Model TTL010M015M020M025M032M038M060M077M115M
Number of Fans111111223
900138019002380304036005700730010900
(264)(404)(557)(696)(891)(1058)(1670)(2144)(3202)
860130518002250288034205400690010400
(250)(383)(527)(660)(844)(1003)(1582)(2031)(3033)
950145020002500320038006000770011500
(278)(425)(586)(733)(938)(1114)(1758)(2257)(3370)
900138019002380300036005700730010900
(264)(404)(557)(696)(891)(1058)(1670)(2144)(3202)
855130518002250288034205400693010350
(250)(383)(527)(660)(844)(1003)(1582)(2031)(3033)
1301802372704404409288071242
(61)(85)(112)(127)(208)(208)(438)(381)(586)
0.40.50.70.80.91.21.42.33.4
(0.2)(0.2)(0.3)(0.4)(0.4)(0.5)(0.6)(1.0)(1.5)
Capacity
BTUH
(WATTS)
Air FlowCFM (L/s)
Refrigerant **
Charge
Evap
Temp.
25°F
(-4°C)
R407A
R407A
R448A
R407C
R404A
R507
R22
R134a
Lbs (Kg)
LOW TEMPERATURE MODELS - CAPACITY *
Model TTL009L013L017L021L028L033L052L066L099L
Number of Fans111111223
81011901620200026603100490063009400
(237)(348)(473)(584)(780)(919)(1448)(1837)(2756)
77011251530189025202970470060008900
(224)(329)(448)(554)(739)(870)(1372)(1741)(2611)
85012501700210028003300520066009900
(249)(366)(498)(615)(821)(967)(1524)(1934)(2901)
81011901620200027003100490063009400
(237)(348)(473)(584)(780)(919)(1448)(1837)(2756)
76511251530189025202970468059408910
(224)(329)(448)(554)(739)(870)(1372)(1741)(2611)
1301802372704404409288071242
(61)(85)(112)(127)(208)(208)(438)(381)(586)
0.40.50.70.80.91.21.42.33.4
(0.2)(0.2)(0.3)(0.4)(0.4)(0.5)(0.6)(1.0)(1.5)
Capacity
BTUH
(WATTS)
Air FlowCFM (L/s)
Refrigerant **
Charge
Evap
Temp.
-20°F
(-28.9°C)
R407A
R407A
R448A
R407C
R404A
R507
R22
R134a
Lbs
(Kg)
* Derate capacity by 5% when using EC Motors
Capacities rated using 10°F (5.6°C) TD & 100°F (38°C) liquid temperature.
Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
For capacities at TD outside of range 8 to 15 °F (4.4 to 8.3°C), or liquid temperature lower than 75°F (24°), consult factory .
Capacities for R448A, R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated suction
temperature and the temperature feeding the evaporator. For dew point ratings, consult factory.
For R449A, use R448A data.
* CAPACITY CORRECTION FACTORS FOR LOW TEMPERATURE UNITS
SATURATED SUCTION
TEMPERATURE °F (°C)0 (-17.8)
FACTOR1.061.031.0
NO CORRECTION FACTOR REQUIRED FOR MEDIUM TEMP. UNITS
Selections based on 90-100°F liquid.
For R407A valves operating below 0F, the pressure limiting charge ‘ZP40’ may be substituted for the ‘Z’ charge.
R407A derated by .95 factor
Selections based on 90-100°F liquid.
For medium temp. R-507, refrigerant designation changes from ‘S’ to ‘P’.
For R404A/R507 valves operating below 0F, the pressure limiting charge ‘ZP’ may be substituted for the ‘Z’ charge.
For R449A, use R448A data.
TTL60Hz
23/06/17
T30-TTL-PDI-16
- 13 -
INSTALLATION INSTRUCTIONS
INSPECTION
Careful inspection of all parts when received for loss
or damage in transit is very important Remember, you, the consignee, must make any
claim necessary against the transportation company.
Shipping damage or missing parts, when discovered
at the outset, will prevent later unnecessary and
costly delays.
Electrical characteristics should also be checked at
this time to ensure that they are as ordered.
APPLICATION
Two-Way evaporators are designed for use in coolers and freezers such as reach in boxes, display
cases, back bars, walk-in rooms and any other
cooler applications where a low velocity, uniform air
ow is required. The compact and low height unit
provides maximum useable product storage space.
o
At room temperatures above 34°F (1.1
C) and evap-
orating temperatures no lower than 27°F (-2.8°C)
the air owing through the coil will accomplish the
defrost (Air Defrost).
o
At room temperatures 34
F and below (to -10oF)
positive defrosting is required (Electric defrost).
These will require the use of:
1. Time Clock (to initiate and terminate the defrost
cycle),
2. Defrost termination thermostat (to prevent
unnecessary prolonged heating and steaming of the
coil once all the frost and ice has melted). And if a
freezer,
3. Fan delay thermostat (to prevent evaporator fans
starting up right away and blowing water on to the
fan blades, guards and oor).
This evaporator coil must not be exposed to any
abnormal environments (acidic or caustic) that can
result in coil corrosion and leaks. Consult factory
for optional baked on phenolic protective coatings.
These evaporators are for use primarily on R448A/
R407A/R407C/R404A/R507/R22 and R134a refrigerants and their approved alternatives / replace-
ments.
INSTALLATION
The installation and start up of evaporators should
only be performed by qualied refrigeration
mechanics. This equipment should be installed in
accordance with all applicable codes, ordinances,
and local by-laws.
LOCATION
The evaporator is designed to be mounted to the
ceiling of the box or cabinet. Refrigeration piping and
electrical connections are routed to the rear sides
(through the knock-outs). The unit must be mounted
to a level ceiling to ensure complete drainage from
the condensate pan to the drain tting. Refer to the
dimensional drawings for the drain tting and
mounting location details.
On freezer applications it is important that warm, hu-
mid inltrated air is not drawn directly towards the
evaporator. Keeping the evaporator away from the
door, using strip curtains, and using door switches
to lock out and de-energize the liquid solenoid valve
are all eective methods to minimize any unnecessary frost build -up of the fan guard. (Air enters the
fan and discharges out each side of the coil).
TXV SELECTION (thermostatic expansion valve)
For normal operating conditions refer to the TXV
selection chart. When selecting valves ensure they
are sized to meet the capacity at the actual evaporating temperature, liquid temperature and operating
TD of the system . All these conditions can greatly
aect the size and selection. Consult the factory or
valve manufacturer for assistance. All models that
use a distributor (larger models) must use a nozzle.
Smaller models do not have distributors or nozzles.
The TXV superheat setting should NOT be initially
adjusted . After the room has reached or is close to
the required operating temperature the TXV superheat should then be checked and only adjusted if
necessary. Refer to Section on SYSTEM CHECK.
To avoid overheating the valve or distributor
wrap a wet cloth around the valve diaphragm
and body.
MOUNTING
Mounting brackets with 7/32 - 5/16” diameter holes
are provided for ush mounting to the ceiling.
Ensure the evaporator is located correctly with
the air owing in the two desired directions. Avoid
discharging the air directly on to glass doors or door
openings.
After mounting the coil check the slope of the drain
pan with a level. If the ceiling is not level the drain
pan slope may not be correct which can result in
defrosting (ice-up) problems.
TTL60Hz
23/06/17
T30-TTL-PDI-16
- 14 -
INSTALLATION INSTRUCTIONS (CONT’D)
DRAIN LINE
The drain line should be run from the drain
connection, sloping at least 4” vertical drop for
every foot of horizontal distance . A trap outside
the room will allow proper draining throughout the
line. Connection should be made to proper drainage
facilities that comply with local codes and regulations.
In freezers, to prevent drain line freeze up problems, the line must be heated and insulated. A heat
input of 20 W per foot in a 0°F room and 30 W
per foot in a -20°F room is usually satisfactory.
Once the line has been completed , double check
the slope in the drain pan to ensure proper drainage
(prevention of ice build-up on pan).
PIPING
Refrigerant line sizes are important and are not
necessarily the same size as the connections at the
condensing unit or evaporator. If in doubt refer to
a recognized source. (Manufacturer’s Engineering
Manual, Ashrae Manuals, etc.)
WIRING
Wire system in accordance with local codes and
regulations. A 36” cord is provided for single fan air
defrost models (AD). Multiple fans have a junction
terminal box for conduit connections.
When fan delay thermostats are installed the fans
may not start up until the coil temperature
reaches approximately 26°F. On initial start up it may
be necessary to bypass (jumper) this control
temporarily until the coil is cold enough.
SYSTEM CHECK
Before Start Up:
1. Ensure wiring is in accordance with codes.
2. Refrigerant lines are properly sized and routed.
3. Thorough leak check, evacuation and dehydration
has been performed.
4. Drain line has been checked for free ow.
After Start Up:
1. Fan has been checked for correct air ow and no
obstructions.
2. Expansion valve superheat has been checked for
proper operation. (Superheat of the coil should be
around 5 to 6°F for a 10°F TD.)
MAINTENANCE
The unit should be periodically inspected for any dirt
or build up on the n surface and cleaned if
necessary with a soft whisk or brush.
The fan motor is permanently lubricated and should
not require service.
PROJECT INFORMATION
System
Model NumberDate of Start-Up
Serial NumberService Contractor
RefrigerantPhone
Electrical SupplyE-Mail
TTL60Hz
23/06/17
T30-TTL-PDI-16
- 15 -
PRODUCT SUPPORT RESOURCES
web: t-rp.com/ttl
email: evaps@t-rp.com
call: 1-844-893-3222 x520
email: troubleshooting@t-rp.com
call: 1-844-893-3222 x529
web: t-rp.com/parts
email: parts@t-rp.com
call: 1-844-893-3222 x501
web: t-rp.com/warranty
email: warranty@t-rp.com
call: 1-844-893-3222 ext. 501
email: orders@t-rp.com
call: 1-844-893-3222 x501
email: shipping@t-rp.com
call: 1-844-893-3222 x503
“AS BUILT” SERVICE PARTS LIST
23/06/17
Service Parts List
Label
To Be Attached
HERE
NATIONAL REFRIGERATION &
AIR CONDITIONING CANADA CORP.