
or substantial property damage.
58
Page 65
Maintenance Procedures
SECTION XVI - Maintenance
Procedures
Maintenance Procedures
WARNING
The PRESTIGE Solo should be inspected and serviced annually, preferably at
the start of the heating season, by a qualified service technician. In addition, the
maintenance and care of the unit as outlined on page 58 and further explained
on pages 59 through 64 should be performed to assure maximum efficiency
and reliability of the unit. Failure to service and maintain the PRESTIGE Solo
and the system components could result
in equipment failure, causing possible
severe personal injury, death or substantial property damage.
NOTICE
The following information provides
detailed instruction for completing the
maintenance items outline in the maintenance schedule on page 58. In addition
to this maintenance, the PRESTIGE
Solo should be serviced at the beginning
of the heating season by a qualified service technician.
Reported Problems
Verify that combustion air inlet area is free of
any contaminates. Refer to the materials listed
on page 5 of this manual. If any of these products are in the area from which the unit takes
its combustion air, they must be removed
immediately or the combustion air intake must
be relocated to another area.
Inspect Burner Area
Remove the boiler front jacket panel and venturi inlet elbow.
Vacuum any dirt or debris from the
burner/blower components.
Re-install venturi inlet elbow and front jacket
panel when completed.
WARNING
Do not use solvents to clean any of the
burner components. The components
could be damaged, resulting in unreliable or unsafe operation.
Check System Piping
Inspect all piping (water and gas) on the boiler
system for leaks and verify that the piping is
leak free and properly supported.
Inspect the fittings and components on the unit
and verify they are leak free.
Any problems reported by the owner should be
checked, verified and corrected before proceeding with any maintenance procedures.
Check Surrounding Area
Verify that the area surrounding the PRESTIGE Solo is free of combustible / flammable
materials or flammable vapors or liquids.
Remove immediately if found.
WARNING
Eliminate all boiler water system leaks.
Continual fresh make-up water will
reduce the heat exchanger life causing
boiler failure. Leaking water may also
cause severe property damage to the surrounding area. Inspect the gas supply
piping using the procedure outlined on
Page 41.
59
Page 66
Maintenance Procedures
Clean Condensate Drain Assembly
1. Loosen the retaining nut from the condensate drain assembly and disconnect the
assembly from the boiler.
2. Empty any water from the trap and drain
assembly. Flush with fresh water as necessary to clean.
3. Check the drain piping from the condensate
drain assembly to the drain. Flush to clean
as necessary.
4. Reassemble the condensate drain assembly
onto the boiler by tightening the retaining
nut with rubber seal onto the boiler. Hand
tight only.
5. Remove the fill plug on the condensate drain
assembly and fill with water. See Fig. 15 on
page 26.
6. Replace the fill plug on drain assembly.
Check Ventilation Air Openings
Inspect Vent and Combustion Air Piping
Visually inspect the venting system and combustion air piping for blockage, deterioration
or leakage. Repair any deficiencies.
Verify that the combustion air inlet piping is
connected, sealed and properly supported.
WARNING
Failure to inspect the vent system and
combustion air inlet piping and to have
any conditions repaired, can result in
severe personal injury or death.
Check Boiler System
Verify all system components are correctly
installed and operating properly.
Check the cold fill pressure for the system, typical cold water fill pressure is 12 psig.
Verify that all ventilation openings to the
mechanical room or building are open and
unobstructed. Check the operation and wiring
of any automatic ventilation dampers.
Check and verify the vent discharge and the
combustion air intake are free of debris and
obstructions.
Verify the system pressure, as the unit operates at
high temperature, to ensure the pressure does not
exceed 25 psig. Excessive pressure reading indicates expansion tank sizing is incorrect or system
performance problems.
Inspect air vent and air separators in the system. Remove the caps on automatic air vents
and briefly depress the valve stem to flush
vent. Replace the cap when completed. Ensure
vents do not leak, replace any leaking vents.
60
Page 67
Maintenance Procedures
Check Expansion Tank
Refer to Section IV - Boiler Piping for recommended location of the expansion tank
and air eliminators.
Closed -Type Tank:
-Ensure tank is partially filled with
water leaving an air gap as a cushion.
Refer to the manufacturer’s instruction
for proper fill level.
-Ensure the tank is fitted with a device
that reduces gravity circulation of airsaturated tank water back into the system. This device prevents air from
bubbling up through the water as it
returns from the system.
-Ensure no automatic air vents are used
in the system. This will allow air to
escape from the system instead of
returning to the tank.
Diaphragm Tank:
-Ensure the system contains a minimum of
one automatic air vent. Recommended
location of the air vent should be atop an
air eliminator.
-Remove the tank from the system and
check the charge pressure. For residential applications the charge pressure is
typically 12 psig. If tank does not hold
a charge pressure, then the membrane is
damaged and the tank should be
replaced.
WARNING
Before manually operating the pressure
relief valve, ensure the discharge piping is
directed to a suitable place of disposal to
avoid a potential scald hazard. The discharge piping must be full size without
restriction and installed to permit complete drainage of both the valve and line.
If after closing the valve, the valve fails to seat
properly or continually weeps, replace the
relief valve. Ensure the cause of the relief
valve to weep is the valve itself, not due to system over-pressurization caused by an expansion tank that is waterlogged or undersized.
Inspection of Ignition Electrode
Remove the ignition electrode from the burner
mounting plate.
Remove any white oxides accumulated on the
electrode using fine grit sandpaper or steel wool.
If the electrode does not clean to a satisfactory
condition, replace the ignitor .
When replacing the ignition electrode, ensure
the gasket is in good condition and correctly
positioned, replace gasket if necessary.
Check Ignition Wiring and Ground Wiring
Inspect the burner wiring from the burner control module to the ground terminal behind the
control panel.
Check Boiler Relief Valve
Inspect the relief valve and lift the lever to verify flow at least annually or as recommended
on the warning tag of the valve.
Ensure wiring is in good condition and securely connected.
Check ground continuity of the wiring to the
boiler jacket or piping using a continuity meter.
Replace and correct ground wire if ground continuity is not completed and satisfactory.
61
Page 68
Maintenance Procedures
Check Control Wiring
Inspect all control wiring. Ensure wiring is in
good condition and properly connected.
Check Control Settings
1. Set the control display to PARAMETER
mode and check all boiler settings. Adjust
setting as necessary see page 47.
2. Check any external limit control settings (if
used). Adjust settings as necessary.
Perform Start-up and Checkout Procedures
Start the unit and perform the start-up procedure as listed in this manual.
Verify the cold water fill pressure is correct and
the operating pressure of the boiler is within
normal operating range.
Complete the checkout procedures as referenced in this manual.
Check Burner Flame
Carefully remove the burner mounting plate
assembly from the heat exchanger. Ensure
combustion chamber insulation is not damaged
during removal of burner mounting plate
assembly. See WARNING on page 64.
Remove the burner head mounting screws and
remove the burner head. Inspect the burner
head for deterioration. Use compressed air or
a vacuum to clean the burner head.
Remove the venturi and gas valve assembly
from the blower.
Use a vacuum cleaner or compressed air to
clean the interior of the blower assembly.
Inspect the blower blades to ensure they are
clean and not damaged.
Re-assemble the venturi and gas valve onto the
blower. Ensure the venturi gasket is in good
condition, positioned correctly and replace gasket if necessary.
Re-assemble the burner head onto the burner
mounting plate. Ensure the burner head gasket
is in good condition, positioned correctly and
replace gasket if necessary.
Inspect the burner flame through the observation port on the heat exchanger.
If flame pattern is not fully blue and covers the
entire burner surface during high fire, shut the
unit down and allow it to cool thoroughly before
disassembly.
Close the external manual gas valve on the gas
supply line and disconnect the gas piping and
rectifier plug.
Disconnect the wiring harness connectors from
the blower and remove the blower retaining
screws or nuts. Remove the blower from the
unit.
Remove the mounting nuts securing the burner
mounting plate to the heat exchanger and set
aside.
Re-assemble the burner mounting plate assembly onto the heat exchanger. Ensure the burner
plate gasket and combustion chamber insulation is in place and not damaged, replace gasket and insulation if necessary. See WARNING
on page 64.
Re-assemble the blower onto the burner
mounting plate and reconnect the wiring harness connectors.
Re-assemble the gas supply connection and
rectifier to gas valve. Open the external manual gas valve. Check gas piping for any leaks as
outlined on page 41 and repair if necessary.
Place the unit back into service.
62
Page 69
Maintenance Procedures
Check Flame Signal
The flame signal can be read from item E of the
information mode. It should be a min. 3μ Α −DC.
Check the ignitor for fouling or damaged
insulation if a low flame signal is read.
Check ground wiring and continuity as a cause
for low flame signal. Replace ignitor if conditions are satisfactory.
Check Combustion Levels
Refer to page 41 of this manual for measuring
combustion levels and burner adjustments.
Check Flue Gas Temperature
1. Adjust the boiler to fire at HIGH fire, see
page 45. Place the control display to INFORMATION mode, see page 47 for procedures.
2. The flue gas temperature is indicated on
the display when the first digit is 5. The
measured temperature (shown as the last 3
digits) should not be more than 54ºF higher than the measured supply water temperature.
3. The measured supply water temperature is
indicated on the information display when
the first digit is 1 and the temperature
shown as the last 3 digits.
4. If the measured flue gas temperature is
higher than 54ºF over the supply water
temperature, shut the boiler down and follow the procedures listed below to clean
the heat exchanger.
- Do not drain the boiler if freeze protection fluid is used in the system.
2. Allow the boiler to cool down to room temperature before servicing.
3. Disconnect the gas piping and rectifier
plug to the gas valve.
4. Disconnect the wiring harness connectors
from the blower and remove the blower
retaining screws or nuts. Remove the blower from the unit.
5. Remove the mounting nuts securing the
burner mounting plate to the heat exchanger and set aside.
6. Carefully remove the burner mounting
plate assembly from the heat exchanger.
Ensure combustion chamber insulation is
not damaged during removal of burner
mounting plate assembly. See WARNING
on page 64.
7. Carefully remove the combustion chamber
insulation from the heat exchanger and set
aside. See WARNING on page 64.
8. Use a vacuum cleaner, compressed air or
water to remove any accumulation from
the heat exchanger flue ways. Do not use
any solvent.
9. Re-install the combustion chamber insulation onto the heat exchanger.
10. Re-assemble the burner mounting plate
assembly onto the heat exchanger. Ensure
the burner plate gasket and combustion
chamber insulation is in place and not damaged, replace gasket and insulation if necessary. See WARNING on page 64.
Clean Heat Exchanger
1. Shut down the boiler:
- Follow the instructions on Page 42 "To
Turn Off Gas to Appliance"
- Do not drain the boiler unless the boiler will be subject to freezing conditions.
11. Re-assemble the blower onto the burner
mounting plate and reconnect the wiring
harness connectors.
12. Reconnect the gas piping and rectifier to
gas valve. Check for leaks, repair if necessary.
13. Close isolation valves on the boiler water
piping to isolate the boiler from the heating
system.
63
Page 70
Maintenance Procedures
14. Attach a hose to the boiler drain valve and
flush the boiler thoroughly with fresh water
by using the purge valves to allow water to
enter through the make-up water line to the
boiler.
15. Once the boiler has been completely
flushed, return the boiler and system piping
back to operation.
16. Perform the required startup and checkout
procedures as outlined on pages 37 to 57.
The combustion chamber insulation
contains ceramic fibers, which are classified as a possible human carcinogen.
When exposed to extremely high temperatures, the ceramic fibers, which
contain crystalline silica, can be converted into cristobalite.
Avoid Breathing and Contact with Skin
and Eyes
Review With Owner
Ensure the owner understands the importance to perform the maintenance schedule
specified in this manual.
Remind the owner of the importance to call
a licensed contractor should the unit or system exhibit any unusual behavior.
2. Wear long sleeved, loose fitting clothing,
gloves and eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes
separately from other laundry and rinse
washing machine thoroughly.
6. Discard used insulation in an air tight
plastic bag.
When removing or repairing the combustion
chamber insulation follow these precaution
measures:
1. Use a NIOSH approved respirator which
meets OSHA requirements for cristobalite
dust, similar to N95. Contact NIOSH at
1-800-356-4676 or on the web at
www.cdc.gov/niosh for latest recommendations.
NIOSH Stated First Aid:
Eye/Skin: Immediately irrigate
Breathing: Clean fresh air
64
Page 71
Replacement Parts
5
9
8
1
3
5
2
6
7
Fig. 26: PRESTIGE Solo Jacket Components
Part #
Item
PRESTIGE
Solo 60
1PSCS01Disply Control Panel
1A----
2PSJKT01BPSJKT03BPSJKT04BBase Panel
3PSJKT01FPSJKT02FFront Jacket Panel
5PSJKT02SPSJKT03SSide Jacket Panel (Left and Right)
Part #
PRESTIGE
Solo 175-250
Part #
PRESTIGE
Solo 399
PSCS02 (Left)
PSCS03 (Right)
Description
Display Control Panel Extensions (Not Shown)
6PSJKT01TPSJKT03TPSJKT05TTop Jacket Panel
7PSJKT02TPSJKT04TPSJKT06TTop Jacket Access Panel
8PSJKT03PSJKT04Control Cover Panel
9PSRKIT21Wall Mounting Braket with 1 Hardware
65
Page 72
Replacement Parts
8
5
9
2
3
4
4
6
7
1
Fig. 27: PRESTIGE Solo 60 Internal Components
ItemPart #Description
1PSRKIT01Heat Exchanger Body
2PSRKIT02Vent Outlet Adapter
3PSRKIT03Combustion Air Inlet Adapter
4PSRKIT04NTC Sensor (NTC1, NTC2 and NTC5)
5PGRKIT20LWCO Pressure Device
6PSRKIT05Condensate Drain Assembly
7PSRKIT06Boiler Piping - Return Assembly
8PSRKIT52Boiler Piping - Supply Assembly
9PSRKIT17Pressure Gauge and Fitting
66
Page 73
Replacement Parts
8
5
4
4
10
9
7
1
3
2
6
Fig. 27A: PRESTIGE Solo 175/250 Internal Components
Part #
Item
1
2PSRKIT27Vent Outlet Adapter
3PSRKIT03Combustion Air Inlet Adapter
4PSRKIT04Supply & Return NTC Sensor (NTC1, NTC2)
5PSRKIT34Flue NTC Sensor (NTC5)
6PGRKIT20LWCO Pressure Device
7PSRKIT05Condensate Drain Assembly
8PSRKIT28Boiler Piping - Return Assembly
9PSRKIT29Boiler Piping - Supply
PRESTIGE
Solo 175/250
PSRKIT25Heat Exchanger Body Solo 175
PSRKIT26Heat Exchanger Body Solo 250
Description
10PSRKIT17Pressure Gauge and Fitting
67
Page 74
Replacement Parts
8
7
10
1
2
3
4
4
5
6
9
Fig. 27B: PRESTIGE Solo 399 Internal Components
Part #
Item
1PSRKIT44Heat Exchanger Body
2PSRKIT45Vent Outlet Adapter
3PSRKIT46Combustion Air Inlet Adapter
4PSRKIT47Supply & Return NTC Sensor (NTC1, NTC2)
5PSRKIT34Flue NTC Sensor (NTC5)
6PGRKIT20LWCO Pressure Device
7PSRKIT05Condensate Drain Assembly
PRESTIGE
Solo 399
Description
8PSRKIT48Boiler Piping - Return Assembly
9PSRKIT49Boiler Piping - Supply Assembly
10PSRKIT17Pressure Gauge and Fitting
68
Page 75
5
2
4
8
1
3
9
6
7
Replacement Parts
Fig. 28: PRESTIGE Solo 60/175/250 Burner Components
9PSRKIT16Sight Glass Assembly (Glass, Gasket and Bracket)
10--Propane Orifice - Not Shown
11--Burner Plate Gasket - Not Shown
Part #
PRESTIGE
Solo 60
Part #
PRESTIGE
Solo 175-250
Description
12PGRKIT15Gas Valve Rectifiier Plug - Not Shown
69
Page 76
Replacement Parts
7
6
9
1
2
10
12
1
3
4
3
5
8
Fig. 28A: PRESTIGE Solo 399 Burner Components
Item
1PSRKIT37Combustion Chamber Insulation
PRESTIGE Solo 399
2PSRKIT38Burner Head with Gasket
3PSRKIT39Burner Plate
4PSRKIT40Blower with Gasket
5PSRKIT41Gas Valve
6--Venturi
7PSRKIT14Ignition Cable
8PSRKIT15Igniter with Gasket
9PSRKIT16Sight Glass Assembly (Glass, Gasket and Bracket)
10--Propane Orifice - Not Shown
11--Burner Plate Gasket - Not Shown
12PSRKIT42Gas Valve Piping
13PSRKIT43Gas Supply Piping
Part #
Description
70
Page 77
3
Replacement Parts
Fig. 29: PRESTIGE Solo Electronic Components
ItemPart #Description
1PSRKIT50Prestige Control Module
2PSRKIT19Transformer with Surge Protection
3PSRKIT20Prestige Control Module Display
71
Page 78
Product Specifications
35.50” [902 mm]
15.43” [392 mm]
9.87” [251 mm]
9.87” [251 mm]
2.2”
[56 mm]
3”
[76 mm]
1 ” NPT Boiler Supply
1/2” NPT Gas Connection
3/4” NPSC Pressure Relief Valve
3” Combustion AIr Inlet
3” Vent Outlet
19.75” [502 mm]
7.31” [186 mm]
1” NPT Boiler Return
Front View PRESTIGE Solo 60
72
Page 79
Product Specifications
Front View PRESTIGE Solo 175/250
73
Page 80
Product Specifications
37.20” [945 mm]
24.70” [628 mm]
20.40” [516 mm]
1
8.60” [473 mm]
13.40” [340 mm]
9.25” [235 mm]
3.27”
[83 mm]
1 1/2” NPT Boiler Supply
1” Gas Connection
1 1/2” NPT Boiler Return
4” Combustion Air Inlet
3/4” NPSC Pressure Relief Valve
4” Vent Outlet
17.87” [454 mm]
Front View PRESTIGE Solo 399
74
Page 81
Product Specifications
Side View PRESTIGE Solo 60
75
Page 82
Product Specifications
Side View PRESTIGE Solo 175/250
76
Page 83
Product Specifications
20.80” [529 mm]
15.40” [490 mm]
14.72” [374 mm]
16.10” [409 mm]
5.90” [150 mm]
1 1/2” NPT Boiler Supply
1 1/2” NPT Boiler Return
1” Gas Connection
4” Combustion Air Inlet
4” Vent Outlet
3/4” NPSC Pressure Relief Valve
Side View PRESTIGE Solo 399
77
Page 84
Product Specifications
94.1%
95.1%
Fuel
Combustion
Efficiency
Input
Note 4
Output
Note 4
Note 5
Thermal
Efficiency
Net IBR
Rating
Note 2
Shipping
Weight
Lbs / Kg
Boiler
Model
379,000
399,000
330,000
2
2
5
/
1
0
2
Natural
SOLO 399
102,500
110 ,000
102,500
Propane
87,000
Fuel
DOE
H
eating Capacity
Note 1 & 4
Input
N
ote 4
DOE Seasonal
Efficiency AFUE
Note 3
Net IBR
R
ating
Note 2
6
0,000
95%
Shipping
Weight
Lbs / Kg
95 / 43
N
atural
Boiler
Model
S
OLO 60
47,000
110 ,000
1
02,500
95%
95 / 43
P
ropane
87,000
154,000
5
4,000
1
70,000
95%
131 / 60
Natural
S
OLO 175
1
34,000
1
02,500
102,500
95%
131 / 60
P
ropane
Propane
8
7,000
2
23,000
2
45,000
9
5%
1
42 / 65
Natural
SOLO 250
1
94,000
102,500
1
10,000
1
02,500
95%
1
42 / 65
8
7,000
Note 1:The heating capacity of the PRESTIGE Solo
60/175/250 is based on the test requirements
of the U.S. Department of Energy.
Note 2:The IBR rating is based on a piping and pick
up allowance of 1.15. This allowance should
be sufficient for the standard radiation
requirements for a building load.
Note 3:Based on the given AFUE the PRESTIGE
Solo 60/175/250 meets the energy efficiency
guidelines established by Energy Star.
DOE
Note 4:Input and output ratings are shown for sea
level applications. The PRESTIGE Solo
automatically derates the input at approximately 2% for every 1,000 Ft. of altitude. No
alterations to the boiler or burner system is
required.
Note 5:PRESTIGE Solo 399 output rating is based
off of the thermal efficiency.
78
Page 85
Product Specifications
Pressure Drop Comparison -Grundfos
Graph 2: Pressure Loss Through Boiler-Grundfos Circulator
Pressure Drop Comparison -Taco
Graph 3: Pressure Loss Through Boiler-Taco Circulators
Note: Minimum allowable flow rate at full input:
- 3 gpm SOLO 60
79
Page 86
Product Specifications
Graph 4: Pressure Loss Through Boiler - Grundfos Circulators
Graph 5: Pressure Loss Through Boiler - Taco Circulators
Note: Minimum allowable flow rate at full input:
- 8 gpm SOLO 175
- 12 gpm SOLO 250
80
Page 87
Product Specifications
Graph 6: Pressure Loss Through Boiler - Grundfos Circulators
Graph 7: Pressure Loss Through Boiler - Taco Circulators
Note: Minimum allowable flow rate at full input:
- 19 gpm SOLO 399
81
Page 88
Additional quality water heating equipment available
from Triangle Tube
Maxi-Flo and Spa Heat Exchangers
SMART Indirect Fired Water Heaters
-Construction of high quality corrosion resistant
stainless steel (AISI 316) or titanium
-Specially designed built-in flow restrictor to assure
maximum heat exchange
-Compact and light weight
-Available in 5 sizes that can accommodate any size
pool or spa